Rosemount 5408:SIS Level Transmitter Manuals & Guides

Page 1
00809-0400-4408, Rev AB
Rosemount™ 5408:SIS Level Transmitter
Non-Contacting Radar
Safety Manual
September 2021
Page 2
Rosemount™ 5408:SIS Level Transmitter – Non-Contacting Radar
NOTICE
Read this manual before working with the product. For personal and system safety, and for optimum product performance, ensure you thoroughly understand the contents before installing, using, or maintaining this product.
For technical assistance, contacts are listed below:
Customer Central
Technical support, quoting, and order-related questions.
United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)
Asia Pacific- 65 777 8211
North American Response Center
Equipment service needs.
1-800-654-7768 (24 hours a day — includes Canada)
Outside of these areas, contact your local Emerson representative.
WARNING
Failure to follow safe installation and servicing guidelines could result in death or serious injury.
Ensure the transmitter is installed by qualified personnel and in accordance with applicable code of practice.
Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment.
For installations in hazardous locations, the transmitter must be installed according to the Rosemount 5408 and 5408:SIS
Product Certifications document and System Control Drawing (D7000002-885).
Explosions could result in death or serious injury.
Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
Before connecting a handheld communicator in an explosive atmosphere, ensure the instruments are installed in accordance
with intrinsically safe or non-incendive field wiring practices.
In Explosion-proof/Flameproof and Non-Incendive/Type n installations, do not remove the transmitter covers when power is
applied to the unit.
Both transmitter covers must be fully engaged to meet Explosion-proof/Flameproof requirements.
Electrical shock could cause death or serious injury.
In Explosion-proof/Flameproof and Non-Incendive/Type n installations, avoid contact with the leads and terminals. High
voltage that may be present on leads can cause electrical shock.
Ensure the mains power to the transmitter is off and the lines to any other external power source are disconnected or not
powered while wiring the transmitter.
Process leaks could result in death or serious injury.
Ensure that the transmitter is handled carefully. If the process seal is damaged, gas might escape from the tank.
Any substitution of non-recognized parts may jeopardize safety. Repair (e.g. substitution of components) may also jeopardize safety and is not allowed under any circumstances.
Unauthorized changes to the product are strictly prohibited as they may unintentionally and unpredictably alter performance
and jeopardize safety. Unauthorized changes that interfere with the integrity of the welds or flanges, such as making additional perforations, compromise product integrity and safety. Equipment ratings and certifications are no longer valid on any products that have been damaged or modified without the prior written permission of Emerson. Any continued use of product that has been damaged or modified without the written authorization is at the customer’s sole risk and expense.
2
Page 3
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
CAUTION
Hot surfaces
The flange and process seal may be hot at high process temperatures. Allow to cool before servicing.
CAUTION
The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings. For information on Rosemount nuclear-qualified products, contact your local Emerson Sales Representative.
3
Page 4
4
Page 5
Safety Manual Contents
00809-0400-4408 September 2021

Contents

Chapter 1 Before you begin........................................................................................................7
1.1 About this document...................................................................................................................7
1.2 About this product.......................................................................................................................7
1.3 Related documents......................................................................................................................8
Chapter 2 Installation and commissioning..................................................................................9
2.1 Safety Instrumented System (SIS) certification............................................................................ 9
2.2 Safety certified identification..................................................................................................... 10
2.3 Installation.................................................................................................................................11
2.4 Configuration............................................................................................................................ 11
2.5 Site acceptance......................................................................................................................... 14
Chapter 3 Proof tests................................................................................................................15
3.1 Overview................................................................................................................................... 15
3.2 1-point level and analog output verification...............................................................................16
3.3 2-point level and analog output verification...............................................................................19
3.4 Analog output verification......................................................................................................... 23
3.5 Level deviation monitoring........................................................................................................ 23
3.6 Smart echo level test................................................................................................................. 23
3.7 Use the TEST terminal................................................................................................................ 26
Chapter 4 Operating constraints.............................................................................................. 29
4.1 Specifications............................................................................................................................ 29
4.2 Product repair............................................................................................................................30
Appendix A Terms and definitions...............................................................................................31
Rosemount 5408:SIS Level Transmitter 5
Page 6
Contents Safety Manual
September 2021 00809-0400-4408
6 Safety Manual
Page 7
Safety Manual Before you begin
00809-0400-4408 September 2021

1 Before you begin

1.1 About this document

This document provides information about how to install, commission, and proof test a Rosemount 5408:SIS Level Transmitter to comply with Safety Instrumented Systems (SIS) requirements.
Note
The following conditions must apply:
The transmitter has been installed correctly and completely according to the
instructions in the Reference Manual and Quick Start Guide.
The installation complies with all applicable safety requirements.
The operator is trained in local and corporate safety standards.

