Rosemount 485 Annubar Threaded Flo-Tap Assembly Quick Start Guide

Quick Start Guide
00825-0500-4809, Rev EB
June 2016
Rosemount™ 485 Annubar™ Threaded Flo-Tap Assembly
Quick Start Guide
June 2016
NOTICE
This guide provides basic guidelines for Rosemount 485 Annubar. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or Intrinsically Safe (I.S.) installations. Refer to Rosemount 485 Annubar Reference Manual instruction. This manual is also available electronically on Emerso nProcess.com/Rosemount
If the Rosemount Annubar was ordered assembled to a Rosemount Pressure Transmitter, see the following Quick Start Guides for information on configuration and hazardous locations certifications:
Rosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flowmeter Quick Start
Guide.
Rosemount 3051S MultiVariable Transmitter and Rosemount 3051SF Series Flowmeter MultiVariable
Tra ns mi tte r Quick Start Guide
Rosemount 3051 Pressure Transmitter and Rosemount 3051CF Series Flowmeter Transmitter Quick
Start Guide.
Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flowmeter Transmitter Quick
Start Guide.
Process leaks may cause harm or result in death. To avoid process leaks, only use gaskets designed to seal with the corresponding flange and o-rings to seal process connections. Flowing medium may cause the Rosemount 485 Annubar Assembly to become hot and could result in burns.
.
for more
.
Contents
Location and orientation. . . . . . . . . . . . . . . . . . 4
Weld mounting hardware. . . . . . . . . . . . . . . . . 8
Install isolation valve . . . . . . . . . . . . . . . . . . . . . 9
Mount drilling machine and drill hole . . . . . . 9
Mount the Rosemount Annubar Assembly . 10
2
Insert the Rosemount Annubar Sensor . . . . . . 11
Mount the transmitter . . . . . . . . . . . . . . . . . . . . 12
Retracting the Rosemount Annubar Assembly 18
Product certifications . . . . . . . . . . . . . . . . . . . . . 19
June 2016
Quick Start Guide
Figure 1. Rosemount 485 Annubar Threaded Flo-Tap Assembly Exploded View
O
N
M
P
L
A
B C D
K
E
J
F
I
H
G
A. Transmitter I. Isolation valve
B. Coplanar flange with drain vents J.Cage nipple
C. Temperature sensor connection housing K. Support plate
D. Direct mount transmitter connection with valves L. Packing gland
E. Head plate M. Packing
F. D ri ve ro ds N. Follower
G. Threaded pipe fitting O. Compression plate
H. Guide nipple P. 2 O-rings
Note
Use an appropriate pipe sealing compound rated for the service temperature on all threaded connections.
3
Quick Start Guide

1.0 Location and orientation

Correct orientation and straight run requirements must be met for accurate and
repeatable flow measurements. Refer to Table 1 for minimum pipe diameter distances from upstream disturbances.
Table 1. Straight Run Requirements
In plane____________Out of plane Upstream pipe diameters
June 2016
Without
straightening
vanes
In
Out of
plane
plane
A
8
1
N/A10N/A
11
2
N/A16N/A
23
3
With straightening
vanes
A’ C C’ B
A
N/A8N/A4N/A
N/A8N/A4N/A
N/A8N/A4N/A
Downstream
pipe diameters
4
4
4
4
4
4
4
N/A28N/A
12
4
N/A12N/A
N/A8N/A4N/A
4
4
4
4
4
4
June 2016
Quick Start Guide
18
5
N/A18N/A
30
6
N/A30N/A
N/A8N/A4N/A
4
N/A8N/A4N/A
4
Note
Consult the factory for instructions regarding use in square or rectangular
ducts.
“In plane A” means the sensor is in the same plane as the elbow. “Out of plane
A” means the sensor is perpendicular to the plane of the elbow.
If proper lengths of straight run are not available, position the mounting such
that 80% of the run is upstream and 20% is downstream.
Use straightening vanes to reduce the required straight run length. Row 6 in Ta bl e 1 applies to gate, globe, plug, and other throttling valves that
are partially opened, as well as control valves.
4
4
4
4

1.1 Misalignment

Rosemount 485 installation allows for a maximum misalignment of 3°.
Figure 2. Misalignment
±3°
±3° ±3°
5
Quick Start Guide

