Rosemount 5300 Level Transmitter Single Probes with Cold Temperature Option Code BR5 Manual Supplement

Manual Supplement
00809-1800-4530, Rev AB
Rosemount™ 5300 Level Transmitter
Single Probes with Cold Temperature Option Code BR5
July 2020
Manual Supplement July 2020
Safety messages...........................................................................................................................3
About the cold temperature option code BR5.............................................................................. 4
Perform Trim Near Zone...............................................................................................................7
Surface threshold for option code BR5......................................................................................... 9
Surface threshold for option code BR5 in combination with High Level Supervision....................11
2 Rosemount 5300 Level Transmitter
July 2020 Manual Supplement

1 Safety messages

WARNING
Failure to follow safe installation and servicing guidelines could result in death or serious injury.
Only qualified personnel should install the equipment.
Use the equipment only as specified in this guide and the Reference
Manual. Refer to the Rosemount 5300 Level Transmitter Reference
Manual for more instruction.
Explosions could result in death or serious injury.
Installation of device in an explosive environment must be in accordance
with appropriate local, national, and international standards, codes, and practices.
Ensure device is installed in accordance with intrinsically safe or non-
incendive field practices.
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be
present on leads can cause electrical shock.
Ensure the mains power to the transmitter is off and the lines to any
other external power source are disconnected or not powered while wiring the transmitter.
Process leaks could result in death or serious injury.
Handle the transmitter carefully.
If the process seal is damaged, gas could escape from the tank when
removing the transmitter head from the probe.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
Manual Supplement 3
Manual Supplement July 2020

2 About the cold temperature option code BR5

The Rosemount 5300 Level Transmitter with option code BR5 has been factory configured for best performance in cold ambient temperature, down to -67 °F (-55 °C).
This document describes option code BR5 factory settings and required commissioning, for Rosemount 5300 with single probes.
For general Rosemount 5300 information, refer to the Rosemount 5300 Level Transmitter Product Data Sheet.
High Level Supervision (HLS)
Specific instructions for HLS in combination with option code BR5 are described in this document. For general HLS information and instructions, refer to the High Level Supervision Manual Supplement.

2.1 Required commissioning

The Trim Near Zone function shall be performed during commissioning, see section Perform Trim Near Zone for further instructions.

2.2 Specification

Rosemount 5300 option code BR5 specification is listed in Table 2-1.
Table 2-1: Rosemount 5300 Option Code BR5 Specification
Option code BR5
Firmware version Requires version 2.M0 or later
Surface threshold factory settings Surface threshold for option code BR5 -
Ambient temperature range during operation for HLS
Start-up time See Start-up sequence
(1) Requires calibration performed within proper ambient temperature range, see
High Level Supervision Manual Supplement.
4 Rosemount 5300 Level Transmitter
factory settings
Surface threshold for option code BR5 in
combination with HLS - factory settings
-67 °F to 158 °F (-55 °C to +70 °C)
(1)
$
&
%
)
(
'
July 2020 Manual Supplement

2.3 Start-up sequence

The Rosemount 5300 start-up time is normally <40 s. However for devices with option code BR5 at temperatures below -40 °F (-40 °C), the start-up sequence is delayed for five minutes with an undefined current value. Refer to Figure 2-1 and Figure 2-2.
Figure 2-1: Start-Up Sequence, Alarm Mode High
A. Current, mA B. Time, s C. High Alarm current (Rosemount or Namur value, according to
configuration)
D. Actual level value
E. Low Alarm current (Rosemount or Namur value, according to
configuration)
F. For option code BR5 at temperatures below -40 °F (-40 °C): Five minutes
delay with an undefined current value
Manual Supplement 5
$
&
%
)
(
'
Manual Supplement July 2020
Figure 2-2: Start-Up Sequence, Alarm Mode Low
A. Current, mA B. Time, s C. High Alarm current (Rosemount or Namur value, according to
configuration)
D. Actual level value
E. Low Alarm current (Rosemount or Namur value, according to
configuration)
F. For option code BR5 at temperatures below -40 °F (-40 °C): Five minutes
delay with an undefined current value
6 Rosemount 5300 Level Transmitter
$$
&
%
July 2020 Manual Supplement

3 Perform Trim Near Zone

During the commissioning of a transmitter with option code BR5, the Trim Near Zone function shall be performed.
Figure 3-1 displays the effect on the echo curve.
Figure 3-1: Echo Curve Before and After Trim Near Zone
A. Reference Peak B. Trim Near Zone C. 0-3.3 ft (0-1 m)
3.1
Manual Supplement 7

Perform Trim Near Zone using Rosemount Radar Master

Prerequisites
Before performing the Trim Near Zone, ensure that:
There is product in the tank.
The product level is below the Near Zone region (0-3.3 ft (0-1 m) below
the Upper Reference Point).
Procedure
1. Select Setup Advanced.
2. Select the Near Zone tab.
3. Select Trim Near Zone and follow the on-screen instructions.
4. When near zone trimming is complete, restart the device. a) Select Tools Restart Device.
Manual Supplement July 2020

