Rosemount 485 Annubar Pak-Lok Assembly Quick Start Guide

Page 1
Quick Start Guide
00825-0300-4809, Rev EB
Rosemount™ 485 Annubar™ Pak-Lok Assembly
June 2016
Page 2
Quick Start Guide
June 2016
NOTICE
This guide provides basic guidelines for Rosemount 485 Annubar. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or Intrinsically Safe (I.S.) installations. Refer to Rosemount 485 Annubar Reference Manual instruction. This manual is also available electronically on Emerso nProcess.com/Rosemount
If the Rosemount Annubar was ordered assembled to a Rosemount Pressure Transmitter, see the following Quick Start Guides for information on configuration and hazardous locations certifications:
Rosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flowmeter Quick Start
Guide.
Rosemount 3051S MultiVariable Transmitter and Rosemount 3051SF Series Flowmeter MultiVariable
Tra ns mi tte r Quick Start Guide
Rosemount 3051 Pressure Transmitter and Rosemount 3051CF Series Flowmeter Transmitter Quick
Start Guide.
Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flowmeter Transmitter Quick
Start Guide.
Process leaks may cause harm or result in death. To avoid process leaks, only use gaskets designed to seal with the corresponding flange and o-rings to seal process connections. Flowing medium may cause the Rosemount 485 Annubar Assembly to become hot and could result in burns.
.
for more
.
Contents
Location and orientation. . . . . . . . . . . . . . . . . . 5
Drill sensor holes . . . . . . . . . . . . . . . . . . . . . . . 11
Weld mounting hardware. . . . . . . . . . . . . . . . 13
2
Insert the Rosemount Annubar Sensor. . . . . 14
Mount the transmitter. . . . . . . . . . . . . . . . . . . 17
Product certifications . . . . . . . . . . . . . . . . . . . 19
Page 3
June 2016
Quick Start Guide
Figure 1. Rosemount 485 Annubar Pak-Lok Assembly Exploded View
A
B
C
D
E
F
(1)
A. Transmitter B. Coplanar flange with drain vents C. 2 O-rings
1. Transmitter and housing are shown for clarity purposes — only supplied if ordered.
D. Direct-mount transmitter connection with valves E. Pak-Lok body F. See Figure 2 for details
3
Page 4
Quick Start Guide
A
B
C
D
E
F
G
Figure 2. Rosemount 485 Annubar Pak-Lok Assembly Detail Exploded View
June 2016
A. Nuts B. Follower C. 3 Packing rings D. Studs
E. Compression plate F. Retaining ring G. Rosemount 485 Annubar Sensor
4
Page 5
June 2016
Quick Start Guide

1.0 Location and orientation

Correct orientation and straight run requirements must be met for accurate and repeatable flow measurements. Refer to Table 1 for minimum pipe diameter distances from upstream and downstream disturbances.
Table 1. Straight Run Requirements
In plane____________Out of plane Upstream pipe diameters
Without
straightening
vanes
In
Out of
plane
plane
A
8
1
N/A10N/A
11
2
N/A16N/A
23
3
With straightening
vanes
A’ C C’ B
A
N/A8N/A4N/A
N/A8N/A4N/A
N/A8N/A4N/A
Downstream
pipe diameters
4
4
4
4
4
4
4
N/A28N/A
12
4
N/A12N/A
N/A8N/A4N/A
4
4
4
4
4
5
Page 6
Quick Start Guide
June 2016
18
5
N/A18N/A
30
6
N/A30N/A
N/A8N/A4N/A
N/A8N/A4N/A
Note
Consult the factory for instructions regarding use in square or rectangular
ducts.
If proper lengths of straight run are not available, position the mounting such
that 80% of the run is upstream and 20% is downstream. This will result in degraded accuracy.
Use straightening vanes to reduce the required straight run length. Row 6 in Ta b l e 1 applies to gate, globe, plug, and other throttling valves that
are partially opened, as well as control valves.

