Rosemount 485 Annubar Threaded Assembly Quick Start Guide

Page 1
Quick Start Guide
00825-0700-4809, Rev BA
June 2016
Rosemount™ 485 Annubar™ Threaded Assembly
Page 2
Quick Start Guide
NOTICE
This guide provides basic guidelines for Rosemount 485. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or Intrinsically Safe (I.S.) installations. Refer to Rosemount 485 Annubar Reference Manual available electronically on Emer sonProces s.com/Rosemo unt
If the Rosemount 485 was ordered assembled to a Rosemount Pressure Transmitter, see the following Quick Start Guides for information on configuration and hazardous locations certifications:
Rosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flowmeter Quick Start
Guide.
Rosemount 3051S MultiVariable Transmitter and Rosemount 3051SF Series Flowmeter MultiVariable
Tra ns mi tte r Quick Start Guide
Rosemount 3051 Pressure Transmitter and Rosemount 3051CF Series Flowmeter Transmitter Quick
Start Guide.
Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flowmeter Transmitter Quick
Start Guide.
Process leaks may cause harm or result in death. To avoid process leaks, only use packings designed to seal with the recommended torque value to seal process connections. Flowing medium may cause the Rosemount 485 Annubar Assembly to become hot and could result in burns.
.
for more instruction. This manual is also
.
Contents
Location and orientation . . . . . . . . . . . . . . . . . . 5
Drill sensor holes . . . . . . . . . . . . . . . . . . . . . . . . 11
Prepare for welding . . . . . . . . . . . . . . . . . . . . . . 11
2
Weld the mounting hardware . . . . . . . . . . . . . 12
Insert the Rosemount Annubar Sensor . . . . . 12
Product certifications . . . . . . . . . . . . . . . . . . . . 15
Page 3
Quick Start Guide
Figure 1. Rosemount 485 Annubar Threaded Assembly Exploded View
E
C
D
G
B
E
A
A
F
A. See Figure 2 for detail. B. Remote mount connection with isolation valves C. Integrated valve low (VL) D. Integrated valve high (VH)
E. 2 Elbows F. Threaded weld coupling G. Remote mount connection
Table 1. Isolation Valves
Name Description Position Purpose
Integrated Isolation
VH
Valv e High
Integrated Isolation
VL
Valv e Low
(1)
(2)
Letter “H” side of the Remote Mount Connection
Letter “L” side of the Remote Mount Connection
Isolates high side or low side pressure from the process
F
1. High pressure
2. Low pressure
3
Page 4
Quick Start Guide
Figure 2. Rosemount 485 Annubar Threaded Packing Assembly Detail
Exploded View
B
A
A. 3 Packaging rings B. Follower C. Nut
(1)
C
D
E
D. Retaining ring E. Rosemount 485 Annubar Sensor
1. Image scale = 3/2.
4
Page 5
Quick Start Guide

1.0 Location and orientation

Correct orientation and straight run requirements must be met for accurate and repeatable flow measurements. Refer to Table 2 for minimum pipe diameter distances from upstream and downstream disturbances.
Table 2. Straight Run Requirements
In plane____________Out of plane Upstream pipe diameters
Without
straightening
vanes
In
Out of
plane
plane
A
8
1
N/A10N/A
11
2
N/A16N/A
23
3
With straightening
vanes
A’ C C’ B
A
N/A8N/A4N/A
N/A8N/A4N/A
N/A8N/A4N/A
Downstream
pipe diameters
4
4
4
4
4
4
4
N/A28N/A
12
4
N/A12N/A
N/A8N/A4N/A
4
4
4
4
4
5
Page 6
Quick Start Guide
3
3
3
18
5
N/A18N/A
30
6
N/A30N/A
N/A8N/A4N/A
4
N/A8N/A4N/A
4
Note
Consult the factory for instructions regarding use in square or rectangular
ducts.
If proper lengths of straight run are not available, position the mounting such
that 80% of the run is upstream and 20% is downstream. This will result in degraded accuracy.
Use straightening vanes to reduce the required straight run length. Row 6 in Ta b l e 2 applies to gate, globe, plug, and other throttling valves that
are partially opened, as well as control valves.

