This guide provides basic guidelines for the Rosemount 4088 MultiVariable Transmitter. It does not provide
instructions for diagnostics, maintenance, service, or troubleshooting. Reference the 4088 MultiVariable
Tra ns mi tt er Reference Manual
EmersonProcess.com/Rosemount
Procedures and instructions in this section may require special precautions to
ensure the safety of the personnel performing the operation. Information that raises
potential safety issues is indicated with a warning symbol (). Refer to the
following safety messages before performing an operation preceded by this
symbol.
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local,
national, and international standards, codes, and practices. Review the approvals section of the 4088
MultiVariable Transmitter Reference Manual
Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments in the loop
are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In an Explosion-proof/Flameproof installation, do not remove the transmitter covers when power is applied
to the unit.
Process leaks may cause harm or result in death.
Install and tighten process connectors before applying pressure.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical
shock.
Conduit/cable entries
Unless marked, the conduit/cable entries in the transmitter housing use a
marked “M20” are M20 ⫻ 1.5 thread form. On devices with multiple conduit entries, all entries will have the
same thread form. Only use plugs, adapters, glands, or conduit with a compatible thread form when closing
these entries.
When installing in a hazardous location, use only appropriately listed or Ex certified plugs, adapters, or
glands in cable/conduit entries.
for more instruction. All documents are available electronically at
.
for any restrictions associated with a safe installation.
3. Mount the transmitter so that the
drain/vent valves are oriented
upward.
2.2 Gas flow applications
1. Place taps in the top or side of the
line.
2. Mount beside or above the taps.
3
Page 4
Quick Start Guide
2.3 Steam flow applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
September 2016
4
Page 5
September 2016
2.4 Mounting brackets
Figure 1. Coplanar Flange
Panel mountPipe mount
Figure 2. Traditional Flange
Quick Start Guide
Panel mountPipe mount
Figure 3. In-Line Flange
Panel mountPipe mount
5
Page 6
Quick Start Guide
4 ⫻ 1.75-in. (44 mm)
4 ⫻ 2.88-in. (73 mm)
A
B
C
4 ⫻ 1.75-in. (44 mm)
D
4 ⫻ 1.50-in. (38 mm)
4 ⫻ 2.25-in. (57 mm)
4 ⫻ 1.75-in. (44 mm)
September 2016
2.5 Bolting considerations
If the transmitter installation requires assembly of a process flange, manifold, or
flange adapters, follow these assembly guidelines to ensure a tight seal for
optimal performance characteristics of the transmitter. Only use bolts supplied
with the transmitter or sold by Emerson Process Management as spare parts.
Figure 4 on page 6 illustrates common transmitter assemblies with the bolt
length required for proper transmitter assembly.
Figure 4. Common Transmitter Assemblies
6
A. Transmitter with coplanar flange
B. Transmitter with coplanar flange and optional flange adapters
C. Transmitter with traditional flange and optional flange adapters
D. Transmitter with coplanar flange and optional Rosemount Conventional Manifold and
flange adapters
Note
For all other manifolds, contact Customer Central technical support.
Bolts are typically carbon steel or stainless steel. Confirm the material by viewing
the markings on the head of the bolt and referencing Table 1. If bolt material is
not shown in Table 1, contact the local Emerson Process Management
representative for more information.
Use the following bolt installation procedure:
1. Carbon steel bolts do not require lubrication and the stainless steel bolts are
coated with a lubricant to ease installation. However, no additional lubricant
should be applied when installing either type of bolt.
Page 7
September 2016
316
316
316
SW
316
STM
316
R
B8M
A
B
A. Flange adapter
B. O-ring
C. PTFE based profile is square
D. Elastomer profile is round
Quick Start Guide
2. Finger-tighten the bolts.
3. Torque the bolts to the initial torque value using a crossing pattern. See
Ta bl e 1 for initial torque value.
4. Torque the bolts to the final torque value using the same crossing pattern. See
Ta bl e 1 for final torque value.
5. Verify the flange bolts are protruding through the sensor module before
applying pressure (see Figure 5).
Table 1. Torque Values for Flange and Flange Adapter Bolts
Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious
injury. Only use the O-ring that is designed for its specific flange adapter.
A
C
D
Whenever the flange or adapters are removed, visually inspect the O-rings. Replace them if there are any signs
of damage, such as nicks or cuts. If the O-rings are replaced, re-torque the flange bolts and alignment screws
after installation to compensate for seating of the O-rings.
