Declaration of Conformity..........................................................................................................43
China RoHS................................................................................................................................ 47
2Rosemount 644
Page 3
May 2022Quick Start Guide
1About this guide
This guide provides basic guidelines for installing the Rosemount 644
Temperature Transmitter. It does not provide instructions for detailed
configuration, diagnostics, maintenance, service, troubleshooting, or
installation. Refer to the Rosemount 644 Reference Manual for more
instruction. The manual and this guide are also available electronically on
Emerson.com/Rosemount.
Safety messages
WARNING
The products described in this document are NOT designed for nuclearqualified applications.
Using non-nuclear qualified products in applications that require nuclearqualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your
local Emerson Sales Representative.
Follow instructions
Failure to follow these installation guidelines could result in death or serious
injury.
Ensure only qualified personnel perform the installation.
Physical access
Unauthorized personnel may potentially cause significant damage to and/or
misconfiguration of end users’ equipment. This could be intentional or
unintentional and needs to be protected against.
Physical security is an important part of any security program and
fundamental to protecting your system. Restrict physical access by
unauthorized personnel to protect end users’ assets. This is true for all
systems used within the facility.
Quick Start Guide3
Page 4
Quick Start GuideMay 2022
WARNING
Explosions
Explosions could result in death or serious injury.
Installation of the transmitters in a hazardous environment must be in
accordance with the appropriate local, national, and international
standards, codes, and practices. Please review the Product Certifications
section for any restrictions associated with a safe installation.
Do not remove the connection head cover in explosive atmospheres
when the circuit is live.
Before connecting a handheld communicator in an explosive
atmosphere, ensure the instruments are installed in accordance with
intrinsically safe or non-incendive field wiring practices.Verify the
operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
All connection head covers must be fully engaged to meet explosionproof requirements.
Process leaks
Process leaks could result in death or serious injury.
Do not remove the thermowell while in operation.
Install and tighten thermowells and sensors before applying pressure.
Electrical shock
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be
present on leads can cause electrical shock.
CAUTION
Conduit/cable entries
Unless otherwise marked, the conduit/cable entries in the housing
enclosure use a ½–14 NPT form. Only use plugs, adapters, glands, or
conduit with a compatible thread form when closing these entries.
Entries marked "M20" are M20 x 1.5 thread form.
When installing in a hazardous location, use only appropriately listed or
Ex certified plugs, glands, or adapters in cable/conduit entries.
4Rosemount 644
Page 5
May 2022Quick Start Guide
2System readiness
2.1Confirm HART® revision capability
If using HART-based control or asset management systems, confirm the
HART capability of those systems prior to transmitter installation. Not all
systems are capable of communicating with HART Revision 7 Protocol. You
can configure the transmitter for either HART Revision 5 or 7.
2.2Confirm correct device driver
Procedure
1. Verify the latest Device Driver files are loaded on your systems to
ensure proper communications.
2. Download the latest Device Driver at Emerson.com/Device-Install-
Kits/Device-Install-Kit-Search
Table 2-1 provides the information necessary to ensure the correct
Device Driver files and documentation are being used.
Table 2-1: Device Revisions and Files
Software
date
June 20121.1.135800809-010
NAMUR
Software
revision
®
HART
Software
revision
HART
Universal
(1)
revision
79
Device
revision
(2)
Manual
Document
Number
0-4728
Changes to
Software
(3)
See
for
list of
changes.
(3)
(1) NAMUR software revision is located on the hardware tag of the device. HART software
revision can be read using a HART communication tool.
(2) Device Driver file names use Device and DD Revision (e.g. 10_01. HART Protocol) is designed
to enable legacy device driver revisions to continue to communicate with new HART devices.
To access new functionality, download the new Device Driver. Emerson recommends
downloading new Device Driver files to ensure full functionality.
Diagnostics (if ordered), Enhanced Accuracy and Stability (if ordered).
Quick Start Guide5
Page 6
Quick Start GuideMay 2022
3Transmitter installation
3.1Mount the transmitter
Mount the transmitter at a high point in the conduit run to prevent moisture
from draining into the transmitter housing.
3.1.1Head mount transmitter with DIN plate style sensor installation
WARNING
Enclosure
Enclosure covers must be fully engaged to meet explosion-proof
requirements.
Procedure
1. Attach the thermowell to the pipe or process container wall.
2. Install and tighten the thermowell before applying process pressure.
3. Verify the transmitter failure mode switch position.
4. Assemble the transmitter to the sensor. Push the transmitter
mounting screws through the sensor mounting plate.
5. Wire the sensor to the transmitter.
6. Insert the transmitter-sensor assembly into the connection head.
a) Thread the transmitter mounting screw into the connection
head mounting holes.
b) Assemble the extension to the connection head.
c) Insert the assembly into the thermowell.
7. If using a cable gland, properly attach the cable gland to a housing
conduit entry.
8. Insert the shielded cable leads into the connection head through the
cable entry.
9. Connect the shielded power cable leads to the transmitter power
terminals.
Avoid contact with sensor leads and sensor connections.