1.1 Misalignment

Rosemount 485 installation allows for a maximum misalignment of 3°.
4
4
4
4
Figure 3. Misalignment
6
Page 7
45
45
Recommended Zone 30
30
Recommended Zone 30
Flow
360
Flow

1.2 Flowmeter orientation

Figure 4. Flowmeter Orientation for Liquid
Remote mount; for low temperature (<450 °F/232 °C)
Horizontal liquid Vertical liquid
Quick Start Guide
(1)
Flow
360
Remote mount; for high temperature (<600 °F/315 °C)
Horizontal liquid Vertical liquid
Flow
45
Recommended Zone 30
30
45
Recommended Zone 30
1. Downward flow is not recommended.
(1)
7
Page 8
Quick Start Guide
45
Recommend Zone 90
45
Flow
360
Flow
45
Recommend Zone 90
45
360
Flow
Figure 5. Flowmeter Orientation for Gas
Remote mount; for low temperature (<450 °F/232 °C)
Horizontal gas Vertical gas
Remote mount; for high temperature (<600 °F/315 °C)
Horizontal gas Vertical gas
8
Page 9
45
45
Recommended Zone 30
30
Recommended Zone 30
Flow
360
Flow
360
Flow
Figure 6. Flowmeter Orientation for Steam
Remote mount; for low temperature (<450 °F/232 °C)
Horizontal steam Vertical steam
Remote mount; for high temperature (<600 °F/315 °C)
Horizontal steam Vertical steam
Quick Start Guide
(1)
(1)
Flow
45
Recommended Zone 30
30
45
Recommended Zone 30
1. Downward flow is not recommended.
9
Page 10
Quick Start Guide

1.3 Top mounting the flowmeter for steam

Top mounting for steam applications is an alternate mounting option in some cases. Consult Rosemount Customer Central for instructions regarding steam on top mounting. Top mounting in steam is an alternative mounting method for steam installations that can be used if there are space restrictions or other concerns. This installation method is intended for applications that run with limited interruptions or shutdowns. Also, top mounting can reduce or eliminate the need for heat tracing in outdoor applications that do not experience shutdowns during cold weather.
Figure 7. Remote Mount; Horizontal Top Mounting for Steam
Recommended
Zone
60°
60° 60°
This orientation can be used for any steam temperature. The impulse piping should slope up slightly from the instrument connections on the Rosemount Annubar to the cross fittings, allowing condensate to drain back into the pipe. From the cross fittings, the impulse piping should be routed downward to the transmitter and the drain legs. The transmitter should be located below the instrument connections of the Rosemount Annubar primary element. Depending on the environmental conditions, it may be necessary to insulate the mounting hardware.
10
Page 11

2.0 Drill sensor holes

1. Determine the sensor size based on the probe width (see Ta bl e 3).
Table 3. Sensor Size/Hole Diameter Chart
Quick Start Guide
Sensor
size
1 0.590-in. (14,99 mm)
2 1.060-in. (26,92 mm) 15/16-in. (34 mm) +1/16-in. (1,6 mm) – 0.00
Sensor width Hole diameter
3
/4-in. (19 mm) +1/32-in (0,8 mm) – 0.00
2. Depressurize and drain the pipe.
3. Select the location to drill the hole.
4. Determine the diameter of the hole to be drilled according to the specifications in Ta bl e 3 . Drill the mounting hole into the pipe with a hole saw or drill. DO NOT TORCH CUT THE HOLE.
Drill to Hole Size
P/N: 28-109001-922 Rev. AC
When drilling the mounting hole, Emerson™ Process Management recommends the use of a magnetic drill o r pipe clamping fixture to safely drill the hole. Use appropriate personal protective equipment and procedures when drilling and weldin g.

