merson designs, manufactures and tests its products to meet many national and international stan-
E
dards. Because these sensors are sophisticated technical products, you MUST properly install, use,
and maintain them to ensure they continue to operate within their normal specifications. The
following instructions MUST be adhered to and integrated into your safety program when installing,
using, and maintaining Rosemount products. Failure to follow the proper instructions may cause any
one of the following situations to occur: loss of life; personal injury; property damage; damage to this
sensor; and warranty invalidation.
•Read all instructions prior to installing, operating, and servicing the product.
• If you do not understand any of the instructions, contact your Emerson representative for
clarification.
• Follow all warnings, cautions, and instructions marked on and supplied with the product.
• Inform and educate your personnel in the proper installation, operation, and maintenance
of the product.
•Install your equipment as specified in the Installation Instructions of the appropriate
Quick Start Guide and per applicable local and national codes. Connect all products to
the proper electrical and pressure sources.
• To ensure proper performance, use qualified personnel to install, operate, update,
program, and maintain the product.
• When replacement parts are required, ensure that qualified people use replacement parts
specified by Emerson. Unauthorized parts and procedures can affect the product's
performance, place the safe operation of your process at risk, and VOID YOUR WARRANTY.
Third-party substitutions may result in fire, electrical hazards, or improper operation.
• Ensure that all equipment doors are closed and protective covers are in place, except when
maintenance is being performed by qualified persons, to prevent electrical shock and
personal injury.
The information contained in this document is subject to change without notice.
CAUTION
Sensor/Process Application Compatibility
The wetted sensor materials may not be compatible with process composition and operating
conditions. Application compatibility is entirely the responsibility of the user.
CAUTION
The 402 and 402VP sensors are retractable. BEFORE RETRACTING THE SENSOR, be absolutely certain the
process pressure is less than 64 psig (542 kPa abs) and the process temperature is at a safe level!
At 1.6 in. Hg (5.2 kPa) air leakage is less than 0.005 SCFM (0.00014 m3/min)
Cell constants
0.01, 0.1, and 1.0/cm
Process connection
Sensor is inserted through 1¼ in. NPT full port ball valve
Cable
10 ft (3.1 m) standard; for longer cable lengths, choose option -60 (integral junction box) and order interconnecting cable
separately; 402VP Interconnecting VP6 cables sold separately. (See
Accessories).
Table 1-2: Weights and shipping weights
Sensor model With 10 ft. (3.1 m) cableWith junction box
At 1.6 in. Hg (5.2 kPa) air leakage is less than 0.005 SCFM (0.00014 m3/min)
2 to 212 °F (0 to 100 °C)
3
16 Stainless Steel
3
raphite
G
2Specifications
Quick Start GuideInstallation
00825-0100-3402May 2019
Section 2: Installation
2.1Unpacking and Inspection
Inspect the outside of the carton for any damage. If damage is detected, contact the carrier
immediately. Inspect the instrument and hardware. Make sure all items in the packing list are
present and in good condition. Notify the factory if any part is missing.
2.2Sensor Installation
Figure 2-1 Sensor orientation
Figure 2-2 Recommended installation
Keep ¼ in. (6 mm) clearance between electrodes and piping. The electrolytes must be completely
submerged in the process liquid, i.e., to the upper edge of the guard (item 10 in Figure 2-4).
Installation3
InstallationQuick Start Guide
May 201900825-0100-3402
2.2Installation and Retraction of Sensor
Figure 2-3 Label
2.1.1Installation
Retraction assembly kit (PN 23765-00) consists of items 1 through 7 shown in Figure 2-4 as well as
a hex key and pipe tape. The sensor assembly includes items 8 through 11.
IMPORTANT
Do not remove or alter the guard (10) on the sensor tube (9).
Figure 2-4 Sensor with retraction assembly kit
1.Make sure the system is shut down and there is no residual pressure.
2.Attach the ball valve (2) to the process piping using the 1–¼-in. FNPT port on the valve
or the 1–¼ in. NPT nipple (1). Use pipe tape on male threads.
4Installation
Quick Start GuideInstallation
00825-0100-3402May 2019
3.Slide the handle lock up on the ball valve handle and close the ball valve (2). If the process
will be restarted before the sensor is installed, make sure the system pressure is at or below
542 kPa abs (64 psig) before proceeding. If the system will not be restarted until after the
ensor installation, leave the valve in the open position.
s
4.If the sensor includes a junction box (8), it must be removed from the sensor to install the
retraction assembly kit. Disconnect the sensor wires inside the junction box prior to
disassembly.
5.Follow
6.Position the sensor tube (9) so that the electrodes (11) are completely withdrawn inside
7.Position the clamp (4) on the sensor tube (9) so that the electrodes (11) will be completely
8.Slide the retainer (5) onto the sensor tube (9).
9.Screw the junction box (8) — hand tight — onto the sensor tube (9). DO NOT OVER
10.Apply pipe tape to the packing adapter (3) threads and screw the packing adapter onto
11.Check to ensure that the packing bushing (6) has been tightened. You should be able to
12.Open the ball valve (2).
