About the cold temperature option code BR5.............................................................................. 4
Perform Trim Near Zone...............................................................................................................7
Surface threshold for option code BR5......................................................................................... 9
Surface threshold for option code BR5 in combination with High Level Supervision....................11
2Rosemount 5300 Level Transmitter
July 2020Manual Supplement
1Safety messages
WARNING
Failure to follow safe installation and servicing guidelines could result in
death or serious injury.
• Only qualified personnel should install the equipment.
• Use the equipment only as specified in this guide and the Reference
Manual. Refer to the Rosemount 5300 Level Transmitter Reference
Manual for more instruction.
Explosions could result in death or serious injury.
• Installation of device in an explosive environment must be in accordance
with appropriate local, national, and international standards, codes, and
practices.
• Ensure device is installed in accordance with intrinsically safe or non-
incendive field practices.
Electrical shock could cause death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be
present on leads can cause electrical shock.
• Ensure the mains power to the transmitter is off and the lines to any
other external power source are disconnected or not powered while
wiring the transmitter.
Process leaks could result in death or serious injury.
• Handle the transmitter carefully.
• If the process seal is damaged, gas could escape from the tank when
removing the transmitter head from the probe.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or
misconfiguration of end users’ equipment. This could be intentional or
unintentional and needs to be protected against.
Physical security is an important part of any security program and
fundamental to protecting your system. Restrict physical access by
unauthorized personnel to protect end users’ assets. This is true for all
systems used within the facility.
Manual Supplement3
Manual SupplementJuly 2020
2About the cold temperature option code BR5
The Rosemount 5300 Level Transmitter with option code BR5 has been
factory configured for best performance in cold ambient temperature, down
to -67 °F (-55 °C).
This document describes option code BR5 factory settings and required
commissioning, for Rosemount 5300 with single probes.
For general Rosemount 5300 information, refer to the Rosemount 5300
Level Transmitter Product Data Sheet.
High Level Supervision (HLS)
Specific instructions for HLS in combination with option code BR5 are
described in this document. For general HLS information and instructions,
refer to the High Level Supervision Manual Supplement.
2.1Required commissioning
The Trim Near Zone function shall be performed during commissioning, see
section Perform Trim Near Zone for further instructions.
2.2Specification
Rosemount 5300 option code BR5 specification is listed in Table 2-1.
Ambient temperature range during
operation for HLS
Start-up timeSee Start-up sequence
(1) Requires calibration performed within proper ambient temperature range, see
High Level Supervision Manual Supplement.
4Rosemount 5300 Level Transmitter
factory settings
• Surface threshold for option code BR5 in
combination with HLS - factory settings
-67 °F to 158 °F (-55 °C to +70 °C)
(1)
$
&
%
)
(
'
July 2020Manual Supplement
2.3Start-up sequence
The Rosemount 5300 start-up time is normally <40 s. However for devices
with option code BR5 at temperatures below -40 °F (-40 °C), the start-up
sequence is delayed for five minutes with an undefined current value. Refer
to Figure 2-1 and Figure 2-2.
Figure 2-1: Start-Up Sequence, Alarm Mode High
A. Current, mA
B. Time, s
C. High Alarm current (Rosemount or Namur value, according to
configuration)
D. Actual level value
E. Low Alarm current (Rosemount or Namur value, according to
configuration)
F. For option code BR5 at temperatures below -40 °F (-40 °C): Five minutes
delay with an undefined current value
Manual Supplement5
$
&
%
)
(
'
Manual SupplementJuly 2020
Figure 2-2: Start-Up Sequence, Alarm Mode Low
A. Current, mA
B. Time, s
C. High Alarm current (Rosemount or Namur value, according to
configuration)
D. Actual level value
E. Low Alarm current (Rosemount or Namur value, according to
configuration)
F. For option code BR5 at temperatures below -40 °F (-40 °C): Five minutes
delay with an undefined current value
6Rosemount 5300 Level Transmitter
$$
&
%
July 2020Manual Supplement
3Perform Trim Near Zone
During the commissioning of a transmitter with option code BR5, the Trim
Near Zone function shall be performed.
Figure 3-1 displays the effect on the echo curve.
Figure 3-1: Echo Curve Before and After Trim Near Zone
A. Reference Peak
B. Trim Near Zone
C. 0-3.3 ft (0-1 m)
3.1
Manual Supplement7
Perform Trim Near Zone using Rosemount Radar Master
Prerequisites
Before performing the Trim Near Zone, ensure that:
• There is product in the tank.