3.0 Prepare for welding

1. Clean off the coating on the bottom of the weld coupling to get the best weld penetration effect.
2. For specific process fluid, the anti-rust oil inside the weld coupling may need to be rinsed thoroughly before welding. If you are not sure about your process fluid, contact an Emerson Process Management representative.
11
Page 12
Quick Start Guide

4.0 Weld the mounting hardware

1. Center the threaded body over the mounting hole, gap 1/16-in. (1,6 mm), and place four 1/4-in. (6 mm) tack welds at 90° increments.
2. Check alignment of the threaded body both parallel and perpendicular to the axis of flow (see Figure 8). If alignment of mounting is within tolerances defined in Figure 3, finish weld per local codes. If alignment is outside of specified tolerance, make adjustments prior to finish weld.
Figure 8. Alignment
A
A. Lower Mounting Height LMH
1. LMH values are as follows:
Sensor size 1 — 2.89-in.(73 mm) Sensor size 2 — 3.92-in.(100 mm)
B
(1)
B. Tack welds
3. To avoid serious burns, allow the mounting hardware to cool before continuing.
4. For flat duct surfaces, the bottom of the weld coupling needs to be ground for mounting. The welding height remains the same as LMH value for respective sensor size.

5.0 Insert the Rosemount Annubar Sensor

Note
Refer to “Rosemount 485 Annubar Threaded Assembly Exploded View” on page 3 for component descriptions.
1. To ensure the primary element contacts the opposite side pipe wall, mark the tip of the sensor with a marker.
2. Insert the flowmeter into the threaded body until the sensor tip contacts the pipe wall, twisting the primary element back and forth.
12
Page 13
Serial No. Date Model
Customer Tag
Pipe I.D. Wall Max. Allow FlowRate Max. Insert/Retract Flow Max. Press. @ Temp Span (20mA)
00-370000-2X1 Rev. AC
B
D
C
A
3. Verify the sensor tip made contact with the opposite side pipe wall by removing the primary element and ensuring that some of the marker has been rubbed off. If the tip did not touch the wall, verify the measured pipe ID and wall match the tagging information and re-insert.
4. Align the flow arrow on the head with the direction of flow. Re-insert the primary element into the threaded weld coupling and install the first packing ring on the sensor between the retaining ring and the follower. Take care not to damage the split packing rings.
5. Install packing rings.
Quick Start Guide
A. Retaining ring C. Nut
B. Follower D. 3 Packing rings
a. Install the first packing ring underneath the follower. b. Use the follower to compress the first packing ring against the retaining
ring.
c. Install the second packing ring underneath the follower. Alternate packing
ring splits by 120° to each other.
d. Use the follower to compress the second packing ring against the first
packing ring.
13
Page 14
Quick Start Guide
e. Install the third packing ring underneath the follower. f. Use the follower to compress the third packing ring.
6. Tighten the nut to the specified torque.
Table 4. Torque Requirements
Sensor size
1 M50 444.4 in-lb (50 N-m) 531 in-lb (60 N-m)
2 M65 708 in-lb (80 N-m) 1416 in-lb (160 N-m)
Open spanner
specification C
Recommended
torque
Maximum torque
a. Inspect the unit for leakage. b. If any leaks exist, tighten the nut in
1
/4 turn increments until there is no
leakage.
Note
Do not exceed the maximum torque listed in Tab l e 4.
Figure 9. Torque Wrench
1. See Ta bl e 4 for “Open spanner specification C”.
(1)
Note
The threaded sealing mechanism will generate significant force at the point where the sensor contacts the opposite pipe wall. Caution needs to be exercised on thin-walled piping (ANSI Sch 10 and lower) to avoid damage to the pipe.
14
Page 15
Quick Start Guide

6.0 Product certifications

6.1 Approved Manufacturing Locations

Rosemount Inc. – Shakopee, Minnesota USA
Rosemount DP Flow Design and Operations – Boulder, Colorado USA
Emerson Process Management GmbH & Co. OHG – Wessling, Germany
Emerson Process Management Asia Pacific Private Limited – Singapore
Emerson Beijing Instrument Co., Ltd – Beijing, China

6.2 European Directive Information

The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at
EmersonProcess.com/Rosemount
our local sales office.
European Pressure Equipment Directive (PED) (97/23/EC)
Rosemount 485 Annubar — Refer to EC declaration of conformity for conformity assessment
Pressure Transmitter — See appropriate Pressure Transmitter QSG