1.2 Horizontal orientation

For proper venting and draining, the sensor should be located in the upper half of
the pipe for air and gas applications. For liquid and steam applications, the sensor should be located in the bottom half of the pipe. The maximum temperature for a direct mounted transmitter is 500 °F (260 °C).
Figure 3. Gas
Recommended zone
30°
June 2016
Figure 4. Liquid and Steam
Recommended zone
30°
Note
Top mounting for steam applications is an appropriate mounting option in many cases. Consult Rosemount Customer Central instructions regarding steam on top mounting.
6
June 2016
360°
360°
Flow
Quick Start Guide

1.3 Vertical orientation

The sensor can be installed in any position around the circumference of the pipe provided the vents are positioned properly for bleeding or venting. Optimal results for liquid or steam are obtained when flow is up. For steam applications, a 90° spacer will be added to provide water legs to ensure the transmitter stays within temperature limits. The maximum temperature for a direct mounted transmitter is 500 °F (260 °C).
Figure 5. Steam
360°
Flow
Figure 6. Liquid
Figure 7. Gas
7
Quick Start Guide

2.0 Weld mounting hardware

Note
Rosemount-supplied mounting has an integral alignment built into the mounting hardware that assists in the correct drilling of the mounting hole. It also assists in the alignment of the sensor to the mounting hole for insertion.
June 2016
1. At the pre-determined position, place the threaded weld coupling on the pipe,
1
/16-in. (1,6 mm), and place four 1/4-in. (6 mm) tack welds at 90°
gap increments.
2. Check alignment of the mounting both parallel and perpendicular to the axis of flow (see Figure8). If alignment of the mounting is within tolerances, finish weld per local codes. If outside of specified tolerance, make adjustments prior to making the finish weld.
Figure 8. Alignment
A
B
A. Lower Mounting Height (LMH)
1. LMH values are as follows:
Sensor size 1 — 1.38-in.(35 mm) Sensor size 2 — 1.56-in.(40 mm) Sensor size 3 — 2.06-in.(52 mm)
(1)
B. Tack welds
3. To avoid serious burns, allow the mounting hardware to cool before continuing.
8
June 2016
A

3.0 Install isolation valve

1. Thread the guide nipple into the mounting.
2. Thread the isolation valve onto the guide nipple. Ensure the valve stem is positioned so that when the Flo-Tap is installed, the insertion rods will straddle the pipe and the valve handle will be centered between the rods (see Figure 9).
Note
Interference will occur if valve is located in line with the rods.
Figure 9. Isolation Valve Orientation
A. Isolation valve

4.0 Mount drilling machine and drill hole

Drilling machine is not provided with assembly.
1. Determine the sensor size based on the probe width (see Table 2).
Table 2. Sensor Size/Hole Diameter Chart
Quick Start Guide
Sensor size Sensor width Hole diameter
1 0.590-in. (14,99 mm)
2 1.060-in. (26,92 mm) 15/16-in. (34 mm) +1/16-in. (1,6 mm) – 0.00
3 1.935-in. (49,15 mm) 21/2-in. (64 mm) +1/16-in. (1,6 mm) – 0.00
3
/4-in. (19 mm) +1/32-in (0,8 mm) – 0.00
2. Mount the drilling machine to the isolation valve.
A
B
A. Isolation valve is fully open when inserting drill B. Pressure drilling machine C. Isolation valve is fully closed after withdrawing drill
C
9
Quick Start Guide
3. Open the valve fully.
4. Drill the hole into the pipe wall in accordance with the instructions provided by the drilling machine manufacturer (use Table 2 to select the proper drill bit for the sensor being used).
5. Retract the drill fully beyond the valve.

5.0 Remove drilling machine

1. Verify the drill has been retracted past the valve.
2. Close the isolation valve to isolate the process.
3. Bleed drilling machine pressure and remove.
4. Check isolation valve and mounting for leakage.

