Read this manual before working with the product. For personal and system safety, and for optimum product performance,
ensure you thoroughly understand the contents before installing, using, or maintaining this product.
For technical assistance, contacts are listed below:
Customer Central
Technical support, quoting, and order-related questions.
• United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)
• Asia Pacific- 65 777 8211
North American Response Center
Equipment service needs.
• 1-800-654-7768 (24 hours a day — includes Canada)
• Outside of these areas, contact your local Emerson representative.
WARNING
Failure to follow safe installation and servicing guidelines could result in death or serious injury.
• Ensure the transmitter is installed by qualified personnel and in accordance with applicable code of practice.
• Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment.
• For installations in hazardous locations, the transmitter must be installed according to the Rosemount 5408 and 5408:SIS
Product Certifications document and System Control Drawing (D7000002-885).
Explosions could result in death or serious injury.
• Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
• Before connecting a handheld communicator in an explosive atmosphere, ensure the instruments are installed in accordance
with intrinsically safe or non-incendive field wiring practices.
• In Explosion-proof/Flameproof and Non-Incendive/Type n installations, do not remove the transmitter covers when power is
applied to the unit.
• Both transmitter covers must be fully engaged to meet Explosion-proof/Flameproof requirements.
Electrical shock could cause death or serious injury.
• In Explosion-proof/Flameproof and Non-Incendive/Type n installations, avoid contact with the leads and terminals. High
voltage that may be present on leads can cause electrical shock.
• Ensure the mains power to the transmitter is off and the lines to any other external power source are disconnected or not
powered while wiring the transmitter.
Process leaks could result in death or serious injury.
• Ensure that the transmitter is handled carefully. If the process seal is damaged, gas might escape from the tank.
Any substitution of non-recognized parts may jeopardize safety. Repair (e.g. substitution of components) may also jeopardize
safety and is not allowed under any circumstances.
• Unauthorized changes to the product are strictly prohibited as they may unintentionally and unpredictably alter performance
and jeopardize safety. Unauthorized changes that interfere with the integrity of the welds or flanges, such as making
additional perforations, compromise product integrity and safety. Equipment ratings and certifications are no longer valid on
any products that have been damaged or modified without the prior written permission of Emerson. Any continued use of
product that has been damaged or modified without the written authorization is at the customer’s sole risk and expense.
2
Page 3
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could
be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access
by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
CAUTION
Hot surfaces
The flange and process seal may be hot at high process temperatures. Allow to cool before servicing.
CAUTION
The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified
products in applications that require nuclear-qualified hardware or products may cause inaccurate readings. For information on
Rosemount nuclear-qualified products, contact your local Emerson Sales Representative.
3
Page 4
4
Page 5
Safety ManualContents
00809-0400-4408September 2021
Contents
Chapter 1Before you begin........................................................................................................7
1.1 About this document...................................................................................................................7
1.2 About this product.......................................................................................................................7
1.3 Related documents......................................................................................................................8
Chapter 2Installation and commissioning..................................................................................9
2.1 Safety Instrumented System (SIS) certification............................................................................ 9
Appendix ATerms and definitions...............................................................................................31
Rosemount 5408:SIS Level Transmitter5
Page 6
ContentsSafety Manual
September 202100809-0400-4408
6Safety Manual
Page 7
Safety ManualBefore you begin
00809-0400-4408September 2021
1Before you begin
1.1About this document
This document provides information about how to install, commission, and proof test a
Rosemount 5408:SIS Level Transmitter to comply with Safety Instrumented Systems (SIS)
requirements.
Note
The following conditions must apply:
• The transmitter has been installed correctly and completely according to the
instructions in the Reference Manual and Quick Start Guide.
• The installation complies with all applicable safety requirements.
• The operator is trained in local and corporate safety standards.
1.2About this product
The Rosemount 5408:SIS is a two-wire transmitter for continuous level measurements
over a broad range of liquids and slurries. The measurement principle is fast-sweep
Frequency Modulated Continuous Wave (FMCW).
The Rosemount 5408:SIS can be used as the level sensor in a Basic Process Control System
(BPCS) or as a safety device in a safety instrumented system.
1.2.1Application examples
• Overfill prevention
• Dry-run prevention
• Level range monitoring
Rosemount 5408:SIS Level Transmitter7
Page 8
Before you beginSafety Manual
September 202100809-0400-4408
1.3Related documents
You can find all product documentation at Emerson.com/Rosemount.