6.3 Hazardous Locations Certifications

For information regarding the transmitter product certification, see the appropriate transmitter QSG:
Rosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series
Flowmeter Quick Start Guide.
Rosemount 3051S MultiVariable Transmitter and Rosemount 3051SF Series
Flowmeter MultiVariable Transmitter Quick Start Guide.
Rosemount 3051 Pressure Transmitter and Rosemount 3051CF Series
Flowmeter Transmitter Quick Start Guide
Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series
Flowmeter Transmitter Quick Start Guide
. A hard copy may be obtained by contacting
.
.
15
Page 16
Quick Start Guide
Figure 10. Rosemount 485 Declaration of Conformity
16
Page 17
Quick Start Guide
17
Page 18
Quick Start Guide
18
Page 19
1B: 含有China RoHS
管控物彯㚨⣏㳻⹎旸ῤ的部件型号列表
Rosemount 485
Table 1B: List of Rosemount 485 Parts with China RoHS Concentration above MCVs
部件名称
Part Name
有害物峐ġİġHazardous Substances
Lead (Pb)
Mercury
(Hg)
Cadmium
(Cd)
六价
Hexavalent
Chromium
(Cr +6)
多ⓤ俼劗
Polybrominated
biphenyls
(PBB)
多ⓤ俼劗慂
Polybrominated
diphenyl ethers
多ⓤ俼劗慂
(PBDE)
䬍ࡦ⑙ᓖՐ ᝏಘཆ༣㓴
Ԧ
Aluminum
RTD
Housing
Assembly
O O O X O O
本表格系依据
SJ/T11364
奬⭂侴⇞ἄįġ
This table is proposed in accordance with the provision of SJ/T11364 O:
󰶃宍悐ẞ䘬㇨㚱⛯峐㛸㕁󰵶宍㚱⭛䈑峐䘬⏓慷⛯ỶḶ
GB/T 26572
奬⭂䘬旸慷天㯪įġ
O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572. X:
󰶃⛐宍悐ẞ㇨ἧ䓐䘬㇨㚱⛯峐㛸㕁慴炻军⮹㚱ᶨ䰣⛯峐㛸㕁󰵶宍㚱⭛䈑峐䘬⏓慷檀Ḷ
GB/T 26572
奬⭂䘬旸慷天㯪įġ
X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.
к䘠⭣᰾ӵ䘲⭘Ҿ䘹ᤙ䬍ࡦཆ༣㓴ԦⲴӗ૱DŽަԆᡰᴹᐞ঻⍱䟿а⅑ݳԦⲴ㓴ԦᡰᴹⲴ China RoHS ㇑᧗⢙䍘⎃ ᓖ൷վҾ GB/T 26572 ᡰ㿴ᇊⲴ䲀䟿㾱≲DŽޣҾᐞ঻⍱䟿䇑䘱ಘ㓴ԦⲴ㇑᧗⢙䍘⎃ᓖⲴ⭣᰾ˈ䈧৲ⴻ䘱ಘⲴᘛ 䙏ᆹ㻵ᤷইDŽ
The disclosure above applies to units supplied with aluminum connection heads. No other components supplied with DP Flow primary elements contain any restricted substances. Please consult the transmitter Quick Start Guide (QIG) for disclosure information on transmitter components.
Quick Start Guide
19
Page 20
Global Headquarters
Emerson Process Management
6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@EmersonProcess.com
North America Regional Office
Emerson Process Management
8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com
Latin America Regional Office
Emerson Process Management
1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@EmersonProcess.com
Europe Regional Office
Emerson Process Management Europe GmbH
Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@EmersonProcess.com
Asia Pacific Regional Office
Emerson Process Management Asia Pacific Pte Ltd
1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.EmersonProcess.com
Middle East and Africa Regional Office
Emerson Process Management
Emerson FZE P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emi rates
+971 4 8118100 +971 4 8865465
RFQ.RMTMEA@Emerson.com
*00825-0700-4809*
Quick Start Guide
00825-0700-4809, Rev BA
Linkedin.com/company/Emerson-Process-Management
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/us er/RosemountMeasur ement
Google.com/+RosemountMeasurement
Standard Terms and Conditions of Sale can be found at
www.Emerson.com/en-us/pages/Terms-of-Use.aspx
The Emerson logo is a trademark and service mark of Emerson Electric Co. Annubar, Rosemount and Rosemount logotype are trademarks of Emerson Process Management. All other marks are the property of their respective owners. © 2016 Emerson Process Management. All rights reserved.
June 2016
Loading...