6.0 Mount the Rosemount Annubar Assembly

1. Install the complete Flo-Tap assembly (fully retracted) onto the isolation valve by threading the close nipple into the valve using the proper thread sealant compound.
2. Rotate the Flo-Tap assembly until the flow arrow on the head aligns with the direction of flow.
3. Ensure the vent valves are closed before proceeding.
4. Quickly open and close the isolation valve to pressurize the sensor and identify any leak points in the installation. Use extreme caution if the flowing medium is steam or caustic.
5. Check the entire installation for leakage. Tighten as required to stop any connection from leaking.
6. Repeat steps 4 and 5 until there is no leakage. a. If Flo-Tap comes equipped with the gear drive option, place the Polyvinyl
chloride (PVC) protector rod assembly over the drive rods and attach to gear drive with supplied hardware.
June 2016
Note
Rosemount 485 Annubar Flowmeter have the potential to carry a large amount of weight at a great distance from the piping, necessitating external support. The support plate has threaded holes to assist in supporting the Rosemount 485.
10
June 2016
Quick Start Guide
Figure 10. Install Flo-Tap Assembly
AA
B
A. Support plate B. Isolation valve

7.0 Insert the Rosemount Annubar Sensor

Standard drive (M)
1. Open the isolation valve fully.
2. Rotate the drive nuts clockwise (as viewed from the top). The nuts must be tightened alternately, about two turns at a time, to prevent binding caused by unequal loading.
3. Continue this procedure until the tip of the sensor firmly contacts the opposite side of the pipe.
a. The orange stripes are visual indication of when the sensor is approaching
the opposite side wall.
b. As the orange stripe approaches the support plate, place a finger above the
packing gland while cranking. When movement stops, the sensor is in contact with the opposite side wall.
c. Turn the handle an additional
1
/4- to 1/2-in. to secure the sensor.
11
Quick Start Guide
A
Gear drive (G)
1. Open the isolation valve fully.
2. Rotate the crank clockwise. If a power drill with an adapter is used, do not exceed 200 rpm. a. Continue rotating the crank until the sensor firmly contacts the opposite
side of the pipe. The orange stripes are visual indication of when the sensor is approaching the opposite side wall.
b. As the orange stripes approach the support plate, remove the power drill
and continue cranking manually. Place a finger above the packing gland while cranking. When movement stops, the sensor is in contact with the opposite side wall.
c. Turn the handle an additional
3. Secure the drive by inserting the drive lock pin as shown in Figure 11.
Note
Do not place finger above packing gland for high temperature applications.
Figure 11. Insert the Sensor
Standard drive (M) Gear drive (G)
1
/4- to 1/2-in. to secure the sensor.
June 2016
A. Drive lock pin

8.0 Mount the transmitter

8.1 Transmitter mounting, direct mount head with valves

It is not necessary to retract the Rosemount Annubar when direct mounting a
transmitter with valves.
1. Place PTFE O-rings into grooves on the Rosemount Annubar head.
2. Align the high side of the transmitter to the high side of the sensor (“Hi” is stamped on the side of the head) and install.
3. Tighten the nuts in a cross pattern to 384 in-lb (43 N-m).
12
June 2016
Quick Start Guide

8.2 Transmitter mounting with remote mount head

Temperatures in excess of 250 °F (121 °C) at the sensor module diaphragms will damage the transmitter. Remote mounted transmitter are connected to the sensor by means of impulse piping, which allows service flow temperatures to decrease to a point where the transmitter is no longer vulnerable.
Different impulse piping arrangements are used depending on the process fluid and must be rated for continuous operation at the pipeline design pressure and temperature. A minimum of with a wall thickness of at least 0.035-in. (1 mm) is recommended. Threaded pipe fittings are not recommended because they create voids where air can become entrapped and create leakage points.
The following restrictions and recommendations apply to impulse piping location:
1. Impulse piping that runs horizontally must slope at least one inch per foot (83 mm/m).
- Slope downward (toward the transmitter) for liquid and steam applications.
- Slope upward (toward the transmitter) for gas applications.
2. Outdoor installations for liquid, saturated gas, or steam may require insulation and heat tracing to prevent freezing.
3. An instrument manifold is recommended for all installations. Manifolds allow an operator to equalize the pressures prior to zeroing and isolates the process fluid from the transmitter.
1
/2-in. (12 mm) outer diameter stainless steel tubing
13
Quick Start Guide
Figure 12. Valve Identification for 5-Valve and 3-Valve Manifolds
5-valve manifold 3-valve manifold
June 2016
To PH To PL
MH
MEH
DVH
To PH
MV
MH
2
ML
MEL
DVL
1
DVH
To PL
ME
2
ML
DVL
1
Table 3. Description of Impulse Valves and Components
Name Description Purpose
Components
1 Tra ns m it te rs Reads Differential P ressure
2 Manifold
Manifold and impulse valves
PH Primary sensor
PL Primary sensor
DVH Drain/vent valve
DVL Drain/vent valve
MH Manifold
ML Manifold
MEH Manifold equalizer
MEL Manifold equalizer
(1)
(2)
(1)
(2)
(1)
(2)
(1)
(2)
ME Manifold equalizer Allows high and low side pressure to equalize
MV Manifold vent valve Vents process fluid
Isolates and equalizes transmitter
High and low side pressure process connections.
Drains (for gas service) or vents (for liquid or steam service) the DP transmitter chambers
Isolates high side or low side pressure from the process
Allows high and low pressure side access to the vent valve, or for isolating the process fluid
1. High pressure
2. Low pressure
14
June 2016