• The product level is below the Near Zone region (0-3.3 ft (0-1 m) below
the Upper Reference Point).
Procedure
1. Select Setup→Advanced.
2. Select the Near Zone tab.
3. Select Trim Near Zone and follow the on-screen instructions.
4. When near zone trimming is complete, restart the device.
a) Select Tools→Restart Device.
Manual SupplementJuly 2020
3.2Perform Trim Near Zone using AMS or a handheld
communicator
Prerequisites
Before performing the Trim Near Zone, ensure that:
• There is product in the tank.
• The product level is below the Near Zone region (0-3.3 ft (0-1 m) below
2. Select Near Zone→Trim Near Zone and follow the instructions.
3. When near zone trimming is complete, restart the device.
a) HART: Select Service Tools→Maintenance.
FOUNDATION Fieldbus: Select Service Tools→Maintenance→Reset/Restart.
b) Select Restart Device.
8Rosemount 5300 Level Transmitter
July 2020Manual Supplement
4Surface threshold for option code BR5
The surface threshold is pre-configured at factory for transmitters with
option code BR5. It is typically not necessary to make manual adjustments to
the pre-configured surface threshold. Manual adjustments are necessary in
the following cases:
• Configuration in transmitter has been reset to factory settings
• Threshold has been overwritten by other actions
4.1Adjust surface threshold using Rosemount Radar Master
Prerequisites
When adjusting the surface threshold manually, the Trim Near Zone
function shall also be performed.
Note
If the adjusted threshold is set lower than the factory settings, Trim Near
Zone must be performed within 72 °F (40 °C) of the expected ambient
operating temperature. For factory settings, see Surface threshold for
option code BR5 - factory settings.
Procedure
1. Select Setup→Echo Curve.
2. Drag and drop the Amplitude Threshold Curve (ATC) points to adjust
the surface threshold according to factory settings.
3. Click Store to save ATC to device.
Postrequisites
Perform Trim Near Zone (if not already done).
Manual Supplement9
D
A
C
B
Manual SupplementJuly 2020
4.2Surface threshold for option code BR5 - factory settings
Figure 4-1 specifies the surface threshold factory settings for Rosemount
5300 with option code BR5.
Figure 4-1: Surface Threshold for Option Code BR5
A. Surface threshold, pre-configured at factory
B. 1500 mV
C. 700 mV
D. 16 in. (40 cm)
10Rosemount 5300 Level Transmitter
July 2020Manual Supplement
5Surface threshold for option code BR5 in
combination with High Level Supervision
The surface threshold is pre-configured at factory for transmitters with
option code BR5 together with the High Level Supervision option. It is
typically not necessary to make manual adjustments to the surface
threshold. Manual adjustments are necessary in the following cases:
• High Level Supervision is retrofitted on existing transmitter
• Configuration in transmitter has been reset to factory settings
• Threshold around reference reflector has been overwritten by other
actions
5.1Adjust surface threshold using Rosemount Radar Master
Prerequisites
When adjusting the surface threshold manually, the Trim Near Zone
function shall also be performed.
Note
If the adjusted threshold is set lower than the factory settings, Trim Near
Zone must be performed within 72 °F (40 °C) of the expected ambient
operating temperature. For factory settings, see Surface threshold for
option code BR5 in combination with HLS - factory settings.
Procedure
1. Select Setup→Echo Curve.
2. Drag and drop the Amplitude Threshold Curve (ATC) points to adjust
the surface threshold according to factory settings.
3. Click Store to save ATC to device.
Postrequisites
Perform Trim Near Zone (if not already done).
Ensure that installation and configuration is properly performed as described
in the High Level Supervision Manual Supplement.
Manual Supplement11
A
C
B
D
Manual SupplementJuly 2020
5.2Surface threshold for option code BR5 in combination
with HLS - factory settings
The surface threshold factory settings is dependent on device mounting
type, as shown in Table 5-1.
Table 5-1: Surface Threshold Depending on Device Mounting Type
Device mounting typeHLS option
3-in. to 6-in. pipe/chamber (inner diameter)HL1See Figure 5-1
Emerson Terms and Conditions of Sale are
available upon request. The Emerson logo is a
trademark and service mark of Emerson Electric
Co. Rosemount is a mark of one of the Emerson
family of companies. All other marks are the
property of their respective owners.