For more information, see the following documents:
00825-0500-4408Quick Start Guide: Process Seal Antenna
00825-0200-4408Product Certifications
8Safety Manual
Page 9
A
A
A
B
B
B
C
C
C
D
E
F
Safety ManualInstallation and commissioning
00809-0400-4408September 2021
2Installation and commissioning
2.1Safety Instrumented System (SIS) certification
For safety instrumented systems usage, the 4-20 mA analog output is used as the primary
safety variable. It is configured to activate the alarm function if an error occurs. If a
measured value goes beyond the measurement range, the transmitter enters saturation
mode.
The measurement signal used by the logic solver must be the analog 4-20 mA signal
proportional to the level or distance (ullage). The HART® protocol can only be used for
setup, calibration, and diagnostic purposes, not for safety critical operation.
The Rosemount™ 5408:SIS Level Transmitter is IEC 61508 certified to:
• Low and high demand: Type B element
• SIL 2 for random integrity @ HFT=0
• SIL 3 for random integrity @ HFT=1
• SIL 3 for systematic capability
Figure 2-1: Safety Instrumented Function (SIF) Configuration Examples
A. Rosemount 5408:SIS Level Transmitter (sensor)
B. Logic-solver
C.
Actuator
D. Single use 1oo1 (1-out-of-1) for SIL2 (SIL 2@ HFT=0)
E. Redundant use 1oo2 for SIL3 (SIL3@ HFT=1)
F. Redundant use 2oo3 for SIL3 (SIL3@ HFT=1)
Rosemount 5408:SIS Level Transmitter9
Page 10
!
MODEL 540 8
FM16US0010X
E
A
B
C
D
SIL 2
Installation and commissioningSafety Manual
September 202100809-0400-4408
2.2Safety certified identification
All Rosemount 5408:SIS Level Transmitters must be identified as safety certified before
installing into SIS systems.
Procedure
1. Verify the transmitter model code starts with “5408F”.
2.
Verify the software (SW) is 1.A3 or later.
Note
The Smart Echo Level Test requires software version 1.C0 or later.
Figure 2-2: Identification
A. Model code
B. Serial number
SW version
C.
D. Yellow stripe for locating device from distance
E. Yellow tag for locating device from distance
10Safety Manual
Page 11
Safety ManualInstallation and commissioning
00809-0400-4408
September 2021
2.3Installation
Refer to the Rosemount 5408 and Rosemount 5408:SIS Reference Manual for installation
instructions. No special installation is required in addition to the standard installation
practices outlined in this manual.
The loop should be designed so the terminal voltage is within the limits specified in section
Power supply.
Check that environmental conditions do not exceed the ratings provided in the
Rosemount 5408 and Rosemount 5408:SIS Product Data Sheet.
Note
The Rosemount 5408:SIS Level Transmitter is not safety-rated during maintenance work,
configuration changes, multidrop, loop test, proof test, or other activity that affects the
safety function. Alternative means should be used to ensure process safety during such
activities.
2.3.1Power supply
The transmitter operates on 12-42.4 Vdc (12-30 Vdc in Intrinsically Safe installations) at
the transmitter terminals.
2.4Configuration
Use a HART-compliant master, such as Rosemount Radar Master Plus, AMS Device
Manager, or a handheld communicator, to communicate with and verify configuration of
the Rosemount 5408:SIS.
2.4.1Make sure you are connected to the correct transmitter
Verify that the serial number on the label matches the one in your configuration tool.
Procedure
1. Write down the serial number from the transmitter label.
2.
Verify the same serial number in your configuration tool.
Follow the Guided Setup wizard for transmitter configuration. When configuring
parameters not included in the Guided Setup, it may be necessary to do additional
verification.
Rosemount 5408:SIS Level Transmitter11
Page 12
Installation and commissioningSafety Manual
September 2021
00809-0400-4408
Configure using Rosemount Radar Master Plus
The options available in the Guided Setup wizard include all items required for basic
operation.
2. Under Safety Instrumented Systems, select Change Operational Mode and follow the
on-screen instructions.
2.4.4Safety mode
When the operational mode is set to Safety (SIS), then the Safety Mode must be enabled
for the transmitter to become operational. When Safety Mode is enabled, the transmitter
is write protected (with or without a password) to prevent unauthorized changes.
