Rosemount 5400M Series Manuals & Guides

Page 1
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Rosemount 5400M Series
Two-Wire Radar Level Transmitter
www.EmersonRosemount.com/mtm
Page 2
The Emerson logo is a trademark and service mark of Emerson Co. Rosemount TankRadar and the Rosemount logotype are registered trademarks of Rosemount Tank Radar AB. All rights reserved. All other marks are the property of their respective owners.
Copyright © Rosemount Tank Radar AB, 2012
Reference Manual Marine Version
1st edition Version AB
November 2012
Rosemount 5400M
Marine Tank Management Emerson Process Management Rosemount Tank Radar AB Gamlestadsvägen 18B Box 13045 SE-40251 Göteborg Sweden
Page 3
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Table of Contents
Rosemount 5400M Series
SECTION 1 Introduction
SECTION 2 Transmitter Overview
SECTION 3 Mechanical Installation
Safety Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Manual Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Service Support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Product Recycling/Disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Theory of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Components of the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
System Architecture. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Marine Application Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Dielectric constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Foam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Transition Zone. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Safety Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Installation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Placement Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Free space requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Pipes Intruding into the Radar Beam . . . . . . . . . . . . . . . . . . . . . . . 3-4
Location of Heating Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Coil Supports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Transmitter Close to Bulkhead an d in Narrow Wing Tanks . . . . . . 3-6
Inclined Tank Bottom . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Cargo Deep Well/Inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Longitudinals or Frames on the Tank Bottom. . . . . . . . . . . . . . . . . 3-8
Deflection Plates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Service Space and Orientation. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Mounting Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Transmitter Socket Requirements . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Gasket Recommendation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
General Recommendation . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Mounting, Cable inlet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Cable Gland . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Cable Protection Hose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
SECTION 4 Electrical Installation
www.EmersonProcess.com/mtm
Safety Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Cable/Conduit Entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Cable Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Hazardous Areas. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
External Circuit Breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Power Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Connecting the Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Non-Intrinsically Safe Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Page 4
Rosemount 5400M Series
Intrinsically Safe Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
IS parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
SECTION 5 Service and Troubleshooting
SECTION 6 Reference Data
SECTION 7 Product Certifications
Safety Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Troubleshooting Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Measurement Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Volume Calculation Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Analog Output Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
EU Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
European ATEX Directive Information. . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Intrinsic Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Special Conditions for Safe Use (X) . . . . . . . . . . . . . . . . . . . . . 7-3
Flameproof . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
Special Conditions for Safe Use (X) . . . . . . . . . . . . . . . . . . . . . 7-4
Hazardous Locations Certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
Factory Mutual (FM) Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
IECEx Approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6
EX Approval Drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-8
2
Page 5
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Rosemount 5400M Series
Section 1 Introduction
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1
Manual Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-2
Service Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-2
Product Recycling/Disposal . . . . . . . . . . . . . . . . . . . . . . .page 1-3
SAFETY MESSAGES Procedures and instructions in this manual may require special precautions to
ensure the safety of the personnel performing the operations. Infor mation that raises potential safety issues is indicated by a warning symbol ( ). Refer to the safety messages listed at the beginning of each section before performing an operation preceded by this symbol.
Failure to follow safe installation and service guidelines could result in death or serious injury
• Make sure only qualified personnel perform installation or service.
• Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment.
• Any substitution of non-authorized parts or repair, other than exchanging the complete transmitter head or antenna assembly, may jeopardize safety and is prohibited.
• Unauthorized changes to the product are strictly prohibited as they may unintentionally and unpredictably alter performance and jeopardize safety. Unauthorized changes that interfere with the integrity of the welds or flanges, such as making additional perforations, compromise product integrity and safety. Equipment ratings and certifications are no longer valid on any products that have been damaged or modified without the prior written permission of Emerson Process Management. Any continued use of product that has been damaged or modified without prior written authorization is at the customer's sole risk and expense.
Explosions could result in death or serious injury
• Verify that the operating environment of the transmitter is consistent with the appropriate hazardous locations specifications.
• In an Explosion-proof/Flameproof installation, do not remove the transmitter cover when power is applied to the unit.
• Before connecting a make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Electrical shock can result in death or serious injury
• Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
• Make sure the main power to the 5400M Series transmitter is off and the lines to any other external power source are disconnected or not powered while wiring the transmitter.
HART® based communicator in an explosive atmosphere,
www.EmersonProcess.com/mtm
Page 6
Reference Manual Marine Version
Ed 01 Rev AB
Rosemount 5400M Series
November 2012
MANUAL OVERVIEW This manual provides installation, configuration and maintenance information
for the Rosemount 5400M Series Radar Transmitter.
Section 2: Transmitter Overview
Theory of operation
Descripton of the transmitter
Process and vessel characteristics
Section 3: Mechanical Installation
Mounting considerations
Mounting
Section 4: Electrical installation
Cable/conduit entries
Grounding
Cable selection
Hazardous areas
External circuit breaker
Power requirements
Connecting the transmitter
Non-intrinsically safe power supply
Intrinsically safe power supply
Optional devices
Section 5: Service and Troubleshooting
Troubleshooting
Error and warning codes
Communication errors
Appendix A: Reference Data
Specifications
Ordering Information
Appendix B: Product Certifications
Examples of labels
European ATEX Directive information
FM approvals
CSA approvals
IECEx approvals
TIIS approval
NEPSI approvals
Approval drawings
SERVICE SUPPORT Contact Marine Tank Management, Emerson Process Management,
Rosemount Tank Radar AB at Gamlestadsvägen 18B, Box 13045 SE-40251 Göteborg, Sweden.
2
Page 7
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Rosemount 5400M Series
PRODUCT RECYCLING/ DISPOSAL
Recycling of equipment and packaging should be taken into consideration and disposed of in accordance with local and national legislation/regulations.
3
Page 8
Rosemount 5400M Series
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
4
Page 9
Reference Manual Marine Version
Time
Level
Distance
Tank Height
Signal Amplitude
Ed 01 Rev AB November 2012
Rosemount 5400M Series
Section 2 Transmitter Overview
Theory of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-1
Components of the transmitter . . . . . . . . . . . . . . . . . . . . .page 2-2
System Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-3
Marine Application Characteristics . . . . . . . . . . . . . . . . . . page 2-4
THEORY OF OPERATION The Rosemount 5400M Series Radar Gauge is a smart, two-wire continuous
level transmitter. A 540 0 transmitter is installed at the top of the tank and emits short microwave pulses towards the product surface in the tank. When a pulse reaches the surface, part of the energy is reflected back to the antenna for subsequent processing by the transmitter electronics. The time difference between the transmitte d and refle cted p ulse is detected by a micro­processor and is converted into a distance, which calculates the level.
The product level is related to the tank height and the measured distance by the following expression:
Level = Tank Height - Distance.
Figure 2-1. Measurement principle for the Rosemount 5400M Series.
www.EmersonProcess.com/mtm
Page 10
Rosemount 5400M Series
Cable Entry:
½" NPT.
Transmitter Head with Radar Electronics
Antenna
Display Panel Terminal side
Cable Entry:
½" NPT.
Flange
Tank Seal
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
COMPONENTS OF THE TRANSMITTER
Figure 2-2. Transmitter components.
The Rosemount 5400M Series Radar Gauge is a vailable with a stainless steel housing containing advanced electronics for signal processing.