B
7
Page 8
Quick Start Guide
A
A
B
September 2016
2.7 Environmental seal for housing
Thread sealing (PTFE) tape or paste on male threads of conduit is required to
provide a water/dust tight conduit seal and meets requirements of NEMA Type
4X, IP66, and IP68. Consult factory if other Ingress Protection ratings are required.
For M20 threads, install conduit plugs to full thread engagement or until
mechanical resistance is met.
2.8 In-line gage transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage
transmitter is located under the sensor module neck label. (See Figure 6.)
Keep the vent path free of any obstruction, including but not limited to paint,
dust, and lubrication by mounting the transmitter so that any contaminants can
drain away.
Figure 6. In-Line Gage Transmitter
A. Low side pressure port (under neck label)
3.0 Consider housing rotation
To improve field access to wiring or to better view the optional LCD display:
1. Loosen the housing rotation set screw.
2. Turn the housing up to 180° left or right of its original (as shipped) position.
3. Re-tighten the housing rotation set screw.
Figure 7. Transmitter Housing Set Screw
A. LCD display B. Housing rotation set screw (3/32-in.)
8
Page 9
September 2016
A
B
Quick Start Guide
Note
Do not rotate the housing more than 180° without first performing a disassembly
procedure [reference Rosemount 4088 MultiVariable Transmitter Reference Manual
more information]. Over-rotation may sever the electrical connection between the sensor
module and the electronics.
3.1 Rotate the LCD display
Transmitters ordered with the LCD display will be shipped with the display
installed.
In addition to housing rotation, the optional LCD display can be rotated in
90-degree increments by squeezing the two tabs, pulling out, rotating and
snapping back into place.
If LCD display pins are inadvertently removed from the interface board, carefully
re-insert the pins before snapping the LCD display back into place.
Use the following procedure and Figure 8 to install the LCD display:
1. If the transmitter is installed in a loop, then secure the loop and disconnect
power.
for
2. Remove the transmitter cover opposite the field terminal side. Do not remove
the instrument covers in explosive environments when the circuit is live.
3. Engage the four-pin connector into the LCD display and snap into place.
4. Install the meter cover and tighten to ensure metal to metal contact.
Figure 8. Optional LCD Display
A. LCD display B. Meter cover
4.0 Set the switches
The transmitter’s default configuration for the AC Termination is in the off
position. The transmitter’s default configuration for the security switch is in the
off position.
1. If the transmitter is installed, secure the bus and remove power.
2. Remove the housing cover opposite the field terminals side. Do not remove
the housing cover in explosive environments.
9
Page 10
Quick Start Guide
A
B
September 2016
3. Slide the security and AC Termination switches into the preferred position by
using a small screwdriver. Note that the security switch will need to be in the
off position in order to make any configuration changes.
4. Reinstall the housing cover and tighten so that the cover is fully seated with
metal to metal contact between the housing and cover in order to meet
explosion proof requirements.
Figure 9. Transmitter Switch Configuration
A. SecurityB. AC termination
5.0 Wiring and power up
Use the following steps to wire the transmitter:
1. Remove the cover on the field terminals side of the housing.
2. Set up based on optional process temperature input.
a. If the optional process temperature input is being utilized, follow the
procedure “Install optional process temperature input (Pt 100 RTD Sensor)”
on page 13.
b. If there will not be an optional temperature input, plug and seal the unused
conduit connection.
3. Connect the transmitter to the RS-485 bus as shown in Figure 10.
a. Connect the A lead to the “A” terminal.
b. Connect the B lead to the “B” terminal.
4. Connect the positive lead from the power source to the “PWR +” terminal, and
the negative lead to the “PWR –” terminal.
Note
The Rosemount 4088 MultiVariable Transmitter uses RS-485 Modbus with 8 data bits, one
stop bit and no parity. The default baud rate is 9600.
Note
Twisted pair wiring is required for RS-485 bus wiring. Wiring runs under 1000 ft (305 m)
should be AWG 22 or larger. Wiring runs from 1000 to 4000 feet (305 to 1219 m) should be
AWG 20 or larger. Wiring should not exceed AWG 16.
5. Ensure full contact with Terminal Block screw and washer. When using a direct
wiring method, wrap wire clockwise to ensure it is in place when tightening
the terminal block screw.
10
Page 11
September 2016
Ω
Quick Start Guide
Note
The use of a pin or a ferrule wire terminal is not recommended as the connection may be
more susceptible to loosening over time or under vibration.