Enable or disable safety mode using Rosemount Radar
Master Plus
Procedure
Under Configure, select Device Setup→Security.
1.
2. Under Safety Mode, select Change and follow the on-screen instructions.
Enable or disable safety mode using AMS Device Manager
and handheld communicator
2. Under Safety Instrumented Systems, select Change Safety Mode and follow the onscreen instructions.
2.4.5Alarm and saturation levels
DCS or safety logic solver should be configured to handle both High alarm and Low alarm.
In addition, the transmitter must be configured for High or Low alarm.
Note
Note that during startup, the Rosemount 5408:SIS always outputs Low alarm current even
if the transmitter is configured for High alarm mode.
Analog signal on alarm
The transmitter automatically and continuously performs self-diagnostic routines. If a
failure or a measurement error is detected, the analog signal will be driven offscale to alert
the user. High or low failure mode is user-configurable.
Table 2-1: Signal on Alarm
StandardHighLow
Rosemount standard≥ 21.75 mA (default)≤ 3.75 mA (option code C8)
NAMUR NE43≥ 22.50 mA (option code C4)≤ 3.6 mA (option code C5)
Analog saturation levels
The transmitter will drive the output to high or low saturation values if measurement goes
outside the 4-20 mA range values.
Table 2-2: Saturation Levels
StandardHighLow
Rosemount standard (default and option code C8)20.8 mA3.9 mA
NAMUR NE43 (option code C4 and C5)20.5 mA3.8 mA
2.5Site acceptance
After installation and/or configuration, proper operation of the transmitter (including
verification of all configuration changes) must be verified. A site acceptance test is
therefore recommended. The proof tests can be used for this.
14Safety Manual
Page 15
Safety ManualProof tests
00809-0400-4408September 2021
3Proof tests
3.1Overview
The Rosemount 5408:SIS must be tested at regular intervals to reveal faults which are
undetected by automatic diagnostics. It is the user's responsibility to choose the type of
testing and the frequency of these tests.
Results from periodic proof tests shall be recorded and periodically reviewed. If an error is
found in the safety functionality, the device shall be put out of operation and the process
shall be kept in a safe state by other measures.
Note
For a valid result, always perform the proof test on the product that will be stored in the
tank while the device is in operation.
3.1.1Suggested proof tests
The following proof tests are suggested:
• (A) 1-point level and analog output verification
• (B) 2-point level and analog output verification
• (C) Analog output verification
• (D) Level deviation monitoring
• (E) Smart echo level test
Table 3-1 can be used as a guidance for selecting the appropriate proof test.
Table 3-1: Suggested Proof Tests
Proof
test #
AComprehensive74%21 FITYesYesYesYes
BComprehensive84%13 FITYesYesYesYes
CPartial35%51 FITYesNoNoYes
DPartial62%30 FITNoYesNoYes
EPartial40%47 FITYesPartiallyNoYes
(1) With the assumption that the BPCS level sensor is used as independent measurement.
TypeProof test
coverage
(%) of DU
Remaining
dangerous,
undetected
failures
Test coverageCan be
Output
circuitry
Measurement
electronics
Antenna
performed
remotely
(1)
(1)
3.1.2Proof test interval
The time intervals for proof testing are defined by the SIL verification calculation (subject
to the PFD
Rosemount 5408:SIS Level Transmitter15
). The SIL verification calculation is an analytical method to calculate an
AVG
Page 16
Proof testsSafety Manual
September 202100809-0400-4408
appropriate proof test interval for the specific safety function based on equipment’s
reliability and required risk reduction for the specific SIF.
The proof tests must be performed more frequently than or as frequently as specified in
the SIL verification calculation, in order to maintain the required safety integrity of the
overall SIF.
3.1.3Tools required
• HART host/communicator or Rosemount Radar Master Plus
3.2.1Perform 1-point level and analog output verification
using Rosemount Radar Master Plus
Prerequisites
WARNING
During the proof test, the transmitter will not output measurement values corresponding
to the product surface level. Ensure systems and people relying on measurement values
from the transmitter are made aware of the changed conditions. Failure to do so could
result in death, serious injury and/or property damage.
Procedure
1. Prior to the test, ensure there are no alarms or warnings present in the transmitter.
a)
Under Service Tools, select Alerts.