8.3 Recommended installations

Gas service
Secure the transmitter above the sensor to prevent condensible liquids from collecting in the impulse piping and the DP cell.
Figure 13. Horizontal Gas
Quick Start Guide
Figure 14. Vertical Gas
15
Quick Start Guide
Steam and liquid service
Secure the transmitter below the sensor to ensure that air will not be introduced
into the impulse piping or the transmitter.
Figure 15. Horizontal Steam and Liquid
June 2016
Figure 16. Vertical Steam and Liquid
16
June 2016
Quick Start Guide
Top mounting for steam service
Top mounting for steam applications is an appropriate mounting option in many cases. Consult Rosemount Customer Central instructions regarding steam on top mounting. For remote mount installations the impulse piping should slope up slightly from the instrument connections on the Rosemount Annubar to the cross fittings allowing condensate to drain back into the pipe. From the cross fittings, the impulse piping should be routed downward to the transmitter and the drain legs. The transmitter should be located below the instrument connections of the Rosemount Annubar. Depending on the environmental conditions, it may be necessary to insulate the mounting hardware.
Figure 17. Horizontal Top Mounting for Steam
Note
Top mounting for steam applications is an appropriate mounting option in many cases. Consult Rosemount Customer Central instructions regarding steam on top mounting.
17
Quick Start Guide
June 2016

9.0 Retracting the Rosemount Annubar Assembly

9.1 Standard drive (M)

1. Rotate the drive nuts counter-clockwise (as viewed from the top). The nuts must be loosened alternately, about two turns at a time, to prevent binding caused by unequal loading.
2. Continue this procedure until the rod end nuts are against the packing body mechanism.

9.2 Gear drive (G)

1. Remove the drive lock pin.
2. Rotate the crank counter-clockwise. If a power drill with an adapter is used, do not exceed 200 rpm.
3. Retract until the rod end nuts are against the gear box mechanism.
18
June 2016

10.0 Product certifications

10.1 Approved Manufacturing Locations

Rosemount Inc. – Shakopee, Minnesota USA
Rosemount DP Flow Design and Operations – Boulder, Colorado USA
Emerson Process Management GmbH & Co. OHG – Wessling, Germany
Emerson Process Management Asia Pacific Private Limited – Singapore
Emerson Beijing Instrument Co., Ltd – Beijing, China

10.2 European Directive Information

The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at
EmersonProcess.com/Rosemount
contacting our local sales office.
European Pressure Equipment Directive (PED) (97/23/EC)
Rosemount 485 Annubar — Refer to EC declaration of conformity for conformity assessment
Pressure Transmitter — See appropriate Pressure Transmitter QSG

