Rosemount 3051S Series Pressure Transmitter with HART Protocol Manuals & Guides

Reference Manual
00809-0100-4801, Rev HB
June 2021
Rosemount™ 3051S Series Scalable™ Pressure, Flow, and Level Solution
with HART® Protocol
Safety messages
NOTICE
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
See listed technical assistance contacts.
Customer Central
Technical support, quoting, and order-related questions.
United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)
Asia Pacific- 65 777 211
Europe/ Middle East/Africa - 49 (8153) 9390
North American Response Center
Equipment service needs.
1-800-654-7768 (24 hours—includes Canada)
Outside of these areas, contact your local Emerson representative.
CAUTION
The products described in this document are NOT designed for nuclear-qualified applications.
Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Emerson Sales Representative.
WARNING
Explosions can result in death or serious injury.
Do not remove the transmitter covers in explosive environments when the circuit is live.
Fully engage both transmitter covers to meet explosion-proof requirements.
Before connecting a communicator in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals.
Process leaks could result in death or serious injury.
Install and tighten all four flange bolts before applying pressure.
Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Replacement equipment or spare parts not approved by Emerson or use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
Improper assembly of manifolds to traditional flange can damage SuperModule™ Platform.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e., bolt hole) but must not contact sensor module housing.
2
WARNING
SuperModule and electronics housing must have equivalent approval labeling in order to maintain hazardous location approvals.
When upgrading, verify SuperModule and electronics housing certifications are equivalent. Differences in temperature class ratings may exist, in which case the complete assembly takes the lowest of the individual component temperature classes (for example, a T4/T5 rated electronics housing assembled to a T4 rated SuperModule is a T4 rated transmitter.)
Severe changes in the electrical loop may inhibit HART® Communication or the ability to reach alarm values. Therefore, Emerson cannot absolutely warrant or guarantee that the correct failure alarm level (HIGH or LOW) can be read by the host system at the time of annunciation.
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
3
4
Reference Manual Contents
00809-0100-4801 June 2021

Contents

Chapter 1 Introduction.............................................................................................................. 7
1.1 Using this manual........................................................................................................................ 7
1.2 Models covered........................................................................................................................... 7
1.3 Product recycling/disposal...........................................................................................................9
Chapter 2 Configuration...........................................................................................................11
2.1 Overview................................................................................................................................... 11
2.2 Commissioning on the bench.................................................................................................... 12
2.3 Field Communicator.................................................................................................................. 13
2.4 Field Communicator menu trees................................................................................................14
2.5 Check output.............................................................................................................................28
2.6 Basic setup.................................................................................................................................29
2.7 LCD display (Optional Order Code)............................................................................................ 35
2.8 Detailed setup........................................................................................................................... 35
2.9 Diagnostics and service..............................................................................................................45
2.10 Advanced functions................................................................................................................. 47
2.11 Multidrop communication ...................................................................................................... 51
Chapter 3 Hardware Installation.............................................................................................. 53
3.1 Overview................................................................................................................................... 53
3.2 Safety messages........................................................................................................................ 53
3.3 Considerations...........................................................................................................................54
3.4 Installation procedures.............................................................................................................. 56
3.5 Rosemount 305, 306, and 304 Manifolds...................................................................................66
3.6 Wiring the device.......................................................................................................................74
Chapter 4 Operation and maintenance overview......................................................................85
4.1 Calibration for HART® Protocol.................................................................................................. 85
4.2 Field upgrades........................................................................................................................... 99
Chapter 5 Troubleshooting.................................................................................................... 101
5.1 Overview................................................................................................................................. 102
5.2 Safety messages...................................................................................................................... 102
5.3 Troubleshooting......................................................................................................................103
5.4 Disassembly procedures.......................................................................................................... 104
5.5 Reassembly procedures...........................................................................................................108
5.6 Service support........................................................................................................................110
Chapter 6 Safety Instrumented Systems................................................................................. 113
6.1 Rosemount 3051S safety certified identification......................................................................113
6.2 Installation in SIS applications..................................................................................................113
5
Contents Reference Manual
June 2021 00809-0100-4801
6.3 Configuring in SIS applications.................................................................................................114
6.4 Damping .................................................................................................................................114
6.5 Alarm and saturation levels......................................................................................................114
6.6 SIS Operation and maintenance...............................................................................................116
6.7 Inspection................................................................................................................................118
Chapter 7 Advanced HART Diagnostic Suite............................................................................119
7.1 Advanced HART® Diagnostic Suite........................................................................................... 119
Appendix A Appendix A: Specifications and Reference Data...................................................... 159
A.1 Product Certifications..............................................................................................................159
A.2 Ordering Information, Specifications, and Drawings................................................................159
6 Emerson.com/RosemountEmerson.com/Rosemount
Reference Manual Introduction
00809-0100-4801 June 2021