2. Bypass the process safety function and take appropriate action to avoid a false trip.
3. Simulate 4.00 mA output and verify loop current.
a) Under Service Tools, select Simulate.
b) Select Loop Test.
c) Select 4 mA and then select Start.
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
Note
The inaccuracy of safety logic solver or current meter needs to be
considered.
16Safety Manual
Page 17
Safety ManualProof tests
00809-0400-4408
September 2021
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
f) Select
Stop to end loop test.
4. Simulate 20.00 mA output and verify loop current.
a) Under Service Tools, select Simulate.
b) Select Loop Test.
c) Select 20 mA and then select Start.
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Note
The inaccuracy of safety logic solver or current meter needs to be
considered.
f) Select Stop to end loop test.
5. Perform a one-point level measurement verification of the transmitter in the
measuring range. Compare with independent measurement (e.g. the BPCS level
sensor).
a)
Under Overview, select All Variables.
b) Verify the current level or distance reading with an independent
measurement is within the safety deviation of 2%.
Note
The inaccuracy of the independent measurement needs to be considered.
6. Remove the bypass and otherwise restore normal operation.
Related information
Use the TEST terminal
Rosemount 5408:SIS Level Transmitter17
Page 18
Proof testsSafety Manual
September 202100809-0400-4408
3.2.2Perform 1-point level and analog output verification
using AMS Device Manager and handheld
communicator
Prerequisites
WARNING
During the proof test, the transmitter will not output measurement values corresponding
to the product surface level. Ensure systems and people relying on measurement values
from the transmitter are made aware of the changed conditions. Failure to do so could
result in death, serious injury and/or property damage.
Procedure
1. Prior to the test, ensure there are no alarms or warnings present in the transmitter.
a)
Select Service Tools→Alerts.
2. Bypass the process safety function and take appropriate action to avoid a false trip.
3. Simulate 4.00 mA output and verify loop current.
a) Select Service Tools→Simulate.
b) Under Analog Out, select Loop test.
c) Select 4mA and then select Next (Enter on Field Communicator).
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Note
The inaccuracy of safety logic solver or current meter needs to be
considered.
f) To end loop test, select Cancel (ABORT on handheld communicator).
4. Simulate 20.00 mA output and verify loop current.
a)
Select Service Tools→Simulate.
b) Under Analog Out, select Loop test.
c) Select 20mA and then select Next (Enter on Field Communicator).
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Note
The inaccuracy of safety logic solver or current meter needs to be
considered.
18Safety Manual
Page 19
Safety ManualProof tests
00809-0400-4408September 2021
f) To end loop test, select Cancel (ABORT on handheld communicator).
5. Perform a one-point level measurement verification of the transmitter in the
measuring range. Compare with independent measurement (e.g. the BPCS level
sensor).
a)
Select Service Tools→Variables→Process.
b) Verify the current level or distance reading with an independent
measurement is within the safety deviation of 2%.
Note
The inaccuracy of the independent measurement needs to be considered.
6. Remove the bypass and otherwise restore normal operation.
Related information
Use the TEST terminal
3.32-point level and analog output verification
3.3.1Perform 2-point level and analog output verification
using Rosemount Radar Master Plus
Prerequisites
WARNING
During the proof test, the transmitter will not output measurement values corresponding
to the product surface level. Ensure systems and people relying on measurement values
from the transmitter are made aware of the changed conditions. Failure to do so could
result in death, serious injury and/or property damage.
Procedure
1. Prior to the test, ensure there are no alarms or warnings present in the transmitter.
Under Service Tools, select Alerts.
a)
2. Bypass the process safety function and take appropriate action to avoid a false trip.
Rosemount 5408:SIS Level Transmitter19
Page 20
Proof testsSafety Manual
September 202100809-0400-4408
3. Simulate 4.00 mA output and verify loop current.
a) Under
Service Tools, select Simulate.
b) Select Loop Test.
c) Select 4 mA and then select Start.
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Note
The inaccuracy of safety logic solver or current meter needs to be
considered.
f) Select Stop to end loop test.
4. Simulate 20.00 mA output and verify loop current.
a)
Under Service Tools, select Simulate.
b) Select Loop Test.
c) Select 20 mA and then select Start.
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Note
The inaccuracy of safety logic solver or current meter needs to be
considered.
f) Select Stop to end loop test.
5. Perform a two-point level measurement verification of the transmitter in the
measuring range. Compare with independent measurement (e.g. the BPCS level
sensor).
a)
Under Overview, select All Variables.
b) Verify the current level or distance reading with an independent
measurement is within the safety deviation of 2%.