1.2 About this product

The Rosemount 5408:SIS is a two-wire transmitter for continuous level measurements over a broad range of liquids and slurries. The measurement principle is fast-sweep Frequency Modulated Continuous Wave (FMCW).
The Rosemount 5408:SIS can be used as the level sensor in a Basic Process Control System (BPCS) or as a safety device in a safety instrumented system.

1.2.1 Application examples

Overfill prevention
Dry-run prevention
Level range monitoring
Rosemount 5408:SIS Level Transmitter 7
Page 8
Before you begin Safety Manual
September 2021 00809-0400-4408

1.3 Related documents

You can find all product documentation at Emerson.com/Rosemount.
For more information, see the following documents:
Table 1-1: Related Documentation
Document Document type
00809-0100-4408 Reference Manual
00813-0100-4408 Product Data Sheet
00825-0100-4408 Quick Start Guide: Cone Antenna
00825-0300-4408 Quick Start Guide: Parabolic Antenna
00825-0500-4408 Quick Start Guide: Process Seal Antenna
00825-0200-4408 Product Certifications
8 Safety Manual
Page 9
A
A
A
B
B
B
C
C
C
D
E
F
Safety Manual Installation and commissioning
00809-0400-4408 September 2021

2 Installation and commissioning

2.1 Safety Instrumented System (SIS) certification

For safety instrumented systems usage, the 4-20 mA analog output is used as the primary safety variable. It is configured to activate the alarm function if an error occurs. If a measured value goes beyond the measurement range, the transmitter enters saturation mode.
The measurement signal used by the logic solver must be the analog 4-20 mA signal proportional to the level or distance (ullage). The HART® protocol can only be used for setup, calibration, and diagnostic purposes, not for safety critical operation.
The Rosemount™ 5408:SIS Level Transmitter is IEC 61508 certified to:
Low and high demand: Type B element
SIL 2 for random integrity @ HFT=0
SIL 3 for random integrity @ HFT=1
SIL 3 for systematic capability
Figure 2-1: Safety Instrumented Function (SIF) Configuration Examples
A. Rosemount 5408:SIS Level Transmitter (sensor)
B. Logic-solver
C.
Actuator
D. Single use 1oo1 (1-out-of-1) for SIL2 (SIL 2@ HFT=0)
E. Redundant use 1oo2 for SIL3 (SIL3@ HFT=1)
F. Redundant use 2oo3 for SIL3 (SIL3@ HFT=1)
Rosemount 5408:SIS Level Transmitter 9
Page 10
!
MODEL 540 8
FM16US0010X
E
A
B
C
D
SIL 2
Installation and commissioning Safety Manual
September 2021 00809-0400-4408

2.2 Safety certified identification

All Rosemount 5408:SIS Level Transmitters must be identified as safety certified before installing into SIS systems.
Procedure
1. Verify the transmitter model code starts with “5408F”.
2.
Verify the software (SW) is 1.A3 or later.
Note
The Smart Echo Level Test requires software version 1.C0 or later.
Figure 2-2: Identification
A. Model code B. Serial number
SW version
C.
D. Yellow stripe for locating device from distance
E. Yellow tag for locating device from distance
10 Safety Manual
Page 11
Safety Manual Installation and commissioning
00809-0400-4408
September 2021

2.3 Installation

Refer to the Rosemount 5408 and Rosemount 5408:SIS Reference Manual for installation instructions. No special installation is required in addition to the standard installation practices outlined in this manual.
The loop should be designed so the terminal voltage is within the limits specified in section
Power supply.
Check that environmental conditions do not exceed the ratings provided in the Rosemount 5408 and Rosemount 5408:SIS Product Data Sheet.
Note
The Rosemount 5408:SIS Level Transmitter is not safety-rated during maintenance work, configuration changes, multidrop, loop test, proof test, or other activity that affects the safety function. Alternative means should be used to ensure process safety during such activities.