1.1 Misalignment

Rosemount 485 Annubar installation allows for a maximum misalignment of 3°.
4
4
4
4
4
4
Figure 3. Misalignment
±3°
6
±3°
±3°
Page 7
June 2016
45° 45°
30°
Recommended
zone 30°
Recommended zone 30°
Flow
360°

1.2 Flowmeter Orientation

Figure 4. Flowmeter Orientation for Liquid
Direct mount
Horizontal liquid Vertical liquid
Quick Start Guide
(1)
Horizontal liquid Vertical liquid
1. Downward flow is not recommended.
Remote mount
(1)
Flow
7
Page 8
Quick Start Guide
45° 45°
Recommended zone 90°
Flow
Figure 5. Flowmeter Orientation for Gas
Direct mount
Horizontal gas Vertical gas
June 2016
360°
Remote mount
Horizontal gas Vertical gas
Flow
8
Page 9
June 2016
360°
Flow
Figure 6. Flowmeter Orientation for Steam
Direct mount
Horizontal steam Vertical steam
45° 45°
Quick Start Guide
(1)
Recommended
zone 30°
Recommended
30°
zone 30°
Remote mount
Horizontal steam Vertical steam
(1)
1. Downward flow is not recommended.
Note
For steam applications with DP readings between 0.75 and 2 inH2O in horizontal pipes, consider installing the primary element/flowmeter mounting in the top mounting for steam configuration.
9
Page 10
Quick Start Guide

1.3 Top mounting the flowmeter for steam

Top mounting in steam is an alternative mounting method for steam installations that can be used if there are space restrictions or other concerns. This installation method is intended for applications that run with limited interruptions or shutdowns. Also, for outdoor applications, top mounting can eliminate the need for heat tracing, if steam is flowing.
Figure 7. Horizontal Top Mounting for Steam
Direct mount
Recommended zone
60°
60° 60°
(1)
Remote mount
June 2016
1. For wet steam, do not mount the flowmeter at the direct vertical position. Mou nting at an angle will avoid measurement inaccuracy due to water running along the bottom of the pipe.
This orientation can be used for any steam temperature. For remote mount installations, the impulse piping should slope up slightly from the instrument connections on the Rosemount Annubar to the cross fittings, allowing condensate to drain back into the pipe. From the cross fittings, the impulse piping should be routed downward to the transmitter and the drain legs. The transmitter should be located below the instrument connections of the Rosemount Annubar. Depending on the environmental conditions, it may be necessary to insulate the mounting hardware.
10
Page 11
June 2016

2.0 Drill sensor holes

1. Determine the sensor size based on the probe width (see Tab le 2 ).
Table 2. Sensor Size/Hole Diameter Chart
Sensor size Sensor width Hole diameter
1 0.590-in. (14,99 mm)
2 1.060-in. (26,92 mm) 15/16-in. (34 mm) +1/16-in. (1,6 mm) – 0.00
3 1.935-in. (49,15 mm) 21/2-in. (64 mm) +1/16-in. (1,6 mm) – 0.00
2. Depressurize and drain the pipe.
3. Select the location to drill the hole.
4. Determine the diameter of the hole to be drilled according to the specifications in Ta bl e 2 . Drill the mounting hole into the pipe with a hole saw or drill. DO NOT TORCH CUT THE HOLE.
Drill to Hole Size
3
/4-in. (19 mm) +1/32-in (0,8 mm) – 0.00
Quick Start Guide
P/N: 28-109001-922 Rev. AC
When drilling the mounting hole(s), Emerson™ Process Manag ement recommends the use of a magnetic drill or pipe clamping fixture to safely drill the hole. Use appropriate personal protective equipment and procedures when drilling and welding.
11
Page 12
Quick Start Guide
Drill the appropriate diameter hole through the pipe wall.
5. Although it is not commonly selected, if an opposite-side support model is supplied, a second identically sized hole must be drilled opposite the first hole so that the sensor can pass completely through the pipe. (To determine if you have an opposite-side support model, measure the distance from the tip to the first slot or hole. If the distance is greater than 1-in. (25,4 mm), it is the opposite-side support model.) To drill the second hole, follow these steps: a. Measure the pipe circumference with a pipe tape, soft wire, or string. (For
the most accurate measurement the pipe tape needs to be perpendicular to the axis of flow.)
b. Divide the measured circumference by two to determine the location of the
second hole.
c. Re-wrap the pipe tape, soft wire, or string from the center of the first hole.
Then, using the number calculated in step b, mark the center of what will become the second hole.
d. Using the diameter determined in step 4, drill the hole into the pipe with a
hole saw or drill. DO NOT TORCH CUT THE HOLE.
Note
Drill the hole 180° from the first hole for opposite- side support models.
June 2016
6. Deburr the drilled holes on the inside of the pipe.
12
Page 13
June 2016
A
B
Quick Start Guide