13.There may be some leakage around the packing bushing (6). Tighten the packing bushing
Figure 2-5 to assemble the sensor and retraction assembly. Keep items 3-7 in the
proper sequence. Items 3, 6, and 7 are factory assembled.
the packing adapter (3). If it is difficult to slide the sensor through the packing rings, loosen
the packing bushing (6).
immersed in the process liquid when the sensor is fully inserted through the ball valve. See
Figure 2-4. Use the hex key to secure the clamp to the sensor tube.
TIGHTEN. Use 2-3 wraps of pipe tape on the tube threads if a NEMA 4 seal is required at the
junction box.
the ball valve.
push the sensor tube (9) against the resistance provided by the packing rings (7).
to stop the leak. Use the junction box (8) or sensor rear to push the sensor through the
valve until the clamp (4) rests against the packing bushing.
14.To secure the sensor tube (9) in place, tighten — hand tighten only — the retainer (5)
against the back of the packing adapter (3). If the sensor tube retracts when the system
pressure is increased, reduce the pressure to 542 kPa abs (64 psig) or less, remove the
retainer (5), and tighten the screw in the clamp (4).
Figure 2-5 Sensor installation
Installation5
InstallationQuick Start Guide
May 201900825-0100-3402
2.1.2Retraction
1.Make sure the system pressure is at or below 542 kPa abs (64 psig) at the valve before
proceeding. Provide adequate working area for retraction.
2.Unscrew the retainer (5) from the packing adapter (3). If it is difficult to unscrew the
retainer, system pressure may be forcing the clamp (4) into the retainer. The packing
bushing (6) may not be tight enough to hold the sensor tube (9) in place. To prevent a
sudden retraction of the sensor tube as the retainer is removed, hold onto the junction
box (8) or sensor rear to restrain the sensor.
3.If the sensor tube (9) does not slide back as the retainer is unscrewed, pull back on the
junction box (8) or sensor tube to retract the sensor.
4.If the sensor tube (9) cannot be retracted, loosen the clamp (4) using the hex key. Pull the
clamp back and slowly loosen the packing bushing (6) in 1/8-turn increments. System pres
sure may cause the tube to retract. If not, pull back on the junction box (8) or sensor tube
(9) to withdraw the sensor.
5.Withdraw the sensor tube until the guard (10) contacts the stop inside the packing adapter
(3). The electrodes (11) are now inside the packing adapter. See
lock up on the valve handle and close the ball valve (2).
Figure 2-6. Slide the handle
IMPORTANT
Failure to withdraw the sensor completely may result in damage to the electrodes when the valve is closed.
6.Unscrew the packing adapter (3) from the ball valve (2) to remove the sensor and
retraction assembly.
Figure 2-6 Rosemount 402 Contacting Conductivity Sensor in Retracted Position
6Installation
Quick Start GuideWiring
00825-0100-3402May 2019
Section 3: Wiring
3.1Wiring for Rosemount 402/402VP
For other wiring diagrams not shown below, please refer to the Liquid Transmitter Wiring Diagrams.
Figure 3-1: Wire color and connections in sensor
Figure 3-2: Wiring for integral junction box
Wiring7
WiringQuick Start Guide
May 201900825-0100-3402
Figure 3-3: Wiring for Rosemount 56 and 1056 transmitters
Figure 3-4: Wiring for Rosemount 56 and 1056 transmitters
8Wiring
Quick Start GuideWiring
00825-0100-3402May 2019
Figure 3-5: Wiring for Rosemount 5081 transmitter
3.1.1Wiring through a Junction Box
If wiring connections are made through a remote junction box (PN 23550-00), wire point-to-point.
Use interconnecting cable 23747-00 (factory-terminated) or 9200275 (no terminations).
Figure 3-6: Pin out diagram for Rosemount 402VP contacting conductivity sensors with
Variopol cable connection
Wiring9
WiringQuick Start Guide
May 201900825-0100-3402
10Wiring
Quick Start GuideCalibration and Maintenance
00825-0100-3402May 2019
Section 4: Calibration and Maintenance
4.1Cleaning the sensor
Use a warm detergent solution and a soft brush or pipe cleaner to remove oil and scale. Isopropyl
alcohol (rubbing alcohol) can also be used to remove oily films. Avoid using strong mineral acids
to clean conductivity sensors.
4.1Calibrating the sensor
Rosemount 402 conductivity sensors are calibrated at the factory and do not need calibration when
first placed in service. Simply enter the cell constant printed on the label into the transmitter. After
a period of service, the sensor may require calibration. The sensor can be calibrated against a
solution having known conductivity or against a referee meter and sensor. If using a standard
solution, choose one having conductivity in the recommended operating for the sensor cell
constant. Refer to the analyzer manual or product data sheet for recommended ranges. Do not
use standard solutions having conductivity less than about 100 µS/cm. They are susceptible to
contamination by atmospheric carbon dioxide, which can alter the conductivity by a variable
amount as great as 1.2 µS/cm (at 25 °C). Because 0.01/cm sensors must be calibrated in low
conductivity solutions, they are best calibrated against a referee meter and sensor in a closed
system. For more information about calibrating refer to Application Data Sheet.
Calibration and Maintenance11
Calibration and MaintenanceQuick Start Guide
May 201900825-0100-3402
12Calibration and Maintenance
Quick Start GuideTroubleshooting
00825-0100-3402May 2019
Section 5: Troubleshooting
5.1Troubleshooting
Table 5-1: Troubleshooting
TroubleProbable CauseRemedy
Wiring is incorrect.Verify wiring.
Temperature element is open or shorted.Check temperature element for open or short
Off-scale reading
circuits. See
Sensor is not in process stream.Be sure sensor is completely submerged in
process stream.
Variopol cable is not properly seated.Loosen connector and reseat.
Sensor has failed.Perform isolation checks. See Figure 5-2.
Figure 5-1.
Sensor is improperly installed in process
Noisy reading
Reading seems wrong (lower
or higher than expected)
Sluggish responseElectrodes are fouled.Clean electrodes.
stream.
Variopol cable is not properly seated.Loosen connector and reseat.
Bubbles trapped in sensor.Be sure sensor is properly oriented in pipe or
Wrong temperature correction algorithm.Check that temperature correction is appro-
Wrong cell constant. Verify that the correct cell constant has been
Sensor is installed in dead area in pipingMove sensor to a location more representative
Be sure sensor is completely submerged in
process stream.
flow cell. See
to flow cell.
priate for the sample. See transmitter manual
for more information.
entered in the analyzer and that the cell
constant is appropriate for the conductivity of
the sample. See transmitter manual.
of the process liquid.
Figure 2-1. Apply back pressure
Note: For any repair or warranty inquiries please contact our Customer Care group.
Troubleshooting13
TroubleshootingQuick Start Guide
May 201900825-0100-3402
5.1.1Checking the temperature element
Disconnect leads and measure resistance shown. The measured resistance should be close to the
value in the table.
Figure 5-1 Checking the temperature element
5.1.2Checking the continuity and leakage
Disconnect electrode leads and measure resistance and continuity as shown. Sensor must be dry
when checking resistance between electrode leads.
Figure 5-2 Checking the continuity and leakage
Temperature
(°C)
0100.01000
10103.91039
20107.81078
30111.71117
40115.51155
50119.41194
Resistance in ohms
Pt 100Pt 1000
14Troubleshooting
Quick Start GuideAccessories
00825-0100-3402May 2019
Section 6: Accessories
6.1Accessories
Table 6-1: Accessories for Rosemount 402/402VP Contacting Conductivity Sensor accessories information
23765-00Retraction assembly kit (includes nipple, ball valve, and retraction body)
23796-00Retraction Body
93400781¼ in. NPT Full Port Ball Valve
05010781899
05010797875
05010782468
05010783002
05000705464
05000709672
05010782147
05010782026
23747-062.5 ft (0.8 m) Interconnecting VP6 Cable
23747-046.4 ft (1.2 m) Interconnecting VP6 Cable
23747-0210 ft (3.0 m) Interconnecting VP6 Cable
23747-0715 ft (4.6 m) Interconnecting VP6 Cable
23747-0820 ft (6.1 m) Interconnecting VP6 Cable
23747-0925 ft (7.6 m) Interconnecting VP6 Cable
23747-1030 ft (9.1 m) Interconnecting VP6 Cable
23747-0350 ft (15.2 m) Interconnecting VP6 Cable
23747-11100 ft (30.5 m) Interconnecting VP6 Cable
Conductivity standard SS-6, 200 µS/cm, 32 oz (0.95 L)
Conductivity standard SS-6A, 200 µS/cm, 1 gal (3.78 L)
Conductivity standard SS-5, 100k0 µS/cm, 32 oz (0.95 L)
Conductivity standard SS-5A, 1000 µS/cm, 1 gal (3.78 L)
Conductivity standard SS-1, 1409 µS/cm, 32 oz (0.95 L)
Conductivity standard SS-1A, 1409 µS/cm, 1 gal (3.78 L)
Conductivity standard SS-7, 5000 µS/cm, 32 oz (0.95 L)
Conductivity standard SS-7A, 5000 µS/cm, 1 gal (3.78 L)
Accessories15
Quick Start Guide
May 201900825-0100-3402
16
Quick Start Guide00825-0100-3402
ay 2019
M
17
00825-0100-3402
Rev. AA
May 2019
www.Emerson.com/Rosemount
Youtube.com/user/Rosemount
Twitter.com/Rosemount_News
Emerson Automation Solutions
8200 Market Blvd.
Chanhassen, MN 55317,
USA
Tel +1 800 999 9307
Fax +1 952 949 7001
The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of
one of the Emerson family of companies. All other marks are the property of their respective
owners.
The contents of this publication are presented for information purposes only, and while effort has
been made to ensure their accuracy, they are not to be construed as warranties or guarantees,
express or implied, regarding the products or services described herein or their use or applicability.
All sales are governed by our terms and conditions, which are available on request. We reserve the
right to modify or improve the designs or specifications of our products at any time without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.