2.3.1 Power supply

The transmitter operates on 12-42.4 Vdc (12-30 Vdc in Intrinsically Safe installations) at the transmitter terminals.

2.4 Configuration

Use a HART-compliant master, such as Rosemount Radar Master Plus, AMS Device Manager, or a handheld communicator, to communicate with and verify configuration of the Rosemount 5408:SIS.

2.4.1 Make sure you are connected to the correct transmitter

Verify that the serial number on the label matches the one in your configuration tool.
Procedure
1. Write down the serial number from the transmitter label.
2.
Verify the same serial number in your configuration tool.
Rosemount Radar Master Plus:Under Overview, select Device Information Identification.
AMS Device Manager and handheld communicator:Select Overview Device Information Identification.

2.4.2 Configure device using Guided Setup

Follow the Guided Setup wizard for transmitter configuration. When configuring parameters not included in the Guided Setup, it may be necessary to do additional verification.
Rosemount 5408:SIS Level Transmitter 11
Page 12
Installation and commissioning Safety Manual
September 2021
00809-0400-4408
Configure using Rosemount Radar Master Plus
The options available in the Guided Setup wizard include all items required for basic operation.
Procedure
1. Start Instrument Inspector Application.
2. Under HART, double-click the device icon.
3. From the
Overview screen, select Rosemount Radar Master Plus.
4. Under Configure, select Guided Setup and follow the on-screen instructions.
Configure using AMS Device Manager
The options available in the Guided Setup wizard include all items required for basic operation.
Procedure
1.
Start AMS Device Manager and connect to the device.
Select Configure Guided Setup.
2.
3. Select Basic Setup and follow the on-screen instructions.
Configure using handheld communicator
The options available in the Guided Setup wizard include all items required for basic operation.
Procedure
1. Turn on the handheld communicator and connect to the device.
2. Select Configure Guided Setup.
3. Select Basic Setup and follow the on-screen instructions.

2.4.3 Operational mode

There are two Operational Modes to choose from for the Rosemount 5408:SIS: Control/Monitoring and Safety (SIS).
If the transmitter is used as safety device in a Safety Instrumented System, the Operational Mode must be set to Safety (SIS).
12 Safety Manual
Page 13
Safety Manual Installation and commissioning
00809-0400-4408
September 2021
Set operational mode using Rosemount Radar Master Plus
The Safety (SIS) operational mode can be activated via the Guided Setup wizard, or as follows:
Prerequisites
When entering the Safety (SIS) operational mode, the analog output will be put into alarm mode until the Safety Mode is enabled.
Procedure
1. Under
2. Under Operational Mode, select Change and follow the on-screen instructions.
Configure, select Device Setup Security.
Set operational mode using AMS Device Manager and handheld communicator
The Safety (SIS) operational mode can be activated via the Guided Setup wizard, or as follows:
Prerequisites
When entering the Safety (SIS) operational mode, the analog output will be put into alarm mode until the Safety Mode is enabled.
Procedure
1. Select Configure Manual Setup Device Setup Security.
2. Under Safety Instrumented Systems, select Change Operational Mode and follow the on-screen instructions.

2.4.4 Safety mode

When the operational mode is set to Safety (SIS), then the Safety Mode must be enabled for the transmitter to become operational. When Safety Mode is enabled, the transmitter is write protected (with or without a password) to prevent unauthorized changes.
Enable or disable safety mode using Rosemount Radar Master Plus
Procedure
Under Configure, select Device Setup Security.
1.
2. Under Safety Mode, select Change and follow the on-screen instructions.
Enable or disable safety mode using AMS Device Manager and handheld communicator
Procedure
1. Select Configure Manual Setup Device Setup Security.
Rosemount 5408:SIS Level Transmitter 13
Page 14
Installation and commissioning Safety Manual
September 2021 00809-0400-4408
2. Under Safety Instrumented Systems, select Change Safety Mode and follow the on­screen instructions.