1 Introduction

1.1 Using this manual

The sections in this manual provide information on installing, operating, and maintaining the Rosemount 3051S Pressure Transmitter with HART® Protocol. The sections are organized as follows:
Section 1: Introduction provides an introduction to the pressure transmitter, how to
use the manual, models covered by this manual, and other support information for the transmitter.
Configuration provides instruction on commissioning and operating Rosemount 3051S
transmitters from a bench computer or a hand held field device. Information on software functions, configuration parameters, and on line variables are also included.
Installation contains instructions for mounting the transmitter, connecting it to the
process, and wiring the transmitter.
Operation and maintenance contains techniques to maintain the transmitter, and
disassembly/assembly directions.
Troubleshooting provides troubleshooting techniques for the most common operating
issues.
Section 6: Safety Instrumented Systems contains identification, commissioning,
maintenance, and operations information for the Rosemount 3051S SIS Safety Transmitter.
Section 7: Advanced HART® Diagnostic Suite contains procedures for installation,
configuration, and operation of the Rosemount 3051S HART Diagnostics option.
Reference data supplies links to updated specifications, ordering information, intrinsic
safety approval information, European ATEX directive information, and approval drawings.
For transmitter with FOUNDATION™ Fieldbus, see Rosemount 3051S Reference Manual.

1.2 Models covered

The following transmitters and the Rosemount 300S Housing Kit are covered in this manual.
The Rosemount 3051S provides a wide range of applications, and many of these different applications have their own reference manuals. This manual covers the Rosemount 3051S HART®, Advanced Diagnostics, and Safety Instrumented Systems (SIS).
Table 1-1: Rosemount 3051S Coplanar
Pressure Transmitter
Performance class Measurement type
Differential Gauge Absolute
Ultra X X X
7
Introduction
Reference Manual
June 2021 00809-0100-4801
Table 1-1: Rosemount 3051S Coplanar™ Pressure Transmitter (continued)
Performance class Measurement type
Differential Gauge Absolute
Ultra for Flow X N/A N/A
Classic X X X
Table 1-2: Rosemount 3051S In-Line Pressure Transmitter
Performance class Measurement type
Differential Gauge Absolute
Ultra N/A X X
Classic N/A X X
Table 1-3: Rosemount 3051S Liquid Level Pressure Transmitter
Performance class Measurement type
Differential Gauge Absolute
Classic X X X
Table 1-4: Rosemount 3051S SIS Safety Certified Transmitter
Performance class Measurement type
Differential Gauge Absolute
Classic X X X
Table 1-5: Rosemount 3051S Transmitter with FOUNDATION Fieldbus Diagnostics Transmitter
Performance class Measurement type
Differential Gauge Absolute
Ultra X X X
Ultra for Flow X N/A N/A
Classic X X X
For information on other Rosemount 3051S transmitters, refer to the following reference manuals:
Rosemount 3051S FOUNDATION Fieldbus Reference Manual
Rosemount 3051S Wireless Reference Manual
Rosemount 3051S Electronic Remote Sensor (ERS™) System Reference Manual
Rosemount 3051S MultiVariableReference Manual
8 Emerson.com/RosemountEmerson.com/Rosemount
Reference Manual Introduction
00809-0100-4801 June 2021
Rosemount 300S Scalable Housing Kits
Kits are available for all models of Rosemount 3051S Pressure Transmitters.

1.3 Product recycling/disposal

Recycling of equipment and packaging should be taken into consideration and disposed of in accordance with local and national legislation/regulations.
9
Introduction Reference Manual
June 2021 00809-0100-4801
10 Emerson.com/RosemountEmerson.com/Rosemount
Reference Manual Configuration
00809-0100-4801 June 2021

2 Configuration

2.1 Overview

This section contains information on commissioning and tasks that should be performed on the bench prior to installation.
Instructions for performing configuration functions are given for handheld communication devices like the Field Communicator or asset management software like Emerson's AMS Device Manager. For convenience, Field Communicator Fast Key sequences (where supported) are labeled “Fast Keys” for each software function below the appropriate headings.
2.1.1

Example software function

The Device Dashboard Fast Keys apply to Device Driver Revision 9 or newer. The HART® 5 with Diagnostics Fast Keys apply to Device Driver Revision 1. The HART 7 Fast Keys apply to Device Driver Revision 2. Contact Emerson™ or refer to previous reference manuals for information on older revisions.
Device Dashboard Fast Keys
HART 5 with Diagnostics Fast Keys 1, 2, 3, etc.
HART 7 Fast Keys 1, 2, 3, etc.

2.1.2 Safety messages

WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices.
Before connecting a handheld communicator in an explosive atmosphere, ensure that the instruments in the loop are installed in accordance with intrinsically safe or non­incendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is applied to the unit.
1, 2, 3, etc.
WARNING
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
11
Configuration Reference Manual
June 2021 00809-0100-4801

2.2 Commissioning on the bench

Commissioning consists of testing the transmitter and verifying transmitter configuration data. Rosemount™ 3051S Pressure Transmitters can be commissioned either before or after installation. Commissioning the transmitter on the bench before installation using a Field Communicator or AMS Device Manager ensures all transmitter components are in working order.
Equipment required to commission on the bench includes a power supply, a milliamp meter, and a Field Communicator or AMS Device Manager. Wire the equipment as shown in Figure 2-1. Verify transmitter terminal voltage is between 10.5–42.4 Vdc. To ensure successful communication, a resistance of at least 250 ohms must be present between the Field Communicator loop connection and the power supply. Connect the Field Communicator leads to the terminals labeled “PWR/COMM” on the terminal block. (Connecting across the “TEST” terminals will prevent successful communication.)
Set all transmitter hardware adjustments during commissioning to avoid exposing the transmitter electronics to the plant environment after installation. Refer to .
When using a Field Communicator, any configuration changes made must be sent to the transmitter by using the Send key. AMS Device Manager configuration changes are implemented when the Apply button is selected.
2.2.1
2.2.2

Setting the loop to manual

Whenever sending or requesting data that would disrupt the loop or change the output of the transmitter, set the process application loop to manual. The Field Communicator or AMS Device Manager will prompt you to set the loop to manual when necessary. Acknowledging this prompt does not set the loop to manual. The prompt is only a reminder; set the loop to manual as a separate operation.