Note
The inaccuracy of the independent measurement needs to be considered.
c) Move the surface in the tank at least 10% of the full measuring span (level
0-100%).
d) Repeat
5.a and 5.b for the second point.
6. Remove the bypass and otherwise restore normal operation.
20Safety Manual
Page 21
Safety ManualProof tests
00809-0400-4408
Related information
Use the TEST terminal
September 2021
3.3.2Perform 2-point level and analog output verification
using AMS Device Manager and handheld
communicator
Prerequisites
WARNING
During the proof test, the transmitter will not output measurement values corresponding
to the product surface level. Ensure systems and people relying on measurement values
from the transmitter are made aware of the changed conditions. Failure to do so could
result in death, serious injury and/or property damage.
Procedure
1. Prior to the test, ensure there are no alarms or warnings present in the transmitter.
a)
Select Service Tools→Alerts.
2. Bypass the process safety function and take appropriate action to avoid a false trip.
3. Simulate 4.00 mA output and verify loop current.
a) Select Service Tools→Simulate.
b) Under Analog Out, select Loop test.
c) Select 4mA and then select Next (Enter on Field Communicator).
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Note
The inaccuracy of safety logic solver or current meter needs to be
considered.
f) To end loop test, select Cancel (ABORT on handheld communicator).
4. Simulate 20.00 mA output and verify loop current.
a)
Select Service Tools→Simulate.
b) Under Analog Out, select Loop test.
c) Select 20mA and then select Next (Enter on Field Communicator).
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
Rosemount 5408:SIS Level Transmitter21
Page 22
Proof testsSafety Manual
September 202100809-0400-4408
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Note
The inaccuracy of safety logic solver or current meter needs to be
considered.
f) To end loop test, select Cancel (ABORT on handheld communicator).
5. Perform a two-point level measurement verification of the transmitter in the
measuring range. Compare with independent measurement (e.g. the BPCS level
sensor).
a)
Select Service Tools→Variables→Process.
b) Verify the current level or distance reading with an independent
measurement is within the safety deviation of 2%.
Note
The inaccuracy of the independent measurement needs to be considered.
c) Move the surface in the tank at least 10% of the full measuring span (level
0-100%).
d) Repeat
5.a and 5.b for the second point.
6. Remove the bypass and otherwise restore normal operation.
Related information
Use the TEST terminal
22Safety Manual
Page 23
Safety ManualProof tests
00809-0400-4408September 2021
3.4Analog output verification
Compare HART Primary Variable digital value with analog output reading. Verify that the
deviation is within the pass limit.
Procedure
1. Obtain the loop current as a digital value, do one of the following:
• In Rosemount Radar Master Plus, under
the current analog output value.
• Read HART command 2 or 3 via the host system.
Command 2: Analog output current and Percent of range
Command 3: Device variables (PV, SV, TV, and QV) and Analog output current
2. Obtain the loop current as an analog value (e.g. by using the safety logic solver or
using the TEST terminal).
3. Compare the current values.
4. Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Overview, select All Variables and read
Note
The inaccuracy of safety logic solver needs to be considered.
Related information
Use the TEST terminal
3.5Level deviation monitoring
Use the analog output to obtain level (or distance) reading and compare with an
independent level measurement. Verify that the deviation is within the pass limit.
Procedure
1. Obtain the level (or distance) measurement value derived from the analog output
(e.g. by checking measurement value in safety logic solver).
Obtain the level (or distance) measurement value from an independent level
2.
measurement (e.g. the BPCS level sensor).
3. Compare the measurements and verify that the deviation is within the safety
deviation of 2%.
3.6Smart echo level test
The function allows you to test the behavior of the transmitter in a real tank environment
without raising the level. During the test, a virtual surface echo is inserted into the radar
signal, and the transmitter will output a level corresponding to the echo position.
Rosemount 5408:SIS Level Transmitter23
Page 24
A
B
C
Proof testsSafety Manual
September 2021
00809-0400-4408
3.6.1Configure the smart echo level
Prerequisites
Disable the Safety Mode.
Procedure
1. In Rosemount Radar Master Plus, under
2. Select Configure Smart Echo.
3. Set the Smart Echo Level to a value above the Upper Range Value.
Note
Ensure the product level is at least 1 ft. (30 cm) below the Smart Echo Level.