The radar electronics produces an electromagnetic pulse that is emitted through the antenna.
The transmitter head has separate compartments for electronics and terminals, and can be removed without opening the tank. The head has two entries for conduit/cable connections.
The tank connection consists of a Tank Seal and a flange (DIN or JIS).
2
Page 11
Reference Manual Marine Version
Integral Display
Rosemount Radar Master or AMS Suite
HART modem
Rosemount 751 Field Signal Indicator
3 x 4-20 mA
DCS
Rosemount 5400 Series Radar Transmitter
Tri-Loop
Ed 01 Rev AB November 2012
Rosemount 5400M Series
SYSTEM ARCHITECTURE
Figure 2-3. HART system architecture
The Rosemount 5400M Series Radar Transmitter is loop-powered, and uses the same two wires for power supply and output signal. The output is a 4-20 mA analog signal superimposed with a digital HART signal.
By using the optional HART T ri-lo op, th e HAR T sign al ca n be converte d up to three additional 4-20 mA analog signals.
With the HART protocol multidrop configuration is possible. In this case, communication is restricted to digital, since current is fixed to the 4 mA minimum value.
The transmitter can be connected to a Rosemount 751 Field Signal Ind ica to r, or it can be equipped with an integral display.
The transmitter can easily be configured using a PC with the Rosemount Radar Master software. Rosemount 5400M Series transmitters can also be configured with the AMS
®
Suite and DeltaV™ software, and other tools that
support Electronic Device Description Language (EDDL) functionality. For HART communication a minimum load resist ance of 2 50Ω within the loop
is required.
3
Page 12
Rosemount 5400M Series
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
MARINE APPLICATION CHARACTERISTICS
A calm surface gives better reflection than a turbulent surface. Maximum measurement range for a Marine application has taken turbulence surface in consideration and in-tank environment. For pr oducts with higher dielectric constant and/or lower turbulence surface measuring range can be extended. Please advice Rosemount Tank Radar AB for details.
Dielectric constant A key parameter for measure ment performance is reflectivity. A high dielectric
constant of the media provides better reflection and enables a longer measuring range.
Foam Rosemount 5400M Series Radar Transmitter measurement in foamy
applications depends on the foam properties; light and airy or dense and heavy, high or low dielectrics, etc. If the foam is conductive and creamy, the transmitter may measure the surface of the foam. If the foam is less conductive, the microwaves may penetrate the foam, and measure the liquid surface.
Transition Zone The measurement accuracy is reduced within the Transition Zone region 6 in.
(150 mm) from the lower end of the antenna. This is normally avoided by following installation drawings and by choice of gauge socket.
4
Page 13
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Rosemount 5400M Series
Section 3 Mechanical Installation
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1
Installation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-2
Mounting Considerations . . . . . . . . . . . . . . . . . . . . . . . . .page 3-9
Mounting, Cable inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-10
SAFETY MESSAGES Procedures and instructions in this section may require special precautions to
ensure the safety of the personnel performing the operations. Infor mation that raises potential safety issues is indicated by a warning symbol ( ). Please refer to the following safety messages before performing an operation preceded by this symbol.
Failure to follow safe installation and service guidelines could result in death or serious injury
• Make sure only qualified personnel perform installation or service.
• Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment.
• Any substitution of non-recognized spare parts may jeopardize safety. Repair, e.g. substitution of components etc. may also jeopardize safety and is under no circumstances allowed.
Explosions could result in death or serious injury
• Verify that the operating environment of the transmitter is consistent with the appropriate hazardous locations specifications.
• In an Explosion-proof/Flameproof installation, do not remove the transmitter cover when power is applied to the unit.
• Before connecting a make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Electrical shock can result in death or serious injury
• Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
• Make sure the main power to the 5400M Series transmitter is off and the lines to any other external power source are disconnected or not powered while wiring the transmitter.
HART® based communicator in an explosive atmosphere,
www.EmersonProcess.com/mtm
Page 14
Rosemount 5400M Series
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
INSTALLATION PROCEDURE
This is a recommended working procedure of how to perform the installation. The procedure presents an overview of the installation steps.
NOTE!
Please refer to Installation drawings for more detailed information.
1. Decide the location of the transmitter.
2. Manufacture the transmitter’s socket (if supplied by the yard), refer to drawings.
3. Cut the hole in the deck
4. Weld the socket to the deck.
5. Mount the transmitter on the socket with the appropriate gasket.
6. Lay out the cables.
7. Fasten the cable and strip the wires. Use the PTFE tape to seal gland and plug.
8. Connect the wires.
9. Fasten the lid.
NOTE!
Retighten glands and clamp ring within one week!
2
Page 15
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Rosemount 5400M Series
PLACEMENT CONSIDERATIONS
Before installing a Rosemount 5400M Series Transmitter, consider specific mounting requirements, vessel, and process characteristics.
The general recommendation in international (ISO) and API measurement standards for location is to place the transmitter as close to the tan k center on deck as possible. This location minimizes the uncertainty from trim/list corrections, as well as avoids excessive liquid turbulence during open sea operations.
This is especially important for tankers, operating in high sea conditions such as shuttle tankers, FPSO’s etc. This reduces excessive errors in the trim/list correction of ullage, minimizes the liquid splashing from the bulkheads and is of essential importance to achieve an acceptable measure ment.
Locating the transmitter close to the vertical line through the center of gravity of the tank, also provides the best accuracy for volume calculation.
Free space requirements When deciding the location of the transmitter on deck, the free space
requirement must be considered. The radar beam must pass unobstructed to the tank bottom. This is the most important requirement in order to get a trouble-free operation of the transmitter . The ideal free space requirem ents for the transmitter is best described as a circular cone, centered around the antenna axis with an angle of 9°. See Figure 3-1 on page -4.
There can be certain exceptions from the ideal free space requirements, for example when the transmitter is installed close to a bulkhead. Exceptions with requirements and recommendations are descr ibed later on in this chapter.
All exceptions from the ideal free space requirements mu st be revised and approved by Rosemount Tank Radar AB before any inst allation arrangement s are planned.
If there are any hesitations about the location of the transmitter, contact Rosemount Tank Radar AB.
3
Page 16
Rosemount 5400M Series
Figure 3-1. Free space requirements.
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
Pipes Intruding into the Radar Beam
4
One pipe with a diameter that equals to or is less than 56 mm (2”) can, withou t restriction, pass through the inner area of the radar beam. Another pipe, without flanged joints, does not seriously affect the performance and can be allowed outside a 9° cone centered around the antenna axis. In doubtful cases contact Rosemount Tank Radar AB for advice.
Location of Heating Coils
Heating coils, should if possible be located outside the radar b eam so that the radar echo is unaffected within the free space requirements.
Page 17
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Figure 3-2. Heating coils placed outside the radar beam (left). Inclined heating coils in order to deflect unwanted radar echo (right).
The unwanted radar echo can be deflected by inclining the coils with an angle of at least 4°. When there is an inclined tank bottom, the coils should be placed as shown in the picture.
Figure 3-3. Heating coils on an inclined tank bottom. The left tank is an example of how to place the coils. The right tank is an example of how NOT to place the coils.
Rosemount 5400M Series
Coil Supports
In order to minimize the radar echo from the coil supports, they should first of all never be placed within the radar beam. If that cannot be avoided, they should be placed on the side that faces away from the radar beam’s center. The top of the support should also be bevel-edged, or the whole holder tilted, in order to avoid a reflecting surface towards the radar beam.