NOTICE
When the enclosed threaded plug is utilized in the conduit opening, it must be installed with a minimum
engagement of five threads in order to comply with explosion-proof requirements. Reference the
Rosemount 4088 MultiVariable Transmitter Reference Manual
6. Reinstall the housing cover and tighten so the cover is fully seated with metal
to metal contact between the housing and cover in order to meet explosion
proof requirements.
Note
Installation of the transient protection terminal block does not provide transient protection
unless the transmitter housing is properly grounded.
for more information.
Figure 10. Transmitter Wiring for RS-485 Bus
C
D
E
A. RS-485 (A)
B. RS-485 (B)
C. RS-485 bus, twisted pair required
5.1 Grounding
Signal wire grounding
B
D
A
D. Bus Termination: AC Termination on 4088
(see “Set the switches” on page 9) or
120 resistor
E. User-provided power supply
Do not run signal wiring in conduit or open trays with power wiring, or near heavy
electrical equipment. Ground the shield of the signal wiring at any one point on
the signal loop. The negative terminal of the power supply is a recommended
grounding point. Device must be properly grounded or earthed according to local
electric codes.
Transmitter case
Always ground the transmitter case in accordance with national and local
11
Page 12
Quick Start Guide
Ω
September 2016
electrical codes. The most effective transmitter case grounding method is a
direct connection to earth ground with minimal impedance (< 1). Methods for
grounding the transmitter case include:
Internal ground connection
The internal ground connection screw is inside the terminal side of the electronics
housing. The screw is identified by a ground symbol ().
Figure 11. Internal Ground Connection
A
A. Ground lug
External ground connection
The external ground connection is on the outside of the sensor module housing.
The connection is identified by a ground symbol (). An external ground
assembly is included with the option codes shown in Table 2 on
available as a spare part (03151-9060-0001).
Figure 12. External Ground Connection
B
A
A. External ground lug B. External ground assembly 03151-9060-0001
K1ATEX Flameproof, Intrinsic Safety, Type n, Dust (combination of E1, I1, N1, and ND)
E7IECEx Flameproof, Dust Ignition-proof
N7IECEx Type n
Quick Start Guide
K7
KA
KC
T1Transient terminal block
D4External ground screw assembly
IECEx Flameproof, Dust Ignition-proof, Intrinsic Safety, and Type n
(combination of E7, I7, and N7)
ATEX and CSA Explosion-proof, Intrinsically Safe, Division 2
(combination of E1, E6, I1, and I6)
FM and ATEX Explosion-proof, Intrinsically Safe, Division 2
(combination of E5, E1, I5, and I1)
Surges/transients
The transmitter will withstand electrical transients of the energy level usually
encountered in static discharges or induced switching transients. However,
high-energy transients, such as those induced in wiring from nearby lightning
strikes, can damage the transmitter.
Optional transient protection terminal block
The transient protection terminal block can be ordered as an installed option
(Option Code T1 in the transmitter model number) or as a spare part to retrofit
existing 4088 MultiVariable Transmitters in the field. For a complete listing of
spare part numbers for transient protection terminal blocks, reference the
Rosemount 4088 MultiVariable Reference Manual
terminal block identifies it as having transient protection.
. A lightning bolt symbol on a
Note
Grounding the transmitter case using the threaded conduit connection may not provide a
sufficient ground. The transient protection terminal block (Option Code T1) will not provide
transient protection unless the transmitter case is properly grounded. See “Trim the
transmitter” on page 18 to ground the transmitter case. Do not run transient protection
ground wire with signal wiring; the ground wire may carry excessive current if a lightning
strike occurs.
5.2 Install optional process temperature input (Pt 100 RTD
Sensor)
Note
To meet ATEX/IECEx Flameproof certification, only ATEX/IECEx Flameproof Cables
(Temperature Input Code C30, C32, C33, or C34) may be used.
1. Mount the Pt 100 RTD Sensor in the appropriate location.
Note
Use shielded four-wire or three-wire cable for the process temperature connection.
13
Page 14
Quick Start Guide
3-Wire4-Wire
A
B
B
A
Red
Red
White
White
September 2016
2. Connect the RTD cable to the Rosemount 4088 MultiVariable Transmitter by
inserting the cable wires through the unused housing conduit and connect to
the screws on the transmitter terminal block. An appropriate cable gland
should be used to seal the conduit opening around the cable.
Note
If power is already connected to the Rosemount 4088 MultiVariable Transmitter, power
should be removed prior to connecting the RTD wires. This will allow the transmitter to
detect the RTD type at startup. Once the RTD is installed, reconnect power. The same
procedure should be followed if the RTD type is changed.