10. Connect and tighten the cable gland.
11. Install and tighten the connection head cover.
6Rosemount 644
Page 7
May 2022Quick Start Guide
A. Connection head cover
B. Connection head
C. Thermowell
D. Transmitter mounting screws
E. Integral mount sensor with flying leads
F. Extension
3.1.2Head mount transmitter with threaded sensor installation (two or
three conduit entries)
WARNING
Enclosure
Enclosure covers must be fully engaged to meet explosion-proof
requirements.
Procedure
1. Attach the thermowell to the pipe or process container wall.
2. Install and tighten thermowells before applying process pressure.
3. Attach necessary extension nipples and adapters to the thermowell.
4. Seal the nipple and adapter threads with silicone tape.
5. Screw the sensor into the thermowell. Install drain seals if required
for severe environments or to satisfy code requirements.
6. Verify the transmitter failure mode switch is in the desired position.
7. Verify the correct installation of Integral Transient Protection (option
code T1).
a) Ensure the transient protector unit is firmly connected to the
transmitter puck assembly.
b) Ensure the transient protector power leads are adequately
secured under the transmitter power terminal screws.
c) Verify the transient protector’s ground wire is secured to the
internal ground screw found within the universal head.
Quick Start Guide7
Page 8
Quick Start GuideMay 2022
Note
The transient protector requires the use of an enclosure of at least
3.5-in. (89 mm) in diameter.
8. Pull the sensor wiring leads through the universal head and
transmitter center hole.
9. Mount the transmitter in the universal head by threading the
transmitter mounting screws into the universal head mounting
holes.
10. Mount the transmitter-sensor assembly into the thermowell, or
remote mount if desired.
11. Seal adapter threads with silicone tape.
12. Pull the field wiring leads through the conduit into the universal
head. Attach the sensor and power leads to the transmitter.
Avoid contact with other terminals.
13. Install and tighten the universal head cover.
A. Threaded thermowell
B. Threaded style sensor
C. Universal head (transmitter inside)
D. Standard extension
E. Conduit entry
3.1.3Field mount transmitter with threaded sensor installation
WARNING
Enclosure
Enclosure covers must be fully engaged to meet explosion-proof
requirements.
Procedure
1. Attach the thermowell to the pipe or process container wall. Install
and tighten thermowells before applying process pressure.
2. Attach necessary extension nipples and adapters to the thermowell.
8Rosemount 644
Page 9
A
C
B
D
E
May 2022Quick Start Guide
3. Seal the nipple and adapter threads with silicone tape.
4. Screw the sensor into the thermowell. Install drain seals if required
for severe environments or to satisfy code requirements.
5. Verify the transmitter failure mode switch is in the desired position.
6. Mount the transmitter-sensor assembly into the thermowell or
remote mount if desired.
7. Seal adapter threads with silicone tape.
8. Pull the field wiring leads through the conduit into the field mount
housing. Wire the sensor and power leads to the transmitter.
Avoid contact with other terminals.
9. Install and tighten the covers of two compartments.
A. Threaded thermowell
B. Threaded style sensor
C. Standard extension
D. Field mount housing (transmitter inside)
E. Conduit entry
Quick Start Guide9
Page 10
Quick Start GuideMay 2022
3.2Wire and apply power
3.2.1Wire the sensor to the transmitter
Figure 3-1: Rosemount 644 Head Mount - Single and Dual Input Wiring
Diagrams
• The transmitter must be configured for at least a three-wire RTD in order
to recognize an RTD with a compensation loop.
• Emerson provides a four-wire sensors for all single element RTDs. Use
these RTDs in three-wire configurations by leaving the unneeded leads
disconnected and insulated with electrical tape.
Figure 3-2: Rosemount 644 Field Mount — Single and Dual Input Wiring
Diagrams
3.2.2Power the transmitter
An external power supply is required to operate the transmitter.
Procedure
1. Remove the housing cover (if applicable).
2. Connect the positive power lead to the “+” terminal. Connect the
negative power lead to the “–” terminal.
10Rosemount 644
Page 11
May 2022Quick Start Guide
If a transient protector is being used, the power leads will now be
connected to the top of the transient protector unit. See the
transient label for indication of “+” and “–“ terminal connections.
3. Tighten the terminal screws. When tightening the sensor and power
wires, the max torque is 6 in-lb (0.7 N-m).
4. Reattach and tighten the cover (if applicable).
WARNING
Enclosue
Enclosure covers must be fully engaged to meet explosion-proof
requirements.
5. Apply power (12–42 Vdc).
3.2.3Load limitation
The power required across the transmitter power terminals is 12 to 42.4
Vdc; the power terminals are rated to 42.4 Vdc. To prevent damaging the
transmitter, do not allow terminal voltage to drop below 12.0 Vdc when
changing the configuration parameters.
3.2.4Ground the transmitter
To ensure proper grounding, it is important the instrument cable shield be:
• Trimmed close and insulated from touching the transmitter housing
• Connected to the next shield if cable is routed through a junction box
• Connected to a good earth ground at the power supply end
Note
Shielded twisted pair cable should be used for best results. Use 24 AWG or
larger wire and do not exceed 5,000 ft. (1500 m).