Wiring diagrams

Bench hook-up
Connect the bench equipment as shown in Figure Figure 2-1, and turn on the Field Communicator or log into AMS Device Manager. The Field Communicator or AMS Device Manager will search for a HART™-compatible device and indicate when the connection is made. If the Field Communicator or AMS Device Manager fail to connect, it indicates that no device was found. If this occurs, refer to Troubleshooting.
Field hook-up
Figure Figure 2-1 illustrate wiring loops for a field hook-up with a Field Communicator or AMS Device Manager. The Field Communicator or AMS Device Manager may be connected at “PWR/COMM” on the transmitter terminal block, across the load resistor, or at any termination point in the signal loop. Signal point may be grounded at any point or left ungrounded.
12 Emerson.com/RosemountEmerson.com/Rosemount
A
B
SAVE
3051S DIAG: HDT 93207 Online
1 Overview
2 Configure 3 Service Tools
Reference Manual Configuration
00809-0100-4801 June 2021
Figure 2-1: Typical Wiring (4–20 mA)
A. Power supply
B. RL ≥ 250Ω

2.3 Field Communicator

2.3.1
For convenience, Field Communicator Fast Key sequences are labeled Fast Keys for each software function below the appropriate headings. The Device Dashboard Fast Keys apply to Device Driver Revision 9 or newer. The HART 5 with Diagnostics Fast Keys apply to Device Driver Revision 1. The HART 7 Fast Keys apply to Device Driver Revision 2.

Field Communicator user interface

Figure 2-2: HART 5 with Diagnostics Dashboard
Note
The corresponding menu tree is shown in Figure 2-3. The Fast Key sequence can be viewed on Device Dashboard Fast Key sequence.
13
Home
Overview
1 Device Status 2 Comm Status 3 Pressure 4 PV Loop Current 5 Pressure URV 6 Pressure LRV 7 Device Information
Device Information
1 Identification 2 Revisions 3 Material of Construction 4 RS Material of Construction 5 Analog Alarm 6 Security
Identification
1 Tag 2 Model 3 Transmitter S/N 4 Date 5 Description 6 Message 7 Model Number 1 8 Model Number 2 9 Model Number 3
Revisions
1 Universal Revision 2 Field Device Revision 3 Software Revision 4 Hardware Revision 5 Device Driver Revision
Materials of Construction
1 Module Configuration 2 Sensor Range 3 Upper Sensor Limit 4 Lower Sensor Limit 5 Isolator Materials 6 Fill Fluid 7 Process Connection 8 Process Connection Material 9 O-Ring Material 10 Drain Vent Material
RS Material of Construction
1 # of Remote Seals 2 RS Seal Type 3 RS Fill Fluid 4 RS Isolator Material
Analog Alarm
1 Alarm Direction 2 High Alarm 3 High Saturation 4 Low Saturation 5 Low Alarm
Security
1 Write Protect Status 2 Local Zero/Span
1 Overview 2 Configure 3 Service Tools
Configuration Reference Manual
June 2021 00809-0100-4801