3. Connect the RTD cable shield wire to the ground lug in the housing.
Verify the installed PT sensor type (3 or 4 wire) matches the device setting.
14
Page 15
September 2016
A
B
C
D
OR
Quick Start Guide
6.0 Verify device configuration
Use RTIS with the Rosemount 4088 DTM or a HART Field Communicator with the
Rosemount 4088 Device Descriptor to communicate with and verify
configuration of the Rosemount 4088 MultiVariable transmitter.
Figure 14 shows the wiring connections necessary to power a Rosemount 4088
MultiVariable Transmitter and enable communications with a PC-based software
tool or handheld Field Communicator.
6.1 Transmitter wiring
Figure 14. Configuration via HART® (local) Port
It is not required to remove the Rosemount 4088 from the RS-485 network when
configuring over the local HART port. The device should be taken out of service or
put in manual prior to performing any configuration changes.
A. Rosemount transmitter interface software (RTIS)
B. HART modem
C. Handheld communicator
D. User-provided power supply
15
Page 16
Quick Start Guide
D
C
B
A
D
E
F
G
Ω
Figure 15. Configuration via RS-485 Network Port
The Rosemount 4088 may be configured with the Rosemount 3095FB
Configuration Software. When using this legacy tool, only functionality that was
available with the Rosemount 3095FB can be accessed. The device must be
®
removed from the Modbus
bus.
network prior to communicating over the RS-485
September 2016
A. RS- 485 (A)
B. RS-485 (B)
C. RS-485 bus, twisted pair required
D. Bus Termination: AC Termination on 4088 (see “Set
the switches” on page 9) or 120 resistor
Note
Device configuration procedures are given for RTIS in the Rosemount 4088 MultiVariable
Transmitter Reference Manual. This manual also includes a detailed Modbus register map.
E. User-provided power supply
F. Rosemount 3095FB
configuration software
G. RS-232/RS485 converter
A check () indicates the basic configuration parameters. At a minimum, these
parameters should be verified as part of the configuration and startup procedure.
Table 3. Fast Keys
CategoryFunctionFast Key sequence
DeviceAvailable Measurements1,9,4
DeviceDisplay2,2,5
DeviceSensor Module Temperature2,2,4
DeviceSensor Module Temperature Units2,2,4,3
16
Page 17
September 2016
Table 3. Fast Keys
CategoryFunctionFast Key sequence
Quick Start Guide
Device
DeviceDevice Address2,2,6,1,1
DeviceDevice Status1,1
DeviceBaud Rate2,2,6,1,2
DeviceTurnaround Delay2,2,6,1,3
DeviceTag2,2,7,1,1
DeviceLong Tag2,2,7,1,2
DeviceTransm itter S/ N2,2,7,1,7
DeviceSecurity Switch1,9,5,1
DP SensorDP2,2,1
DP SensorCalibration3,4,1,8
DP SensorDP Units2,2,1,3
DP SensorDP Damping2,2,1,4
DP SensorVeri fica tion3,4,1,9
DP Sensor
Sensor Module Temperature Upper Alert Limit
Sensor Module Temperature Lower Alert Limit
Upper Alert Limit
Lower Alert Limit
2,2,4,4
2,2,4,5
2,2,1,6
2,2,1,7
PT SensorSensor Matching2,2,3,8
PT SensorPT2,2,3
PT SensorCalibration3,4,3,8
PT SensorPT Units2,2,3,3
PT SensorPT Damping2,2,3,4
PT SensorSensor Type2,2,3,5
PT SensorVeri fica tion3,4,3,9
PT Sensor
PT SensorTem p Mod e Set up2,2,3,7
SP SensorAP2,2,2,7
SP SensorSP Units2,2,2,3
SP SensorGP2,2,2,6
SP SensorSP Damping2,2,2,4
SP SensorCalibration3,4,2,8
SP SensorVerific atio n3,4,2,9
Upper Alert Limit
Lower Alert Limit
2,2,3,6,1
2,2,3,6,2
SP Sensor
Upper Alert Limit
Lower Alert Limit
2,2,2,6,3
2,2,2,6,4
17
Page 18
Quick Start Guide
September 2016
7.0 Trim the transmitter
Transmitters are shipped fully calibrated per request or by the factory default of
full scale.
Use RTIS with the Rosemount 4088 DTM or a HART Field Communicator with the
Rosemount 4088 Device Descriptor to communicate with and perform
maintenance on the Rosemount 4088 MultiVariable Transmitter.
