Rosemount 4088 Transmitter Utility Upgrade User Manual Manual Supplement

Page 1
Manual Supplement
00809-0300-4088, Rev BA November 2018
Rosemount™ 4088 Transmitter Utility Upgrade User Manual
Installation and user guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1
Upgrade utility release information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2
System requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2
Hardware requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2
Connecting to the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2
Using the upgrade utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3
Technical support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4

1.0 Installation and user guide

This guide provides information required to install and use the Rosemount™ 4088 Firmware Upgrade Utility.
NOTICE
Per the license agreement, do not share this tool, with anyone outside your organization. If you do share the tool with others within your organization, let any additional users know that this tool is proprietary and absolutely cannot be shared outside of the organization.

2.0 What update was made to the firmware?

As of January 5th, 2018, the Rosemount 4088 firmware was updated from firmware revision 5 to revision
6. Firmware revision 6 has updated the default damping on process temperature from five seconds to two seconds, allowing for faster temperature measurement response times as well as reduced
calibration time required. Firmware revision 6 also enhanced the calibration process between Emerson flow computers and the Rosemount 4088 transmitter, creating tighter integration and reduced maintenance time.
Page 2
Rosemount 4088 Transmitter Utility Upgrade User Manual
2018

3.0 Upgrade utility release information

Utility version: 1.0.0.5 Released date: January, 2018 Released by: Emerson

4.0 System requirements

Microsoft® Windows™ 7 Operating System (32 or 64 bit)

5.0 Hardware requirements

Serial to RS-485 Modem (computer must have serial port)
If computer does not have a serial port, a USB to serial modem converter must be used.
The tool may work with many different modems and converters, but all testing at Rosemount was completed with the following modems:
Manual Supplement
00809-0300-4088, Rev BA
Modem 1: Rosemount serial to RS-485 modem, Part # 03095-5106-0002
Modem 2: B&B Electronics, Model 485SD9TB

6.0 Connecting to the transmitter

Transmitter covers should not be removed in explosion-proof areas with power applied.
To ensure there are no connection interruptions, the Rosemount 4088 communications should be
isolated from any other transmitter or flow computer when the firmware flash is in process.
Connect a reliable power source to the PWR (+) and (-) terminals on the transmitter.
Connect the communication leads from the modem to the RS-485 (A) and (B) terminals of the
transmitter.
2
Rosemount 4088 Transmitter Utility Upgrade User Manual
Page 3
Manual Supplement
00809-0300-4088, Rev BA
Rosemount 4088 Transmitter Utility Upgrade User Manual

7.0 Using the upgrade utility

1. Enter the Modbus® address for the transmitter.
2. Ensure the baud rate in the transmitter and utility tool match.
3. Select the proper serial port on your PC.
4. Select the Flash button.
2018
Each transmitter will take about 10 minutes to upgrade at 9600 Baud.
Device configuration and calibration will be maintained throughout the update process, so there is
no need to recalibrate or reconfigure after the update completes.

7.1 Error message

If an error message is received during the upgrade process, it will appear as follows.
Rosemount 4088 Transmitter Utility Upgrade User Manual
3
Page 4
Rosemount 4088 Transmitter Utility Upgrade User Manual
2018
If this happens, ensure the transmitter communication is isolated, the power supply is providing sufficient power, all connections are good, and simply start the upgrade process over.
Manual Supplement
00809-0300-4088, Rev BA

8.0 Technical support

If issues arise during upgrade, contact your local Emerson sales representative for help or answers to your questions.
4
Rosemount 4088 Transmitter Utility Upgrade User Manual
Page 5
Manual Supplement
00809-0300-4088, Rev BA
Rosemount 4088 Transmitter Utility Upgrade User Manual
2018
Rosemount 4088 Transmitter Utility Upgrade User Manual
5
Page 6
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com
North America Regional Office
Emerson Automation Solutions
8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com
Latin America Regional Office
Emerson Automation Solutions
1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
Manual Supplement
00809-0300-4088, Rev BA
November 2018
Europe Regional Office
Emerson Automation Solutions Europe GmbH
Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office
Emerson Automation Solutions
1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions
Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465 RFQ.RMTMEA@Emerson.com
Linkedin.com/company/Emerson-Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/RosemountMeasurement
Google.com/+RosemountMeasurement
Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners.
© 2018 Emerson. All rights reserved.
Loading...