2.4.5 Alarm and saturation levels

DCS or safety logic solver should be configured to handle both High alarm and Low alarm. In addition, the transmitter must be configured for High or Low alarm.
Note
Note that during startup, the Rosemount 5408:SIS always outputs Low alarm current even if the transmitter is configured for High alarm mode.
Analog signal on alarm
The transmitter automatically and continuously performs self-diagnostic routines. If a failure or a measurement error is detected, the analog signal will be driven offscale to alert the user. High or low failure mode is user-configurable.
Table 2-1: Signal on Alarm
Standard High Low
Rosemount standard ≥ 21.75 mA (default) ≤ 3.75 mA (option code C8)
NAMUR NE43 ≥ 22.50 mA (option code C4) ≤ 3.6 mA (option code C5)
Analog saturation levels
The transmitter will drive the output to high or low saturation values if measurement goes outside the 4-20 mA range values.
Table 2-2: Saturation Levels
Standard High Low
Rosemount standard (default and option code C8) 20.8 mA 3.9 mA
NAMUR NE43 (option code C4 and C5) 20.5 mA 3.8 mA

2.5 Site acceptance

After installation and/or configuration, proper operation of the transmitter (including verification of all configuration changes) must be verified. A site acceptance test is therefore recommended. The proof tests can be used for this.
14 Safety Manual
Page 15
Safety Manual Proof tests
00809-0400-4408 September 2021

3 Proof tests

3.1 Overview

The Rosemount 5408:SIS must be tested at regular intervals to reveal faults which are undetected by automatic diagnostics. It is the user's responsibility to choose the type of testing and the frequency of these tests.
Results from periodic proof tests shall be recorded and periodically reviewed. If an error is found in the safety functionality, the device shall be put out of operation and the process shall be kept in a safe state by other measures.
Note
For a valid result, always perform the proof test on the product that will be stored in the tank while the device is in operation.

3.1.1 Suggested proof tests

The following proof tests are suggested:
(A) 1-point level and analog output verification
(B) 2-point level and analog output verification
(C) Analog output verification
(D) Level deviation monitoring
(E) Smart echo level test
Table 3-1 can be used as a guidance for selecting the appropriate proof test.
Table 3-1: Suggested Proof Tests
Proof test #
A Comprehensive 74% 21 FIT Yes Yes Yes Yes
B Comprehensive 84% 13 FIT Yes Yes Yes Yes
C Partial 35% 51 FIT Yes No No Yes
D Partial 62% 30 FIT No Yes No Yes
E Partial 40% 47 FIT Yes Partially No Yes
(1) With the assumption that the BPCS level sensor is used as independent measurement.
Type Proof test
coverage (%) of DU
Remaining dangerous, undetected failures
Test coverage Can be
Output circuitry
Measurement electronics
Antenna
performed remotely
(1)
(1)

3.1.2 Proof test interval

The time intervals for proof testing are defined by the SIL verification calculation (subject to the PFD
Rosemount 5408:SIS Level Transmitter 15
). The SIL verification calculation is an analytical method to calculate an
AVG
Page 16
Proof tests Safety Manual
September 2021 00809-0400-4408
appropriate proof test interval for the specific safety function based on equipment’s reliability and required risk reduction for the specific SIF.
The proof tests must be performed more frequently than or as frequently as specified in the SIL verification calculation, in order to maintain the required safety integrity of the overall SIF.

3.1.3 Tools required

HART host/communicator or Rosemount Radar Master Plus
Current meter
Safety logic solver
Independent measuring device (e.g. BPCS level sensor, measuring tape)

3.2 1-point level and analog output verification

3.2.1 Perform 1-point level and analog output verification using Rosemount Radar Master Plus

Prerequisites
WARNING
During the proof test, the transmitter will not output measurement values corresponding to the product surface level. Ensure systems and people relying on measurement values from the transmitter are made aware of the changed conditions. Failure to do so could result in death, serious injury and/or property damage.
Procedure
1. Prior to the test, ensure there are no alarms or warnings present in the transmitter. a)
Under Service Tools, select Alerts.
2. Bypass the process safety function and take appropriate action to avoid a false trip.
3. Simulate 4.00 mA output and verify loop current. a) Under Service Tools, select Simulate.
b) Select Loop Test.
c) Select 4 mA and then select Start.
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
Note
The inaccuracy of safety logic solver or current meter needs to be considered.
16 Safety Manual
Page 17
Safety Manual Proof tests
00809-0400-4408
September 2021
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
f) Select
Stop to end loop test.
4. Simulate 20.00 mA output and verify loop current. a) Under Service Tools, select Simulate.
b) Select Loop Test.
c) Select 20 mA and then select Start.
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Note
The inaccuracy of safety logic solver or current meter needs to be considered.
f) Select Stop to end loop test.
5. Perform a one-point level measurement verification of the transmitter in the
measuring range. Compare with independent measurement (e.g. the BPCS level sensor).
a)
Under Overview, select All Variables.
b) Verify the current level or distance reading with an independent
measurement is within the safety deviation of 2%.
Note
The inaccuracy of the independent measurement needs to be considered.
6. Remove the bypass and otherwise restore normal operation.
Related information
Use the TEST terminal
Rosemount 5408:SIS Level Transmitter 17
Page 18
Proof tests Safety Manual
September 2021 00809-0400-4408

