This guide provides basic guidelines for Rosemount 485. It does not provide instructions for configuration,
diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or Intrinsically Safe (I.S.)
installations. Refer to Rosemount 485 Annubar Reference Manual
available electronically on Emer sonProces s.com/Rosemo unt
If the Rosemount 485 was ordered assembled to a Rosemount Pressure Transmitter, see the following Quick
Start Guides for information on configuration and hazardous locations certifications:
Rosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flowmeter Quick Start
Guide.
Rosemount 3051S MultiVariable Transmitter and Rosemount 3051SF Series Flowmeter MultiVariable
Tra ns mi tte r Quick Start Guide
Rosemount 3051 Pressure Transmitter and Rosemount 3051CF Series Flowmeter Transmitter Quick
Start Guide.
Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flowmeter Transmitter Quick
Start Guide.
Process leaks may cause harm or result in death. To avoid process leaks, only use packings designed to seal
with the recommended torque value to seal process connections. Flowing medium may cause the
Rosemount 485 Annubar Assembly to become hot and could result in burns.
Correct orientation and straight run requirements must be met for accurate and
repeatable flow measurements. Refer to Table 2 for minimum pipe diameter
distances from upstream and downstream disturbances.
Table 2. Straight Run Requirements
In plane____________Out of planeUpstream pipe diameters
Without
straightening
vanes
In
Out of
plane
plane
A
8
1
N/A10N/A
11
2
N/A16N/A
23
3
With straightening
vanes
A’CC’B
A
N/A8N/A4N/A
N/A8N/A4N/A
N/A8N/A4N/A
Downstream
pipe diameters
4
4
4
4
4
4
4
N/A28N/A
12
4
N/A12N/A
N/A8N/A4N/A
4
4
4
4
4
5
Page 6
Quick Start Guide
3
3
3
June 2016
18
5
N/A18N/A
30
6
N/A30N/A
N/A8N/A4N/A
4
N/A8N/A4N/A
4
Note
Consult the factory for instructions regarding use in square or rectangular
ducts.
If proper lengths of straight run are not available, position the mounting such
that 80% of the run is upstream and 20% is downstream. This will result in
degraded accuracy.
Use straightening vanes to reduce the required straight run length.
Row 6 in Ta b l e 2 applies to gate, globe, plug, and other throttling valves that
are partially opened, as well as control valves.
1.1 Misalignment
Rosemount 485 installation allows for a maximum misalignment of 3°.
4
4
4
4
Figure 3. Misalignment
6
Page 7
June 2016
45
45
Recommended
Zone 30
30
Recommended
Zone 30
Flow
360
Flow
1.2 Flowmeter orientation
Figure 4. Flowmeter Orientation for Liquid
Remote mount; for low temperature (<450 °F/232 °C)
Horizontal liquidVertical liquid
Quick Start Guide
(1)
Flow
360
Remote mount; for high temperature (<600 °F/315 °C)
Horizontal liquidVertical liquid
Flow
45
Recommended
Zone 30
30
45
Recommended
Zone 30
1. Downward flow is not recommended.
(1)
7
Page 8
Quick Start Guide
45
Recommend Zone 90
45
Flow
360
Flow
45
Recommend Zone 90
45
360
Flow
Figure 5. Flowmeter Orientation for Gas
Remote mount; for low temperature (<450 °F/232 °C)
Horizontal gasVertical gas
June 2016
Remote mount; for high temperature (<600 °F/315 °C)
Horizontal gasVertical gas
8
Page 9
June 2016
45
45
Recommended
Zone 30
30
Recommended
Zone 30
Flow
360
Flow
360
Flow
Figure 6. Flowmeter Orientation for Steam
Remote mount; for low temperature (<450 °F/232 °C)
Horizontal steamVertical steam
Remote mount; for high temperature (<600 °F/315 °C)
Horizontal steamVertical steam
Quick Start Guide
(1)
(1)
Flow
45
Recommended
Zone 30
30
45
Recommended
Zone 30
1. Downward flow is not recommended.
9
Page 10
Quick Start Guide
1.3 Top mounting the flowmeter for steam
Top mounting for steam applications is an alternate mounting option in some
cases. Consult Rosemount Customer Central for instructions regarding steam on
top mounting. Top mounting in steam is an alternative mounting method for
steam installations that can be used if there are space restrictions or other
concerns. This installation method is intended for applications that run with
limited interruptions or shutdowns. Also, top mounting can reduce or eliminate
the need for heat tracing in outdoor applications that do not experience
shutdowns during cold weather.