2.4 Field Communicator menu trees

Device Dashboard menu tree
Figure 2-3: Overview
14 Emerson.com/RosemountEmerson.com/Rosemount
Home
1 Overview 2 Configure 3 Service Tools
1 Pressure Alert 2 Temperature Alert
Alert Setup
Configure
1 Guided Setup 2 Manual Setup 3 Alert Setup
Pressure Alert
1 Alert Mode 2 High Alert Value 3 Low Alert Value
Temperature Alert
1 Alert Mode 2 High Alert Value 3 Low Alert Value
Guided Setup
1 Basic Setup 2 Zero 3 Configure Display 4 Variable Mapping 5 Configure Alarm and Sat levels 6 Process Alerts 7 Scaled Variable
Manual Setup
1 Basic Setup 2 Scaled Variable 3 Display 4 HART 5 Device Information 6 Materials of Construction 7 Security
Basic Setup
1 Tag 2 Unit 3 Range Values 4 Transfer Function 5 Pressure Damping 6 Module Temperature Units 7 Configure Alarm and Sat Levels 8 Range by Applying Pressure
Scaled Variable
1 SV Data Points 2 SV Units 3 SV Transfer Function 4 SV Linear Offset 5 SV Config
Display
1 Pressure 2 Scaled Variable 3 Module Temperature 4 Percent of Range
HART
1 Variable Mapping 2 Polling Address 3 Burst Mode 4 Burst Option
Device Information
1 Tag 2 Model 3 Transmitter S/N 4 Date 5 Description 6 Message 7 Model Number 1 8 Model Number 2 9 Model Number 3
Range Values
1 Pressure URV 2 Pressure LRV
Variable Mapping
1 Primary Variable 2 Secondary Variable 3 Third Variable
Materials of Construction
1 Process Connection 2 Process Connection Material 3 Drain Vent Material 4 # of Remote Seals 5 RS Seal Type 6 RS Fill Fluid 7 RS Isolator Material
Security
1 Write Protect Status 2 Local Zero/Span
Burst Option
PV % range/current Dyn Vars/current
Tag, Description, Message, Date, Pressure Units, Temperature Units, Transfer Function, URV, LRV
Reference Manual Configuration
00809-0100-4801 June 2021
Figure 2-4: Configure
15
Home
1 Overview 2 Configure 3 Service Tools
Service Tools
1 Device Alerts 2 Variables 3 Trends 4 Routine Maintenance 5 Simulate
Variables
1 Pressure 2 Scaled Variable 3 Module Temperature
Trends
1 Pressure 2 Scaled Variable 3 Module Temperature
Routine Maintenance
1 Pressure Calibration 2 Analog Output Calibration 3 Recall Factory Calibration
Simulate
1 Loop Test
Device Alerts
1 Refresh Alerts 2 Configuration Changed
Only Active Alerts show up
Trend Graph
Pressure Calibration
1 Upper Sensor Trim 2 Lower Sensor Trim 3 Zero 4 Last Calibration Points 5 Sensor Limits
Last Calibration Points
1 Upper Calibration Point 2 Lower Calibration Point
Sensor Limits
1 Upper 2 Lower 3 Minimum Span
Configuration Reference Manual
June 2021 00809-0100-4801
Figure 2-5: Service Tools
16 Emerson.com/RosemountEmerson.com/Rosemount
Home
1 Overview 2 Configure 3 Service Tools
Overview
1 Status 2 Primary Purpose Variable 3 Shortcuts
Status
1 Device Status: Good 2 Communications: Polled
Shortcuts
1 Calibration 2 SPM Status 3 All Variables 4 View Logs 5 Device Information
Calibration
1 Pressure 2 Analog Output 3 Restore Factory Calibration
Pressure
1 Sensor Calibration 2 Range Values 3 Current Measurement 4 Last Calibration Points 5 Sensor Limits
Primary Purpose Variable
1 Pressure 2 Analog Output
SPM Status
1 Detection Status 2 Statistical Values 3 Time Stamp 4 Trends
Analog Output
1 Analog Output 2 Percent of Range 3 Analog Calibration
Detection Status
1 SPM Status 2 SPM Status (cont.) 3 Standard Deviation Sensitivity* 4 Mean Sensitivity**
*If CV is selected, "Coefficient of Variation Sensitivity" **If CV is selected, this is not shown
Statistical Values
1 Standard Deviation* 2 Mean
*Or Coefficient of Variation
Time Stamp
1 Time Since Detection 2 Total Operating Time
Trends
1 Standard Deviation* 2 Mean
*If CV is selected, "Coefficient of Variation"
All Variables
1 Primary Variable 2 2nd Variable 3 3rd Variable 4 4th Variable 5 Other Variables
Primary Variable
1 <Mapped variable>
2nd Variable
1 <Mapped variable>
3rd Variable
1 <Mapped variable>
4th Variable
1 <Mapped variable>
Other Variables
1 <Unmapped variable> 2 <Unmapped variable>
Device Information
1 General 2 Model Numbers 3 Revision Numbers 4 Materials of Construction 5 Alarm and Security
View Logs
1 Diagnostic Log 2 Pressure Variable Logging 3 Temperature Variable Logging
Diagnostic Log
1 Most Recent Status Event 2 View Other Status Events 3 Total Operating Time 4 Clear Log
Pressure Variable Logging
1 Pressure Variable Log 2 Time Outside Sensor Limits 3 Pressure 4 Total Operating Time 5 Reset All Pressure Events
Temperature Variable Logging
1 Temperature Variable Log 2 Time Outside Sensor Limits 3 Module Temperature 4 Total Operating Time 5 Reset All Temperature Events
Sensor Calibration
1 Upper Sensor Trim 2 Lower Sensor Trim 3 Zero
Range Values
1 Upper Range value (20 mA) 2 Lower Range Value (4 mA)