3.0 Weld mounting hardware

1. Center the Pak-Lok body over the mounting hole, gap 1/16-in. (1,6 mm), and place four
2. Check alignment of the Pak-Lok body both parallel and perpendicular to the axis of flow (see Figure 8). If alignment of mounting is within tolerances, finish weld per local codes. If alignment is outside of specified tolerance, make adjustments prior to finish weld.
Figure 8. Alignment
1
/4-in. (6 mm) tack welds at 90° increments.
A. Lower Mounting Height (LMH) B. Tack welds
1. LMH values are as follows:
Sensor size 1 — 2.89-in.(73 mm) Sensor size 2 — 3.92-in.(100 mm) Sensor size 3 — 3.96-in.(101 mm)
(1)
3. If opposite side support is being used, center the fitting for the opposite side support over the opposite side hole, gap 1/16-in. (1,6 mm), and place four
1
/4-in. (6 mm) tack welds at 90° increments. Insert the sensor into the mounting hardware. Verify that the tip of the sensor is centered in the opposite side fitting and that the plug will fit around sensor. Finish weld per local codes. If the alignment of the sensor does not allow enough clearance to insert the opposite side plug, make the necessary adjustments prior to making the finish weld.
4. To avoid serious burns, allow the mounting hardware to cool before continuing.
13
Page 14
Quick Start Guide

4.0 Insert the Rosemount Annubar Sensor

Note
Refer to “Rosemount 485 Annubar Pak-Lok Assembly Exploded View” on page 3 for component descriptions.
1. Thread studs into the Pak-Lok body.
2. To ensure that the flowmeter contacts the opposite side pipe wall, mark the tip of the sensor with a marker. (Do not mark if ordered with option code P2 or PA. )
3. Insert the flowmeter into the Pak-Lok body until the sensor tip contacts the pipe wall (or support plug), twisting the flowmeter back and forth.
4. Verify that the sensor tip made contact with the opposite side pipe wall by removing the flowmeter and ensuring that some of the marker has been rubbed off. For special-cleaned sensors, look for wear marks on the tip. If the tip did not touch the wall, verify the measured pipe ID and wall match the tagging information and re-insert.
Serial No. Date Model
Customer Tag
Pipe I.D. Wall Max. Allow FlowRate Max. Insert/Retract Flow Max. Press. @ Temp Span (20mA)
00-370000-2X1 Rev. AC
June 2016
5. Align the flow arrow on the head with the direction of flow. Re-insert the flow meter into the Pak-Lok body and install the first packing ring on the sensor between the retaining ring and the follower. Take care not to damage the split packing rings.
Figure 9. Packing Ring Detail
A
B
A. Retaining ring B. 3 Packing rings
14
D
C
C. Follower D. Compression plate
Page 15
June 2016
Quick Start Guide
6. Push the packing ring into the Pak-Lok body and against the weld retaining ring. Repeat this process for the two remaining rings, alternating the location of the packing ring split by 120°. a. Install the first packing ring underneath the follower.
b. Use the follower and the compression plate to compress the first packing
ring against the retaining ring.
c. Install the second packing ring underneath the follower. Alternate packing
ring splits by 120 degrees to each other.
d. Use the follower and the compression plate to compress the second
packing ring against the first packing ring.
e. Install the third packing ring underneath the follower. f. Use the follower and the compression plate to compress the third packing
ring against the second packing ring.
7. Tighten the nuts onto the studs: a. Place the included split-ring lock washer between each of the nuts and the
compression plate. Give each nut one half turn in succession until the split-ring lock washer is flat between the nut and the compression plate. Torque is as follows.
15
Page 16
Quick Start Guide
Gap
Table 3. Torque Requirements
Sensor size Tor que
1 40 in-lb (4,5 N-m)
2 100 in-lb (11,3 N-m)
3 250 in-lb (28,2 N-m)
b. Inspect the unit for leakage. If any exists, tighten the nuts in one-quarter
turn increments until there is no leakage.
Note
On sensor size 1, failure to use the split-ring Lock washers, improper washer orientation, or over-tightening the nuts may result in flowmeter damage.
Figure 10. Split-Ring Lock Washer Orientation
Before tightening After tightening
June 2016
Note
Pak-Lok sealing mechanisms generate significant force at the point where the sensor contacts the opposite pipe wall. Caution needs to be exercised on thin-walled piping (ANSI Sch 10 and lower) to avoid damage to the pipe.
8. Verify that a gap exists between the compression plate and the Pak-Lok body. If the gap is not within the tolerances shown in Ta bl e 4 , repeat steps 6 and 7 to ensure the packing was installed correctly. If the gap is still not within tolerances, contact your Emerson Process Management representative for technical support.
16
Page 17
June 2016
Quick Start Guide
Table 4. Minimum and Maximum Gap Dimensions
Sensor size
1 2 3
Minimum gap in. (mm) 0.52 (13,3) 0.52 (13,3) 1.19 (30,2)
Maximum gap in. (mm) 1.25 (31,8) 1.93 (48,9) 1.93 (48,9)