Figure 7. Remote Mount; Horizontal Top Mounting for Steam
June 2016
Recommended
Zone
60°
60°60°
This orientation can be used for any steam temperature. The impulse piping
should slope up slightly from the instrument connections on the Rosemount
Annubar to the cross fittings, allowing condensate to drain back into the pipe.
From the cross fittings, the impulse piping should be routed downward to the
transmitter and the drain legs. The transmitter should be located below the
instrument connections of the Rosemount Annubar primary element. Depending
on the environmental conditions, it may be necessary to insulate the mounting
hardware.
10
Page 11
June 2016
2.0 Drill sensor holes
1. Determine the sensor size based on the probe width (see Ta bl e 3).
4. Determine the diameter of the hole to be drilled according to the
specifications in Ta bl e 3 . Drill the mounting hole into the pipe with a hole saw
or drill. DO NOT TORCH CUT THE HOLE.
Drill to Hole Size
P/N: 28-109001-922 Rev. AC
When drilling the mounting hole, Emerson™ Process Management recommends the use of a magnetic drill o r
pipe clamping fixture to safely drill the hole. Use appropriate personal protective equipment and procedures
when drilling and weldin g.
3.0 Prepare for welding
1. Clean off the coating on the bottom of the weld coupling to get the best weld
penetration effect.
2. For specific process fluid, the anti-rust oil inside the weld coupling may need to
be rinsed thoroughly before welding. If you are not sure about your process
fluid, contact an Emerson Process Management representative.
11
Page 12
Quick Start Guide
4.0 Weld the mounting hardware
1. Center the threaded body over the mounting hole, gap 1/16-in. (1,6 mm), and
place four 1/4-in. (6 mm) tack welds at 90° increments.
2. Check alignment of the threaded body both parallel and perpendicular to the
axis of flow (see Figure 8). If alignment of mounting is within tolerances
defined in Figure 3, finish weld per local codes. If alignment is outside of
specified tolerance, make adjustments prior to finish weld.
3. To avoid serious burns, allow the mounting hardware to cool before
continuing.
4. For flat duct surfaces, the bottom of the weld coupling needs to be ground for
mounting. The welding height remains the same as LMH value for respective
sensor size.
5.0 Insert the Rosemount Annubar Sensor
Note
Refer to “Rosemount 485 Annubar Threaded Assembly Exploded View” on page 3 for
component descriptions.
1. To ensure the primary element contacts the opposite side pipe wall, mark the
tip of the sensor with a marker.
2. Insert the flowmeter into the threaded body until the sensor tip contacts the
pipe wall, twisting the primary element back and forth.
3. Verify the sensor tip made contact with the opposite side pipe wall by
removing the primary element and ensuring that some of the marker has been
rubbed off. If the tip did not touch the wall, verify the measured pipe ID and
wall match the tagging information and re-insert.
4. Align the flow arrow on the head with the direction of flow. Re-insert the
primary element into the threaded weld coupling and install the first packing
ring on the sensor between the retaining ring and the follower. Take care not
to damage the split packing rings.
5. Install packing rings.
Quick Start Guide
A. Retaining ringC. Nut
B. FollowerD. 3⫻ Packing rings
a. Install the first packing ring underneath the follower.
b. Use the follower to compress the first packing ring against the retaining
ring.
c. Install the second packing ring underneath the follower. Alternate packing
ring splits by 120° to each other.
d. Use the follower to compress the second packing ring against the first
packing ring.
13
Page 14
Quick Start Guide
e. Install the third packing ring underneath the follower.
f. Use the follower to compress the third packing ring.
6. Tighten the nut to the specified torque.
Table 4. Torque Requirements
Sensor size
1M50444.4 in-lb (50 N-m)531 in-lb (60 N-m)
2M65708 in-lb (80 N-m)1416 in-lb (160 N-m)
Open spanner
specification C
Recommended
torque
June 2016
Maximum torque
a. Inspect the unit for leakage.
b. If any leaks exist, tighten the nut in
1
/4 turn increments until there is no
leakage.
Note
Do not exceed the maximum torque listed in Tab l e 4.