7.1 Zero trim
A zero trim is a single-point adjustment used for compensating mounting
position and line pressure effects on static and differential pressure sensors.
When performing a zero trim, ensure that the equalizing valve is open and all wet
legs are filled to the correct level.
The transmitter will allow up to 95% of URL zero error to be trimmed through a
lower trim procedure.
If zero offset is less than 5% of URL, follow the user interface software instructions
below.
Performing a zero trim using the Field Communicator
1. Block, equalize, and vent the transmitter and connect the Field Communicator
(for more information on connecting the Field Communicator, see Figure 14
on page 15).
2. If the device is equipped with a static pressure sensor, trim the sensor by
inputting the following Fast Key sequence at the 4088 MultiVariable
Transmitter menu:
Fast KeysDescription
3,4,2,8Static Pressure Sensor Trim Options
3. Follow the static pressure trim procedure.
Zero Trim for Gauge Pressure Sensors
OR
Lower Sensor Trim for Absolute Pressure Sensors
Note
When performing a lower sensor trim on an absolute pressure sensor, it is possible to
degrade the performance of the sensor if inaccurate calibration equipment is used. Use a
barometer that is at least three times as accurate as the absolute sensor of the 4088
MultiVariable Transmitter.
4. Zero the differential pressure sensor by inputting the following Fast Key
sequence at the Rosemount 4088 MultiVariable Transmitter menu:
Fast KeysDescription
3,4,1,8,5Differential Pressure Sensor Zero Trim
5. Follow the zero DP trim procedure.
18
Page 19
September 2016
Quick Start Guide
8.0 Product certifications
Rev 1.3
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local,
national, and international standards, codes, and practices. Review this document for any restrictions
associated with a safe installation.
Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments in the loop
are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In an Explosion-proof/Flameproof installation, do not remove the transmitter covers when power is
applied to the unit.
Conduit/cable entries
Unless marked, the conduit/cable entries in the transmitter housing use a 1/2-14 NPT thread form.
Entries marked "M20" are M20 ⫻ 1.5 thread form. On devices with multiple conduit entries, all entries
will have the same thread form. Only use plugs, adapters, glands, or conduit with a compatible thread
form when closing these entries.
When installing in a hazardous location, use only appropriately listed or Ex certified plugs, adapters, or
glands in cable/conduit entries.
8.1 European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the Quick
Start Guide. The most recent revision of the EU Declaration of Conformity can be
found at EmersonProcess.com/Rosemount.
8.2 Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that the
design meets the basic electrical, mechanical, and fire protection requirements
by a nationally recognized test laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).
8.3 Installing Equipment in North America
The US National Electrical Code (NEC) and the Canadian Electrical Code (CEC)
permit the use of Division marked equipment in Zones and Zone marked
equipment in Divisions. The markings must be suitable for the area classification,
gas, and temperature class. This information is clearly defined in the respective
codes.
USA
E5 FM Explosionproof (XP), Dust-Ignitionproof (DIP) and Nonincendive (NI)
Certificate: 3045445 / 3052850
Standards: FM Class 3600 - 2011, FM Class 3611 - 2004, FM Class 3615 - 2005,
FM Class 3616 2011, FM 3810 - 2005, ANSI/NEMA 250 - 1991,
ANSI/IEC 60529 - 2004
Markings: XP Class I, Division 1, Groups B, C, D (Ta = -50 °C to 85 °C);
DIP Class II and Class III, Division 1, Groups E, F, G (T
Class I Zone 0/1 AEx d IIC T5 (T
Nonincendive Class I, Division 2, Groups A, B, C, D; T4(-50 °C ≤ T
enclosure Type 4X/IP66/IP68; conduit seal not required
= -50 °C to 80 °C);
a
= -50 °C to 85 °C);
a
≤ 70 °C);
a
19
Page 20
Quick Start Guide
September 2016
Note
Transmitters marked with NI CL 1, DIV 2 can be installed in Division 2 locations using
general Division 2 wiring methods or Nonincendive Field Wiring (NIFW). See Drawing
04088-1206.
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm. Installation, maintenance, and use shall take
into account the environmental conditions to which the diaphragm will be subjected.
The manufacturers instruction for maintenance shall be followed in detail to assure
safety during its expected lifetime.
2. In case of repair contact the manufacturer for information on the dimensions of the
flameproof joint.
3. Appropriate cable, glands, and plugs need to be suitable for a temperature of 5 °C
greater than the maximum specified temperature for location where installed.