Ungrounded thermocouple, mV, and RTD/Ohm inputs
Each process installation has different requirements for grounding. Use the
grounding options recommended by the facility for the specific sensor type,
or begin with grounding option 1 (the most common).
Quick Start Guide11
Page 12
A
B
C
DCS
D
Quick Start GuideMay 2022
Ground the transmitter: option 1
Procedure
1. Connect sensor wiring shield to the transmitter housing.
2. Ensure the sensor shield is electrically isolated from surrounding
fixtures that may be grounded.
3. Ground signal wiring shield at the power supply end.
A. Sensor wires
B. Transmitter
C. Shield ground point
D. 4-20 mA loop
12Rosemount 644
Page 13
A
B
C
D
DCS
May 2022Quick Start Guide
Ground the transmitter: option 2
Procedure
1. Connect signal wiring shield to the sensor wiring shield.
2. Ensure the two shields are tied together and electrically isolated from
the transmitter housing.
3. Ground shield at the power supply end only.
4. Ensure the sensor shield is electrically isolated from the surrounding
grounded fixtures.
A. Sensor wires
B. Transmitter
C. Shield ground point
D. 4-20 mA loop
Note
Connect shields together, electrically isolated from the transmitter.
Quick Start Guide13
Page 14
DCS
A
B
C
D
Quick Start GuideMay 2022
Ground the transmitter: option 3
Procedure
1. Ground sensor wiring shield at the sensor if possible.
2. Ensure the sensor wiring and signal wiring shields are electrically
isolated from the transmitter housing.
3. Do not connect the signal wiring shield to the sensor wiring shield.
4. Ground the signal wiring shield at the power supply end.
A. Sensor wires
B. Transmitter
C. Shield ground point
D. 4-20 mA loop
14Rosemount 644
Page 15
DCS
A
B
C
D
May 2022Quick Start Guide
Grounded thermocouple inputs
Ground the transmitter: option 4
Procedure
1. Ground sensor wiring shield at the sensor.
2. Ensure the sensor wiring and signal wiring shields are electrically
isolated from the transmitter housing.
3. Do not connect the signal wiring shield to the sensor wiring shield.
4. Ground signal wiring shield at the power supply end.
A. Sensor wires
B. Transmitter
C. Shield ground point
D. 4–20 mA loop
3.3
Set the alarm switch
Set the alarm switch before putting the device into operation.
Procedure
1. Set the loop to manual (if applicable) and disconnect the power.
2. Remove the LCD display by detaching from the transmitter (if
applicable).
3. Set the switch to the desired position.
H indicates High; L indicates Low.
4. Reattach the LCD display to the transmitter (if applicable).
5. Reattach the housing cover. Ensure covers must be fully engaged to
meet explosion-proof requirements.
6. Apply power and set the loop to automatic control (if applicable).
Quick Start Guide15
Page 16
A
Rosemount 644 Transmitter
Rosemount 644 Field Mount
Quick Start GuideMay 2022
Figure 3-3: Alarm Switch Placement
A. Alarm switch
Note
If using an LCD display, remove the display by detaching it from the
top of the device, set the switch to the desired position, reattach the
LCD display, and reattach the housing cover.
WARNING
Enclosure
Enclosure covers must be fully engaged to meet explosion-proof
requirements.
3.4Verify configuration
Upon receiving your transmitter, verify its configuration using any HART®compliant configuration tool. See the Rosemount 644 Reference Manual for
configuration instructions using AMS Device Manager.
The transmitter communicates using the Field Communicator
(communication requires a loop resistance between 250 and 1100 ohms).
Do not operate when power is below 12 Vdc at the transmitter terminal. See
the Field Communicator Reference Manual for more information.
3.4.1Verify configuration with a Field Communicator
To verify configuration, you must install a Rosemount 644 DD (Device
Descriptor) on the Field Communicator.
Fast Key sequences for the latest DD are shown in Table 3-1. For Fast Key
sequences using legacy DD's, contact your local Emerson representative.
Perform the following steps to determine if an upgrade is required.
16Rosemount 644
Page 17
May 2022Quick Start Guide
Procedure
1. Connect the sensor.
See the wiring diagram located on the device’s top label.
2. Connect the bench power supply to the power terminals (“+” or “–”).
3. Connect a Field Communicator to the loop across a loop resistor or at
the power/signal terminals on the transmitter.
The following message will appear if the communicator has a previous
version of the DDs:
Device Description Not Installed…The Device
Description for manufacturer 0x26 model 0x2618 dev
rev 8/9 is not installed on the System Card…see
Programming Utility for details on Device
Description updates…Do you wish to proceed in
forward compatibility mode?
If this notice does not appear, the latest DD is installed. If the latest version is
not available, the communicator will communicate properly; however, when
the transmitter is configured to utilize advanced transmitter features, there
will be trouble communicating and a prompt to turn off the communicator
will display. To prevent this from happening, upgrade to the latest DD or
answer NO to the question and default to the generic transmitter
functionality.
Note
Emerson recommends installing the latest DD to access the complete
functionality. Visit Emerson.com/Field-Communicator for information on
updating the DD Library.