Current Measurement
1 Pressure 2 Damping 3 Transfer Function
Last Calibration Points
1 Upper 2 Lower
Sensor Limits
1 Upper 2 Lower 3 Minimum Span
SPM Status (cont.)
1 SPM Insufficient Variability 2 SPM Low Pressure Status
Most Recent Status Event
1 Event 1 - Time since
View Other Status Events
1 Event 2 - Time since 2 Event 3 - Time since 3 Event 4 - Time since 4 Event 5 - Time since 5 Event 6 - Time since 6 Event 7 - Time since 7 Event 8 - Time since 8 Event 9 - Time since 9 Event 10 - Time since
Pressure Variable Log
1 Minimum Pressure 2 Time Since Minimum Event 3 Reset Minimum 4 Maximum Pressure 5 Time Since Maximum Event 6 Reset Maximum
Time Outside Sensor Limits
1 Above Upper Sensor Limit 2 Below Lower Sensor Limit 3 Reset Time Since 1st Events
Temperature Variable Log
1 Minimum Temperature 2 Time Since Minimum Event 3 Reset Minimum 4 Maximum Temperature 5 Time Since Maximum Event 6 Reset Maximum
Time Outside Sensor Limits
1 Above Upper Sensor Limit 2 Below Lower Sensor Limit 3 Reset Time Since 1st Events
General
1 Tag 2 Model 3 Date 4 Descriptor 5 Message 6 Serial Number
Model Numbers
1 Model Number 1 2 Model Number 2 3 Model Number 3
Revision Numbers
1 HART Universal 2 Field Device 3 Electronics SW 4 Electronics HW 5 Sensor SW 6 Sensor HW
Materials of Construction
1 Sensor Module Information 2 Flange Information 3 Remote Seal Information
Alarm and Security
1 Alarm Direction 2 High Alarm 3 High Saturation 4 Low Saturation 5 Low Alarm 6 Write Protect Status 7 Local ZERO/SPAN Buttons
Serial Number
1 Transmitter 2 Electronics
Sensor Module Information
1 Serial Number 2 Type 3 Configuration 4 Sensor Range 5 Sensor Limits 6 Isolator Material 7 Fill Fluid
Flange Information
1 Process Connection 2 Process Connection Material 3 O-ring Material 4 Drain Vent Material
Remote Seal Information
1 Number 2 Type 3 Diaphragm Material 4 Fill Fluid
Reference Manual Configuration
00809-0100-4801 June 2021
HART 5 with Diagnostic menu trees
Figure 2-6: Overview
17
Home
1 Overview 2 Configure 3 Service Tools
Configure
1 Guided Setup 2 Manual Setup 3 Alert Setup (see Figure 7-33)
Guided Setup
1 Initial Setup 2 Diagnostics Setup 3 Optional Configuration
Manual Setup
1 Process Variables 2 Analog Output 3 Scaled Variable 4 Display Options 5 HART 6 Security 7 Device Information
Initial Setup
1 Basic Setup 2 Zero Trim
Diagnostics Setup
1 Statistical Process Monitoring 2 Power Advisory 3 Process Alerts 4 Service Alert
Optional Configuration
1 Configure Display 2 Configure Burst Mode
Basic Setup
1 Device Tagging 2 Units of Measure 3 Pressure Damping 4 Variable Mapping 5 Analog Output 6
Config Alarm & Saturation Levels
Display Options 1 Pressure: On or Off 2 Scaled Variable: On or Off 3 Module Temperature: On or Off 4 Percent of Range: On or Off 5 Standard Deviation: On or Off 6 Mean: On or Off 7 Coefficient of Variation: On or Off
Process Variables
1 Pressure Setup 2 Module Temperature Setup
Analog Output
1 Set Range Points 2 Set Range Points Manually 3 Sensor Limits 4 Readings 5 Alarm and Saturation Levels
Pressure Setup
1 Pressure 2 Units 3 Damping 4 Transfer Function
Module Temperature Setup
1 Module Temperature 2 Units
Set Range Points
1 PV Upper Range Value 2 PV Lower Range Value 3 Primary Variable
Set Range Points Manually
1 Range By Applying Pressure
Sensor Limits
1 Upper 2 Lower 3 Minimum Span
Readings
1 Analog Output 2 Percent of Range
Alarm and Saturation Levels
1 Alarm Direction 2 High Alarm 3 High Saturation 4 Low Saturation 5 Low Alarm 6 Config Alarm & Saturation Levels
Scaled Variable Setup
1 Scaled Variable 2 Units 3 Transfer Function 4 Linear Options* 5 Configure Scaled Variable
*If Square Root is selected for Transfer Function, "Square Root Options"
Linear Options
1 Offset
Square Root Options
1 Cutoff Mode 2 Low Flow Cutoff
Display
1 Display Options
Display Options
1 Pressure: On or Off 2 Scaled Variable: On or Off 3 Module Temperature: On or Off 4 Percent of Range: On or Off 5 Standard Deviation: On or Off 6 Mean: On or Off 7 Coefficient of Variation: On or Off
HART
1 Variable Mapping 2 Burst Mode Configuration 3 Communication Settings
Variable Mapping
1 Primary Variable 2 2nd Variable 3 3rd Variable 4 4th Variable
Burst Mode Configuration
1 Mode 2 Option
Communication Settings
1 Polling Address
Security
1 Write Protect Status 2 Local ZERO/SPAN Buttons
Device Information
1 Identification 2 Flange Information 3 Remote Seal Information
Identification
1 Tag 2 Model 3 Date 4 Descriptor 5 Message 6 Transmitter Serial Number 7 Model Numbers
Flange Information
1 Process Connection 2 Process Connection Material 3 O-ring Material 4 Drain/Vent Material