5
Page 18
Rosemount 5400M Series
Figure 3-4. Placement of coil support.
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
Transmitter Close to Bulkhead and in Narrow Wing Tanks
Because of circular polarization, there is no clearance distance requirement from the tank wall if it is flat and free of obstructions such as heating coils and ladders. The optimal location is 1/4 of the inner beam diameter from the tank wall.
Inclined Tank Bottom Avoid, if possible, to locate the transmitter over an inclined tank bottom. The
bottom echo with an empty tank may be too weak for reliable indication. If a placement over an inclined tank bottom cannot be avoided, the transmitter should be placed over the deepest part of the tank.
If the bottom inclination exceeds 2°, a square steel target plate should be installed as a bottom reflector perpendicular to the ships vertical axis (within ±1°). It should be installed as deep in the t ank as possible, however , the whole target plate must be inside the radar beam.
The target plate must be installed under the antenna, measured from the ship´s vertical axis below the antenna, and have a size according to the table below.
Table 3-1. Target plate size. .
Tank height Plate size Plate center from radar beam axis
(m) (mm) (mm) 0 - 5 120 x 120 max. 100 5 - 10 160 x 160 max. 200
The plate should be designed to endure high-pressure tank washing. Do not mount the target plate in a way that creates a pocket. Mount in a way
that allows cleaning.
6
Page 19
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Figure 3-5. A target plate installed on an inclined tank bottom.
Rosemount 5400M Series
Cargo Deep Well/Inlet The transmitter must not be located directly above a cargo deep well or cargo
inlet. The deep well or inlet can cause disturbances on the product surface when loading or discharging. These disturbances can prevent the measurement or cause inaccurate me as ur em e nts.
Figure 3-6. A cargo inlet at the bottom of the tank. To the left is an example of how to place the transmitter. To the right is an example of how NOT to place the transmitter.
Locate the transmitter so far away from cargo deep wells or inlets that the disturbances on the product surface do not intrude into the radar beam; hence the measurement will not be affected.
7
Page 20
Rosemount 5400M Series
Figure 3-7. A cargo inlet at the top of the tank. To the left is an example of how to place the transmitter. To the right is an example of how NOT to place the transmitter.
Figure 3-8. A deep well in the bottom of the tank. To the left is an example of how to place the transmitter. To the right is an example of how NOT to place the transmitter.
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
Longitudinals or Frames on the Tank Bottom
Longitudinals, frames or pipes on the tank bottom may give a radar echo that can be mistaken for the cargo surface echo. To avoid this, the radar echo from these objects must be avoided, either by using deflection plates or an alternative location of the transmitter.
Deflection Plates If the interfering objects cannot be moved, deflection plates must be welded
onto the objects. Deflection plates are necessary when any longitudinals intrude into the free space requir ement which is best de scri bed as a 28 ° wide cone centered around the antenna axis. The deflection plates should be mounted so that the part of the beam that hits the deflection plates is deflected away from the radar beam’s center. Note also that deflection plates should never be used on heating coils.
Do not mount the deflection plate in a way that creates a pocket. Mount in a way that allows cleaning.
All longitudinals, frames, platforms etc. intruding into the free space requirement cone must be provided with deflection plates. The deflection plates must be 10% wider than the width of the top surface of the long itu dinal to completely cover the beam. The plate must cover all parts of the interfering object that is in the beam.
8
Page 21
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Figure 3-9. Deflection plates placed on a square frame and on a pipe.
Rosemount 5400M Series
Service Space and Orientation
MOUNTING CONSIDERATIONS
Transmitter Socket Requirements
The transmitter should be located so that there is free space above the transmitter in order to have the transmitter easily accessible for maintenance and service. See installation drawing for free space area.
Place the transmitter so that the cable inlet for the cable is directed towards center line.
Refer to the mechanical Installation drawing s in your documentation b inder for more detailed information.
The transmitter is to be mounted on a deck socket. Transmitter sockets are either delivered by Emerson Process Management (optional) or manufactured by the yard according to dr awings supplied.
The transmitter must be installed so that it is always above the highest possible tank content level. The standard height of the socket is 375 mm. Please refer to the Installation Drawings.
The socket is welded to the deck when a suitable hole has been cut in deck satisfying the minimal requirement to avoid any disturbing echoes.
The socket must be installed so that the flange is horizontal at even keel within ± 1°.
Refer to installation drawings in your documentation binder for more detailed information.
Gasket Recommendation To properly seal a tank several factors have to be taken into consideration,
such as the flatness of the transmitter flange, socket flange and th e properties of the selected gasket. It is important that the selected type of gasket and its material can withstand the cargo and the pressure the tank is approved for.
One of the functions the gasket has is to compensate for irregularities between the socket flange and the transmitter flange. For the gasket to seal properly the socket flange and the transmitter flange must provide the gasket with the gasket minimum surface pressure.
9
Page 22
Rosemount 5400M Series
General Recommendation
The choice of gasket is usually made by the yard, as the end customer may have special requests concerning the selection of gasket. Due to the wide variety of gaskets and the properties th ey have, we r ecommend, as a gener al rule, a gasket which will allow at least 30% compression ratio relative to its thickness, the reason for this is to be able to compensate for any irregularities between the flanges.
The guide that follows below is only intended as a first step in the selection of what type of gasket to be used, the final decision is up to the yard.
Due to the fact that local manufacturing variations in the gasket composition are very common, always check that the selected gasket endures the exposition of the intended cargoes of the ship. Hence the different types of gasket materials listed below are only a rough guidance in the selection of the gasket.
MOUNTING, CABLE INLET
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
Cable Gland The cable gland prevents water from enter ing the transmitte r housing throug h
the cable inlet. Holes in the transmitter housing that are not used are deliv­ered with a plug. The cable gland must be tightened so that it is completely tight around the cable. Use the PTFE tape to properly seal gland and plug.
NOTE!
Make sure the installation is performed in dry conditions!
10
Page 23
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Cable Protection Hose
Figure 3-10. The Cable Protection Hose and the Cable gland, disassembled. For cable length, L, see table for installation data.
The Cable Protection Hose (CPH) is intended for flexible and mechanical protection of the cable connection to deck equipment. The standard hose is ventilated in order to drain water and protect from pressurized water ingress in the cable pipe. The ventilation holes are positioned in a vertical alignment. As the cabling for Rosemount 5400M is sealed at the cable gland a waterproof hose is not required. Tightness at cable gland is of utmost importance and hence require the hose to be round and smooth, do not use an oval shaped hose or hoses that are ribbed or indented in any other way.
Rosemount 5400M Series
Table 3-2. .
Use the PTFE tape to seal gland and plug to the housing. The CPH is mounted between the transmitter cable gland and the ship cable
pipe to protect the cable. The inside is made of a nitrile rubber hose and the outside is made of chloroprene armored with textile spiral construction.
Installation Data for the Cable Protection Hose
Cable Ø (mm)
6 - 13 M20 19 31 100 655
Thread deck end ISO 228/1-G1 1/4” can also be fitted with optional JIS or DIN flanges on request.