Quick Start Guide17
Page 18
Quick Start GuideMay 2022
3.4.2Field Communicator user interface
Two user interfaces are available to configure this device.
Figure 3-4 may be used for transmitter configuration and startup.
Figure 3-4: Device Dashboard Field Communicator Interface
Table 3-1: Device Revision 8 and 9 (HART® 5 and 7), DD Revision 1 Fast
Key Sequence
FunctionHART 5HART 7
Alarm values2, 2, 5, 62, 2, 5, 6
Analog calibration3, 4, 53, 4, 5
Analog output2, 2, 5, 12, 2, 5, 1
Average temperature setup2, 2, 3, 32, 2, 3, 3
Burst mode2, 2, 8, 42, 2, 8, 4
Comm statusN/A1, 2
Configure additional messagesN/A2, 2, 8, 4, 7
Configure Hot Backup
D/A trim3, 4, 4, 13, 4, 4, 1
Damping values2, 2, 1, 52, 2, 1, 6
Date2, 2, 7, 1, 22, 2, 7, 1, 3
Display setup2, 1, 42, 1, 4
Descriptor2, 2, 7, 1, 42, 2, 7, 1, 5
18Rosemount 644
™
2, 2, 4, 1, 32, 2, 4, 1, 3
Page 19
May 2022Quick Start Guide
Table 3-1: Device Revision 8 and 9 (HART® 5 and 7), DD Revision 1 Fast
Key Sequence (continued)
FunctionHART 5HART 7
Device information1, 8, 11, 8, 1
Differential temperature setup2, 2, 3, 12, 2, 3, 1
3.4.3Input or verify Callendar Van-Dusen constants
If using sensor matching with this combination of a transmitter and sensor,
verify the constants input.
Procedure
1. From the HOME screen, select 2 Configure → 2 Manual Setup → 1
Sensor.
2. Set the control loop to manual and select OK.
3. At the ENTER SENSOR TYPE prompt, select Cal VanDusen.
4. At the ENTER SENSOR CONNECTION prompt, select the appropriate
number of wires.
5. Enter the Ro, Alpha, Delta, and Beta values from the stainless steel
tag attached to the special-order sensor when prompted.
6. Return the control loop to automatic control and select OK.
7. To disable the transmitter-sensor matching feature from the HOME
screen select 2 Configure→2 Manual Setup→1 Sensor→10Sensor Matching-CVD.
8. Choose the appropriate sensor type from the ENTER SENSOR TYPE
prompt.
3.4.4Verify configuration with local operator interface (LOI)
The optional LOI can be used for commissioning the device. The LOI is a twobutton design. To activate the LOI, push any button.
LOI button functionality is shown on the bottom corners of the display. See
Table 3-2 and Figure 3-6 for button operation and menu information.
20Rosemount 644
Page 21
May 2022Quick Start Guide
Figure 3-5: Local Operator Interface
Table 3-2: LOI Button Operation
Button
LeftNoSCROLL
RightYesENTER
Figure 3-6: LOI Menu
Quick Start Guide21
Page 22
Quick Start GuideMay 2022
3.4.5Switch HART Revision mode
Not all systems are capable of communicating with HART® Revision 7
Protocol. You can configure this transmitter for either HART Revision 5 or 7
using a HART capable configuration tool.
Updated configuration menus include a HART Universal Revision parameter
that can be configured to 5 or 7 if accessible by your system. See Table 3-1
for the Fast Key sequence.
If the HART configuration tool is not capable of communicating with HART
Revision 7, the configuration menus in Table 3-1 will not be available. To
switch the HART Universal Revision parameter from generic mode, follow
the instructions below.
Procedure
Go to Configure → Manual Setup → Device Information → Identification
→ Message.
a) To change your device to HART Revision 7, enter HART7 in the
Message field.
b) To change your device to HART Revision 5, enter HART5 in the
Message field.
Note
See Table 3-1 to change HART Revision when the correct Device Driver is
loaded.
3.5
Perform a loop test
The loop test command verifies transmitter output, loop integrity, and
operation of any recorders or similar devices installed in the loop.
3.5.1Perform a loop test using a Field Communicator
Procedure
1. Connect an external ampere meter in series with the transmitter loop
(so the power to the transmitter goes through the meter at some
point in the loop).
2. From the Home screen, enter the Fast Key sequence.
Device dashboard Fast Keys
3. In the test loop, verify the transmitter’s actual mA output and the
HART mA reading are the same value.
If the readings do not match, either the transmitter requires an
output trim or the meter is malfunctioning.
22Rosemount 644
3, 5, 1
Page 23
May 2022Quick Start Guide
After completing the test, the display returns to the loop test screen
and allows the user to choose another output value.
4. To end the loop test, select End and Enter.
3.5.2Perform a loop test using Device Manager
Procedure
1. Right click on the device and select Service Tools.
2. In the left navigation pane select Simulate.
3. On the Simulate tab in the Analog Output Verification group box,
select the Perform Loop Test button.
4. Follow the guided instructions and select Apply when complete.
3.5.3Perform a loop test using the LOI
Reference the figure below to find the path to the Loop Test in the LOI
menu.