Remote Seal Information
1 Number 2 Type 3 Diaphragm Material 4 Fill Fluid
Configuration Reference Manual
June 2021 00809-0100-4801
Figure 2-7: Configure (Guided Setup and Manual Setup)
18 Emerson.com/RosemountEmerson.com/Rosemount
Home
1 Overview 2 Configure 3 Service Tools
Configure
1 Guided Setup 2 Manual Setup 3 Alert Setup
Alert Setup
1 Statistical Process
Monitoring
2 Power Advisory Diagnostic 3 Device Diagnostics 4 Process Alerts 5 Service Alerts
Statistical Process Monitoring
Status Baseline Configuration Detection Configuration Operational Values
Status
1 Detection Status 2 SPM Control 3 Statistical Values 4 Time Stamp 5 Trends
Detection Status
1 SPM Status 2 SPM Status (cont.) 3 Standard Deviation Sensitivity* 4 Mean Sensitivity**
*If CV is selected, "Coefficient of Variation Sensitivity" **If CV is selected, this is not shown
SPM Control
1 Mode 2 Reset 3 Relearn
Statistical Values
1 Standard Deviation* 2 Mean
*Or Coefficient of Variation
Time Stamp
1 Time Since Detection 2 Total Operating Time
Trends
1 View Standard Deviation Trend* 2 View Mean Trend
*Or Coefficient of Variation
Baseline Configuration
1 Learn Settings 2 Verification Criteria
Learn Settings
1 SPM Variable 2 Learn/Monitor Period 3 Power Interruption Action 4 Low pressure Cut-off *
*Shown only when CV is selected
Verification Criteria
1 Insufficient Variability 2 Standard Deviation Difference 3 Mean Difference
Detection Configuration
1 Standard Deviation Detection Settings*
2 Mean Detection Settings**
*If CV is selected, "Coefficient of Variation Detection Settings" **If CV is selected, this is not shown
Standard Deviation Change*
1 Standard Deviation Sensitivity 2 Threshold Value** 3 Configure Sensitivity 4 Action 5 Alert Delay 6 High Detection Message 7 Low Detection Message
* If CV is selected, “Coefficient of Variation Change” **Shown only if Sensitivity is set to "Custom"
Mean Change**
1 Mean Sensitivity 2 Threshold Value 3 Configure Sensitivity 4 Action 5 Mean Change Message
**If CV is selected, this is not shown
Operational Values
1 Standard Deviation 2 Mean 3 Coefficient of Variation 4 SPM Detection Values 5 Number of Relearns 6 Reset Relearn Counter
SPM Detection Values
1 Standard Deviation 2 Mean 3 Coefficient of Variation
Power Advisory Diagnostic
1 Power Advisory Diagnostic 2 Loop Power Characterization
Power Advisory Diagnostic
1 Terminal Voltage 2 Terminal Voltage Deviation Limit 3 Action 4 Reset Alert
Loop Power Characterization
1 Resistance 2 Power Supply 3 Characterization Time Stamp 4 Characterize Loop
Resistance
1 Previous Baseline 2 Baseline
Power Supply
1 Previous Baseline 2 Baseline
Characterization Time Stamp
1 Previous Characterization 2 Time Since Characterization
Device Diagnostics
1 mA Output Diagnostic 2 Transmitter Power Consumption
mA Output Diagnostic
1 Action 2 Reset Alert
Transmitter Power Consumption
1 Action 2 Reset Alert
Process Alerts
1 Pressure Alerts 2 Temperature Alerts
Pressure Alerts
1 View Trend 2 Pressure 3 Alert Settings 4 Pressure Alert Events
Temperature Alerts
1 View Trend 2 Module Temperature 3 Alert Settings 4 Module Temperature Alert Events
Service Alerts
1 Time Remaining 2 Message 3 Alert Mode 4 Configure 5 Reset Alert
Alert Settings
1 Alert Mode 2 High Alert Value 3 Low Alert Value
Pressure Alert Events
1 High Alert Events 2 Low Alert Events 3 Reset Alert Events
Alert Settings
1 Alert Mode 2 High Alert Value 3 Low Alert Value
Temperature Alert Events
1 High Alert Events 2 Low Alert Events 3 Reset Alert Events
Reference Manual Configuration
00809-0100-4801 June 2021
Figure 2-8: Configure (Alert Setup)
19
Home
1 Overview 2 Configure 3 Service Tools
Service Tools
1 Device Alerts 2 Variables 3 Trends 4 Routine Maintenance 5 Simulate
Variables
1 Pressure 2 Scaled Variable 3 Module Temperature
Trends
1 Pressure 2 Scaled Variable 3 Module Temperature
Routine Maintenance
1 Pressure Calibration 2 Analog Output Calibration 3 Recall Factory Calibration
Simulate
1 Loop Test
Device Alerts
1 Refresh Alerts 2 Configuration Changed
Only Active Alerts show up
Trend Graph
Pressure Calibration
1 Upper Sensor Trim 2 Lower Sensor Trim 3 Zero 4 Last Calibration Points 5 Sensor Limits
Last Calibration Points
1 Upper Calibration Point 2 Lower Calibration Point
Sensor Limits
1 Upper 2 Lower 3 Minimum Span
Configuration Reference Manual
June 2021 00809-0100-4801
Figure 2-9: Service Tools
20 Emerson.com/RosemountEmerson.com/Rosemount
Reference Manual Configuration
00809-0100-4801 June 2021
HART 7 menu trees
Figure 2-10: Overview
21
Configuration Reference Manual
June 2021 00809-0100-4801
Figure 2-11: Configure (Guided Setup and Manual Setup)
22 Emerson.com/RosemountEmerson.com/Rosemount