Gland Internal Ø
(mm)
External Ø (mm)
Bending radius
Max. Length L (mm)
11
Page 24
Rosemount 5400M Series
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
12
Page 25
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Rosemount 5400M Series
Section 4 Electrical Installation
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1
Cable/Conduit Entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-2
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-3
Cable Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 4-3
Hazardous Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-3
External Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-3
Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-3
Connecting the Transmitter . . . . . . . . . . . . . . . . . . . . . . . .page 4-4
Non-Intrinsically Safe Power Supply . . . . . . . . . . . . . . . .page 4-5
Intrinsically Safe Power Supply . . . . . . . . . . . . . . . . . . . . page 4-6
SAFETY MESSAGES Procedures and instructions in this section may require special precautions to
ensure the safety of the personnel performing the operations. Infor mation that raises potential safety issues is indicated by a warning symbol ( ). Please refer to the following safety messages before performing an operation preceded by this symbol.
Failure to follow safe installation and service guidelines could result in death or serious injury
• Make sure only qualified personnel perform installation or service.
• Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment.
• Any substitution of non-recognized spare parts may jeopardize safety. Repair, e.g. substitution of components etc. may also jeopardize safety and is under no circumstances allowed.
Explosions could result in death or serious injury
• Verify that the operating environment of the transmitter is consistent with the appropriate hazardous locations specifications.
• In an Explosion-proof/Flameproof installation, do not remove the transmitter cover when power is applied to the unit.
• Before connecting a make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Electrical shock can result in death or serious injury
• Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
• Make sure the main power to the 5400 Series transmitter is off and the lines to any other external power source are disconnected or not powered while wiring the transmitter.
HART® based communicator in an explosive atmosphere,
www.EmersonProcess.com/mtm
Page 26
Rosemount 5400M Series
Remove the orange protective plastic plugs, used for transportation. Seal any unused port with the enclosed metal plug.
Cable Entry Cable Entry
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
CABLE/CONDUIT ENTRIES
Figure 4-1. Cable Entries.
The electronics housing has two entries with ½ - 14 NPT threads. Cable protective hoses delivered from Emerson Process Management
requires special cable glands, supplied by Emerson Process Management. Properly seal unused ports to prevent moisture or other contamination from
entering the terminal compartment of the electronics housing. Install wiring with a drip loop with the bottom of the loop lower than the cable/conduit entry.
NOTE!
Use the enclosed metal plug to seal the unused port. The temporary orange plastic plugs used at delivery are not sufficient seals! Failure to use the metal plug to seal the unused port invalidates product certification. Use the PTFE tape to seal metal plug.
2
Page 27
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Rosemount 5400M Series
GROUNDING The housing should always be grounded according to national and local
electrical codes. Failure to do so may impair the protection provided by the equipment. The most effective grounding metho d is direct connection to earth ground with minimal impedance. There are two grounding screw connecti ons provided. One is inside the Terminal compartment of the housing and the other is located on one of the cooling fins below the housing . Th e int erna l ground screw is identified by a ground symbol: .
NOTE!
Using the threaded conduit connection for grounding may not be sufficient!
NOTE!
After installation and commissioning, make sure that no ground cur rent s exist from high ground potential differences in the installation.
CABLE SELECTION Use shielded twisted pair wiring for the Rosemount 5400 Series. The cables
must be suitable for the supply voltage and approved for use in hazardous areas, where applicable. For instance, in the U.S., explosion-proof conduits must be used in the vicinity of the vessel. For the ATEX flameproof approval version of the Rosemount 5400 Series, suitable conduits with sealing device or flameproof (EEx d) cable glands must be used depending on local requirements.
Use 18 AWG to 12 A WG wiri ng to minimize the volt age drop to the transmitter.
HAZARDOUS AREAS When the Rosemount 5400 Series transmitter is installed in a hazardous
area, all national and local regulations and specifications in applicable certificates must be observed.
EXTERNAL CIRCUIT BREAKER
POWER REQUIREMENTS
Table 4-1. Minimum input voltage (UI) at different currents.
For compliance with Low Voltage Directive 73/23/EEG, an external circuit breaker should be installed.
Terminals in the transmitter housing provide connections for signal wiring. The 5400 transmitter operates with the following power supplies:
Current
Hazardous approval
Non-Hazardous Installations and Intrinsically Safe Installations
Explosion-proof / Flameproof Installations
3.75 mA 21.75 mA Minimum input voltage (UI)
16 Vdc 11 Vdc
20 Vdc 15.5 Vdc
3
Page 28
Rosemount 5400M Series
5
11
3
2
4
Cable entries.
Internal Ground screw.
Terminals for signal and power supply.
Locking screw.
External Ground screw.
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
CONNECTING THE TRANSMITTER
The Rosemount 5400 Series accepts power supplies ranging from 16 Vdc to
42.4 Vdc. It uses 4-20 mA power superimposed with a HART signal. To connect the transmitter:
1. Make sure the housing is grounded (including IS ground inside the Terminal compartment) according to Hazardous Locations Certifications, national, and local electrical codes.
2. Make sure the power supply is disconnecte d.
3. Remove the terminal block cover.
4. Pull the cable through the cable gland/conduit. For Explosion-proof/ Flameproof installations, use cable glands or conduit entry devices certified Explosion-proof or Flameproof. Install the wiring with a drip loop, with the bottom of the loop lower than the cable/conduit entry.
5. Connect the wires according to Figure 4-3 for non-intrinsically safe power supplies, and according to Figure 4-6 for intrinsically safe power supplies.
6. Remove the orange protective plastic plugs used for transportation and seal any unused port with the enclosed metal plug.
7. Mount the cover and tighten the cable gland, making sure the cover is secure to meet explosion-proof requirements. For A TEX and IECEx installations, lock the cover with the Locking screw
.
8. Connect the power supply.
Figure 4-2. Terminal compartment and external ground screw.
NOTE!
Use PTFE tape or other sealant at the NPT threads in the Cable Entries.
4
Page 29
Reference Manual Marine Version
Power supply
Load resistance
HART Modem
Rosemount 5400 Series Radar Level Transmitter
PC
250 Ohm
Operating Region
Maximum Load Resistance
External Power Supply Voltage
Ed 01 Rev AB November 2012
Rosemount 5400M Series
NON-INTRINSICALLY SAFE POWER SUPPLY
Figure 4-3. Wiring for non­intrinsically safe power supply.
With a non-intrinsically safe power supply in non-hazardous installations or Explosion-proof/Flameproof installations, wire the transmitter as shown in Figure 4-3.
NOTE!
Make sure that the power supply is off when connecting the transmitter.
Figure 4-4. Maximum load resistance for Non-hazardous installation.
A HART Modem require a minimum load resist ance of 250Ohm within the loop to function properly. For maximum loop resistance, see Figure 4-4.
See Figure 4-3 for wiring information.
NOTE!
The diagram is valid only if the HART load resistance is at the + side and if the
- side is grounded, otherwise the load resistance value is limited to 435Ohm.
5
Page 30
Rosemount 5400M Series
NOTE This diagram is valid only if the HART load resistance is at the + side and if the - side is grounded, otherwise the maximum load resistance is limited to 435Ohm.
Operating Region
Maximum Load Resistance
External Power Supply Voltage
Power supply
HART Modem
Rosemount 5400 Series Radar Level Transmitter
Approved IS Barrier
Load resistance
250 Ohm
PC
Figure 4-5. Maximum load resistance for Explosion-Proof/ Flameproof installation.
See Figure 4-6 for wiring information.
NOTE!