4. The applicable temperature class, ambient temperature range and process temperature
range of the equipment is as follows:
T4 for –50 °C ≤ T
T5 for –50 °C ≤ T
T6 for –50 °C ≤ T
≤ 80 °C with T process = –50 °C to 120 °C
a
≤ 80 °C with T process = –50 °C to 80 °C
a
≤ 65 °C with T process = –50 °C to 65 °C
a
I5 FM Intrinsic Safety (IS) and Nonincendive (NI)
Certificate: 3052850
Standards: FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 - 2004,
FM Class 3810 - 2005, ANSI/NEMA 250 - 1991, ANSI/ISA 60529 - 2004,
ANSI/ISA 61010-1 - 2004
Markings: Intrinsic Safety Class I, Division 1, Groups C, D; Class II, Groups E, F, G;
Class III; Class I Zone 0 AEx ia IIB T4; Nonincendive Class I, Division 2, Groups
A, B, C, D; T4(-50 °C
≤ T
≤ 70 °C); when connected per Rosemount drawing
a
04088-1206; Type 4X
Special Conditions for Safe Use (X):
1. The maximum permitted ambient temperature of the Model 4088 Pressure Transmitter
is 70 °C. To avoid the effects of process temperature and other thermal effects care shall
be taken to ensure the surrounding ambient and the ambient inside the transmitter
housing does not exceed 70 °C.
2. The enclosure may contain aluminum and is considered to present a potential risk of
ignition by impact or friction. Care must be taken during installation and use to prevent
impact or friction.
3. The Model 4088 Transmitters fitted with transient protection are not capable of
withstanding the 500V test. This must be taken into account during installation.
Note
Transmitters marked with NI CL 1, DIV 2 can be installed in Division 2 locations using
general Division 2 wiring methods or Nonincendive Field Wiring (NIFW). See Drawing
04088-1206.
20
Page 21
September 2016
Canada
All CSA hazardous approved transmitters are dual seal certified per ANSI/ISA
12.27.01–2003.
E6 CSA Explosionproof, Dust-Ignitionproof, and Division 2
Markings: Class I, Division 1, Groups C, D, Temp Code T3C; Class I Zone 0 Ex ia IIB T4;
when installed per Rosemount Drawing 04088-1207; Type 4X
Quick Start Guide
Europe
E1 ATEX Flameproof
Certificate: FM12ATEX0030X
Standards: EN 60079-0:2012, EN 60079-1:2007, EN 60079-26:2008,
EN 60529:1991+A1:2000
Markings: II 1/2 G Ex d IIC T6…T4, T4/T5 T
T6 Ta=-50 °C to 65 °C, Ga/Gb
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm. Installation, maintenance and use shall take
into account the environmental conditions to which the diaphragm will be subjected.
The manufacturer's instruction for maintenance shall be followed in detail to assure
safety during its expected lifetime.
2. In case of repair, contact the manufacturer for information on the dimensions of the
flameproof joint.
3. Appropriate cable, glands, and plugs need to be suitable for a temperature of 5 °C
greater than the maximum specified temperature for location where installed.
4. The applicable temperature class, ambient temperature range and process temperature
range of the equipment is as follows:
T4 for –50 °C ≤ T
T5 for –50 °C ≤ T
T6 for –50 °C ≤ T
≤ 80 °C with T process = –50 °C to 120 °C
a
≤ 80 °C with T process = –50 °C to 80 °C
a
≤ 65 °C with T process = –50 °C to 65 °C
a
5. The Transmitter can be installed in the boundary wall between an area of Category 1
and Category 2. In this configuration, the process connection is installed in Category 1,
while the transmitter housing is installed in Category 2.
=-50 °C to 80 °C,
a
21
Page 22
Quick Start Guide
I1 ATEX Flameproof
Certificate: Baseefa13ATEX0221X
Standards: EN 60079-0:2012, EN 60079-11:2012
Markings: II 1 G Ex ia IIB T4 Ga (-60 °C
≤ T
≤ +70 °C)
a
SupplyModbusRTD
September 2016
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
22 V9 V15.51 V
147 mA26 mA20.89 mA
1 W1 W80.94 mW
000
000
Special Conditions for Safe Use (X):
1. The 4088 MV Transmitters fitted with transient protection are not capable of
withstanding the 500V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must
be taken into account during installation.
2. The Model 4088 MV enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it from impact or
abrasion if located in a Zone 0 area.