Figure 3-7: Configuring the Tag with LOI
Quick Start Guide23
Page 24
Quick Start GuideMay 2022
4Safety instrumented systems
For Safety Certified installations, refer to the Rosemount 644 Reference
Manual. The manual is available electronically at Emerson.com/Rosemount
or by contacting an Emerson representative.
24Rosemount 644
Page 25
May 2022Quick Start Guide
5Product certifications
Rev 4.15
5.1European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EU Declaration of
Conformity can be found at Emerson.com/Rosemount.
5.2Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine
that the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health Administration (OSHA).
5.3North America
The US National Electrical Code® (NEC) and the Canadian Electrical Code
(CEC) permit the use of Division marked equipment in Zones and Zone
marked equipment in Divisions. The markings must be suitable for the area
classification, gas, and temperature class. This information is clearly defined
in the respective codes.
5.4USA
5.4.1E5 USA Explosion-proof, Non-Incendive, Dust Ignition-proof
Certificate:
Standards:
Markings:
5.4.2I5 USA Intrinsic Safety and Non-Incendive
Certificate:
Standards:
Markings:
Quick Start Guide25
1091070
FM Class 3600: 2011, FM Class 3615: 2006, FM Class 3616:
2011, ANSI/ISA 60079-0: Ed. 5, UL Std. No. 50E, CAN/CSA
C22.2 No. 60529-05
XP CL I, DIV 1, GP B, C, D; DIP CL II / III, DIV 1, GP E, F, G;
T5(-50 °C ≤ Ta ≤ +85 °C); Type 4X; IP66; See I5 description for
Non-Incendive markings.
1091070
FM Class 3600: 2011, FM Class 3610: 2010, FM Class 3611:
2004, ANSI/ISA 60079-0: Ed. 5, UL Std. No. 60079-11: Ed. 6,
UL Std. No. 50E, CAN/CSA C22.2 No. 60529-05
IS CL I/II/III, DIV I, GP A, B, C, D, E, F, G; CL I ZONE 0 AEx ia IIC;
NI CL I, DIV 2, GP A, B, C, D
Page 26
Quick Start GuideMay 2022
Special Conditions for Safe Use (X):
1. When no enclosure option is selected, the Rosemount 644
Temperature Transmitter shall be installed in a final enclosure
meeting type of protection IP20 and meeting the requirements of
ANSI/ISA 61010-1 and ANSI/ISA 60079-0.
2. Option code K5 is only applicable with a Rosemount enclosure.
However, K5 is not valid with enclosure options S1, S2, S3, or S4.
3. An enclosure option must be selected to maintain a Type 4X rating.
4. The Rosemount 644 Transmitter optional housings may contain
aluminum and is considered a potential risk of ignition by impact or
friction. Care must be taken during installation and use to prevent
impact and friction.
CL I/II/III, DIV 1, GP B, C, D, E, F, G
See I6 description for Intrinsic Safety and Division 2 markings
26Rosemount 644
Page 27
May 2022Quick Start Guide
5.6Europe
5.6.1E1 ATEX Flameproof
Certificate:
Standards:
Markings:
DEKRA 19ATEX0076 X
EN IEC 60079-0: 2018, EN 60079-1: 2014
II 2 G Ex db IIC T6…T1 Gb, T6(–60 °C ≤ Ta ≤ +70 °C), T5…
T1(–60 °C ≤ Ta ≤ +80 °C)
Special Conditions for Safe Use (X):
1. Flameproof joints are not intended for repair.
2. Non-Standard Paint options may cause risk from electrostatic
discharge. Avoid installations that cause electrostatic build-up on
painted surfaces, and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
Additional Specific Conditions of Use (X) when “XA” designation is
ordered:
Guard DIN Style sensors against impacts greater than 4J.
Process Temperature
Range at Sensor
Connection (°C)
-60 °C to +70 °C-60 °C to +70 °CT6
-60 °C to +80 °C-60 °C to +80 °CT5…T1
(1) Sensor Connection is where the sensor threads into the transmitter or junction
box housing.
(1)
Ambient Temperature
Range (°C)
Temperature Class
5.6.2I1 ATEX Intrinsic Safety
Certificate:
Standards:
Markings:
See Table 5-5 for entity parameters and temperature classifications.
[HART]: II 1 G Ex ia IIC T6…T4 Ga
[Fieldbus/PROFIBUS]: II 1 G Ex ia IIC T4 Ga
Page 28
Quick Start GuideMay 2022
Special Conditions for Safe Use (X):
1. The equipment must be installed in an enclosure which affords it a
degree of protection of at least IP20 in accordance with the
requirements of IEC 60529. Non-metallic enclosures must have a
surface resistance of less than 1 GΩ; light alloy or zirconium
enclosures must be protected from impact and friction when
installed in a Zone 0 environment.
2. When fitted with the Transient Protector Assembly, the equipment is
not capable of withstanding the 500 V test as defined in Clause
6.3.13 of EN 60079-11:2012. This must be taken into account during
installation.