3.2.2 Perform 1-point level and analog output verification using AMS Device Manager and handheld communicator

Prerequisites
WARNING
During the proof test, the transmitter will not output measurement values corresponding to the product surface level. Ensure systems and people relying on measurement values from the transmitter are made aware of the changed conditions. Failure to do so could result in death, serious injury and/or property damage.
Procedure
1. Prior to the test, ensure there are no alarms or warnings present in the transmitter. a)
Select Service Tools Alerts.
2. Bypass the process safety function and take appropriate action to avoid a false trip.
3. Simulate 4.00 mA output and verify loop current. a) Select Service Tools Simulate.
b) Under Analog Out, select Loop test.
c) Select 4mA and then select Next (Enter on Field Communicator).
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Note
The inaccuracy of safety logic solver or current meter needs to be considered.
f) To end loop test, select Cancel (ABORT on handheld communicator).
4. Simulate 20.00 mA output and verify loop current. a)
Select Service Tools Simulate.
b) Under Analog Out, select Loop test.
c) Select 20mA and then select Next (Enter on Field Communicator).
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Note
The inaccuracy of safety logic solver or current meter needs to be considered.
18 Safety Manual
Page 19
Safety Manual Proof tests
00809-0400-4408 September 2021
f) To end loop test, select Cancel (ABORT on handheld communicator).
5. Perform a one-point level measurement verification of the transmitter in the
measuring range. Compare with independent measurement (e.g. the BPCS level sensor).
a)
Select Service Tools Variables Process.
b) Verify the current level or distance reading with an independent
measurement is within the safety deviation of 2%.
Note
The inaccuracy of the independent measurement needs to be considered.
6. Remove the bypass and otherwise restore normal operation.
Related information
Use the TEST terminal

3.3 2-point level and analog output verification

3.3.1 Perform 2-point level and analog output verification using Rosemount Radar Master Plus

Prerequisites
WARNING
During the proof test, the transmitter will not output measurement values corresponding to the product surface level. Ensure systems and people relying on measurement values from the transmitter are made aware of the changed conditions. Failure to do so could result in death, serious injury and/or property damage.
Procedure
1. Prior to the test, ensure there are no alarms or warnings present in the transmitter. Under Service Tools, select Alerts.
a)
2. Bypass the process safety function and take appropriate action to avoid a false trip.
Rosemount 5408:SIS Level Transmitter 19
Page 20
Proof tests Safety Manual
September 2021 00809-0400-4408
3. Simulate 4.00 mA output and verify loop current.
a) Under
Service Tools, select Simulate.
b) Select Loop Test.
c) Select 4 mA and then select Start.
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Note
The inaccuracy of safety logic solver or current meter needs to be considered.
f) Select Stop to end loop test.
4. Simulate 20.00 mA output and verify loop current.
a)
Under Service Tools, select Simulate.
b) Select Loop Test.
c) Select 20 mA and then select Start.
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Note
The inaccuracy of safety logic solver or current meter needs to be considered.
f) Select Stop to end loop test.
5. Perform a two-point level measurement verification of the transmitter in the
measuring range. Compare with independent measurement (e.g. the BPCS level sensor).
a)
Under Overview, select All Variables.
b) Verify the current level or distance reading with an independent
measurement is within the safety deviation of 2%.
Note
The inaccuracy of the independent measurement needs to be considered.
c) Move the surface in the tank at least 10% of the full measuring span (level
0-100%).
d) Repeat
5.a and 5.b for the second point.
6. Remove the bypass and otherwise restore normal operation.
20 Safety Manual
Page 21
Safety Manual Proof tests
00809-0400-4408
Related information
Use the TEST terminal
September 2021