ND ATE X Dust
Certificate: FM12ATEX0030X
Standards: EN 60079-0:2012, EN 60079-31:2009, EN 60529:1991+A1:2000
Markings: CII 2 D Ex tb IIIC T95 °C, T
=-20 °C to 85 °C Db
a
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at
least IP66/68.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the
ingress protection of the enclosure to at least IP66/68.
3. Cable entries and blanking plugs must be suitable for the ambient range of the
apparatus and capable of withstanding a 7J impact test.
N1 ATEX Type n
Certificate: Baseefa13ATEX0222X
Standards: EN 60079-0:2012, EN 60079-15: 2010
Markings: II 3 G Ex nA IIC T5 Gc (-40 °C
Special Condition for Safe Use (X):
1. The Model 4088 MV Transmitters fitted with transient protection are not capable of
withstanding the 500V test as defined in Clause 6.5.1 of EN 60079-15:2010. This must
be taken into account during installation.
22
≤ T
≤ 70 °C)
a
Page 23
September 2016
Quick Start Guide
International
E7 IECEx Flameproof
Certificate: IECEx FMG 13.0024X
Standards: IEC 60079-0:2011, IEC 60079-1: 2007, IEC 60079-26: 2006
Markings: Ex d IIC T6…T4, T4/T5 T
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm. Installation, maintenance and use shall take
into account the environmental conditions to which the diaphragm will be subjected.
The manufacturer's instruction for maintenance shall be followed in detail to assure
safety during its expected lifetime.
2. In case of repair, contact the manufacturer for information on the dimensions of the
flameproof joint.
3. Appropriate cable, glands, and plugs need to be suitable for a temperature of 5 °C
greater than the maximum specified temperature for location where installed.
4. The applicable temperature class, ambient temperature range and process temperature
range of the equipment is as follows:
T4 for –50 °C ≤ T
T5 for –50 °C ≤ T
T6 for –50 °C ≤ T
≤ 80 °C with T process = –50 °C to 120 °C
a
≤ 80 °C with T process = –50 °C to 80 °C
a
≤ 65 °C with T process = –50 °C to 65 °C
a
5. The Transmitter can be installed in the boundary wall between an area of EPL Ga and the
less hazardous area, EPL Gb. In this configuration, the process connection is installed in
EPL Ga, while the transmitter housing is installed in EPL Gb.
=-50 °C to 80 °C, T6 Ta=-50 °C to 65 °C, Ga/Gb
a
I7 IECEx Intrinsic Safety
Certificate: IECEx BAS 13.0110X
Standards: IEC 60079-0:2011, IEC 60079-11:2011
Markings: Ex ia IIB T4 Ga (-60 °C ≤ T
SupplyModbusRTD
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
22 V9 V15.51 V
147 mA26 mA20.89 mA
1 W1 W80.94 mW
i
000
000
≤ +70 °C)
a
Special Conditions for Safe Use (X):
1. The Model 4088 MV Transmitters fitted with transient protection are not capable of
withstanding the 500V test as defined in Clause 6.3.13 of IEC 60079-11:2012. This must
be taken into account during installation.
2. The Model 4088 MV enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it from impact or
abrasion if located in a Zone 0 area.
NK IECEx Dust
Certificate: IECEx FMG 13.0024X
Standards: IEC 60079-0:2011, IEC 60079-31:2013
Markings: Ex tb IIIC T95 °C, T
=-20 °C to 85 °C, Db
a
23
Page 24
Quick Start Guide
September 2016
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at
least IP66/68.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the
ingress protection of the enclosure to at least IP66/68.
3. Cable entries and blanking plugs must be suitable for the ambient range of the
apparatus and capable of withstanding a 7J impact test.
N7 IECEx Type n
Certificate: IECEx BAS 13.0111X
Standards: IEC 60079-0:2011, IEC 60079-15: 2010
Markings: Ex nA IIC T5 Gc (-40 °C ≤ T
≤ +70 °C)
a
Special Condition for Safe Use (X):
1. The Model 4088 MV Transmitters fitted with transient protection are not capable of
withstanding the 500V test as defined in Clause 6.5.1 of IEC 60079-15:2010. This must
be taken into account during installation.
1. This device contains a thin wall diaphragm. Installation, maintenance and use shall take
into account the environmental conditions to which the diaphragm will be subjected.
The manufacturer's instructions for installation and maintenance shall be followed in
detail to assure safety during its expected lifetime.
2. In case of repair, contact the manufacturer for information on the dimensions of the
flameproof joints.
3. Appropriate cable, glands, and plugs need to be suitable for a temperature of 5 °C
greater than the maximum specified temperature for the location where it is installed.