Reference Manual Configuration
00809-0100-4801 June 2021
Figure 2-12: Configure (Alert Setup)
23
Configuration Reference Manual
June 2021 00809-0100-4801
Figure 2-13: Service Tools
Device Dashboard Fast Key sequence
The following menu indicates Fast Key sequences for common functions. A check () indicates the basic configuration parameters. At minimum, these parameters should be verified as part of the configuration and startup procedure.
Function Fast Key sequence
Alarm and Saturation Levels 1, 4, 5
Alarm Level Configuration 1, 7, 5
Analog Output Alarm Direction 1, 7, 5, 1
Burst Mode Control 2, 2, 4, 3
Burst Option 2, 2, 4, 4
Custom Display Configuration 2, 1, 3
24 Emerson.com/RosemountEmerson.com/Rosemount
Reference Manual Configuration
00809-0100-4801 June 2021
Function Fast Key sequence
Damping 2, 2, 1, 5
Date 2, 2, 5, 4
Descriptor 2, 2, 5, 5
Digital to Analog Trim (4 - 20 mA Output) 3, 4, 2
Disable Zero & Span Adjustment 2, 2, 7, 2
Field Device Information 1, 7
LCD Display Configuration 2, 2, 3
Loop Test 3, 5, 1
Lower Sensor Trim 3, 4, 1, 2
Message 2, 2, 5, 6
Module Temperature/Trend 3, 3, 3
Poll Address 1, 2, 2
Pressure Alert Configuration 2, 3, 1
Range Values 2, 2, 1, 3
Re-mapping 2, 2, 4, 1
Rerange - Keypad Input 1, 5
Rerange with Keypad 2, 2, 1, 3
Saturation Level Configuration 2, 2, 1, 7
Scaled D/A Trim (4–20 mA Output) 3, 4, 2
Scaled Variable Configuration 2, 2, 2
Sensor Information (Materials of Construction) 1, 7, 3
Sensor Trim 3, 4, 1
Sensor Trim Points 3, 4, 1, 4
Tag 2, 2, 5, 1
Temperature Alert Configuration 2, 3, 2
Transfer Function (Setting Output Type) 2, 2, 1, 4
Transmitter Security (Write Protect) 2, 2, 7, 1
Units (Process Variable) 2, 2, 1, 2
Upper Sensor Trim 3, 4, 1, 1
Zero Trim 3, 4, 1, 3
HART 5 with Diagnostics Fast Key sequence
The following menu indicates Fast Key sequences for common functions. A check () indicates the basic configuration parameters. At minimum, these parameters should be verified as part of the configuration and startup procedure.
25
Configuration Reference Manual
June 2021 00809-0100-4801
Function Fast Key sequence
Alarm and Saturation Levels 2, 2, 2, 5
Alarm Level Configuration 2, 1, 1, 1, 6
Analog Output Alarm Direction 2, 2, 2, 5, 5, 1
Burst Mode On/Off 2, 2, 5, 2, 1
Burst Option 2, 2, 5, 2, 2
Damping 2, 2, 1, 1, 3
Date 2, 2, 7, 1, 3
Descriptor 2, 2, 7, 1, 4
Digital to Analog Trim (4–20 mA Output) 3, 4, 1, 2, 3
Field Device Information 1, 3, 5
LCD Display Configuration 2, 2, 4
Loop Test 3, 5
Lower Sensor Trim 3, 4, 1, 1, 1, 2
Message 2, 2, 7, 1, 5
Module Temperature 2, 2, 1, 2
Poll Address 2, 2, 5, 3, 1
Pressure Alert Configuration 2, 3, 4, 1, 3
Range Values 3, 4, 1, 1, 2
Re-mapping 2, 2, 5, 1
Rerange - Keypad Input 2, 2, 2, 1
Rerange with Pressure Source 2, 2, 2, 2
Saturation Level Configuration 2, 1, 1, 1, 6
Scaled Variable Configuration 2, 2, 3, 5
Sensor Information 1, 3, 5, 4, 1
Sensor Trim Points 1, 3, 1, 1, 4
Tag 2, 2, 7, 1, 1
Temperature Alert Configuration 2, 3, 4, 2, 3
Transfer Function (Setting Output Type) 2, 2, 1, 1, 4
Transmitter Security (Write Protect) 1, 3, 5, 5, 6
Units (Process Variable) 2, 2, 1, 1, 2
Upper Sensor Trim 3, 4, 1, 1, 1, 1
Zero Trim 3, 4, 1, 1, 1, 3
26 Emerson.com/RosemountEmerson.com/Rosemount
Reference Manual Configuration
00809-0100-4801 June 2021
HART 7 Fast Key sequence
Function Fast Key sequence
Alarm and Saturation Levels 2, 2, 2, 5
Alarm Level Configuration 2, 2, 2, 5, 6
Analog Output Alarm Direction 2, 2, 2, 5, 1
Burst Mode Control 2, 2, 5, 3
Burst Option 2, 2, 5, 3, 1
Damping 2, 2, 1, 1, 3
Date 2, 2, 5, 4
Descriptor 2, 2, 7, 1, 4
Digital to Analog Trim (4–20 mA Output) 3, 4, 1, 2, 3, 1
Disable Zero & Span Adjustment 2, 2, 6, 4
Field Device Information 1, 7
LCD Display Configuration 2, 2, 4
Loop Test 3, 5, 1
Lower Sensor Trim 3, 4, 1, 2
Message 2, 2, 7, 1, 6
Module Temperature/Trend 3, 3, 2
Poll Address 2, 2, 5, 2, 1
Pressure Alert Configuration 2, 3, 4, 1
Range Values 2, 2, 2, 2
Re-mapping 2, 2, 5, 1
Rerange - Keypad Input 2, 2, 2, 2, 1
Rerange with Keypad 2, 2, 2, 3
Saturation Level Configuration 2, 2, 2, 5, 6
Scaled D/A Trim (4–20 mA Output) 3, 4, 1, 2, 3, 2
Scaled Variable Configuration 2, 2, 3, 7
Sensor Information (Materials of Construction) 1, 7, 3, 1
Sensor Trim 3, 4, 1, 1, 1
Sensor Trim Points 3, 4, 1, 1, 4
Tag 2, 2, 7, 1, 1
Temperature Alert Configuration 2, 3, 4, 2
Transfer Function (Setting Output Type) 2, 2, 3, 3
Transmitter Security (Write Protect) 1, 7, 4, 6, 1
Units (Process Variable) 2, 2, 1, 1, 2
27
Configuration Reference Manual
June 2021 00809-0100-4801
Function Fast Key sequence
Upper Sensor Trim 3, 4, 1, 1
Zero Trim 3, 4, 1, 3