Figure 9. Torque Wrench
1. See Ta bl e 4 for “Open spanner specification C”.
(1)
Note
The threaded sealing mechanism will generate significant force at the point where the
sensor contacts the opposite pipe wall. Caution needs to be exercised on thin-walled piping
(ANSI Sch 10 and lower) to avoid damage to the pipe.
14
Page 15
June 2016
Quick Start Guide
6.0 Product certifications
6.1 Approved Manufacturing Locations
Rosemount Inc. – Shakopee, Minnesota USA
Rosemount DP Flow Design and Operations – Boulder, Colorado USA
Emerson Process Management GmbH & Co. OHG – Wessling, Germany
Emerson Process Management Asia Pacific Private Limited – Singapore
Emerson Beijing Instrument Co., Ltd – Beijing, China
6.2 European Directive Information
The EC declaration of conformity for all applicable European directives for this
product can be found on the Rosemount website at
EmersonProcess.com/Rosemount
our local sales office.
European Pressure Equipment Directive (PED) (97/23/EC)
Rosemount 485 Annubar — Refer to EC declaration of conformity for conformity
assessment
Pressure Transmitter — See appropriate Pressure Transmitter QSG
6.3 Hazardous Locations Certifications
For information regarding the transmitter product certification, see the
appropriate transmitter QSG:
Rosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series
Flowmeter Quick Start Guide.
Rosemount 3051S MultiVariable Transmitter and Rosemount 3051SF Series
Rosemount 3051 Pressure Transmitter and Rosemount 3051CF Series
Flowmeter Transmitter Quick Start Guide
Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series
Flowmeter Transmitter Quick Start Guide
. A hard copy may be obtained by contacting
.
.
15
Page 16
Quick Start Guide
Figure 10. Rosemount 485 Declaration of Conformity
June 2016
16
Page 17
June 2016
Quick Start Guide
17
Page 18
Quick Start Guide
June 2016
18
Page 19
June 2016
表表格
1B: 含有China RoHS
管控物峐超彯㚨⣏㳻⹎旸ῤ的部件型号列表
Rosemount 485
Table 1B: List of Rosemount 485 Parts with China RoHS Concentration above MCVs
部件名称
Part Name
有害物峐ġİġHazardous Substances
摭
Lead
(Pb)
汞
Mercury
(Hg)
擱
Cadmium
(Cd)
六价撔
Hexavalent
Chromium
(Cr +6)
多ⓤ俼劗
Polybrominated
biphenyls
(PBB)
多ⓤ俼劗慂
Polybrominated
diphenyl ethers
多ⓤ俼劗慂
(PBDE)
䬍ࡦᓖՐ
ᝏಘཆ༣㓴
Ԧ
Aluminum
RTD
Housing
Assembly
O O O X O O
本表格系依据
SJ/T11364
的奬⭂侴⇞ἄįġ
This table is proposed in accordance with the provision of SJ/T11364
O:
意宍悐ẞ䘬㚱⛯峐㛸㕁宍㚱⭛䈑峐䘬⏓慷⛯ỶḶ
GB/T 26572
所奬⭂䘬旸慷天㯪įġ
O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of
GB/T 26572.
X:
意⛐宍悐ẞἧ䓐䘬㚱⛯峐㛸㕁慴炻军⮹㚱ᶨ䰣⛯峐㛸㕁宍㚱⭛䈑峐䘬⏓慷檀Ḷ
GB/T 26572
所奬⭂䘬旸慷天㯪įġ
X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above
the limit requirement of GB/T 26572.
к䘠⭣᰾ӵ䘲⭘Ҿ䘹ᤙ䬍ࡦཆ༣㓴ԦⲴӗ૱DŽަԆᡰᴹᐞ⍱䟿а⅑ݳԦⲴ㓴ԦᡰᴹⲴ China RoHS ㇑᧗⢙䍘⎃
ᓖ൷վҾ GB/T 26572 ᡰ㿴ᇊⲴ䲀䟿㾱≲DŽޣҾᐞ⍱䟿䇑䘱ಘ㓴ԦⲴ㇑᧗⢙䍘⎃ᓖⲴ⭣᰾ˈ䈧৲ⴻ䘱ಘⲴᘛ
䙏ᆹ㻵ᤷইDŽ
The disclosure above applies to units supplied with aluminum connection heads. No other components supplied
with DP Flow primary elements contain any restricted substances. Please consult the transmitter Quick Start
Guide (QIG) for disclosure information on transmitter components.