5.0 Mount the transmitter

5.1 Mounting a transmitter with a direct mount head and valves

It is not necessary to retract the Rosemount Annubar when direct mounting a transmitter with valves.
1. Place PTFE O-rings into grooves on the Rosemount Annubar Head.
2. Align the high side of the transmitter to the high side of the sensor (“Hi” is stamped on the side of the head) and install.
3. Tighten the nuts in a cross pattern to 384 in-lb (43 N-m).

5.2 Mounting a transmitter with a remote mount head

Temperatures in excess of 250 °F (121 °C) at the transmitter sensor module diaphragms will damage the transmitter. Remote mounted transmitters are connected to the sensor by means of impulse piping, which allows process temperatures to decrease to a point where the transmitter is no longer vulnerable.
Different impulse piping arrangements are used depending on the process fluid and must be rated for continuous operation at the pipeline design pressure and temperature. A minimum of with a wall thickness of at least 0.035-in. (0,9 mm) is recommended for 600# ANSI (DN50 PN100) and below. Above 600# ANSI (DN50 PN100), stainless steel tubing with a minimum wall thickness of are not recommended because they add potential leak points. The following restrictions and recommendations apply to impulse piping location:
1. Impulse piping that runs horizontally must slope at least one inch per foot (83 mm/m).
- Slope downward (toward the transmitter) for liquid and steam applications.
- Slope upward (toward the transmitter) for gas applications.
2. Outdoor installations for liquid, saturated gas, or steam may require insulation and/or heat tracing to prevent freezing.
3. An instrument manifold is recommended for all installations. Manifolds allow an operator to equalize the pressures prior to zeroing and isolates the process fluid from the transmitter.
1
/2-in. (12 mm) outer diameter stainless steel tubing
1
/16-in.(1,6 mm). Threaded pipe fittings
17
Page 18
Quick Start Guide
Figure 11. Valve identification for 5-valve and 3-Valve Manifolds
5-valve manifold 3-valve manifold
June 2016
To PH To PL
MH
MEH
DVH
To PH
MV
MH
2
ML
MEL
DVL
1
DVH
To PL
ME
2
1
Table 5. Description of Impulse Valves and Components
Name Description Purpose
Components
1 Tran sm it ter s Reads Differential Pressure
2 Manifold Isolates and equalizes electronics
Manifold and impulse valves
PH Primary sensor
PL Primary sensor
DVH Drain/vent valve(1)
DVL Drain/vent valve(2)
MH Manifold valve high(1)
ML Manifold valve low(2)
MEH Manifold equalizer(1)
MEL Manifold equalizer(2)
ME Manifold equalizer Allows high and low side pressure to equalize
MV Manifold vent valve Vents process fluid
(1)
(2)
High and low side pressure process connections.
Drains (for gas service) or vents (for liquid or steam service) the DP sensor diaphragms
Isolates high side or low side pressure from the process
Allows high and low pressure side access to the vent valve, or for isolating the process fluid
ML
DVL
1. High pressure
2. Low pressure
18
Page 19
June 2016
Quick Start Guide

6.0 Product certifications

6.1 Approved Manufacturing Locations

Rosemount Inc. – Shakopee, Minnesota USA
Rosemount DP Flow Design and Operations – Boulder, Colorado USA
Emerson Process Management GmbH & Co. OHG – Wessling, Germany
Emerson Process Management Asia Pacific Private Limited – Singapore
Emerson Beijing Instrument Co., Ltd – Beijing, China

6.2 European Directive Information

The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at
EmersonProcess.com/Rosemount
our local sales office.
European Pressure Equipment Directive (PED) (97/23/EC)
Rosemount 485 Annubar — Refer to EC declaration of conformity for conformity assessment
Pressure Transmitter — See appropriate Pressure Transmitter QSG