For Explosion-proof/Flameproof installations make sure the tran smitter is grounded to the I.S. ground terminal inside the terminal compartment in accordance with national and local electrical codes.
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
INTRINSICALLY SAFE POWER SUPPLY
Figure 4-6. Wiring diagram for intrinsically safe power supply.
With an intrinsically safe power supply, wire the transmitter as shown in Figure 4-6.
NOTE!
Make sure the instruments in the loop are installed according to intrinsically safe field wiring practices.
6
A HART Modem require a minimum load resistance within the loop of 250Ohm to function properly. For maximum load resistance see Figure 4-7.
Page 31
Reference Manual Marine Version
Operating Region
Maximum Load Resistance
External Power Supply Voltage
Ed 01 Rev AB November 2012
IS parameters
U
=30 V.
i
I
=130 mA.
i
P
=1 W.
i
C
=7.26 nF.
i
L
=0 H.
i
Figure 4-7. Maximum load resistance for Intrinsically Safe installation.
Rosemount 5400M Series
7
Page 32
Rosemount 5400M Series
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
8
Page 33
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Rosemount 5400M Series
Section 5 Service and Troubleshooting
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1
Troubleshooting Overview . . . . . . . . . . . . . . . . . . . . . . . . .page 5-2
SAFETY MESSAGES Procedures and instructions in this manual may require special precautions to
ensure the safety of the personnel performing the operations. Infor mation that raises potential safety issues is indicated by a warning symbol ( ). Refer to the safety messages listed at the beginning of each section before performing an operation preceded by this symbol.
NOTE!
The antenna seal assembly, under no circumstances, should be disassembled.
Failure to follow these installation guidelines could result in death or serious injury.
• Make sure only qualified personnel perform the installation.
• Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment.
Explosions could result in death or serious injury.
• Verify that the operating environment of the transmitter is consistent with the appropriate hazardous locations certifications.
• Before connecting a HART make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
• Any substitution of non-recognized parts may jeopardize safety. Repair, e.g. substitution of components etc., may also jeopardize safety and is under no circumstances allowed.
• Substitution of components may impair Intrinsic Safety.
Electrical shock could cause death or serious injury.
• Use extreme caution when making contact with the leads and terminals.
• To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing.
High voltage that may be present on leads could cause electrical shock:
• Avoid contact with leads and terminals.
• Make sure the main power to the 5400 transmitter is off and the lines to any other external power source are disconnected or not powered while wiring the transmitter.
®
-based communicator in an explosive atmosphere,
www.EmersonProcess.com/mtm
Page 34
Rosemount 5400M Series
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
TROUBLESHOOTING OVERVIEW
Table 5-1. Troubleshooting chart
Symptom Possible cause Action
No level reading
No HART communication
Analog Out is set in Alarm
Incorrect level reading
Integral display does not work
Temperature Measurement Failure
Level Measurement Failure
Volume Measurement Failure
No surface echo
(1) If the 5400 transmitter has been exposed to temperatures outside the specified limits, the device may stop its normal oper a t ion. (2) If the 5400 transmitter has been exposed to temperatures outside the specified limits, the device may stop its normal oper a t ion.
(3) A malfunctioning display panel may only be replaced by service personnel at Emerson Process Management Service Department. (4) If the 5400 transmitter has been exposed to temperatures outside the specified limits, the device may stop its normal oper a t ion.
Table 5-1 below gives information on the possible causes of system malfunctions. It also lists the symptoms and necessary actions to be taken.
• Power disconnected
• Data communication cables disconnected
• COM Port configuration does not match the connected COM Port
• Cables may be disconnected
• Wrong HART address is used
• Hardware failure
• HART resistor
• Measurement Failure or Transmitter Failure
• Configuration error
• Disturbing objects in the tank
• Check the power supply
• Check the cables for serial data communication
• Check LED/Display
• Check that correct COM Port is selected in the HART server (see “Specifying the COM Port” on page -14)
• Check the COM port buffer, “Specifying the COM Port” on page -14
• Check wiring diagram
• Verify that the 250 Ohm resistor is in the loop, see Figure 4-10 on page -10
• Check cables
• Make sure that correct HART short address is used. Try address=0
• Check the COM Port Buffer setting, see page -14
• Check Analog Output current value to verify that transmitter hardware works
• Check ambient temperature
• Restart transmitter
• Contact Emerson Process Management Service Department
• Check ambient temperature
• Restart transmitter
• Contact Emerson Process Management Service Department
• Check the display configuration in Rosemount Radar Master (open menu Setup>General)
• Diagnostics
• Contact Emerson Process Management Service Department
• Check ambient temperature
• Restart transmitter
• Contact Emerson Process Management Service Department
• Check Power Supply
• Check the transmitter configuration
• Check that the mechanical installation is correct
• Restart transmitter
• Check transmitter configuration using PC Based configuration tool
• Check signal strength
• Restart transmitter
• Contact Emerson Process Management Service Department
(3)
(1)
(2)
(4)
2
Page 35
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Rosemount 5400M Series
Errors Error messages that may be displayed on the Integral Display, in AMS, or in
the Rosemount Radar Master (RRM) program, are shown in Table 5-2. Errors normally result in Analog Output alarm.
Errors are indicated in RRM in the Diagnostics window.
Table 5-2. Error messages.
Message Description Action
An error in the transmitter data
RAM Error
FPROM Error
HREG Error
MWM Error An error in the microwave module.
Display Error An error in the LCD.
Modem Error Modem hardware failure.
Analog Out Error An error in the Analog Out Module.
Internal Temp Error
Other HW Error
Meas Error
Config Error
SW Error
memory (RAM) has been detected during the startup tests. Note: this resets the transmitter automatically.
An error in the transmitter program memory (FPROM) has been detected during the startup tests. Note: this resets the transmitter automatically.
An error in the transmitter configuration memory (EEPROM) has been detected. The error is either a checksum error that can be solved by loading the default database or a hardware error. NOTE: the default values are used until the problem is solved.
An error in the internal temperature measurement.
An unspecified hardware error has been detected.
A serious measurement error has been detected.
At least one configuration parameter is outside allowed range. NOTE: the default values are used until the problem is solved.
An error has been detected in the transmitter software.
Contact Emerson Process Management Service Department.
Contact Emerson Process Management Service Department.
Load default database and restart the transmitter. Contact Emerson Process Management Service Department if the problem persists.
Contact Emerson Process Management Service Department.
Contact Emerson Process Management Service Department.
Contact Emerson Process Management Service Department.
Contact Emerson Process Management Service Department.
Contact Emerson Process Management Service Department.
Contact Emerson Process Management Service Department.
Contact Emerson Process Management Service Department.
Contact Emerson Process Management Service Department
Contact Emerson Process Management Service Department.
3
Page 36
Reference Manual Marine Version
Ed 01 Rev AB
Rosemount 5400M Series
November 2012
Measurement Status Measurement Status messa ges that may appear on the Integral Display are
shown in Table 5-3:
Table 5-3. Measurement status.
Message Description Action
The transmitter leaves the Full Tank state
Full tank
Empty tank
Reference pulse invalid
Sweep linearization warning The sweep is not correctly linearized.
Tank signal clip warning The last Tank Signal was clipped.
No surface echo
Predicted level Sampling failed The sampling of the last tank signal failed. Check Warning Messages.
Invalid volume value The given volume value is invalid. Check Volume Status for details.