4. The transmitter can be installed in the boundary wall between an area of EPL Ga and the
less hazardous area, EPL Gb. In this configuration, the process connection is installed in
EPL Ga, while the transmitter housing is installed in EPL Gb.
5. The applicable temperature class, ambient temperature range and process temperature
range of the equipment is as follows:
T4 for –50 °C ≤ T
T5 for –50 °C ≤ T
T6 for –50 °C ≤ T
≤ 80 °C with T process = –50 °C to 120 °C
a
≤ 80 °C with T process = –50 °C to 80 °C
a
≤ 65 °C with T process = –50 °C to 65 °C
a
I2 INMETRO Intrinsic Safety
Certificate: UL-BR 15.0720X
Standards: ABNT NBR IEC60079-0:2008 + Errata 1:2011, ABNT NBR IEC60079-11:2009
Markings: Ex ia IIB T4 Ga, T4(-60 °C ≤ T
≤ +70 °C)
a
24
Page 25
September 2016
Quick Start Guide
SupplyModbusRTD
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
22 V9 V15.51 V
147 mA26 mA20.89 mA
1 W1 W80.94 mW
000
000
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90V transient suppressor, it is not capable of
withstanding the 500V insulation test required by ABNT NBR IRC 60079-11. This must
be taken into account when installing the equipment.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane
paint finish; however, care should be taken to protect it from impact or abrasion in
zones that require EPL Ga.
Technical Regulations Customs Union (EAC)
EM EAC Flameproof
Certificate: RU C-US.M
Markings: Ga/Gb Ex d IIC T6…T4 X, T5/T4(-50 °C
ю62.B.02349
≤ Ta ≤ +80 °C), T6(-50 °C ≤ Ta ≤ +65 °C)
Special Condition for Safe Use (X):
See certificate for special conditions
IM EAC Intrinsically Safe
Certificate: RU C-US.M
ю62.B.02349
Markings: 0Ex ia IIB T4 Ga X, T4(-60 °C
Special Condition for Safe Use (X):
See certificate for special conditions
Combinations
K1 Combination of E1, I1, N1, and ND
K2 Combination of E2 and I2
K5 Combination of E5 and I5
K6 Combination of E6 and I6
K7 Combination of E7, I7, N7, and NK
KA Combination of E1, I1, E6, and I6
KB Combination of E5, I5, E6, and I6
KC Combination of E1, I1, E5, and I5
KD Combination of E1, I1, E5, I5, E6, and I6
KM Combination of EM and IM
≤ Ta ≤ +70 °C)
25
Page 26
Quick Start Guide
Figure 16. Rosemount 4088 Declaration of Conformity
September 2016
26
Page 27
September 2016
Quick Start Guide
27
Page 28
Quick Start Guide
September 2016
28
Page 29
September 2016
Quick Start Guide
29
Page 30
Quick Start Guide
ᴹ
China RoHS
㇑᧗⢙䍘䎵䗷ᴰབྷ⎃ᓖ䲀٬Ⲵ䜘Ԧරࡇ㺘
Rosemount 4088A
List of Rosemount 4088A Parts with China RoHS Concentration above MCVs
䜘Ԧ〠
Part Name
ᴹᇣ⢙䍘䍘
/ Hazardous Substances
䫵
Lead
(Pb)
⊎
Mercury
(Hg)
䭹
Cadmium
(Cd)
ޝԧ䬜䬜
Hexavalent
Chromium
(Cr +6)
ཊⓤ㚄㚄㤟
Polybrominated
biphenyls
(PBB)
ཊⓤ㚄㚄㤟䟊
Polybrominated
diphenyl ethers
(PBDE)
⭥ᆀ㓴Ԧ
Electronics
Assembly
XO OOOO
༣փ㓴Ԧ
Housing
Assembly
XO OXOO
Րᝏಘ㓴Ԧ
Sensor
Assembly
XO OXOO
ᵜ㺘Ṭ㌫ᦞ
SJ/T11364
Ⲵ㿴ᇊ㘼ࡦ
This table is proposed in accordance with the provision of SJ/T11364.
O:
Ѫ䈕䜘ԦⲴᡰᴹ൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿൷վҾ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of
GB/T 26572.
X:
Ѫ൘䈕䜘Ԧᡰ֯⭘Ⲵᡰᴹ൷䍘ᶀᯉ䟼ˈ㠣ቁᴹа㊫൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿儈Ҿ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above
the limit requirement of GB/T 26572.