3.3.2 Perform 2-point level and analog output verification using AMS Device Manager and handheld communicator

Prerequisites
WARNING
During the proof test, the transmitter will not output measurement values corresponding to the product surface level. Ensure systems and people relying on measurement values from the transmitter are made aware of the changed conditions. Failure to do so could result in death, serious injury and/or property damage.
Procedure
1. Prior to the test, ensure there are no alarms or warnings present in the transmitter. a)
Select Service Tools Alerts.
2. Bypass the process safety function and take appropriate action to avoid a false trip.
3. Simulate 4.00 mA output and verify loop current. a) Select Service Tools Simulate.
b) Under Analog Out, select Loop test.
c) Select 4mA and then select Next (Enter on Field Communicator).
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Note
The inaccuracy of safety logic solver or current meter needs to be considered.
f) To end loop test, select Cancel (ABORT on handheld communicator).
4. Simulate 20.00 mA output and verify loop current. a)
Select Service Tools Simulate.
b) Under Analog Out, select Loop test.
c) Select 20mA and then select Next (Enter on Field Communicator).
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
Rosemount 5408:SIS Level Transmitter 21
Page 22
Proof tests Safety Manual
September 2021 00809-0400-4408
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Note
The inaccuracy of safety logic solver or current meter needs to be considered.
f) To end loop test, select Cancel (ABORT on handheld communicator).
5. Perform a two-point level measurement verification of the transmitter in the
measuring range. Compare with independent measurement (e.g. the BPCS level sensor).
a)
Select Service Tools Variables Process.
b) Verify the current level or distance reading with an independent
measurement is within the safety deviation of 2%.
Note
The inaccuracy of the independent measurement needs to be considered.
c) Move the surface in the tank at least 10% of the full measuring span (level
0-100%).
d) Repeat
5.a and 5.b for the second point.
6. Remove the bypass and otherwise restore normal operation.
Related information
Use the TEST terminal
22 Safety Manual
Page 23
Safety Manual Proof tests
00809-0400-4408 September 2021

3.4 Analog output verification

Compare HART Primary Variable digital value with analog output reading. Verify that the deviation is within the pass limit.
Procedure
1. Obtain the loop current as a digital value, do one of the following:
In Rosemount Radar Master Plus, under
the current analog output value.
Read HART command 2 or 3 via the host system.
Command 2: Analog output current and Percent of range Command 3: Device variables (PV, SV, TV, and QV) and Analog output current
2. Obtain the loop current as an analog value (e.g. by using the safety logic solver or using the TEST terminal).
3. Compare the current values.
4. Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Overview, select All Variables and read
Note
The inaccuracy of safety logic solver needs to be considered.
Related information
Use the TEST terminal

3.5 Level deviation monitoring

Use the analog output to obtain level (or distance) reading and compare with an independent level measurement. Verify that the deviation is within the pass limit.
Procedure
1. Obtain the level (or distance) measurement value derived from the analog output (e.g. by checking measurement value in safety logic solver).
Obtain the level (or distance) measurement value from an independent level
2. measurement (e.g. the BPCS level sensor).
3. Compare the measurements and verify that the deviation is within the safety deviation of 2%.

3.6 Smart echo level test

The function allows you to test the behavior of the transmitter in a real tank environment without raising the level. During the test, a virtual surface echo is inserted into the radar signal, and the transmitter will output a level corresponding to the echo position.
Rosemount 5408:SIS Level Transmitter 23
Page 24
A B
C
Proof tests Safety Manual
September 2021
00809-0400-4408

3.6.1 Configure the smart echo level

Prerequisites
Disable the Safety Mode.
Procedure
1. In Rosemount Radar Master Plus, under
2. Select Configure Smart Echo.
3. Set the Smart Echo Level to a value above the Upper Range Value.
Note
Ensure the product level is at least 1 ft. (30 cm) below the Smart Echo Level.
Figure 3-1: Smart Echo Level
A. Smart Echo Level B. Upper Range Value (100%/20 mA)
Minimum 1 ft. (30 cm)
C.
Service Tools, select Proof Test.
4. Select Save.
Postrequisites
Enable the Safety Mode.
Related information
Safety mode