5.6.3N1 ATEX Type n – with enclosure
Certificate:
Standards:
Markings:
BAS00ATEX3145
EN 60079-0: 2012+A11: 2013, EN 60079-15: 2010
II 3 G Ex nA IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C)
5.6.4NC ATEX Type n – without enclosure
Certificate:
Standards:
Markings:
Special Conditions for Safe Use (X):
1. The Rosemount 644 Temperature Transmitter must be installed in a
2. When fitted with the Transient Protector Assembly, the equipment is
[Headmount Fieldbus/PROFIBUS, Railmount HART]: II 3 G
Ex nA IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C)
[Headmount HART]: II 3 G Ex nA IIC T6…T5 Gc; T6(–60 °C ≤
Ta ≤ +40 °C); T5(–60 °C ≤ Ta ≤ +85 °C)
suitably certified enclosure such that it is afforded a degree of
protection of at least IP54 in accordance with IEC 60529 and EN
60079-15.
not capable of withstanding the 500 V test as defined in Clause 6.5 of
EN 60079-15: 2010. This must be taken into account during
installation.
28Rosemount 644
Page 29
May 2022Quick Start Guide
5.6.5ND ATEX Dust
Certificate:
Standards:
Markings:
DEKRA 19ATEX0076 X
EN IEC 60079-0: 2018, EN 60079-31: 201
II 2 D Ex tb IIIC T130 °C Db, (–60 °C ≤ Ta ≤ +80 °C)
Specific Condition of Use (X):
Non-Standard Paint options may cause risk from electrostatic discharge.
Avoid installations that cause electrostatic build-up on painted surfaces, and
only clean the painted surfaces with a damp cloth. If paint is ordered through
a special option code, contact the manufacturer for more information.
Additional Specific Conditions of Use (X) when “XA” designation is
ordered:
The spring loaded adapter style sensors and DIN style sensors must be
installed in a thermowell to maintain Ex tb protection.
Process Temperature
Range at Sensor
Connection (°C)
-60 °C to +80 °C-60 °C to +80 °CT130 °C
(1) Sensor Connection is where the sensor threads into the transmitter or junction
box housing.
(1)
5.7International
5.7.1E7 IECEx Flameproof
Ambient Temperature
Range (°C)
Maximum surface
temperature “T”
Certificate:
Standards:
Markings:
IECEx DEK 19.0041X
IEC 60079-0: 2017, IEC 60079-1: 2014
Ex db IIC T6…T1 Gb, T6(–60 °C ≤ Ta ≤ +70 °C), T5…T1(–60 °C ≤
Ta ≤ +80 °C)
See Table 5-1 for process temperatures.
Special Conditions for Safe Use (X):
1. Flameproof joints are not intended for repair.
2. Non-Standard Paint options may cause risk from electrostatic
discharge. Avoid installations that cause electrostatic build-up on
painted surfaces, and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
Quick Start Guide29
Page 30
Quick Start GuideMay 2022
Additional Specific Conditions of Use (X) when “XA” designation is
ordered:
Guard DIN Style sensors against impacts greater than 4J.
Process temperature
range at sensor
connection
-60 °C to +70 °C-60 °C to +70 °CT6
-60 °C to +80 °C-60 °C to +80 °CT5...T1
(1) Sensor Connection is where the sensor threads into the transmitter or junction
(1)
box housing.
(°C)
5.7.2I7 IECEx Intrinsic Safety
Certificate:
Standards:
Markings:
See Table 5-5 for Entity Parameters and Temperature Classifications.
Special Conditions for Safe Use (X):
1. The equipment must be installed in an enclosure which affords it a
[Headmount HART®]: IECEx BAS 12.0069X
[Headmount Fieldbus/PROFIBUS®, Railmount HART]: IECEx
BAS 07.0053X
IEC 60079-0: 2017, IEC 60079-11: 2011
Ex ia IIC T6…T4 Ga
degree of protection of at least IP20 in accordance with the
requirements of IEC 60529. Non-metallic enclosures must have a
surface resistance of less than 1G Ω; light alloy or zirconium
enclosures must be protected from impact and friction when
installed in a Zone 0 environment.
Ambient temperature
range (°C)
Temperature class
2. When fitted with the Transient Protector Assembly, the equipment is
not capable of withstanding the 500 V test as defined in Clause
6.3.13 of IEC 60079-11:2011. This must be taken into account during
installation.
5.7.3N7 IECEx Type n – with enclosure
Certificate:
Standards:
Markings:
30Rosemount 644
IECEx BAS 07.0055
IEC 60079-0: 2011, IEC 60079-15: 2010
Ex nA IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C)
Page 31
May 2022Quick Start Guide
5.7.4NG IECEx Type n – without enclosure
Certificate:
Standards:
Markings:
Special Conditions for Safe Use (X):
1. The Rosemount 644 Temperature Transmitter must be installed in a
suitably certified enclosure such that it is afforded a degree of
protection of at least IP54 in accordance with IEC 60529 and IEC
60079-15.
2. When fitted with the Transient Protector Assembly, the equipment is
not capable of withstanding the 500 V test. This must be taken into
account during installation.