Simulation Mode
Advanced Simulation Mode
Tracking Extra Echo Bottom Projection The bottom projection function is active. Contact Rosemount Tank Radar AB.
Using pipe measurement Pipe Measurement is active. No action needed.
Surface close to registered false echo.
Sudden level jump detected.
The level measurement is in Full Tank state. The transmitter waits for the surface echo to be detected at the top of the tank.
The level measurement is in Empty Tank state. The transmitter waits for the surface echo to be detected at the bottom of the tank.
An error in the reference pulse in the last sampled tank signal.
The Surface Echo Pulse cannot be detected.
The presented level is predicted. The surface echo could not be detected.
The simulation mode is active. The presented measurement values are simulated.
The advanced simulation mode is active. The given measurements are simulated.
The transmitter is in the empty tank state tracking an extra echo.
Close to a registered false echo measurement accuracy may be slightly reduced.
This may result from various measurement problems.
when the product surface gets below the Full Tank Detection Area, see “Full Tank Handling” on page -5 and “Full Tank Handling” on page -10.
The transmitter leaves the Empty Tank state when the product surface gets above the Empty Tank Detection Area, see “Empty Tank Handling” on page -4 and “Empty Tank Handling” on page -7.
Check Warning messages. If MicroWave Module (MWM) Warning is active, this might indicate a transmitter error. Contact Emerson Process Management Service Department.
Check Warning messages. If MWM Warning is active, this might indicate a transmitter error. Contact Emerson Process Management Service Department.
Check Warning Messages. If MWM Warning is active, this might indicate a transmitter error. Contact Emerson Process Management Service Department.
Check if the configuration can be changed so that the surface echo can be tracked in this current region.
See No surface echo above.
No action needed.
Contact Rosemount Tank Radar AB.
Contact Rosemount Tank Radar AB.
By using the Register False Echo function, the transmitter can track the product surface in the vicinity of disturbing objects. Contact Rosemount Tank Radar AB.
Check the tank to find out what causes problem tracking the surface.
4
Page 37
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Rosemount 5400M Series
Volume Calculation Status
Table 5-4. Volume status.
Level is below lowest strapping point.
Level is above highest strapping point.
Level out of range.
Strap table length not valid.
Strap table not valid.
Level not valid.
Volume configuration missing.
Volume not valid. The calculated volume is not valid.
Volume Calculatio n Status messages that may appear on the Integral Display are shown in Table 5-4:
Message Description Action
The measured level is below the lowest point in the given strapping table.
The measured level is above the highest point in the given strapping table.
The measured level is outside the given tank shape.
The configured strap table length is too small or too large.
The strapping table is not correctly configured.
The measured level is not valid. No volume value can be calculated.
No volume calculation method is chosen.
For a correct volume calculation in this region, change the strapping table.
For a correct volume calculation in this region, change the strapping table.
Check if the correct tank type is chosen, and check the configured Tank Height.
Change the strapping table size to a valid number of strapping points. A maximum number of 20 strapping points can be entered.
Check that both level and volume values in the strapping table are increasing with strapping table index.
Check Measurement Status, W arning, and Error Messages.
Configure Volume. Check the other volume status
messages for the reason.
5
Page 38
Reference Manual Marine Version
Ed 01 Rev AB
Rosemount 5400M Series
November 2012
Analog Output Status Analog Output Status messages that may appear on the Integral Display are
shown in Table 5-5:
Table 5-5. Analog Output status.
Message Description Action
Not connected
Alarm Mode The analog output is in Alarm Mode.
Saturated
Multidrop
Fixed Current mode
Invalid Limits
Analog output hardware is not connected.
The analog output signal value is saturated, i.e. equal to the saturation value.
The transmitter is in Multidrop Mode. The analog output is fixed at 4 mA.
The analog output is in fixed current mode.
The given Upper and Lower Range Values are invalid.
Contact Emerson Process Management Service Department.
Check Error and Warning Messages to find the reason for the Alarm.
No action needed.
This is the normal setting when a device is used in Multidrop configuration.
This mode is used when calibrating the Analog Output channel.
Check that the difference between the Upper and Lower Range Value is greater than the Minimum Span.
6
Page 39
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Rosemount 5400M Series
Section 6 Reference Data
SPECIFICATIONS
General
Product Rosemount 5400 Series Radar Level Transmitter Measurement Principle Microwave Output Power < 1 mW
Beam Angle 4" Cone Antenna 9°
Measuring Performance
Measuring Range 30 ft (10 m) from flange Instrument Accuracy at reference conditions
(2)
Repeatability ± 0.04 in. (± 1 mm) at 16.4 ft (5 m) distance Resolution 0.04 in. (1 mm) Near Zone Distance 1.3 ft (0.4 m) from lower end of the antenna Near Zone Accuracy 5402: ± 0.6 in. (± 15 mm) Transition Zone Minimum Dielectric Constant Temperature Drift 0.05 %/10 K in temperature range -40°F to 176°F (-40°C to 80°C) Update Interval 1 second Max Level Rate 1.6 in./s (40 mm/s) as default, adjustable to 7.9 in./s (200 mm/s)
Display / Configuration / Communication
Integral Display
Output Variables
Output Units
Configuration Tools
(3)
Pulsed, free propagating radar 5402: ~26 GHz
(1)
5402: ± 0.1 in. (± 3 mm)
6 in. (150 mm) from lower end of the antenna
ε
= 1.4
r
5-digit integral display. The process variables listed below can be presented. If more than one variable is chosen, carousel toggling of data is used. The display also shows diagnostics and error information.
Level, Distance, Volume, Level Rate, Signal Strength, Internal Temperature, Analog Output Current, and % of Range
Level and Distance: ft, inch, m, cm or mm Volume: ft Level Rate: ft/s, m/s Temperature: °F, °C
HART Suite or any other EDDL or enhanced-EDDL host.
3
, inch3, US gals, Imp gals, barrels, yd3, m3, or liters
®
: Rosemount RadarMaster, Rosemount 275/375 Handheld Communicator, AMS
www.EmersonProcess.com/mtm
Page 40
Reference Manual Marine Version
Ed 01 Rev AB
Rosemount 5400M Series
Electric
Terminal Supply Voltage See “Power Requirements” on page -3 Internal Power Consumption < 50 mW in normal operation Output HART
Signal on Alarm (configurable), HART
Saturation Levels, HART
®
®
IS Parameters See “Product Certifications” on page -1
Cable Entry
Output Cabling 18-12 AWG, twisted shielded pairs
Mechanical
Antennas 4” cone antenna
Material Exposed to Tank Atmosphere
Housing / Enclosure SST Grade CF8M (ASTM A743) Dimensions and Weights
Environment
Ambient Temperature
(4)
Storage Temperature -58°F to 194°F (-50°C to 90°C). LCD: -40°F to 185°F (-40°C to 85 °C) Flange Temperature 120°C for 10K and 100°C for PN16 . Process Pressure PN16 / 10K . Humidity 0 - 100% Relative Humidity, non condensating Factory Sealed Yes Ingress Protection Type 4X, IP66, IP67 EU Directive compliance CE mark, 93/68/EEC Radio Approvals
(5)(6)
Pressure Equipment Directive (PED) 97/23/EC Certification Marine type approved according to E10 IACS E10, ABS, BV, DNV, GL, LR, RS
(1) Ideal metal plate with no disturbing objects.