3.6.2 Perform a smart echo level test

24 Safety Manual
Simulate a surface echo above the Upper Range Value (i.e. analog out in high saturation) and verify loop current.
Prerequisites
This test is available for transmitters with:
Page 25
Safety Manual Proof tests
00809-0400-4408 September 2021
Device software revision 1.C0 or later
Option code ET
Prior to and during the test, ensure that:
The product surface is calm.
The smart echo level is not closer than 1 ft. (0.3 m) to the liquid surface.
The tank is not being filled or emptied.
WARNING
During the proof test, the transmitter will not output measurement values corresponding to the product surface level. Ensure systems and people relying on measurement values from the transmitter are made aware of the changed conditions. Failure to do so could result in death, serious injury and/or property damage.
Procedure
1. Ensure there are no alarms or warnings present in the transmitter.
a)
In Rosemount Radar Master Plus, under Service Tools, select Alerts.
2. Bypass the process safety function and take appropriate action to avoid a false trip.
3. Perform the Smart Echo Level test.
a) Under Service Tools, select Proof Test.
b) Select Smart Echo Level Test.
c) Select Start.
The analog output goes to high saturation.
d) Measure loop current (e.g. reading the safety logic solver or using the TEST
terminal).
e) Verify the current deviation is within the safety deviation of 2% (±0.32 mA).
Note
The inaccuracy of safety logic solver or current meter needs to be considered.
f) Select Stop to end test mode.
4. Remove the bypass and otherwise restore normal operation.
Related information
Analog saturation levels Use the TEST terminal
Rosemount 5408:SIS Level Transmitter 25
Page 26
H2.5 mm
Proof tests Safety Manual
September 2021 00809-0400-4408

3.7 Use the TEST terminal

Prerequisites
WARNING
Verify that the installation is consistent with the appropriate hazardous locations certifications when the instrument used for loop current measurement is connected.
For Explosion-proof/Flameproof and Non-Incendive/Type n installations, the cover must not be opened in an explosive atmosphere.
Note
Disconnect the blue plug only during the loop current measurement procedure. To meet the stated EMC specification during normal operation, the blue plug must be plugged in.
Procedure
1. Turn the jam screw clockwise until it is completely threaded into the housing.
2. Remove the cover.
3. Remove the blue plug from the TEST terminal.
26 Safety Manual
Page 27
H2.5 mm
Safety Manual Proof tests
00809-0400-4408 September 2021
4. Connect the ampere meter leads to the terminals labeled “+” and “TEST”.
5. Measure the loop current.
6. Attach the blue plug to the TEST terminal.
7. Attach and tighten the cover.
a) Verify the cover jam screw is completely threaded into the housing.
b) Attach and tighten the cover.
Make sure the cover is fully engaged. There should be no gap between the
cover and the housing.
Rosemount 5408:SIS Level Transmitter 27
Page 28
Proof tests Safety Manual
September 2021 00809-0400-4408
c) Turn the jam screw counterclockwise until it contacts the cover.
Required for explosion-proof/flameproof installations only.
d) Turn the jam screw an additional ½ turn counterclockwise to secure the
cover.
28 Safety Manual
Page 29
Safety Manual Operating constraints
00809-0400-4408 September 2021

4 Operating constraints

4.1 Specifications

The Rosemount 5408:SIS must be operated according to the functional and performance specifications provided in the Rosemount 5408 and Rosemount 5408:SIS Product Data
Sheet.

4.1.1 Measuring range

The maximum measuring range is 82 ft. (25 m) for the Rosemount 5408:SIS Level Transmitter in Safety (SIS) mode.

4.1.2 Failure rate data

The FMEDA report includes failure rate data, assessment details, and assumptions regarding failure rate analysis.