Figure 3-1: Smart Echo Level
A. Smart Echo Level
B. Upper Range Value (100%/20 mA)
Minimum 1 ft. (30 cm)
C.
Service Tools, select Proof Test.
4. Select Save.
Postrequisites
Enable the Safety Mode.
Related information
Safety mode
3.6.2Perform a smart echo level test
24Safety Manual
Simulate a surface echo above the Upper Range Value (i.e. analog out in high saturation)
and verify loop current.
Prerequisites
This test is available for transmitters with:
Page 25
Safety ManualProof tests
00809-0400-4408September 2021
• Device software revision 1.C0 or later
• Option code ET
Prior to and during the test, ensure that:
• The product surface is calm.
• The smart echo level is not closer than 1 ft. (0.3 m) to the liquid surface.
• The tank is not being filled or emptied.
WARNING
During the proof test, the transmitter will not output measurement values corresponding
to the product surface level. Ensure systems and people relying on measurement values
from the transmitter are made aware of the changed conditions. Failure to do so could
result in death, serious injury and/or property damage.
Procedure
1. Ensure there are no alarms or warnings present in the transmitter.
a)
In Rosemount Radar Master Plus, under Service Tools, select Alerts.
2. Bypass the process safety function and take appropriate action to avoid a false trip.
3. Perform the Smart Echo Level test.
a) Under Service Tools, select Proof Test.
b) Select Smart Echo Level Test.
c) Select Start.
The analog output goes to high saturation.
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Note
The inaccuracy of safety logic solver or current meter needs to be
considered.
f) Select Stop to end test mode.
4. Remove the bypass and otherwise restore normal operation.
Related information
Analog saturation levels
Use the TEST terminal
Rosemount 5408:SIS Level Transmitter25
Page 26
H2.5 mm
Proof testsSafety Manual
September 202100809-0400-4408
3.7Use the TEST terminal
Prerequisites
WARNING
Verify that the installation is consistent with the appropriate hazardous locations
certifications when the instrument used for loop current measurement is connected.
For Explosion-proof/Flameproof and Non-Incendive/Type n installations, the cover must
not be opened in an explosive atmosphere.
Note
Disconnect the blue plug only during the loop current measurement procedure. To meet
the stated EMC specification during normal operation, the blue plug must be plugged in.
Procedure
1. Turn the jam screw clockwise until it is completely threaded into the housing.
2. Remove the cover.
3. Remove the blue plug from the TEST terminal.
26Safety Manual
Page 27
H2.5 mm
Safety ManualProof tests
00809-0400-4408September 2021
4. Connect the ampere meter leads to the terminals labeled “+” and “TEST”.
5. Measure the loop current.
6. Attach the blue plug to the TEST terminal.
7. Attach and tighten the cover.
a) Verify the cover jam screw is completely threaded into the housing.
b) Attach and tighten the cover.
Make sure the cover is fully engaged. There should be no gap between the
cover and the housing.
Rosemount 5408:SIS Level Transmitter27
Page 28
Proof testsSafety Manual
September 202100809-0400-4408
c) Turn the jam screw counterclockwise until it contacts the cover.
Required for explosion-proof/flameproof installations only.
d) Turn the jam screw an additional ½ turn counterclockwise to secure the
cover.
28Safety Manual
Page 29
Safety ManualOperating constraints
00809-0400-4408September 2021
4Operating constraints
4.1Specifications
The Rosemount 5408:SIS must be operated according to the functional and performance
specifications provided in the Rosemount 5408 and Rosemount 5408:SIS Product Data
Sheet.
4.1.1Measuring range
The maximum measuring range is 82 ft. (25 m) for the Rosemount 5408:SIS Level
Transmitter in Safety (SIS) mode.
4.1.2Failure rate data
The FMEDA report includes failure rate data, assessment details, and assumptions
regarding failure rate analysis.
4.1.3Safety deviation
±2.0% of analog output span
4.1.4Transmitter response time
• < 6 s at damping value 2 s (default)
• < 2 s at damping value 0 s (minimum)
The transmitter response time will be a function of the configured Damping value.
Rosemount Radar Master Plus has a built-in function to calculate the transmitter’s
measurement response time (requires option code EF2).
(1)
4.1.5Diagnostic test interval
< 90 min
(2)
4.1.6Turn-on time
(3)
< 40 s
(1)
(1) Step response time as per IEC 61298-2.