Temperature: + 68 °F (20 °C). Pressure: 14-15 psi (960-1060 mbar).
Humidity: 25-75 % RH. (2) If the reference conditions are not met, an offset adjustment for the zero reference point may be necessary. The offset may be up to (3) The measurement accuracy is reduced within the Transition Zone region 6 in. (150 mm) from the lower end of the antenna. (4) Temperature may be limited by the selected product certificate, see “Product Certifications” on page -1. (5) Only a limited selection is presented. Contact your local Emerson Process Management representative for more information. (6) For Japan: “Install device on tanks or pipes made of metal”. (7) For 5402: “This device is authorized for use in tank-mounted applications, including metal tanks as well as concrete, plastic, glass and other non-conductive
tanks.”
®
4-20 mA current loop
High=21.75 mA (standard setting) Low=3.75 mA (option, model code C8) Namur NE43: High=22.5 mA (option, model code C4)
Standard: Low=3.9 mA, High=20.8 mA Namur NE43: Low=3.8 mA, High=20.5 mA
Two integrated ½-in. NPT threads. One metal plug to seal any unused ports and one cable gland is enclosed with the transmitter delivery.
Cone Antenna
• 316 / 316 L SST (EN 1.4404)
• PTFE fluoropolymer
• O-ring material, fluorosilicone
11 kg (DN100 PN16/ JIS 10K-100A), 12.5kg (DN150 PN16 /JIS 10K – 150A).
LCD readable in: -4°F to 158°F (-20°C to 70°C).
FCC part 15C (1998)
(7)
, R&TTE (EU directive 1999/5/EC), and IC (RSS210-5)
November 2012
± 10 mm.
2
Page 41
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Rosemount 5400M Series
Section 7 Product Certifications
Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-1
EU Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 7-2
European ATEX Directive Information . . . . . . . . . . . . . . . page 7-3
Hazardous Locations Certifications . . . . . . . . . . . . . . . . .page 7-5
EX Approval Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-8
SAFETY MESSAGES Procedures and instructions in this section may require special precautions to
ensure the safety of the personnel performing the operations. Infor mation that raises potential safety issues is indicated by a warning symbol ( ). Please refer to the following safety messages before performing an operation preceded by this symbol.
Explosions could result in death or serious injury:
Verify that the operating environment of the transmitter is consistent with the appropriate hazardous locations certifications.
Before connecting a HART-based communicator in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non­incendive field wiring practices.
Do not remove the transmitter cover in explosive atmospheres when the circuit is alive.
Failure to follow safe installation and servicing guidelines could result in death or serious injury:
Make sure the transmitter is installed by qualified personnel and in accordance with applicable code of practice.
Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment.
Do not perform any service other than those contained in this manual unless you are qualified.
Substitution of components may impair Intrinsic Safety. To prevent ignition of flammable or combustible atmospheres, disconnect power before
servicing.
www.EmersonProcess.com/mtm
Page 42
Reference Manual Marine Version
Ed 01 Rev AB
Rosemount 5400M Series
High voltage that may be present on leads could cause electrical shock:
Avoid contact with leads and terminals. Make sure the main power to the Radar Transmitter is off and the lines to any other
external power source are disconnected or not powered while wiring the transmitter.
November 2012
EU CONFORMITY The EC declaration of conformity for all applicable European directives for this
product can be found on the Emerson Process Management website at www.emersonprocess.com/mtm. A hard copy may be obtained by contacting our local sales representative.
2
Page 43
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Rosemount 5400M Series
EUROPEAN ATEX DIRECTIVE INFORMATION
Intrinsic Safety The Rosemount 5400 Series Tr ansmitter with the following attached label has
been certified to comply with Directive 94/9/EC of the European Parliament and the Council as published in the Official Journal of the European Communities No. L 100/1 on 19-April-1994.
Figure 7-1. Approval Label ATEX
I1 The following information is provided as part of the label of the
transmitter:
Name and address of the manufacturer (Rosemount).
CE Conformity Marking
Complete model number
The serial number of the device
Year of construction
Marking for explosion protection:
EEx ia IIC T4 (-50 °C
4-20 mA/HART model: Ui=30 V, Ii=130 mA, Pi=1.0 W, Ci=7.26 nF, Li=0.
Nemko ATEX certificate number: Nemko 04ATEX1073X
Installation Drawing: 9150 079-907
Special Conditions for Safe Use (X)
The intrinsically safe circuits do not withstand the 500V AC test as specified in EN 50020 clause 6.4.12.
Parts of the rod-antenna and the All PTFE antenna are no n-conducting and the area of the non-conducting part exceeds the maximum permissible areas for Group IIC according to EN 50014 clause 7.3 (20 cm according to EN 50284 clause 4.4.3 (4 cm used in a potentially explosive atmosphere, appropriate measures must be taken to prevent electrostatic discharge.
Impact and friction hazards need then to be considered according to EN 50284 clause 4.3.1 when the transmitter and part of antennas exposed to the exterior atmosphere of the tank is made with light metal alloys and used in category II 1 G.
(1) Other temperature restrictions may apply, please refer to “Temperature and Pressure Rat-
ings” on page -4.
Ta +70 °C)
(1)
2
2
). Therefore, when the antenna is
) and Category II 1 G
3
Page 44
Reference Manual Marine Version
Ed 01 Rev AB
Rosemount 5400M Series
November 2012
Flameproof The Rosemount 5400 Series Tr ansmitter with the following attached label has
been certified to comply with Directive 94/9/EC of the European Parliament and the Council as published in the Official Journal of the European Communities No. L 100/1 on 19-April-1994.
Figure 7-2. Approval Label ATEX
E1 The following information is provided as part of the label of the
transmitter:
Name and address of the manufacturer (Rosemount).
CE Conformity Marking
Complete model number
The serial number of the device
Year of construction
Marking for explosion protection:
EEx iad IIC T4 (-40
•U
=250 V
m
Nemko ATEX certificate number: Nemko 04ATEX1073X
Special Conditions for Safe Use (X)
The intrinsically safe circuits do not withstand the 500V AC test as specified in EN 50020 clause 6.4.12.
Parts of the rod-antenna and the All PTFE antenna are no n-conducting and the area of the non-conducting part exceeds the maximum permissible areas for Group IIC according to EN 50014 clause 7.3 (20 cm according to EN 50284 clause 4.4.3 (4 cm used in a potentially explosive atmosphere, appropriate measures must be taken to prevent electrostatic discharge.
Impact and friction hazards need then to be considered according to EN 50284 clause 4.3.1 when the transmitter and part of antennas exposed to the exterior atmosphere of the tank is made with light metal alloys and used in category II 1 G.
°C<Ta< +70 °C)
2
2
). Therefore, when the antenna is
) and Category II 1 G
4
Page 45
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Rosemount 5400M Series
HAZARDOUS LOCATIONS CERTIFICATIONS
Factory Mutual (FM) Approvals
Figure 7-3. Approval Labels Factory Mutual (FM)
The Rosemount 5400 Series Transmitters with the following attached labels have been certified to comply with the requirements of the approval agencies noted.
Project ID: 3020497.
E5 Explosion-Proof for Class I, Division 1, Groups B, C and D.
Dust-Ignition proof for Class II/III, Division 1, Groups E, F and G with intrinsically safe connections to Class I, II, III, Div 1, Groups B, C, D, E, F and G.