6.3 Hazardous Locations Certifications

For information regarding the transmitter product certification, see the appropriate transmitter QSG:
Rosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series
Flowmeter Quick Start Guide
Rosemount 3051S MultiVariable Transmitter and Rosemount 3051SF Series
Flowmeter MultiVariable Transmitter Quick Start Guide.
Rosemount 3051 Pressure Transmitter and Rosemount 3051CF Series
Flowmeter Transmitter Quick Start Guide.
Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series
Flowmeter Transmitter Quick Start Guide
. A hard copy may be obtained by contacting
.
.
19
Page 20
Quick Start Guide
Figure 12. Rosemount Primary Element Declaration of Conformity
June 2016
20
Page 21
June 2016
Quick Start Guide
21
Page 22
Quick Start Guide
June 2016
22
Page 23
June 2016
1B: 含有China RoHS
管控物彯㚨⣏㳻⹎旸ῤ的部件型号列表
Rosemount 485
Table 1B: List of Rosemount 485 Parts with China RoHS Concentration above MCVs
部件名称
Part Name
有害物峐ġİġHazardous Substances
Lead (Pb)
Mercury
(Hg)
Cadmium
(Cd)
六价
Hexavalent
Chromium
(Cr +6)
多ⓤ俼劗
Polybrominated
biphenyls
(PBB)
多ⓤ俼劗慂
Polybrominated
diphenyl ethers
多ⓤ俼劗慂
(PBDE)
䬍ࡦ⑙ᓖՐ ᝏಘཆ༣㓴
Ԧ
Aluminum
RTD
Housing
Assembly
O O O X O O
本表格系依据
SJ/T11364
奬⭂侴⇞ἄįġ
This table is proposed in accordance with the provision of SJ/T11364 O:
󰶃宍悐ẞ䘬㇨㚱⛯峐㛸㕁󰵶宍㚱⭛䈑峐䘬⏓慷⛯ỶḶ
GB/T 26572
奬⭂䘬旸慷天㯪įġ
O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572. X:
󰶃⛐宍悐ẞ㇨ἧ䓐䘬㇨㚱⛯峐㛸㕁慴炻军⮹㚱ᶨ䰣⛯峐㛸㕁󰵶宍㚱⭛䈑峐䘬⏓慷檀Ḷ
GB/T 26572
奬⭂䘬旸慷天㯪įġ
X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.
к䘠⭣᰾ӵ䘲⭘Ҿ䘹ᤙ䬍ࡦཆ༣㓴ԦⲴӗ૱DŽަԆᡰᴹᐞ঻⍱䟿а⅑ݳԦⲴ㓴ԦᡰᴹⲴ China RoHS ㇑᧗⢙䍘⎃ ᓖ൷վҾ GB/T 26572 ᡰ㿴ᇊⲴ䲀䟿㾱≲DŽޣҾᐞ঻⍱䟿䇑䘱ಘ㓴ԦⲴ㇑᧗⢙䍘⎃ᓖⲴ⭣᰾ˈ䈧৲ⴻ䘱ಘⲴᘛ 䙏ᆹ㻵ᤷইDŽ
The disclosure above applies to units supplied with aluminum connection heads. No other components supplied with DP Flow primary elements contain any restricted substances. Please consult the transmitter Quick Start Guide (QIG) for disclosure information on transmitter components.
Quick Start Guide
23
Page 24
Global Headquarters
Emerson Process Management
6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@EmersonProcess.com
North America Regional Office
Emerson Process Management
8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com
Latin America Regional Office
Emerson Process Management
1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@EmersonProcess.com
Europe Regional Office
Emerson Process Management Europe GmbH
Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@EmersonProcess.com
Asia Pacific Regional Office
Emerson Process Management Asia Pacific Pte Ltd
1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.EmersonProcess.com
Middle East and Africa Regional Office
Emerson Process Management
Emerson FZE P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emi rates
+971 4 8118100 +971 4 8865465
RFQ.RMTMEA@Emerson.com
*00825-0300-4809*
Quick Start Guide
00825-0300-4809, Rev EB
Linkedin.com/company/Emerson-Process-Management
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/us er/RosemountMeasur ement
Google.com/+RosemountMeasurement
Standard Terms and Conditions of Sale can be found at
www.Emerson.com/en-us/pages/Terms-of-Use.aspx
The Emerson logo is a trademark and service mark of Emerson Electric Co. Annubar, Rosemount and Rosemount logotype are trademarks of Emerson Process Management. All other marks are the property of their respective owners. © 2016 Emerson Process Management. All rights reserved.
June 2016
Loading...