3.2 Perform Trim Near Zone using AMS or a handheld communicator

Prerequisites
Before performing the Trim Near Zone, ensure that:
There is product in the tank.
The product level is below the Near Zone region (0-3.3 ft (0-1 m) below
the Upper Reference Point).
Procedure
1. HART®: Select Overview Echo Tuning.
FOUNDATION™ Fieldbus: Configure Manual Setup Avanced.
2. Select Near Zone Trim Near Zone and follow the instructions.
3. When near zone trimming is complete, restart the device. a) HART: Select Service Tools Maintenance.
FOUNDATION Fieldbus: Select Service Tools Maintenance Reset/Restart.
b) Select Restart Device.
8 Rosemount 5300 Level Transmitter
July 2020 Manual Supplement

4 Surface threshold for option code BR5

The surface threshold is pre-configured at factory for transmitters with option code BR5. It is typically not necessary to make manual adjustments to the pre-configured surface threshold. Manual adjustments are necessary in the following cases:
Configuration in transmitter has been reset to factory settings
Threshold has been overwritten by other actions

4.1 Adjust surface threshold using Rosemount Radar Master

Prerequisites
When adjusting the surface threshold manually, the Trim Near Zone function shall also be performed.
Note
If the adjusted threshold is set lower than the factory settings, Trim Near Zone must be performed within 72 °F (40 °C) of the expected ambient operating temperature. For factory settings, see Surface threshold for
option code BR5 - factory settings.
Procedure
1. Select Setup Echo Curve.
2. Drag and drop the Amplitude Threshold Curve (ATC) points to adjust the surface threshold according to factory settings.
3. Click Store to save ATC to device.
Postrequisites
Perform Trim Near Zone (if not already done).
Manual Supplement 9
D
A
C
B
Manual Supplement July 2020

4.2 Surface threshold for option code BR5 - factory settings

Figure 4-1 specifies the surface threshold factory settings for Rosemount
5300 with option code BR5.
Figure 4-1: Surface Threshold for Option Code BR5
A. Surface threshold, pre-configured at factory B. 1500 mV C. 700 mV
D. 16 in. (40 cm)
10 Rosemount 5300 Level Transmitter
July 2020 Manual Supplement
5 Surface threshold for option code BR5 in
combination with High Level Supervision
The surface threshold is pre-configured at factory for transmitters with option code BR5 together with the High Level Supervision option. It is typically not necessary to make manual adjustments to the surface threshold. Manual adjustments are necessary in the following cases:
High Level Supervision is retrofitted on existing transmitter
Configuration in transmitter has been reset to factory settings
Threshold around reference reflector has been overwritten by other
actions

5.1 Adjust surface threshold using Rosemount Radar Master

Prerequisites
When adjusting the surface threshold manually, the Trim Near Zone function shall also be performed.
Note
If the adjusted threshold is set lower than the factory settings, Trim Near Zone must be performed within 72 °F (40 °C) of the expected ambient operating temperature. For factory settings, see Surface threshold for
option code BR5 in combination with HLS - factory settings.
Procedure
1. Select Setup Echo Curve.
2. Drag and drop the Amplitude Threshold Curve (ATC) points to adjust the surface threshold according to factory settings.
3. Click Store to save ATC to device.
Postrequisites
Perform Trim Near Zone (if not already done).
Ensure that installation and configuration is properly performed as described in the High Level Supervision Manual Supplement.
Manual Supplement 11
A
C
B
D
Manual Supplement July 2020

5.2 Surface threshold for option code BR5 in combination with HLS - factory settings

The surface threshold factory settings is dependent on device mounting type, as shown in Table 5-1.
Table 5-1: Surface Threshold Depending on Device Mounting Type
Device mounting type HLS option
3-in. to 6-in. pipe/chamber (inner diameter) HL1 See Figure 5-1
8-in. pipe/chamber (inner diameter) HL2 See Figure 5-2
10-in. pipe/chamber or bigger (inner diameter) or Open tank (tank without pipe)
code
HL3 See Figure 5-2
Surface threshold factory settings
Figure 5-1: Surface Threshold for Option Code BR5 Together with HL1, (3-in. to 6-in. Pipe/Chamber)
A. Surface threshold, pre-configured at factory B. 1500 mV C. 700 mV
D. 13 ft. (4.4 m)
12 Rosemount 5300 Level Transmitter
A
C
B
D
July 2020 Manual Supplement
Figure 5-2: Surface Threshold for Option Code BR5 Together with HL2/ HL3, (8-in. Pipe/Chamber or Bigger, or Open Tank)
A. Surface threshold, pre-configured at factory B. 900 mV C. 700 mV
D. 13 ft. (4.4 m)
Manual Supplement 13
Manual Supplement July 2020
14 Rosemount 5300 Level Transmitter
July 2020 Manual Supplement
Manual Supplement 15
*00809-1800-4530*
Manual Supplement
00809-1800-4530, Rev. AB
July 2020
Emerson Automation Solutions
6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com
Latin America Regional Office
Emerson Automation Solutions 1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office
Emerson Automation Solutions 1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com
North America Regional Office
Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com
Europe Regional Office
Emerson Automation Solutions Europe GmbH Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465 RFQ.RMTMEA@Emerson.com
Linkedin.com/company/Emerson-
Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/
RosemountMeasurement
©
2020 Emerson. All rights reserved.
Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners.