Model 3244MV™ MultiVariable Temperature
Transmitter with Profibus-PA
(Device Revision 2)
Profibus-PA
www.rosemount.com
Reference Manual
00809-0100-4799, Rev BA
September 2002
Model 3244MV
Model 3244MV MultiVariable
Temperature Transmitter with
Profibus-PA
NOTICE
Read this manual before working with the product. For personal and system safety, and for
optimum product performance, make sure to thoroughly understand the contents before
installing, using, or maintaining this product.
The United States has two toll-free assistance numbers and one International number.
Customer Central
1-800-999-9307
(7:00 a.m. to 7:00 P.M. CST)
International
1-(952) 906-8888
National Response Center
1-800-654-7768
(24 hours a day)
Equipment service needs
The products described in this document are NOT designed for nuclear-qualified
applications. Using non-nuclear qualified products in applications that require
nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact a local Rosemount Sales
Representative.
USING THIS MANUALThis manual is intended to assist in installing, operating, and maintaining
Rosemount
Profibus-PA.
Section 2: Installation
•Considerations
•Mounting and Installation
•Wiring
•Power
•Switches
Section 3: Commissioning
•Profibus-PA Installation
•Configuration
•Parameter Blocks
Section 4: Maintenance
•Diagnostic messaging
•Maintaining the hardware
Appendix A: Specifications and Reference Data
•Specifications
•Dimensional Drawings
•Tagging
•Options
®
Model 3244MV MultiVariable Temperature Transmitters with
www.rosemount.com
Appendix B: Approvals
•Hazardous Locations Certificates
•Installation Drawings
Reference Manual
00809-0100-4799, Rev BA
Model 3244MV
September 2002
OVERVIEW
TransmitterEnhanced measurement capability allows the Model 3244MV to communicate
multiple variables to a Profibus-PA host or configuration tool. This
temperature transmitter has the ability to accept simultaneous inputs from two
temperature sensing elements. The differential temperature measurement
capability can be used to detect sensor drift in a dual-element sensor. The
Model 3244MV with Profibus-PA combines the effects of transmitter drift,
sensor interchangeability error, temperature effects, and reference accuracy
to better account for actual process conditions and to assure maximum
accuracy.
The Model 3244MV with Profibus-PA provides superior performance in
non-critical applications involving basic process monitoring as well as
simultaneous measurement of separate and independent temperature points
with one transmitter. With this feature instrument costs are reduced by as
much as 50 percent. In addition, the multi-drop capability of Profibus-PA
results in additional savings through reduced wiring costs.
PROFIBUS Technology Profibus-PA is an all digital, serial, two-way communication system that
interconnects field equipment such as sensors, actuators, and controllers.
Profibus-PA is a Local Area Network (LAN) for instruments used in both
process and manufacturing automation. The profibus environment is the base
level group of digital networks in the hierarchy of plant networks.
Profibus-PA communication retains the desirable features of the 4–20 mA
analog system, including a standardized physical interface to the wire,
bus-powered devices on a single pair of wires, and intrinsic safety options. It
also enables additional capabilities, such as the following:
•increased capabilities due to full digital communications
•reduced wiring and wire terminations due to multiple devices on one
pair of wires
•increased selection of suppliers due to interoperability
•reduced loading on control room equipment with the distribution of
some control and input/output functions to field devices
SAFETY MESSAGESInstructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
raises potential safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or serious injury:
• Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury:
• Do not remove the transmitter cover in explosive atmospheres
when the circuit is live.
• Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
• Both transmitter covers must be fully engaged to meet
explosion-proof requirements.
Electrical shock could cause death or serious injury. If the sensor is installed in a
high-voltage environment and a fault condition or installation error occurs, high voltage may
be present on transmitter leads and terminals.
• Use extreme caution when making contact with the leads and terminals.
Process leaks could result in death or serious injury:
• Install and tighten thermowells or sensors before applying pressure, or process
leakage may result.
• Do not remove the thermowell while in operation. Removing while in operation
may cause process fluid leaks.
www.rosemount.com
Reference Manual
00809-0100-4799, Rev BA
Model 3244MV
September 2002
CONSIDERATIONS
GeneralElectrical temperature sensors such as RTDs and thermocouples produce
low-level signals proportional to temperature. The Model 3244MV
temperature transmitter converts the analog sensor signal to a digital signal
that is relatively insensitive to lead length and electrical noise. This current
signal is then transmitted over the bus to the configuration device and the
control room.
Electrical Proper electrical installation is necessary to prevent errors due to sensor lead
resistance and electrical noise. Shielded, twisted cable should be used for
best results in electrically noisy environments. Refer to “Sensor Connections”
on page 2-9 for more information.
Power Supply
The transmitter requires between 9 and 32 V dc to operate and provide
complete functionality. The dc power supply should provide power with less
than 2% ripple.
Power Filter
A profibus segment requires a power conditioner to isolate the power supply
filter and decouple the segment from other segments attached to the same
power supply.
Mechanical The Model 3244MV transmitter can be mounted directly to the sensor or apart
from the sensor using an optional mounting bracket. Using the bracket, the
transmitter can be mounted either to a flat surface or to a 2-inch diameter pipe
(see “Mounting Brackets” on page A-7).
Mounting
The transmitter may require supplementary support under high-vibration
conditions, particularly if used with extensive thermowell lagging or long
extension fittings. Pipe-stand mounting, using one of the optional mounting
brackets, is recommended for use in high-vibration applications.
Access Requirements
When choosing an installation location and position, take into account the
need for access to the transmitter.
Electronics Housing
Mount the transmitter so the terminal side and terminal side is accessible.
Be sure to allow adequate clearance for cover removal. When adding a
LCD meter, mount the circuit-side of the transmitter in a visible position.
Tagging
2-2
Commissioning Tag
The Model 3244MV has been supplied with a removable commissioning
tag that contains both the Device ID and a space to record the device tag.
The Device ID is a unique code that identifies a particular device in the
absence of a device tag. The device tag is used as an operational
identification for the device and is usually defined by the Piping and
Instrumentation Diagram (P & ID).
Model 3244MV
When commissioning more than one device on a profibus segment, it can
be difficult to identify which device is at a particular location. The
removable tag provided with the transmitter can aid in this process by
linking the Device ID and a physical location. The installer should note the
physical location in both places on the removable commissioning tag and
tear off the bottom portion. This should be done for each device on the
segment. The bottom portion of the tags can be used for commissioning
the segment in the control system.
Environmental Temperature Environments
The transmitter will operate within specifications for ambient temperatures
between –40 and 185 °F (–40 and 85 °C).In a direct mounting configuration,
heat from the process is transferred from the thermowell to the transmitter
housing. If the expected process temperature is near or beyond the
specification limits, consider the use of additional thermowell lagging, an
extension nipple, or a remote mounting configuration to isolate the transmitter
from these excessive temperatures. Figure 2-1 provides an example of the
relationship between transmitter housing temperature rise and extension
length. Use Figure 2-1 and the accompanying example to determine
adequate thermowell extension length.
Reference Manual
00809-0100-4799, Rev BA
September 2002
Figure 2-1. Transmitter Housing
Temperature Rise
60 (108)
50 (90)
40 (72)
30 (54)
22
20 (36)
ABOVE AMBIENT °C (°F)
HOUSING TEMPERATURE RISE
10 (18)
0
3456789
3.6
EXTENSION LENGTH, INCHES (E)
Transmitter Housing
Temperature Rise vs.
Extension Length for
a Test Installation
815 °C (1,500 °F)
Oven Temperature
540 °C (1,000 °F)
Oven Temperature
250 °C (482°F)
Oven Temperature
3044-0123A
EXAMPLE:
The rated temperature specification is 85 °C. If the maximum ambient
temperature is 40 °C and the temperature to be measured is 540 °C, the
maximum allowable housing temperature rise is the rated temperature
specification limit minus the existing ambient temperature (85 – 40), or
45 °C.
As shown in Figure 2-1, an extension (E) dimension of 3.6 inches will result
in a housing temperature rise of 22 °C. An “E” dimension of 4 inches would
therefore be the minimum recommended length and would provide a
safety factor of about 25 °C. A longer “E” dimension, such as 6 inches,
would be desirable in order to reduce errors caused by transmitter
temperature effect, although in that case the transmitter would probably
require extra support. If a thermowell with lagging is used, the “E”
dimension may be reduced by the length of the lagging.
2-3
Model 3244MV
Reference Manual
00809-0100-4799, Rev BA
September 2002
Moist or Corrosive Environments
The Model 3244MV has a highly reliable, dual-compartment housing
designed to resist moisture and corrosives. The electronics module assembly
is mounted in a compartment that is isolated from the terminal side conduit
entries. O-ring seals protect the interior of each compartment from the
environment when the covers are installed. In humid environments it is
possible for moisture to accumulate in conduit lines and drain into the
housing.
Proper installation of the transmitter can ensure maximum operation and
service life. It can also have a significant impact on preventing moisture from
accumulating in the housing. Refer to Figures 2-2 and 2-3 before mounting
the transmitter.
Mount the transmitter at a high point in the conduit run so moisture from the
conduits will not drain into the housing. If the transmitter is mounted at a low
point in the conduit run the terminal compartment could fill with water. In some
instances the installation of a poured conduit seal, such as the one pictured in
Figure 2-3, is advisable. Remove the terminal compartment cover periodically
and inspect the transmitter for moisture damage and corrosion.
Figure 2-2. Incorrect
Conduit Installation
Figure 2-3. Process Mounting
with Drain Seal
Thermowell
Conduit
Lines
Sealing
Compound
Sensor Hex
Union Coupling with Extension
Conduit
Lines
Conduit for
Field Wiring
Poured Conduit Seal
(Where Required)
3144-0429A, B
3144-0430B
MOUNTING AND
INSTALLATION
2-4
Installation consists of mounting the transmitter and sensor and making
electrical connections.
Use the typical North American process mounting configuration illustrated in
“Typical North American Installation” on page 2-5 or the typical European
process mounting configuration illustrated in “Typical European Installation”
on page 2-6.
Model 3244MV
Reference Manual
00809-0100-4799, Rev BA
September 2002
For transmitter locations remote from the sensor, use conduit or suitable
shielded cable and cable glands between the sensor and transmitter. The
transmitter accepts male conduit fittings with
PG 13.5 (PG 11), or JIS G
1
/2 threads.
1
/2–14 NPT, M 20 1.5 (CM 20),
Typical North American
Installation
1. Mount the thermowell to the pipe or process container wall. Be sure to
tighten thermowells and sensors. Perform a leak check before starting
the process.
2. Attach any necessary unions, couplings, and extension fittings. Be sure
to seal the fitting threads with silicone or tape (if required).
3. Screw the sensor into the thermowell or directly into the process
(depending on installation requirements).
4. Verify all sealing requirements for severe environments or to satisfy code
requirements.
5. Attach the transmitter to the thermowell/sensor assembly. Be sure to
seal all threads with silicone or tape (if required).
6. Pull sensor leads through the extensions, unions, or couplings into the
terminal side of the transmitter housing.
7. Install field wiring conduit to the remaining transmitter conduit entry.
8. Pull the field wiring leads into the terminal side of the transmitter housing.
Avoid contact with the leads and terminals.
9. Attach the sensor leads to the transmitter sensor terminals. Attach the
power leads to the transmitter power terminals. Avoid contact with the
leads and terminals.
10. Attach and tighten both transmitter covers. Both transmitter covers must
be fully engaged to meet explosion-proof requirements.
Figure 2-4. Typical North
American Mounting
Configuration.
Union or
Thermowell
NOTE: Dimensions are in inches (millimeters).
Extension
Coupling
Extension
Fitting
Length
Conduit for Field
Wiring (dc power)
3.2
(81)
NOTE
The National Electrical Code requires that a barrier or seal be used in addition
to the primary (sensor) seal to prevent process fluid from entering the
electrical conduit and continuing to the control room. Professional safety
assistance is recommended for installation in potentially hazardous
processes.
3144-0433B
2-5
Model 3244MV
Reference Manual
00809-0100-4799, Rev BA
September 2002
Typical European
Installation
Figure 2-5. Typical European
Process Mounting
Configuration.
1. Mount the thermowell to the pipe or the process container wall. Install
and tighten thermowells and sensors. Perform a leak check before
starting the process.
2. Attach a connection head to the thermowell.
3. Insert the sensor into the thermowell and wire it to the connection head.
The wiring diagram is located on the inside of the connection head.
4. Mount the transmitter to a 2-inch (50 mm) pipe or a suitable panel using
one of the optional mounting brackets. The B4 bracket is shown in
Figure 2-5.
5. Attach cable glands to the shielded cable running from the connection
head to the transmitter conduit entry.
6. Run the shielded cable from the opposite conduit entry on the transmitter
back to the control room.
7. Insert the shielded cable leads through the cable entries into the
connection head and the transmitter. Connect and tighten the cable
glands.
8. Connect the shielded cable leads to the connection head terminals
(located inside of the connection head) and the sensor wiring terminals
(located inside of the transmitter housing). Avoid contact with the leads
and the terminals.
2-inch
Cable
Gland
Pipe
B4
Mounting
Bracket
2-6
Shielded Cable from
Sensor to Transmitter
Shielded Cable
from Transmitter
to Control Room
644-0000B05B
Reference Manual
00809-0100-4799, Rev BA
Model 3244MV
September 2002
CONNECT THE WIRING
AND POWER UP
Field WiringAll power to the transmitter is supplied over the signal wiring. Signal wiring
should be shielded, twisted pair for best results. Do not run unshielded signal
wiring in conduit or open trays with power wiring or near heavy electrical
equipment. Do not remove the transmitter cover in explosive atmospheres
when the circuit is live.
If the sensor is installed in a high-voltage environment and a fault condition or
installation error occurs, the sensor leads and transmitter terminals could
carry lethal voltages. Use extreme caution when making contact with the
leads and terminals.
NOTE
Do not apply high voltage (e.g. ac line voltage) to the transmitter terminals.
Abnormally high voltage can damage the unit. (Sensor and transmitter power
terminals are rated to 42.4 V dc.)
Power ConnectionsUse ordinary copper wire of sufficient size to ensure that the voltage across the
transmitter power terminals does not drop below 9 V dc. To power the
transmitter, connect the power leads to the terminals marked “+” and “T” as
shown in Figure 2-7. The power terminals are polarity insensitive, which
means the electrical polarity of the power leads does not matter when
connecting to the power terminals. When wiring to screw terminals, the use of
crimped lugs is recommended. Tighten the terminal screws to ensure
adequate contact. No additional power wiring is needed.
Figure 2-6. Hardware Setup
Figure 2-7. Transmitter Terminal
Block
Power
connection
for coupler
L+
L–
Power Terminals
(polarity insensitive)
Front of Coupler
Power connection
for segment
P+
P–
Connector to
Siemens Card
installed into PC
Sensor Terminals
Ground
Ter min al
200E01C
2-7
Reference Manual
00809-0100-4799, Rev BA
Model 3244MV
September 2002
GroundingTransmitters are electrically isolated to 500 V ac rms. Ground the signal
wiring at any single point, if desired. When using a grounded thermocouple,
the grounded junction serves as this point.
NOTE
Do not ground the signal wire at both ends.
Shielded Wire
Recommended grounding techniques for shielded wire usually call for a
single grounding point for each shielded wire to avoid grounding the loop. The
following two examples employ the single point grounding technique:
Example 1
1.Connect the signal wiring shield to the sensor wiring shield.
2.Ensure that the two shields are tied together and electrically isolated
from the transmitter housing.
3.Ground the shield at power supply end.
Example 2
1.Connect the sensor wiring shield to the ground terminal (located
inside the terminal compartment of the transmitter housing).
2.Cut the signal wiring shield and isolate from the transmitter housing.
3.Grounded the shield at the power supply end only. Never connect the
shield for the signal wiring to the ground terminal inside the
transmitter housing.
Transmitter Housing
Ground the transmitter housing in accordance with local electrical
requirements. The internal ground terminal is standard. An optional external
ground lug assembly (option code G1) can also be ordered if needed. This
external grounding method is recommended when using the optional transient
protector (option code T1).
Surges/TransientsThe transmitter will withstand electrical transients usually encountered in
static discharges or induced switching transients. However, high-energy
transients, such as those induced in wiring from nearby lightning strikes, can
damage both the transmitter and the sensor.
A transient protection will be available at a later date for adding to the Model
3244MV with Profibus-PA.
2-8
Reference Manual
00809-0100-4799, Rev BA
Model 3244MV
September 2002
Sensor ConnectionsThe Model 3244MV transmitter is compatible with many RTD and
thermocouple sensor types. Figure 2-8 shows the correct sensor terminal
input connections on the transmitter. To ensure an adequate sensor
connection, anchor the sensor lead wires beneath the flat washer on the
terminal screw.
If the sensor is installed in a high voltage environment and a fault condition or
installation error occurs, the sensor leads and transmitter terminals could
carry lethal voltages. Use extreme caution when making contact with the
leads and terminals.
RTD or Ohm Inputs
Various RTD configurations, including 2-wire, 3-wire, 4-wire, and
compensation loop designs, are used in industrial applications. If the
transmitter is mounted remotely from a 3- or 4-wire RTD, it will operate within
specifications, without recalibration, for lead wire resistances of up to 10 ohms
per lead (equivalent to 1,000 feet of 20 AWG wire). In this case, the leads
between the RTD and transmitter should be shielded. If using only two leads
(or a compensation loop lead wire configuration), both RTD leads are in
series with the sensor element, so significant errors can occur if the lead
lengths exceed one foot of 20 AWG wire.
Figure 2-8. Transmitter Sensor
Wiring.
Thermocouple or Millivolt Inputs
For direct-mount applications, connect the thermocouple directly to the
transmitter. If mounting the transmitter remotely from the sensor, use
appropriate thermocouple extension wire. Make connections for millivolt
inputs with copper wire. Use shielding for long runs of wire.
NOTE
The use of two grounded thermocouples with a Model 3244MV is not
recommended. For applications in which the use of two thermocouples is
desired, connect either two ungrounded thermocouples, one grounded and
one ungrounded thermocouple, or one dual element thermocouple.
2-wire RTD
and Ohms
3-wire RTD
and Ohms
4-wire RTD
and Ohms
Thermocouples
and Millivolts
RTD with
Compensation
Loop*
2-9
T/Hot
Backup/Dual
Sensor with 2
RTDs
* The transmitter must be configured for a 3-wire RTD in order to recognize an RTD with a
compensation loop.
T/Hot
Backup/Dual
Sensor with 2
TCs
T/Hot
Backup/Dual
Sensor with
RTD/TC
T/Hot
Backup/Dual
Sensor with
TC/RTD
T/Hot
Backup/Dual
Sensor with 2
RTDs with
Compensation
Loop
3144-0000F05A
Reference Manual
00809-0100-4799, Rev BA
Model 3244MV
September 2002
SET THE SWITCHES
SecurityAfter the transmitter is configured, it is possible to protect the configuration
data from unwarranted changes. Each transmitter is equipped with a security
switch that can be positioned “ON” to prevent the accidental or deliberate
change of configuration data. The switch is located on the front side of the
electronics module and is labeled SECURITY (see Figure 2-9).
SimulateThe simulate switch is used in conjunction with the Analog Input (AI) function
block. This switch is used to simulate the temperature measurement and is
used as a lock-out feature for the AI function block. To enable the simulate
feature, the switch must transition from “OFF” to “ON” after power is applied to
the transmitter (see Figure 2-9). This feature prevents the transmitter from
being accidentally left in simulator mode.
SAFETY MESSAGESInstructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
raises potential safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or serious injury:
• Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury:
• Do not remove the transmitter cover in explosive atmospheres
when the circuit is live.
• Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
• Both transmitter covers must be fully engaged to meet
explosion-proof requirements.
Electrical shock could cause death or serious injury. If the sensor is installed in a
high-voltage environment and a fault condition or installation error occurs, high voltage may
be present on transmitter leads and terminals.
• Use extreme caution when making contact with the leads and terminals.
Process leaks could result in death or serious injury:
• Install and tighten thermowells or sensors before applying pressure, or process
leakage may result.
• Do not remove the thermowell while in operation. Removing while in operation
may cause process fluid leaks.
www.rosemount.com
Model 3244MV
Reference Manual
00809-0100-4799, Rev BA
September 2002
INSTALLATION
PROCEDURE
Profibus Device
Description and GSD File
Changing the Mode of
aBlock
Specific installation procedures use Siemens’ PDM Configuration tool as a
reference. For other configuration tools, use that products reference manual.
All devices are shipped with a default address of 126.
Use the following steps to install the Profibus Device Description and
GSD file.
1.Go to the Rosemount web site, located at
<http://www.rosemount.com/products/temperature/m3244pa.html>.
2.Download the Rosemount 3244 DD zip file.
3.Read the “read me” file on how to install DDs and GSD files.
(It is important to read this file because it is unique to each
Profibus- PA interface tool.)
4.Click the “Next” button when the program begins.
5.Provide the path “c:\Temp\3244MVM.devices at the appropriate
prompt.
6.Select “Search in” and click Next
7.Indicate the device where the DD is to be installed (in this case select
3244MVM(PA).
8.Click “Finish.”
9.Close the application when installation is completed.
Use the following steps to change the mode of a block.
1.Select “Device Mode,” located under the “Device” pull-down menu.
2.Choose “Out of Service (O/S)” to change parameter settings.
3.Indicate the mode desired for the block and press the
download button.
4.Select the “Load into PG/PG” option, located under the “Device”
pull-down menu.
5.Upon completion, the block will be in the mode set.
3-2
NOTE
Changing the mode of one transducer block changes all the transducer blocks
to that same mode.
Reference Manual
00809-0100-4799, Rev BA
Model 3244MV
September 2002
CONFIGURATION
Physical Block1.Place the physical block into “Out of Service (O/S)” mode.
2.Select the “Display” mode, located under the “Device”
pull-down menu.
3.Turn on the valves to be displayed. Set the desired decimal place.
4.Download the device.
5.Select the “Load into PG/PG” option (UPLOAD), located under the
“Device” pull-down menu.
6.Place the Physical Block into Auto mode.
Transducer Block1.Select the “Master Reset” option, located under the “Device”
pull-down menu.
2.Input the following as desired
•1 to select restart with defaults
•4 to restart processor
3.Click “download” to download the device.
4.Once the device has restarted, click close.
5.Select “Change Sensor Type,” method located under the “Device”
pull-down menu. When this method begins, select the desired sensor
type and the connection.
6.Perform step five for all sensors.
7.Select the “Load into PG/PG” option (UPLOAD), located under the
“Device” pull-down menu.
8.Place the transducer block into “Out of Service (O/S)” mode. Set the
filter time constant to the desired value (perform for all transducer
blocks).
9.Select the “Load into PG/PG” option (UPLOAD), located under the
“Device” pull-down menu.
10. Place the Transducer block into Auto mode.
AI blocks1.Place the AI block into “Out of Service (O/S)” mode and
then UPLOAD.
2.Configure the channel for each block by right-clicking on the
parameter for each block. Select “On-line Option” and then the
channel. Choose a option and UPLOAD.
3.Right-click on the “Process Scale Variable” parameter. Indicate the
desired upper, lower and unit values. Download these parameters
onto the device (performed for each block). UPLOAD.
4.Right-click on the “Output Signal” parameter. Indicate the desired
upper, lower and unit values. Download these parameters onto the
device (performed for each block).
5.Select the “Load into PG/PG” option (UPLOAD), located under the
“Device” pull-down menu.
6.To set User Warning and Alarm Limits, right-click on “Upper Limit
Alarm,” “Upper lImit Warning,” “Lower Limit Warning,” and “Lower
Limit Alarm.” Select values and UPLOAD.
7.Place the AI block into Auto mode.
3-3
Reference Manual
00809-0100-4799, Rev BA
Model 3244MV
September 2002
CALIBRATION
2-point trimThe following provide the steps necessary to calibrate the transmitter:
1.Place the sensor transducer blocks into “Out of Service (O/S)” mode.
2.Select the “Calibration” option, located under the “Device” pull-down
menu.
3.Choose the sensor to calibrate and click the calibrate button.
4.Select the “USER_cal” option in the Input window. Click OK.
5.Read the instructions. Click OK.
6.Set the new value for the “Lower_cal point.” Click OK.
7.Repeat steps 4 – 6 to perform the same task for the
“Upper_cal point.”
8.Close the calibration window when finished performing calibrations.
NOTE
To perform a single-point calibration, click the cancel button when the two
Upper_cal point windows are open.
PARAMETER BLOCKSThe following tables provide information regarding
0.1BLOCK_OBJECT.ReservedContains the characteristics of the blocks.RUnsigned81
0.2BLOCK_OBJECT.Block ObjectContains the characteristics of the blocks.RUnsigned81
0.3BLOCK_OBJECT.Parent ClassContains the characteristics of the blocks.RUnsigned81
0.4BLOCK_OBJECT.ClassContains the characteristics of the blocks.RUnsigned81
0.5BLOCK_OBJECT.DD ReferenceContains the characteristics of the blocks.RUnsigned32 4
0.6BLOCK_OBJECT.DD RevisionContains the characteristics of the blocks.RUnsigned16 2
0.7BLOCK_OBJECT.ProfileContains the characteristics of the blocks.RUnsigned16 2
0.8BLOCK_OBJECT.Profile RevisionContains the characteristics of the blocks.RUnsigned16 2
0.9BLOCK_OBJECT.Execution TimeContains the characteristics of the blocks.RUnsigned81
0.10BLOCK_OBJECT.Highest_Rel_OffsetContains the characteristics of the blocks.RUnsigned16 2
0.11BLOCK_OBJECT.Index View_1Contains the characteristics of the blocks.RUnsigned16 2
0.12BLOCK_OBJECT.Num. Of ViewsContains the characteristics of the blocks.RUnsigned81
1ST_REVA block has static block parameters that are not
2TAG_DESCEvery block can be assigned a textural TAG
ParameterDescriptionAccess
RUnsigned16 2
changed by the process. Values are assigned to
this parameter during the configuration or
optimization. The value of ST_REV must increase
by 1 after every change of a static block parameter.
This provides a check of the parameter revision.
R/WOctet(32)32
description. The TAG_DESC is the address of the
block. The TAG_DESC must be unambiguous and
unique in the Profibus system.
Data Type/
Structure
Size –
Bytes
3-4
Model 3244MV
Reference Manual
00809-0100-4799, Rev BA
September 2002
PA Index
Number
3STRATEGYGrouping of Function Block. The STRATEGY field
4ALERT_KEYThis parameter contains the identification number
6.4MODE_BLK.normal
7ALARM_SUMThis parameter contains the current state of the
10OUTValue and status of the block outputR/WDS-335
11PV_SCALEConversion of the Process Variable into percent
12OUT_SCALEThe high and low scale values, units code, and
14CHANNELReference to the active Transducer Block which
16PV_FTIMEFilter time of the Process VariableR/WFloat4
19ALARM_HYSThe amount the alarm value must return within the
21HI_HI_LIMThe setting of the alarm limit used to detect the HI
23HI_LIMThe setting of the alarm limit used to detect the HI
25LO_LIMThe setting of the alarm limit used to detect the LO
27LO_LO_LIMThe setting of the alarm limit used to detect the LO
30HI_HI_ALARMThe HI HI alarm dataRDS-3916
31HI_ALARMThe HI alarm dataRDS-3916
32LO_ALARMThe LO alarm dataRDS-3916
33LO_LO_ALARMThe LO LO alarm dataRDS-3916
34SIMULATE.Simulate Status R/WDS-506
ParameterDescriptionAccess
can be used to group blocks.
of the plant unit. It helps to identify the location
(plant unit) of an event (crossing a limit).
mode normally set by a control application or an
operator.
These blocks contain the actual, permitted and
normal modes of the block
block alarms
using the hand low scale values, engineering units
code and number of digits tot he right of the
decimal point. The engineering unit of PV_SCALE
must be the same as the one of the related
Transducer Block
number of digits to the right of the decimal point
associated with OUT.
provides the measurement value to the Function
Block
alarm limit before the associated active alarm
condition clears.
HI alarm condition
alarm condition
alarm condition
LO alarm condition
R/WUnsigned16 2
R/WUnsigned81
R/WUnsigned81
RDS-3736.3MODE_BLK.permitted
RDS-428
R/WDS-3611
R/WDS-3611
R/WUnsigned16 2
R/WFloat4
R/WFloat4
R/WFloat4
R/WFloat4
R/WFloat4
Data Type/
Structure
Size –
Bytes
3-5
Model 3244MV
Physical Block (Slot 2)
Reference Manual
00809-0100-4799, Rev BA
September 2002
PA Index
Number
0.1BLOCK_OBJECT.ReservedContains the characteristics of the blocks.RUnsigned81
0.2BLOCK_OBJECT.Block ObjectContains the characteristics of the blocks.RUnsigned81
0.3BLOCK_OBJECT.Parent ClassContains the characteristics of the blocks.RUnsigned81
0.4BLOCK_OBJECT.ClassContains the characteristics of the blocks.RUnsigned81
0.5BLOCK_OBJECT.DD ReferenceContains the characteristics of the blocks.RUnsigned32 4
0.6BLOCK_OBJECT.DD RevisionContains the characteristics of the blocks.RUnsigned16 2
0.7BLOCK_OBJECT.ProfileContains the characteristics of the blocks.RUnsigned16 2
0.8BLOCK_OBJECT.Profile RevisionContains the characteristics of the blocks.RUnsigned16 2
0.9BLOCK_OBJECT.Execution TimeContains the characteristics of the blocks.RUnsigned81
0.10BLOCK_OBJECT.Highest_Rel_OffsetContains the characteristics of the blocks.RUnsigned16 2
0.11BLOCK_OBJECT.Index View_1Contains the characteristics of the blocks.RUnsigned16 2
0.12BLOCK_OBJECT.Num. Of ViewsContains the characteristics of the blocks.RUnsigned81
1ST_REVA block has static block parameters that are not
2TAG_DESCRIPTIONEvery block can be assigned a textural TAG
3STRATEGYGrouping of Function Block. The STRATEGY field
4ALERT_KEYThis parameter contains the identification number
6.3MODE_BLK.normal
7ALARM_SUMThis parameter contains the current state of the
8SOFTWARE_REVISIONSoftware revision, includes a major, minor, and
9HARDWARE_REVISIONHardware revisionROctet(16)16
10DEVICE_MAN_IDIdentification code of the field device manufacturer.
11DEVICE_ID Identification of the device: 3244 = Rosemount
12DEVICE_SER_NUMSerial number of the device (output board serial
13DIAGNOSISDetailed information of the device, bitwise coded.
14DIAGNOSIS_EXTENSIONAdditional manufacturer specific information of the
15DIAGNOSIS_MASKDefinition of supported DIAGNOSIS information
ParameterDescriptionAccess
RUnsigned16 2
changed by the process. Values are assigned to
this parameter during the configuration or
optimization. The value of ST_REV must increase
by 1 after every change of a static block parameter.
This provides a check of the parameter revision.
description. The TAG_DESC is the address of the
block. The TAG_DESC must be unambiguous and
unique in the Profibus system.
can be used to group blocks.
of the plant unit. It helps to identify the location
(plant unit) of an event (crossing a limit).
mode normally set by a control application or an
operator.
These blocks contain the actual, permitted and
normal modes of the block
block alarms
build revisions
38 = Rosemount
Model 3244 Temperature Transmitter
number)
More than one message possible at once. If MSB
of byte 4 is set to 1 than more diagnosis information
is available in the DIAGNOSIS_EXTENSION
parameter
device, bitwise coded. More than one message
possible at once.
bits: 0 = not supported, 1 = supported
R/WOctet(32)32
R/WUnsigned16 2
R/WUnsigned81
R/WUnsigned81
RDS-3736.2MODE_BLK.permitted
R4*Octet(2)8
ROctet(16)16
RUnsigned16 2
ROctet(16)16
ROctet(16)16
ROctet(4)4
ROctet(6)6
ROctet(4)4
Data Type/
Structure
Size –
Bytes
3-6
Model 3244MV
Reference Manual
00809-0100-4799, Rev BA
September 2002
PA Index
Number
16DIAGNOSIS_MASK_EXTENSIONDefinition of supported DIAGNOSIS_EXTENSION
17DEVICE_CERTIFICATIONCertification of the field deviceR/WOctet(16)16
18SECURITY_LOCKINGStorage location for a password used by the host
19FACTORY_RESETCommand for restarting device: 1 = Restart with
20DESCRIPTORUser-definable text to describe the deviceR/WOctet(32)32
21DEVICE_MESSAGEuser-definable message to the device or
22DEVICE_INSTALL_DATEDate of installation of the deviceR/WOctet(8)8
45FINAL_ASSEMBLY_NUMBERFinal Assembly Number – Number that is used for
22DOWNLOAD_MODEGives access to the boot block code for the
47DISPLAY_MODEProvides interface to configure LCD displayR/WOctet(1)1
ParameterDescriptionAccess
ROctet(6)6
information bits:
0 = Not supported
1 = Supported
R/WUnsigned16 2
software to check if the device parameter is
accessible – default value 0x2457
WUnsigned16 2
default, 4 = Restart processor
R/WOctet(32)32
application in plant
R/WUnsigned32 4
identification purposes and is associated with the
overall Field Devices
R/WUnsigned81
over-the-wire downloads
Data Type/
Structure
Transducer 1 (Sensor 1) and Transducer 2 (Sensor 2) Block (Slots 3 and 4)
Size –
Bytes
PA Index
Number
0.1BLOCK_OBJECT.ReservedContains the characteristics of the blocks.RUnsigned81
0.2BLOCK_OBJECT.Block ObjectContains the characteristics of the blocks.RUnsigned81
0.3BLOCK_OBJECT.Parent ClassContains the characteristics of the blocks.RUnsigned81
0.4BLOCK_OBJECT.ClassContains the characteristics of the blocks.RUnsigned81
0.5BLOCK_OBJECT.DD ReferenceContains the characteristics of the blocks.RUnsigned32 4
0.6BLOCK_OBJECT.DD RevisionContains the characteristics of the blocks.RUnsigned16 2
0.7BLOCK_OBJECT.ProfileContains the characteristics of the blocks.RUnsigned16 2
0.8BLOCK_OBJECT.Profile RevisionContains the characteristics of the blocks.RUnsigned16 2
0.9BLOCK_OBJECT.Execution TimeContains the characteristics of the blocks.RUnsigned81
0.10BLOCK_OBJECT.Highest_Rel_OffsetContains the characteristics of the blocks.RUnsigned16 2
0.11BLOCK_OBJECT.Index View_1Contains the characteristics of the blocks.RUnsigned16 2
0.12BLOCK_OBJECT.Num. Of ViewsContains the characteristics of the blocks.RUnsigned81
1ST_REVA block has static block parameters that are not
2TAG_DESCEvery block can be assigned a textural TAG
3STRATEGYGrouping of Function Block. The STRATEGY field
4ALERT_KEYThis parameter contains the identification number
ParameterDescriptionAccess
RUnsigned16 2
changed by the process. Values are assigned to
this parameter during the configuration or
optimization. The value of ST_REV must increase
by 1 after every change of a static block parameter.
This provides a check of the parameter revision.
R/WOctet(32)32
description. The TAG_DESC is the address of the
block. The TAG_DESC must be unambiguous and
unique in the Profibus system.
R/WUnsigned16 2
can be used to group blocks.
R/WUnsigned81
of the plant unit. It helps to identify the location
(plant unit) of an event (crossing a limit).
RUnsigned162
changed by the process. Values are assigned to
this parameter during the configuration or
optimization. The value of ST_REV must increase
by 1 after every change of a static block parameter.
This provides a check of the parameter revision.
description. The TAG_DESC is the address of the
block. The TAG_DESC must be unambiguous and
unique in the Profibus system.
can be used to group blocks.
of the plant unit. It helps to identify the location
(plant unit) of an event (crossing a limit).
mode normally set by a control application or an
operator.
These blocks contain the actual, permitted and
normal modes of the block
block alarms
corrected by BIAS_
differential form channel 1 and 2
Thermocouples, Rrd., Pyrometers or linear
1
/2
R/WOctet(32)32
R/WUnsigned162
R/WUnsigned81
R/WUnsigned81
RDS-3736.3MODE_BLK.permitted
RDS-428
RDS-335
R/WUnsigned81
R/WUnsigned81
Data Type/
Structure
Size –
Bytes
3-10
Model 3244MV
Reference Manual
00809-0100-4799, Rev BA
September 2002
PA Index
Number
20TEMPERATURE_UNITSelect the unit of the temperature. (Example: °C,
SAFETY MESSAGESInstructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
raises potential safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or serious injury:
• Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury:
• Do not remove the transmitter cover in explosive atmospheres
when the circuit is live.
• Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
• Both transmitter covers must be fully engaged to meet
explosion-proof requirements.
Electrical shock could cause death or serious injury. If the sensor is installed in a
high-voltage environment and a fault condition or installation error occurs, high voltage may
be present on transmitter leads and terminals.
• Use extreme caution when making contact with the leads and terminals.
Process leaks could result in death or serious injury:
• Install and tighten thermowells or sensors before applying pressure, or process
leakage may result.
• Do not remove the thermowell while in operation. Removing while in operation
may cause process fluid leaks.
www.rosemount.com
Reference Manual
00809-0100-4799, Rev BA
Model 3244MV
September 2002
HARDWARE
DiagnosticsIf a malfunction is suspected, despite the absence of diagnostic messages,
follow the procedures described in Table 4-1 to verify that transmitter
hardware and process connections are in good working order. Under each of
four major symptoms, specific suggestions are offered for solving problems.
Always address the most likely and easiest-to-check conditions first.
Table 4-1. Troubleshooting.
SymptomPotential SourceCorrective Action
Transmitter does
not communicate
with the
Configuration
Interface
High OutputSensor Input
Erratic OutputLoop Wiring
Low Output or
No Output
Loop Wiring
Failure or
Connection
Loop Wiring
Power Supply
Electronics Module
Electronics Module
Sensor Element
Loop Wiring
Electronics Module
• Check for adequate voltage to the transmitter.
The transmitter requires between 9.0 and 32.0 V
at the terminals to operate and provide complete
functionality
• Check for intermittent shorts, open circuits, and
multiple grounds.
• Enter the transmitter test mode to isolate a
sensor failure.
• Check for a sensor open circuit.
• Verify the process variable is not out of range.
• Check for dirty or defective terminals,
interconnecting pins, or receptacles.
• Check for adequate voltage to the transmitter.
The transmitter requires between 9.0 and 32.0 V
at the terminals to operate and provide complete
functionality
• Enter the transmitter test mode to isolate a
module failure.
• Check the sensor limits to ensure calibration
adjustments are within the sensor range.
• Check for adequate voltage to the transmitter.
The transmitter requires between 9.0 and 32.0 V
at the terminals to operate and provide complete
functionality
• Check for intermittent shorts, open circuits, and
multiple grounds.
• Enter the transmitter test mode to isolate module
failure.
• Enter the transmitter test mode to isolate a
sensor failure.
• Verify the process variable is not out of range.
• Check for adequate voltage to the transmitter.
The transmitter requires between 9.0 and 32.0 V
at the terminals to operate and provide complete
functionality
• Check for shorts and multiple grounds.
• Check the loop impedance.
• Check wire insulation to detect possible shorts to
ground.
• Check the sensor limits to ensure calibration
adjustments are within the sensor range.
• Enter the transmitter test mode to isolate an
electronics module failure.
4-2
Reference Manual
00809-0100-4799, Rev BA
Model 3244MV
September 2002
MaintenanceThe Model 3244MV transmitter has no moving parts and requires a minimum
amount of scheduled maintenance. The transmitter features a modular design
for easy maintenance. If a malfunction is suspected, check for an external
cause before performing the diagnostics presented below.
Sensor Checkout
If the sensor is installed in a high-voltage environment and a fault condition or
installation error occurs, the sensor leads and transmitter terminals could
carry lethal voltages.
To determine whether the sensor is causing the malfunction, either replace it
with another Rosemount sensor or connect a test sensor locally at the
transmitter. This can be very useful, especially when checking the wiring for a
remote mounted sensor. Please consult a Rosemount representative for more
information.
ELECTRONICS
HOUSING
DisassemblyThe transmitter is designed with a dual-compartment housing; one
compartment contains the Profibus-PA electronics module assembly and the
other contains all sensor, power/communication, and internal ground lug
terminals.
The transmitter’s electronics module assembly is located in the compartment
opposite the terminal block.
Removing the Profibus-PA Electronics Module Assembly
Use the following procedure to remove the Profibus-PA electronics
module assembly:
NOTE
Part of the electronics are sealed in a moisture-proof plastic enclosure
referred to as the electronics module. The module is a non-repairable unit; if a
malfunction occurs the entire unit must be replaced.
1.Disconnect the power to the transmitter.
2.Remove the cover from the electronics side of the transmitter
housing. Do not remove any covers in explosive atmospheres when
the circuit is live.
3.Loosen the two screws that anchor the electronics module assembly
to the transmitter housing.
4.Firmly grasp the screws and assembly and pull it straight out of the
housing, taking care not to damage the interconnecting pins.
NOTE
Note the transmitter’s security switch position (ON or OFF). If the electronics
module is being replaced with a new one, ensure the security switch is set in
the same position (see “Security” on page 2-10).
4-3
Reference Manual
00809-0100-4799, Rev BA
Model 3244MV
AssemblyReplacing the Profibus-PA Electronics Module Assembly
Use the following procedure to reassemble the Profibus-PA electronics
module assembly.
1.Ensure that the transmitter security switch on the electronics module
assembly is in the same position as the one that is being replaced.
2.Carefully insert the electronics module assembly to mate the
interconnecting pins with the necessary receptacles on the
electronics board attached to the housing.
3.Tighten the two mounting screws.
4.Replace the cover. Tighten the cover
begins to compress the o-ring. Both transmitter covers must be fully
engaged to meet explosion-proof requirements.
User-selectable. See “Accuracy” on page A-3
(Sensor terminals are rated to 42.4 V dc.)
Outputs
Manchester-encoded digital signal that conforms to IEC 1158-2
and ISA 50.02
Model 3244MV
Isolation
Input/output isolation tested to 500 V rms (707 V dc)
Power Supply
External power supply is required. Transmitter operation is between 9.0 and
32.0 V dc, 17.5 mA maximum. (Transmitter power terminals are rated to 42.4
V dc.)
Rosemount Conformance to Specification
You can be confident that a Rosemount product not only meets our published
specifications, but most likely exceeds them. Our advanced manufacturing
techniques and use of Statistical Process Control provide specification
conformance to at least ± 3
improvement ensures that product design, reliability, and performance get better
every year.
For example, the Reference Accuracy distribution for the Model 3244MV
MultiVariable Temperature Transmitter with Profibus-PA is shown to the right. Our
Specification Limits are ± 0.10 °C, but, as the shaded area shows, approximately
68% of the units perform three times better than the limits. Therefore, it is very
likely that you will receive a device that performs much better than our published
specifications.
Conversely, a vendor who “grades” product without using Process Control, or who
is not committed to ± 3 performance, will ship a much higher percentage of units
that are barely within (or even outside of) advertised specification limits.
(1)
. In addition, our commitment to continual
Lower
Specification
Limit
–3
–2–1
Typical Accuracy
+1
Specification
+2
Upper
Limit
+3
www.rosemount.com
Model 3244MV
(1) Sigma () is the Standard Deviation of a statistical distribution, and describes the dispersion (spread) of the distribution.
Profibus-PA
Reference Manual
00809-0100-4799, Rev BA
September 2002
Table A-1. Block Information
.
BlockExecution Time (milliseconds)Slot Number
Physical (PB)—2
Transducer (TB)—3, 4, 5,
Transducer (TB)—3, 4, 5,
Transducer (TB)—3, 4, 5,
Analog Input 1 (AI1)506
Analog Input 2 (AI2)507
Analog Input 3 (AI3)508
Temperature Limits
Ambient
• –40 to 185 °F (–40 to 85 °C).
Storage
• –60 to 250 °F (–50 to 120 °C).
Transient Protection Option (available at a later date)
The transient protector helps to prevent damage to the transmitter from
transients induced on the loop wiring by lightning, welding, heavy electrical
equipment, or switch gears. The transient protection electronics are contained
in an add-on assembly that attaches to the standard transmitter terminal
block. The transient protector is tested per the following standard:
Cu 10
Thermocouples°C°F°C°F
NIST Type B
NIST Type E
NIST Type J
NIST Type K
NIST Type N
NIST Type R
NIST Type S
NIST Type T
Millivolt Input
2-, 3-, 4-Wire Ohm Input0 to 2000 ohms±0.35 ohm
(1) The transmitter’s accuracy is valid for the entire input range of the sensor.
(2) IEC 751; α = 0.00385, 1995.
(3) JIS 1604, 1981.
(4) Edison Curve No. 7.
(5) Edison Copper Winding No. 15.
(6) NIST Monograph 175.
(7) Accuracy for NIST Type B T/C is ±3.0 °C (5.4 °F) from 100 to 300 °C (212 to 572°F).
(8) Total accuracy for thermocouple only: sum of accuracy +0.25 °C (cold junction accuracy).
(9) Millivolt inputs are not approved for use with CSA option code I6.
(6) (7) (8)
(5) (8)
(6) (8)
(6) (8)
(6) (8)
(6) (8)
(6) (8)
(6) (8)
(9)
(2)
(3)
200 to 850–328 to 1562± 0.10± 0.18
200 to 645–328 to 1193± 0.100.18±
200 to 850–328 to 1562± 0.22± 0.40
200 to 850–328 to 15620.14± 0.25
200 to 300–328 to 572± 0.08± 0.14
200 to 300–94 to 572± 0.08± 0.14
200 to 250–58 to 482± 1.00± 1.80
212 to 3308100 to 1820± 0.75± 1.35
–58 to 1832–50 to 1000± 0.20± 0.36
–292 to 1400–180 to 760± 0.25± 0.45
–292 to 2502–180 to 1372± 0.50± 0.90
32 to 23720 to 1300± 0.40± 0.72
32 to 32140 to 1768± 0.60± 1.08
32 to 32140 to 1768± 0.50± 0.90
–328 to 752–200 to 400± 0.25± 0.45
–10 to 100 mV± 0.015 mV
(1)
Stability
±0.1% of reading or 0.1 °C, whichever is greater, for 24 months for RTDs.
±0.1% of reading or 0.1 °C, whichever is greater, for 12 months
for thermocouples.
Sensor Lead Wire Resistance Effect
RTD Input
When using a 4-wire RTD, the effect of lead resistance is eliminated and has
no impact on accuracy. However, a 3-wire sensor will not fully cancel lead
resistance error because it cannot compensate for imbalances in resistance
between the lead wires. A 2-wire sensor will produce the largest error
because it directly adds the lead wire resistance to the sensor resistance. For
2- and 3-wire RTDs, an additional lead wire resistance error is induced with
ambient temperature variations. Table A-2 and the examples shown below
help quantify these errors.
4-wire RTDNone (independent of lead wire resistance)
3-wire RTD± 1.0 Ω in reading per ohm of unbalanced lead wire resistance
2-wire RTD1.0 Ω in reading per ohm of lead wire resistance
(1) Unbalanced lead wire resistance = maximum imbalance between any two leads.
Examples of Approximate Basic Error Calculation:
Given:
• Total cable length = 150 m
• Unbalance of the lead wires @ 20 °C = 0.5
Ω
• Resistance/length (18 AWG Cu) = 0.025 Ω/m
• Temperature Coefficient (Cu) = 0.0039
Ω/Ω/ °C
• Approximate Pt 100 resistance variation with temperature = 0.39
Pt 100 3-wire RTD:
• Lead wire resistance seen by the transmitter = 0.5
Ω
• Basic error = 0.5 Ω/(0.39 Ω/ °C) = 1.3 °C
• Error due to an ambient temperature variation of ± 25 °C = ± 0.13 °C
Pt 100 2-wire RTD:
• Lead wire resistance seen by the transmitter =
150 m 2 wires 0.025
Ω/m = 7.5 Ω
• Basic error = 7.5 Ω/(0.39 Ω/°C) = 19.2 °C
• Error due to an ambient temperature variation of ± 25 °C = ± 1.9 °C
Worst case RFI Effect is equivalent to the transmitter’s nominal accuracy
specification per “Accuracy” on page A-3 when tested in accordance with EN
61000-4-3, 10 V/m, 80 to 1000 MHz, and 30 V/m, 26-500 MHz (Increased
NAMUR), with twisted shielded cables (Type A Profibus type).
Vibration Effect
Transmitters tested to the following specifications with no effect
on performance:
FrequencyAcceleration
10–60 Hz0.21 mm peak displacement
60–2000 Hz3 g’s
Self Calibration
The transmitter’s analog-to-digital circuitry automatically self-calibrates for
each temperature update by comparing the dynamic measurement to
extremely stable and accurate internal reference elements.
A-4
Reference Manual
00809-0100-4799, Rev BA
September 2002
Model 3244MV
Ambient Temperature Effect
Transmitters may be installed in locations where the ambient temperature is
between –40 and 85 °C. Each transmitter is individually characterized over
this ambient temperature range at the factory in order to maintain excellent
accuracy performance in dynamic industrial environments. This special
manufacturing technique is accomplished through extreme hot and cold
temperature profiling with individual adjustment factors programmed into each
transmitter. Transmitters automatically adjust for component drift caused by
changing environmental conditions.
Sensor OptionsAccuracy per 1.0 °C (1.8 °F) Change in Ambient
2-, 3-, 4-Wire RTDs
Pt 100 ( = 0.00385)0.0015 °C
Pt 100 ( = 0.003916)0.0015 °C
Pt 5000.0023 °C
Pt 2000.0015 °C
Pt 10000.0015°C
Ni 1200.0010 °C
Cu 100.015 °C
Thermocouples
NIST Type B0.014 °C if reading ≥ 1000 °C
0.029 °C – 0.0021% of (reading–300) if 300 °C ≤ reading < 1000 °C
0.046 °C – 0.0086% of (reading–100) if 100 °C ≤ reading < 300 °C
NIST Type E0.004 °C + 0.00043% of reading
NIST Type J0.004 °C + 0.00029% of reading if reading ≥ 0 °C
0.004 °C + 0.0020% of abs. val. reading if reading < 0 °C
NIST Type K0.005 °C + 0.00054% of reading if reading ≥ 0 °C
0.005 °C + 0.0020% of abs. val. reading if reading < 0 °C
NIST Type N0.005 °C + 0.00036% of reading
NIST Type R0.015 °C if reading ≥ 200 °C
0.021 °C – 0.0032% of reading if reading < 200 °C
NIST Type S0.015 °C if reading ≥ 200 °C
0.021 °C – 0.0032% of reading if reading < 200 °C
NIST Type T0.005 °C if reading ≥ 0 °C
0.005 °C + 0.0036% of abs. val. reading if reading < 0 °C
3244MVW Temperature Transmitter with Dual Sensor Input and Profibus-PA Digital Signal
CodeHousingConduit Thread
1Aluminum½–14 NPT
2AluminumM20 1.5 (CM20)
3AluminumPG 13.5 (PG 11)
4AluminumJIS G ½
5SST½–14 NPT
6SSTM20 1.5 (CM20)
7SSTPG 13.5 (PG 11)
8SSTJIS G ½
CodeHazardous Locations Certifications
NANo Approval Required
E5FM Explosion-Proof and Non-Incendive Approval
E6CSA Explosion-Proof and Non-Incendive Approval
E9ISSeP/ CENELEC Flame-Proof Approval
N1BASEEFA/CENELEC Type n Approval
I1BASEEFA/CENELEC Intrinsic Safety Approval
I6CSA Intrinsic Safety and Non-Incendive Field Circuit Approval
C6CSA Explosion-Proof and Intrinsic Safety Approval
CodeOptions
Accessory
B4Universal Mounting Bracket for 2-inch Pipe Mounting and Panel Mounting—SST Bracket and Bolts
B5Universal “L” Mounting Bracket for 2-inch Pipe Mounting—SST Bracket and Bolts
M5LCD Meter
G1External Ground Lug Assembly
T1Transient Protector
Custom Configuration
U4Two Independent Sensors
U5Differential Temperature
C1Factory Configuration of Date, Descriptor, and Message Fields–CDS required
C2Transmitter-Sensor Matching - Trim to Specific Rosemount RTD Calibration Schedule
C45-Point Calibration (use option code Q4 to generate a Calibration Certificate)
F550 Hz Line Voltage Filter
(2)
X1
X2Assemble Transmitter to a Sensor Assembly (hand tight, no Tef lo n (PTFE) tape, unwired)
(2)
X3
Q4Calibration Certificate (3-Point standard; use C4 with Q4 option for a 5-Point Calibration Certificate)
Typical Model Number: 3244MVW 1 NA B4 M5 X1
(1) Additional approvals available or pending. Contact Rosemount Customer Central for more information.
(2) Option codes X1 and X3 are no available with CSA approvals
Assembly
Assemble Transmitter to a Sensor Assembly (hand tight, Tef lo n® (PTFE) tape where appropriate, fully wired)
Assemble Transmitter to a Sensor Assembly (wrench tight, Tefl on (PTFE) tape where appropriate, fully wired)
Calibration Certification
(1)
Reference Manual
September 2002
A-8
Reference Manual
00809-0100-4799, Rev BA
September 2002
Model 3244MV
Spare Parts List
Part DescriptionPart Number
Profibus-PA foundation electronics module assembly03144-4230-0001
LCD Meter (includes meter display, captive mounting hardware, and 10-pin inter-connection header)03144-3020-1002
Meter Cover Kit (includes O-ring)
Aluminum Meter Cover Kit
Stainless Steel Meter Cover Kit
LCD Meter with Meter Cover Kit
(includes meter display, captive mounting hardware, 10-pin inter-connection, header, and cover kit)
LCD Meter with Meter Cover Kit – Aluminum
LCD Meter with Meter Cover Kit – Stainless Steel
Mounting Bracket Kit
B4 Mounting Bracket Kit
B5 Mounting Bracket Kit
Housing Cover (includes O-ring and wiring diagram label)
Aluminum Standard Cover
Stainless Steel Standard Cover
O-ring for cover (package of 12)
Option code C1 allows you to specify the following data in addition to the
standard configuration parameters.
•Date: day, month, year
•Descriptor: 16 alphanumeric characters
•Message: 32 alphanumeric characters
Trim to Specific Rosemount RTD Calibration Schedule
(Transmitter-to-Sensor Matching) (option code C2)
Option code C2 allows you to order the transmitter trimmed to a specific
calibration schedule. This option requires that you order a Rosemount Series
65, 68, or 78 RTD sensor with a special calibration schedule. For information
on ordering sensors calibrated to specific calibration schedules, refer to the
Rosemount Sensors Product Data Sheets, publication number
00813-0100-2654 (Volume 1) or publication number 00813-0101-2654
(Volume 2).
September 2002
Five Point Calibration (option code C4)
Option code C4 specifies that the transmitter be calibrated and verified at
five-points: 0, 25, 50, 75, and 100% digital output points.
Trim to Special non-Standard Sensor (option code C7)
You may order the transmitter with option code C7 when connecting
non-standard sensors, adding a special sensor, or expanding input ranges on
a standard sensor. Refer to Table 7-1 on page 7-1 for a list of standard sensor
types.
A characterization schedule for any RTD can be entered using Callandar-Van
Dusen constants with a Profibus configuration tool. The constants can be
entered on site or at the factory. For information on ordering sensors matched
to the transmitter using Callandar-Van Dusen constants, refer to the
Rosemount Sensors Product Data Sheet 00813-0100-2654 (Volume 1) or
00813-0101-2654 (Volume 2).
When a non-standard sensor is used as the input to the transmitter, the
resistance versus temperature curve for a non-standard RTD, or the millivolt
versus temperature curve for a non-standard thermocouple, is stored in the
transmitter memory. This process is performed at the factory. The transmitter
must be configured for a “special” sensor calibration to access the special
curve, but you may use any standard input when the transmitter is configured
for a “standard” sensor.
A-10
Reference Manual
00809-0100-4799, Rev BA
September 2002
Figure A-1. External
Ground-Lug Assembly Installed
on a Model 3244MV
Transmitter.
Model 3244MV
Mounting Brackets (option codes B4 and B5)
The transmitter can be mounted directly to the sensor, or in a remote location
with one of two stainless steel mounting brackets. Refer to Figures 2-5 and
2-6 on page 2-7. The brackets facilitate mounting to a panel or a 2-inch pipe,
and include stainless steel bolts. When installing the transmitter with a
bracket, torque the bolts to 125 in-lb (14 n-m).
External Ground Lug Assembly (option code G1)
The external ground-lug assembly provides an auxiliary grounding point for
the transmitter housing. The lug attaches to either side of the housing. See
Figure A-1.
Institut Scientifique de Service Public (ISSeP)/ CENELEC Flame-proof
Approval
E9 EEx d IIC T6 (T
Certificate: 95D.103.1211
Certificate implies Flame-Proof approval of the following:
1. Transmitter with Rosemount “E9” sensor installed per drawing
003144-0224
2. Transmitter with remote mounted Flame-Proof sensor and connection
head assembly installed per drawing 3144-0224.
British Approvals Service for Electrical Equipment in Flammable
Atmospheres (BASEEFA) Approvals
N1 Type n Approval,
EEx nL IIC T5 (T
Certificate: ExBAS98ATEX3358X
ATEX Marking: Ex II 3 G
Maximum Input Voltage: 55 Vdc
Special Conditions for Safe Use (x):
The transmitter is not capable of withstanding the 500V insulation test
required by EN50021:1998. This must be taken into account when
installing the apparatus.
I1CENELEC Intrinsic Safety,
EEx ia IIC T4 (T
Certificate: ExBAS98ATEX1357X
ATEX Marking: Ex II 1 G
Input Entity Parameters:
Power/Loop
U
I
P
C
L
= 30 V dc
max:in
= 300 mA
max:in
= 1.3 W
max:in
= 0.005 µF
i
= 20 µH
i
= –20 to 60 °C).
amb
= –40 to 70 °C)
amb
= –60 to 60 °C)
amb
www.rosemount.com
Model 3244MV
Reference Manual
00809-0100-4799, Rev BA
September 2002
Special Conditions for Safe Use (x):
The apparatus is not capable of withstanding the 500V insulation test
required by Clause 6.4.12 of EN 50020: 1994. This must be taken into
account when installing the apparatus.
Factory Mutual
E5 Explosion-Proof for Class I, Division 1, Groups A, B, C, and D. Dust-
Ignition-Proof for Class II, Division 1, Groups E, F, and G.
Dust-Ignition-Proof for Class III, Division 1 hazardous locations.
Non-Incendive for Class I, Division 2, Groups A, B, C, and D (T
Indoor and outdoor use. Ambient Temperature Limit: –50 to 85 °C.
Explosion-Proof approval only when installed per Rosemount drawing
03144-0220. For Group A, seal all conduits within 18-inches of
enclosures; otherwise, conduit seal not required for compliance with
NEC 501-5a(1).
Canadian Standards Association (CSA) Approvals
E6 Explosion-Proof for Class I, Division 1, Groups A, B, C, and D; Class II,
Division 1, Groups E, F, and G; Class III, Division 1 hazardous locations.
Suitable for Class I, Division 2, Groups A, B, C, and D. Conduit seal not
required. Ambient Temperature Limit: –50 to 85 °C.
I6Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D; Class II,
Division 1, Groups E, F, G; Class III, Division 1 hazardous locations when
installed per Rosemount drawing 03144-0222. Ambient Temperature
Limit: – 60 to 60 °C.
Once a device labeled with multiple approval types is installed, it should not
be reinstalled using any of the other labeled approval types. To ensure this,
the approval label should be permanently marked to distinguish the used from
the unused approval type(s).
B-3
Model 3244MV
Figure B-1. SAA Flame-Proof Installation Drawing 03144-0220, Rev D. Page 1 of 1
Reference Manual
00809-0100-4799, Rev BA
September 2002
B-4
3244_03144-0220
Reference Manual
00809-0100-4799, Rev BA
September 2002
Figure B-2. FM Intrinsic Safety and Non-Incendive Installation Drawing 03144-0221, Rev AE. Page 1 of 4
Model 3244MV
B-5
3244_03144-0221-1
Reference Manual
00809-0100-4799, Rev BA
Model 3244MV
Figure B-3. FM Intrinsic Safety and Non-Incendive Installation Drawing 03144-0221, Rev AE. Page 2 of 4
September 2002
B-6
3244_03144-0221-2
Reference Manual
00809-0100-4799, Rev BA
September 2002
Figure B-4. FM Intrinsic Safety and Non-Incendive Installation Drawing 03144-0221, Rev AE. Page 3 of 4
Model 3244MV
B-7
3244_03144-0221-3
Reference Manual
00809-0100-4799, Rev BA
Model 3244MV
Figure B-5. FM Intrinsic Safety and Non-Incendive Installation Drawing 03144-0221, Rev AE. Page 4 of 4
September 2002
B-8
3244_03144-0221-4
Reference Manual
00809-0100-4799, Rev BA
September 2002
Figure B-6. CSA Intrinsic Safety Installation Drawing 03144-0222, Rev AB. Page 1 of 2
Model 3244MV
B-9
3244_03144-0222-1
Model 3244MV
Figure B-7. CSA Intrinsic Safety Installation Drawing 03144-0222, Rev AB. Page 2 of 2
Reference Manual
00809-0100-4799, Rev BA
September 2002
B-10
3244_03144-0222-2
Reference Manual
00809-0100-4799, Rev BA
September 2002
Figure B-8. ISSEP/CENELEC Flame-Proof Installation Drawing 03144-0224, Rev C. Page 1 of 1
Model 3244MV
B-11
3244_03144-0224-1
Model 3244MV
Reference Manual
00809-0100-4799, Rev BA
September 2002
B-12
Reference Manual
00809-0100-4799, Rev BA
September 2002
Index
Model 3244MV
B
Blocks
. . . . . . . . . . . . . . . 3-3, 3-4
AI
Parameter . . . . . . . . . . . . . 3-4
Physical . . . . . . . . . . . 3-3, 3-6
Transducer . . . . . . . . . . . . . 3-3
Transducer 1 . . . . . . . . . . . 3-7
Transducer 2 . . . . . . . . . . . 3-7
Transducer 3 . . . . . . . . . . 3-10
C
Calibration . . . . . . . . . . . . . . . . . 3-4
2-point trim . . . . . . . . . . . . . 3-4
Configuration . . . . . . . . . . . . . . . 3-3
AI Block . . . . . . . . . . . . . . . 3-3
Physical Block . . . . . . . . . . . 3-3
Transducer Block . . . . . . . . 3-3
Considerations . . . . . . . . . . . . . 2-2
Electrical . . . . . . . . . . . . . . 2-2
Power Filter . . . . . . . . . 2-2
Power Supply . . . . . . . . 2-2
Environmental . . . . . . . . . . . 2-3
Moist or Corrosive . . . . . 2-4
Temperature . . . . . . . . . 2-3
General . . . . . . . . . . . . . . . 2-2
Mechanical . . . . . . . . . . . . . 2-2
Access Requirements . . 2-2
Mounting . . . . . . . . . . . 2-2
Tagging . . . . . . . . . . . . 2-2
D
Drawings
Dimensional
Installation . . . . . . . . . . . . . B-3
Switch Location . . . . . . . . . 2-10
Wiring . . . . . . . . . . . . . . . . 2-9
. . . . . . . . . . . . A-6
E
Electronics Housing . . . . . . . . . . 4-3
Removing the Electronics . . . 4-3
Replacing the Electronics . . . 4-4
G
Grounding . . . . . . . . . . . . . . . . 2-8
Housing . . . . . . . . . . . . . . . 2-8
Shielded Wire . . . . . . . . . . . 2-8
H
Hardware . . . . . . . . . . . . . . . . . 4-2
Diagnostics . . . . . . . . . . . . 4-2
Maintenance . . . . . . . . . . . 4-3
Sensor Checkout . . . . . 4-3
Hazardous Certifications . . . . . . B-1
Hazardous Locations Certifications
Installation Drawings . . . . . . B-3
I
Installation . . . . . . . . . . . . .2-4, 3-2
Changing the Block Mode . . 3-2
Device Description . . . . . . . 3-2
European . . . . . . . . . . . . . . 2-6
GSD File . . . . . . . . . . . . . . 3-2
North American . . . . . . . . . 2-5
Installation Drawings . . . . . . . . . B-3
M
Mounting . . . . . . . . . . . . . . . . . 2-4
European . . . . . . . . . . . . . . 2-6
North American . . . . . . . . . 2-5
O
Options . . . . . . . . . . . . . . . . . A-10
Ordering Information . . . . . . . . . A-8
Spare Parts . . . . . . . . . . . . A-9
Transmitter . . . . . . . . . . . . . A-8
P
Power Connections . . . . . . . . . . 2-7
PV Status Byte Codes . . . . . . . 3-12
S
Security Switch . . . . . . . . . . . . 2-10
Sensor Connections . . . . . . . . . .2-9
Millivolt . . . . . . . . . . . . . . . .2-9
Ohm . . . . . . . . . . . . . . . . . .2-9
RTD . . . . . . . . . . . . . . . . . .2-9
Thermocouple . . . . . . . . . . . 2-9
Set the Switches . . . . . . . . . . . .2-10
Security . . . . . . . . . . . . . . .2-10
Simulate . . . . . . . . . . . . . .2-10
Simulate Switch . . . . . . . . . . . .2-10
Specifications . . . . . . . . . . . . . . A-1
Functional . . . . . . . . . . . . . A-1
Performance . . . . . . . . . . . A-3
Physical . . . . . . . . . . . . . . A-5
Profibus-PA . . . . . . . . . . . . A-2
Surges/Transients . . . . . . . . . . .2-8
T
Tagging . . . . . . . . . . . . . . . . . . A-9
Hardware . . . . . . . . . . . . . A-9
Software . . . . . . . . . . . . . A-10
W
Wiring . . . . . . . . . . . . . . . . . . . .2-7
Diagram . . . . . . . . . . . . . . .2-9
Field Wiring . . . . . . . . . . . . .2-7
Grounding . . . . . . . . . . . . . .2-8
Housing . . . . . . . . . . . .2-8
Shield Wire . . . . . . . . . .2-8
Power Connections . . . . . . .2-7
Sensor Connections . . . . . . .2-9
Millivolt . . . . . . . . . . . . .2-9
Ohm . . . . . . . . . . . . . . .2-9
RTD . . . . . . . . . . . . . . .2-9
Thermocouple . . . . . . . .2-9
Surges/Transients . . . . . . . .2-8
www.rosemount.com
Model 3244MV
Reference Manual
00809-0100-4799, Rev BA
September 2002
Index-2
Model 3244MV
Reference Manual
00809-0100-4799, Rev BA
September 2002
Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.
Multivariable (MV) is a trademark of Rosemount Inc.
Teflon is a registered trademark of E.I. du Pont de Nemours & Company
All other marks are the property of their respective owners.
Emerson Process Management
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN 55317 USA
T (U.S.) 1-800-999-9307
T (International) (952) 906-8888
F (952) 949-7001
www.rosemount.com
Rosemount Temperature GmbH
Frankenstrasse 21
63791 Karlstein
Germany
T 49 (6188) 992 0
F 49 (6188) 992 112
Emerson Process Management Asia
Pacific Private Limited
1 Pandan Crescent
Singapore 128461
T (65) 777 8211
F (65) 777 0947
AP.RMT-Specialist@emersonprocess.com