Temperature code T4. Ambient temperature limits: -50 Seal not required.
I5 Intrinsically Safe for Class I, II, III, Division 1, Groups A, B, C, D, E, F
and G. Class I, Zone 0, AEX ia IIC T4 when installed per Control Drawing: 9150079-905.
Non-incendive for Class I, Division 2, Groups A, B, C and D. Suitable for Class II, III, Division 2, Groups F and G;
Max operation 42.4 V, 25 mA. Temperature code T4.
Ambient Temperature Limits: -50
°C to + 70 °C.
°C to + 70 °C.
5
Page 46
Rosemount 5400M Series
IECEx Approval I7 Intrinsic Safety
Figure 7-4. Approval Label IECEx Intrinsic Safety
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
Ex ia IIC T4 (T IECEx NEM 06.0001X. Ui=30 V, Ii=130 mA, Pi=1 W, Ci=7.25 nF, Li=0 mH. Installation Drawing: 9150 079-907.
Conditions of Certification
The intrinsically safe circuits do not withstand the 500V AC test as specified in EN 50020 clause 6.4.12.
Impact and friction hazards need then to be considered according to IEC 60079-0 clause 8.1.2 when the transmitter and pa rt of antennas exposed to the exterior atmosphere of the tank is made with light metal alloys and used in Zone 0.
Parts of the rod-antenna and the All PTFE antenna are no n-conducting and the area of the non-conducting part exceeds the maximum permissible areas for Group IIC according to IEC 60079-1 clause 7.3: 20 cm
2
cm
for Zone 0. Therefore, when the antenna is used in a po tentially explosive atmosphere, appropriate measures must be taken to prevent electrostatic discharge.
= -50 °C to +70 °C)
amb
(1)
.
2
for Zone 1 and 4
(1) Other temperature restrictions may apply, please refer to “Specifications” on page -1.
6
Page 47
Reference Manual Marine Version
Ed 01 Rev AB November 2012
E7 Flameproof
Figure 7-5. Approval Labels IECEx Flameproof
Rosemount 5400M Series
Ex iad IIC T4 (T IECEx NEM 06.0001X.
Conditions of Certification
The intrinsically safe circuits do not withstand the 500V AC test as specified in EN 50020 clause 6.4.12.
Impact and friction hazards need then to be considered according to IEC 60079-0 clause 8.1.2 when the transmitter and pa rt of antennas exposed to the exterior atmosphere of the tank is made with light metal alloys and used in Zone 0.
:-40° C to +70 °C).
amb
7
Page 48
Rosemount 5400M Series
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
EX APPROVAL DRAWINGS
This section contains Factory Mutual and Canadian Standards Association system control drawings and an ATEX installation drawing. The installation guidelines must be followed to maintain certified ratings for installed transmitters.
This section contains the following drawings: Rosemount Drawing 9150079-905: System Control Drawing for hazardous location installation of intrinsically safe
FM approved apparatus. Rosemount Drawing 9150079-907: Installation Drawing for hazardous location installation of ATEX and IECEx
approved apparatus.
8
Page 49
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Figure 7-6. System Control Drawing for hazardous location inst allati on of intri nsically safe FM approved app ar atus.
Rosemount 5400M Series
9
Page 50
Reference Manual Marine Version
Ed 01 Rev AB
Rosemount 5400M Series
Figure 7-7. Installation Drawing for hazardous location installation of ATEX and IECEx approved apparatus.
November 2012
10
Page 51
Reference Manual Marine Version
Ed 01Rev AB November 2012
Index
Rosemount 5400M Series
A
AMS Suit . . . . . . . . . . . . . . . 2-3
Analog Output Status . . . . . . . 5-6
Antenna . . . . . . . . . . . . . . . . 2-2
Approval Drawings . . . . . . . . . 7-8
C
Cable entry . . . . . . . . . . . . . . 2-2
Cable gland . . . . . . . . . . . . . 3-10
Cable Protection Hose . . . . . 3-11
Cable Selection . . . . . . . . . . . 4-3
Cable/conduit entries . . . . . . . 4-2
Canadian Standards Association
approval system control drawing . 7-10
Components
Antenna
Cable Entry . . . . . . . . . . 2-2
Display Panel . . . . . . . . . 2-2
Flange . . . . . . . . . . . . . . 2-2
Tank Seal . . . . . . . . . . . . 2-2
Terminal side . . . . . . . . . 2-2
CPH . . . . . . . . . . . . . . . . . . 3-11
. . . . . . . . . . . . . 7-5
. . . . . . . . . . . . . 2-2
D
Diagnostic Messages . . . . . . . 5-3
Dielectric constant . . . . . . . . . 2-4
Display panel . . . . . . . . . . . . 2-2
E
Electrical installation
connecting the transmitter Intrinsically Safe Output . . 4-6
Non-Intrinsically Safe Output 4-5
Errors . . . . . . . . . . . . . . . . . . 5-3
European ATEX Directive Information
4-4
7-3
External circuit breaker . . . . . . 4-3
F
Factory Mutual
approval
system control drawing . . 7-9
Flange . . . . . . . . . . . . . . . . . 2-2
Foam . . . . . . . . . . . . . . . . . . 2-4
. . . . . . . . . . . . . 7-5
G
Grounding . . . . . . . . . . . . . . 4-3
H
Hazardous Locations Certifications
7-5
I
Installation
cable selection
cable/conduit entries . . . . 4-2
grounding . . . . . . . . . . . 4-3
placement considerations 3-3
power requirements . . . . 4-3
procedure . . . . . . . . . . . 3-2
. . . . . . . . 4-3
L
Loop-powered . . . . . . . . . . . . 2-3
M
Marine Application Characteristics 2-4 Maximum load resistance .4-5, 4-6
Measurement principle . . . . . . 2-1
Measurement Status . . . . . . . 5-4
Mounting requirements . . . . . 3-3
P
Power Requirements . . . . . . . 4-3
Product Certifcates . . . . . . . . 7-1
R
Rosemount 751 . . . . . . . . . . 2-3
S
System Integration . . . . . . . . 2-3
T
Tank height . . . . . . . . . . . . . 2-1
Tank Seal . . . . . . . . . . . . . . . 2-2
Temperature and Pressure Ratings
6-2
TGU 51xx
Mounting . . . . . . . . . . . 3-10
Theory of Operation . . . . . . . 2-1
Transition Zone . . . . . . . . . . . 2-4
Transmitter head . . . . . . . . . .2-2
V
Volume Calculation Status . . . .5-5
www.EmersonProcess.com/mtm
Page 52
Rosemount 5400 Series
Reference Manual Marine Version
Ed 01 Rev AB
November 2012
Index-2
Page 53
Page 54
Reference Manual Marine Version
Ed 01 Rev AB November 2012
Rosemount 5400M Series
The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. The content of this publication are presented f or information purposes only, and while e fforts have been made to ensure their accuracy, they are not to be construed as warranties or guarantees, expressed or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice. Rosemount Tank Radar AB accepts no responsibility for any errors that may appear in this publication.
As each system may be configured for each delivery, the content and illustrations in this manual may differ from your system.
© 2012 Rosemount Inc. All rights reserved.
Marine Tank Management
Emerson Process Management Rosemount Tank Radar AB Box 13045 SE-40251 Sweden T +46 31 337 00 00 F +46 31 25 30 22 www.EmersonProcess.com/mtm
Loading...