10.3 Hazardous Locations Certifications

For information regarding the transmitter product certification, see the appropriate transmitter QSG:
Rosemount 3051S Series Pressure Transmitter and Rosemount 3051SF
Series Flowmeter Quick Start Guide
Rosemount 3051S MultiVariable Transmitter and Rosemount 3051SF Series
Flowmeter MultiVariable Transmitter Quick Start Guide.
Rosemount 3051 Pressure Transmitter and Rosemount 3051CF Series
Flowmeter Transmitter Quick Start Guide.
Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series
Flowmeter Transmitter Quick Start Guide
. A hard copy may be obtained by
.
.
Quick Start Guide
19
Quick Start Guide
Figure 18. Rosemount Primary Element Declaration of Conformity
June 2016
20
June 2016
Quick Start Guide
21
Quick Start Guide
June 2016
22
June 2016
管控物彯㚨⣏㳻⹎旸ῤ的部件型号列表
部件名称
有害物峐ġİġ
六价
多ⓤ俼劗
多ⓤ俼劗慂
多ⓤ俼劗慂
Quick Start Guide
1B: 含有China RoHS
Table 1B: List of Rosemount 485 Parts with China RoHS Concentration above MCVs
Rosemount 485
Hazardous Substances
Part Name
Lead
Mercury
(Pb)
䬍ࡦ⑙ᓖՐ ᝏಘཆ༣㓴
Ԧ
Aluminum
RTD
Housing
Assembly
本表格系依据
This table is proposed in accordance with the provision of SJ/T11364 O: O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572. X: X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.
SJ/T11364
󰶃宍悐ẞ䘬㇨㚱⛯峐㛸㕁󰵶宍㚱⭛䈑峐䘬⏓慷⛯ỶḶ
󰶃⛐宍悐ẞ㇨ἧ䓐䘬㇨㚱⛯峐㛸㕁慴炻军⮹㚱ᶨ䰣⛯峐㛸㕁󰵶宍㚱⭛䈑峐䘬⏓慷檀Ḷ
(Hg)
O O O X O O
奬⭂侴⇞ἄįġ
Cadmium
(Cd)
Hexavalent
Chromium
(Cr +6)
GB/T 26572
Polybrominated
biphenyls
(PBB)
奬⭂䘬旸慷天㯪įġ
Polybrominated diphenyl ethers
GB/T 26572
(PBDE)
奬⭂䘬旸慷天㯪įġ
к䘠⭣᰾ӵ䘲⭘Ҿ䘹ᤙ䬍ࡦཆ༣㓴ԦⲴӗ૱DŽަԆᡰᴹᐞ঻⍱䟿а⅑ݳԦⲴ㓴ԦᡰᴹⲴ China RoHS ㇑᧗⢙䍘⎃ ᓖ൷վҾ GB/T 26572 ᡰ㿴ᇊⲴ䲀䟿㾱≲DŽޣҾᐞ঻⍱䟿䇑䘱ಘ㓴ԦⲴ㇑᧗⢙䍘⎃ᓖⲴ⭣᰾ˈ䈧৲ⴻ䘱ಘⲴᘛ 䙏ᆹ㻵ᤷইDŽ
The disclosure above applies to units supplied with aluminum connection heads. No other components supplied with DP Flow primary elements contain any restricted substances. Please consult the transmitter Quick Start Guide (QIG) for disclosure information on transmitter components.
23
Global Headquarters
Emerson Process Management
6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@EmersonProcess.com
North America Regional Office
Emerson Process Management
8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com
Latin America Regional Office
Emerson Process Management
1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@EmersonProcess.com
Europe Regional Office
Emerson Process Management Europe GmbH
Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@EmersonProcess.com
Asia Pacific Regional Office
Emerson Process Management Asia Pacific Pte Ltd
1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.EmersonProcess.com
Middle East and Africa Regional Office
Emerson Process Management
Emerson FZE P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emi rates
+971 4 8118100 +971 4 8865465
RFQ.RMTMEA@Emerson.com
*00825-0500-4809*
Quick Start Guide
00825-0500-4809, Rev EB
Linkedin.com/company/Emerson-Process-Management
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/us er/RosemountMeasur ement
Google.com/+RosemountMeasurement
Standard Terms and Conditions of Sale can be found at
www.Emerson.com/en-us/pages/Terms-of-Use.aspx
The Emerson logo is a trademark and service mark of Emerson Electric Co. Annubar, Rosemount and Rosemount logotype are trademarks of Emerson Process Management. All other marks are the propert y of their respective owners. © 2016 Emerson Process Management. All rights reserved.
June 2016
Loading...