5.7.5NK IECEx Dust
Certificate:
Standards:
Markings:
[Headmount Fieldbus/PROFIBUS®, Railmount HART®]: IECEx
BAS 13.0053X
[Headmount HART]: IECEx BAS 12.0070U
IEC 60079-0: 2017, IEC 60079-15: 2010
[Headmount Fieldbus/PROFIBUS, Railmount HART]: Ex nA IIC
T5 Gc (–40 °C ≤ Ta ≤ +70 °C)
[Headmount HART]: Ex nA IIC T6…T5 Gc; T6(–60 °C ≤ Ta ≤ +40
°C); T5(–60 °C ≤ Ta ≤ +85 °C)
IECEx DEK 19.0041X
IEC 60079-0: 2017, IEC 60079-31: 2013
Ex tb IIIC T130 °C Db, (–60 °C ≤ Ta ≤ +80 °C)
Specific Condition of Use (X):
Non-Standard Paint options may cause risk from electrostatic discharge.
Avoid installations that cause electrostatic build-up on painted surfaces, and
only clean the painted surfaces with a damp cloth. If paint is ordered through
a special option code, contact the manufacturer for more information.
Additional Specific Conditions of Use (X) when “XA” designation is
ordered:
The spring loaded adapter style sensors and DIN style sensors must be
installed in a thermowell to maintain Ex tb protection.
Quick Start Guide31
Page 32
Quick Start GuideMay 2022
Process temperature
range at sensor
connection
-60 °C to +80 °C-60 °C to +80 °CT130 °C
(1) Sensor Connection is where the sensor threads into the transmitter or junction
(1)
box housing.
(°C)
Ambient temperature
range (°C)
5.8Brazil
5.8.1E2 Brazil Flameproof and Dust
Certificate:
Standards:
Markings:
Special Conditions for Safe Use (X):
1. See product description for ambient temperature limits and process
2. The non-metallic label may store an electrostatic charge and become
[Fieldbus]: Ex ia IIC T* Ga (–60 °C ≤ Ta ≤ +** °C) [HART]: Ex ia
IIC T* Ga (–60 °C ≤ Ta ≤ +** °C)
degree of protection of at least IP20.
Page 33
May 2022Quick Start Guide
2. Non-metallic enclosures must have a surface resistance of less than 1
GΩ; light alloy or zirconium enclosures must be protected from
impact and friction when installed in a zone 0 environment.
3. When fitted with the Transient Protector Assembly, the equipment is
not capable of withstanding the 500 V test as defined on ABNT NBR
IEC 60079-11. This must be taken into account during installation.
5.10.1 EM Technical Regulation Customs Union TR CU 012/2011 (EAC)
Flameproof
Standards:
Markings:
See Table 5-1 for process temperatures.
Special Conditions for Safe Use (X):
1. See certificate TR CU 012/2011 for ambient temperature range.
2. Guard the LCD display cover against impact energies greater than 4
3. Flameproof joints are not intended for repair.
4. Non-standard paint options may cause risk from electrostatic
Quick Start Guide37
GOST 31610.0-2014, GOST IEC 60079-1-2011
1Ex d IIC T6…T1 Gb X, T6 (-55 °C ≤ Ta ≤ +40 °C), T5…T1(-55 °C
≤ Ta≤ +60 °C);
joules.
discharge. Avoid installations that cause electrostatic build-up on
painted surfaces, and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special code, contact the
manufacturer for more information.
Page 38
Quick Start GuideMay 2022
5.10.2 IM Technical Regulation Customs Union TR CU 012/2011 (EAC)
Intrinsic Safety
Standards:
Markings:
GOST 31610.0-2014, GOST 31610.11-2014
[HART®]: 0Ex ia IIC T6…T4 Ga X; [Fieldbus, FISCO, PROFIBUS
PA]: 0Ex ia IIC T4 Ga X
See Table 5-5 for Entity Parameters and Temperature Classifications.
Special Conditions for Safe Use (X):
1. The equipment must be installed in an enclosure which affords it a
degree of protection of at least IP20 in accordance with the
requirements of GOST 14254-96. Non-metallic enclosures must have
a surface resistance of less than 1 Ω; light alloy or zirconium
enclosures must be protected from impact and friction when
installed in a Zone 0 environment.
2. When fitted with the Transient Protector Assembly, the equipment is
not capable of withstanding the 500 V test as defined in GOST
31610.11-2014. This must be taken into account during installation.
3. See certificate TR CU 012/2011 for ambient temperature range.
5.10.3 KM Technical Regulation Customs Union TR CU 012/2011 (EAC)
Flameproof, Intrinsic Safety, and Dust Ignition-proof
Standards:
Markings:
GOST 31610.0-2014, GOST IEC 60079-1-2011, GOST
31610.11-2014, GOST R IEC 60079-31-2010
Ex tb IIIC T130 °C Db X (-55 °C ≤ Ta ≤ +70 °C); IP66
®
See Table 5-1 for process temperatures.
See EM for Flameproof Markings and see IM for Intrinsic Safety Markings.
Special Conditions for Safe Use (X):
1. The non-metallic label may store an electrostatic charge and become
a source of ignition in Group III environments. Label must be cleaned
by the damp cloth with antistatic to avoid store an electrostatic
discharge.
2. Guard the LCD display cover against impact energies greater than 4
joules.