4.1.3 Safety deviation

±2.0% of analog output span

4.1.4 Transmitter response time

< 6 s at damping value 2 s (default)
< 2 s at damping value 0 s (minimum)
The transmitter response time will be a function of the configured Damping value. Rosemount Radar Master Plus has a built-in function to calculate the transmitter’s measurement response time (requires option code EF2).
(1)

4.1.5 Diagnostic test interval

< 90 min
(2)

4.1.6 Turn-on time

(3)
< 40 s
(1)
(1) Step response time as per IEC 61298-2. (2) A majority of the self-diagnostic tests are performed once every second and an action (if necessary) is taken in less than 30
seconds (default).
(3) Time from when power is applied to the transmitter until performance is within specifications.
Rosemount 5408:SIS Level Transmitter 29
Page 30
Operating constraints Safety Manual
September 2021 00809-0400-4408

4.1.7 Useful lifetime

50 years
based on worst case component wear-out mechanisms
not based on wear-out of process wetted materials

4.2 Product repair

The Rosemount 5408:SIS is repairable by major component replacement. All failures detected by the device diagnostics or by the proof test must be reported. Feedback can be submitted electronically at Go.EmersonAutomation.com/Contact-Us (Contact Us).
30 Safety Manual
Page 31
Safety Manual Terms and definitions
00809-0400-4408 September 2021

A Terms and definitions

λ
DU
λ
DD
λ
SU
λ
SD
Diagnostic test interval
Element
FIT
FMEDA
HART® protocol
HFT
High demand mode
Low demand mode
Dangerous Undetected failure rate
Dangerous Detected failure rate
Safe Undetected failure rate
Safe Detected failure rate
The time from when a dangerous failure/condition occurs until the device has set the safety related output in a safe state (total time required for fault detection and fault reaction).
Term defined by IEC 61508 as “part of a subsystem comprising a single component or any group of components that performs one or more element safety functions”
Failure In Time per billion hours
Failure Modes, Effects and Diagnostic Analysis
Highway Addressable Remote Transducer
Hardware Fault Tolerance
The safety function is only performed on demand, in order to transfer the EUC (Equipment Under Control) into a specified safe state, and where the frequency of demands is greater than one per year (IEC 61508-4).
The safety function is only performed on demand, in order to transfer the EUC into a specified safe state, and where the frequency of demands is no greater than one per year (IEC 61508-4).
PFD
AVG
PFH
Proof test coverage factor
Safety deviation
Rosemount 5408:SIS Level Transmitter 31
Average Probability of Failure on Demand
Probability of dangerous Failure per Hour: the term "probability" is misleading, as IEC 61508 defines a rate.
The effectiveness of a proof test is described using the coverage factor which specifies the share of detected dangerous undetected failures (λDU). The coverage factor is an indication of a proof test’s effectiveness to detect dangerous undetected faults.
The maximum allowed deflection of the safety output due to a failure within the device (expressed as a percentage of span).
Any failure causing the device output to change less than the Safety Deviation is considered as a "No Effect" failure. All failures causing the device output to change more than the Safety Deviation and with the device output still within the active range (non-alarm state) are considered dangerous failures.
Page 32
Terms and definitions Safety Manual
September 2021 00809-0400-4408
Note
The Safety Deviation is independent of the normal performance specification or any additional application specific measurement error.
SIF
SIL
SIS
Systematic capability
Transmitter response time
Type B device
Useful lifetime
Safety Instrumented Function
Safety Integrity Level – a discrete level (one out of four) for specifying the safety integrity requirements of the safety instrumented functions to be allocated to the safety instrumented systems. SIL 4 has the highest level of safety integrity, and SIL 1 has the lowest level.
Safety Instrumented System – an instrumented system used to implement one or more safety instrumented functions. An SIS is composed of any combination of sensors, logic solvers, and final elements.
A measure (expressed on a scale of SC 1 to SC 4) of the confidence that the systematic safety integrity of an element meets the requirements of the specified SIL, in respect of the specified element safety function, when the element is applied in accordance with the instructions specified in the compliant item safety manual for the element.
The time from a step change in the process until transmitter output reaches 90% of its final steady state value (step response time as per IEC 61298-2).
Complex device using controllers or programmable logic, as defined by the standard IEC 61508.
Reliability engineering term that describes the operational time interval where the failure rate of a device is relatively constant. It is not a term which covers product obsolescence, warranty, or other commercial issues.
The useful lifetime is highly dependent on the element itself and its operating conditions (IEC 61508-2).
32 Safety Manual
Page 33
Safety Manual
00809-0400-4408 September 2021
Rosemount 5408:SIS Level Transmitter 33
Page 34
00809-0400-4408
Rev. AB
2021
For more information:
©
2021 Emerson. All rights reserved.
www.emerson.com
Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners.
Loading...