(2) A majority of the self-diagnostic tests are performed once every second and an action (if necessary) is taken in less than 30
seconds (default).
(3) Time from when power is applied to the transmitter until performance is within specifications.
Rosemount 5408:SIS Level Transmitter29
Page 30
Operating constraintsSafety Manual
September 202100809-0400-4408
4.1.7Useful lifetime
50 years
• based on worst case component wear-out mechanisms
• not based on wear-out of process wetted materials
4.2Product repair
The Rosemount 5408:SIS is repairable by major component replacement. All failures
detected by the device diagnostics or by the proof test must be reported. Feedback can be
submitted electronically at Go.EmersonAutomation.com/Contact-Us (Contact Us).
30Safety Manual
Page 31
Safety ManualTerms and definitions
00809-0400-4408September 2021
ATerms and definitions
λ
DU
λ
DD
λ
SU
λ
SD
Diagnostic test
interval
Element
FIT
FMEDA
HART® protocol
HFT
High demand
mode
Low demand
mode
Dangerous Undetected failure rate
Dangerous Detected failure rate
Safe Undetected failure rate
Safe Detected failure rate
The time from when a dangerous failure/condition occurs until the
device has set the safety related output in a safe state (total time
required for fault detection and fault reaction).
Term defined by IEC 61508 as “part of a subsystem comprising a
single component or any group of components that performs one or
more element safety functions”
Failure In Time per billion hours
Failure Modes, Effects and Diagnostic Analysis
Highway Addressable Remote Transducer
Hardware Fault Tolerance
The safety function is only performed on demand, in order to transfer
the EUC (Equipment Under Control) into a specified safe state, and
where the frequency of demands is greater than one per year (IEC
61508-4).
The safety function is only performed on demand, in order to transfer
the EUC into a specified safe state, and where the frequency of
demands is no greater than one per year (IEC 61508-4).
PFD
AVG
PFH
Proof test
coverage factor
Safety deviation
Rosemount 5408:SIS Level Transmitter31
Average Probability of Failure on Demand
Probability of dangerous Failure per Hour: the term "probability" is
misleading, as IEC 61508 defines a rate.
The effectiveness of a proof test is described using the coverage
factor which specifies the share of detected dangerous undetected
failures (λDU). The coverage factor is an indication of a proof test’s
effectiveness to detect dangerous undetected faults.
The maximum allowed deflection of the safety output due to a failure
within the device (expressed as a percentage of span).
Any failure causing the device output to change less than the Safety
Deviation is considered as a "No Effect" failure. All failures causing the
device output to change more than the Safety Deviation and with the
device output still within the active range (non-alarm state) are
considered dangerous failures.
Page 32
Terms and definitionsSafety Manual
September 202100809-0400-4408
Note
The Safety Deviation is independent of the normal performance
specification or any additional application specific measurement
error.
SIF
SIL
SIS
Systematic
capability
Transmitter
response time
Type B device
Useful lifetime
Safety Instrumented Function
Safety Integrity Level – a discrete level (one out of four) for specifying
the safety integrity requirements of the safety instrumented
functions to be allocated to the safety instrumented systems. SIL 4
has the highest level of safety integrity, and SIL 1 has the lowest level.
Safety Instrumented System – an instrumented system used to
implement one or more safety instrumented functions. An SIS is
composed of any combination of sensors, logic solvers, and final
elements.
A measure (expressed on a scale of SC 1 to SC 4) of the confidence
that the systematic safety integrity of an element meets the
requirements of the specified SIL, in respect of the specified element
safety function, when the element is applied in accordance with the
instructions specified in the compliant item safety manual for the
element.
The time from a step change in the process until transmitter output
reaches 90% of its final steady state value (step response time as per
IEC 61298-2).
Complex device using controllers or programmable logic, as defined
by the standard IEC 61508.
Reliability engineering term that describes the operational time
interval where the failure rate of a device is relatively constant. It is
not a term which covers product obsolescence, warranty, or other
commercial issues.
The useful lifetime is highly dependent on the element itself and its
operating conditions (IEC 61508-2).
Emerson Terms and Conditions of Sale are available upon
request. The Emerson logo is a trademark and service mark of
Emerson Electric Co. Rosemount is a mark of one of the
Emerson family of companies. All other marks are the property
of their respective owners.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.