See EM for Flameproof Specific Conditions of Use and see IM for Intrinsic
Safety Specific Conditions of Use.
38Rosemount 644
Page 39
May 2022Quick Start Guide
5.11Japan
5.11.1 E4 Japan Flameproof
Certificate:
Markings:
Special Conditions for Safe Use:
1. Flameproof joints are not intended for repair.
2. Models with LCD display cover shall have the display cover protected
3. For Models 65 and 185, the user shall ensure the external surface
4. Non-standard paint options may cause risk from electrostatic
5. The wiring used shall be suitable for temperatures over 80 °C.
CML 17JPN1316X
Ex db IIC T6...T1 Gb; T6 (-50 °C < Ta < +40 °C); T5…T1(-50 °C ≤
Ta ≤ 60 °C)
from impact energies greater than 4 joules.
temperature of the equipment and the neck of the DIN Style probe
does not exceed 130 °C.
discharge.
5.11.2 I4 Japan Intrinsic Safety
Certificate:
Standards:
Markings:
Special Conditions for Safe Use (X):
1. The apparatus must be installed in an enclosure which affords it a
degree of protection of at least IP20.
CML 18JPN2118X
JNIOSH-TR-46-1, JNIOSH-TR-46-6
[Fieldbus] Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +60 °C);
2. Non-metallic enclosures must have a surface resistance of less than 1
G Ω; light alloy or zirconium enclosures must be protected from
impact and friction when installed in a zone 0 environment.
5.12
Korea
5.12.1 EP Korea Flameproof and Dust-Ignitionproof
Certificate:
Markings:
Quick Start Guide39
13-KB4BO-0559X
Ex db IIC T6…T1 Gb; Ex tb IIIC T130 °C Db
Page 40
Quick Start GuideMay 2022
Special Condition for Safe Use (X):
See certificate for special conditions for safe use.
5.12.2 IP Korea Intrnsic Safety
Certificate:
Markings:
Special Condition for Safe Use (X):
See certificate for special conditions for safe use.
13-KB4BO-0531X
Ex ia IIC T6…T4 Ga
5.13Combinations
K1
K2
K5
K7
KA
KB
KC
KD
KP
Combination of E1, I1, N1, and ND
Combination of E2 and I2
Combination of E5 and I5
Combination of E7, I7, N7, and NK
Combination of K6, E1, and I1
Combination of K5 and K6
Combination of I5 and I6
Combination of E5, I5, K6, E1, and I1
Combination of EP and IP
5.14Additional certifications
5.14.1 SBS American Bureau of Shipping (ABS) Type Approval
Certificate:
21-2157984-PDA
5.14.2 SBV Bureau Veritas (BV) Type Approval
Certificate:
Requirements:
Application:
26325 BV
Bureau Veritas Rules for the Classification of Steel Ships
Class notations: AUT-UMS, AUT-CCS, AUT-PORT and AUTIMS
For use in environmental categories ENV1, ENV2, ENV3, and
ENV5.
5.15Specification tables
Table 5-1: Process Temperature Limits
Sensor only
(no
transmitter
installed)
Any
extension
length
Table 5-2: Process Temperature Limits without LCD Display Cover
Transmitter Process temperature [°C]
No extension 131 °F
3-in.
extension
6-in.
extension
9-in.
extension
Process temperature [°C]
GasDust
T6T5T4T3T2T1T130 °C
85 °C
(185 °F )
GasDust
T6T5T4T3T2T1T130 °C
(55 °C)
131 °F
(55 °C)
140 °F
(60 °C)
149 °F
(65 °C)
100 °C
(212 °F)
158 °F
(70 °C)
158 °F
(70 °C)
158 °F
(70 °C)
167 °F
(75 °C)
135 °C
(275 °F)
212 °F
(100 °C)
230 °F
(110 °C)
248 °F
(120 °C)
266 °F
(130 °C)
200 °C
(392 °F)
338 °F
(170 °C)
374 °F
(190 °C)
392 °F
(200 °C)
392 °F
(200 °C)
300 °C
(572 °F)
536 °F
(280 °C)
572 °F
(300 °C)
572 °F
(300 °C)
572 °F
(300 °C)
450 °C
(842 °F)
824 °F
(440 °C)
842 °F
(450 °C)
842 °F
(450 °C)
842 °F
(450 °C)
130 °C
(266 °F)
212 °F
(100 °C)
230 °F
(110 °C)
230 °F
(110 °C)
248 °F
(120 °C)
Adhering to the process temperature limitation of Table 5-3 will ensure that
the service temperature limitations of the LCD cover are not exceeded.
Process temperatures may exceed the limits defined in Table 5-3 if the
Temperature of the LCD cover is verified to not exceed the service
temperatures in Table 5-4 and the process temperatures do not exceed the
values specified in Table 5-2.
Quick Start Guide41
Page 42
Quick Start GuideMay 2022
Table 5-3: Process Temperature Limits with LCD Display Cover
Emerson Terms and Conditions of Sale are
available upon request. The Emerson logo
is a trademark and service mark of
Emerson Electric Co. Rosemount is a mark
of one of the Emerson family of
companies. All other marks are the
property of their respective owners.
Emerson.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.