2.5 Check output

Before performing other transmitter on-line operations, review the digital output parameters to ensure that the transmitter is operating properly and is configured to the appropriate process variables.

2.5.1 Process variables

The process variables for the Rosemount 3051S provide transmitter output, and are continuously updated. The pressure reading in both engineering units and percent of range will continue to track with pressures outside of the defined range from the lower to the upper range limit of the SuperModule™.
View Process Variables on the Field Communicator
Table 2-1: Field Communicator Fast Key Sequences
Device Dashboard Fast Keys 3, 2
HART 5 with Diagnostics Fast Keys 3, 2, 1
HART 7 Fast Keys 3, 2, 2
Enter the Fast Key sequence Process Variables to view the process variables.
Note
Regardless of the range points, the Rosemount 3051S will measure and report all readings within the digital limits of the sensor. For example, if the 4 and 20 mA points are set to 0 and 10 inH2O, and the transmitter detects a pressure of 25 inH2O, it digitally outputs the 25 inH2O reading and a 250 percent of span reading.
View Process Variables on the AMS Device Manager
Procedure
1. Right click on the device and select Overview from the menu.
2. Select All Variables to display the primary, secondary, tertiary, and quaternary
variables.
2.5.2
28 Emerson.com/RosemountEmerson.com/Rosemount

Module temperature

The Rosemount 3051S contains a temperature sensor near the pressure sensor in the SuperModule. When reading this temperature, keep in mind module temperature is not a process temperature reading.
Reference Manual Configuration
00809-0100-4801 June 2021
View the Module Temperature reading on the Field Communicator
Table 2-2: Field Communicator Fast Key Sequences
Device Dashboard Fast Keys 3, 2, 3
HART 5 with Diagnostics Fast Keys 3, 2, 1, 2
HART 7 Fast Keys 3, 2, 2, 2
Enter the Fast Key sequence Module Temperature to view the module temperature reading.
View the Module Temperature reading on the AMS Device Manager
Procedure
1. Right click on the device and select Overview from the menu.
2. Click All Variables.

2.6 Basic setup

2.6.1 Set Process Variable Units

The PV Unit command sets the process variable units to allow you to monitor your process using the appropriate units of measure.
Set Process Variable Units on the Field Communicator
Device Dashboard Fast Keys
HART 5 with Diagnostics Fast Keys 2, 2, 1, 1, 2
HART 7 Fast Keys 2, 2, 1, 1, 2
Enter the Fast Key sequence Set Process Variable Units. Select from the following engineering units:
inH2O
inHg mbar atm
ftH2O g/cm
mmH2O kg/cm
mmHg Pa mmH2O at 4 °C
bar torr
2
2, 2, 1, 2
MPa
2
inH2O at 4 °C
psi kPa
29
Configuration Reference Manual
June 2021 00809-0100-4801
Set Process Variable Units on the AMS Device Manager
Procedure
1. Right click on the device and select Configure from the menu.
2. Select Manual Setup from the left window pane.
3. Select the Process Variables tab.
4. Click the Unit drop down menu to select units.

2.6.2 Set output (transfer function)

The Rosemount 3051S has two output settings: linear and square root. Activate the square root output option to make analog output proportional to flow. As input approaches zero, the pressure transmitter automatically switches to linear output in order to ensure a more smooth, stable output near zero (see Figure 2-14 ).
From 0 to 0.6 percent of the ranged pressure input, the slope of the curve is unity (y = x). This allows accurate calibration near zero. Greater slopes would cause large changes in output (for small changes at input). From 0.6 to 0.8 percent , curve slope equals 42 (y = 42x) to achieve continuous transition from linear to square root at the transition point.
Note
If low flow cutoff configuration is desired, use Scaled variable configuration to configure square root and Re-mapping to map the scaled variable as the primary variable.
Note
If scaled variable is mapped as the primary variable and square root mode is selected, ensure that transfer function is set to linear. Do not set the transfer function to square root if square root mode is selected for the primary variable as this would cause the square root function to be performed twice.
Set Output on the Field Communicator
Device Dashboard Fast Keys
HART 5 with Diagnostics Fast Keys 2, 2, 1, 1, 4
HART 7 Fast Keys 2, 2, 1, 1, 4
Procedure
1. Enter the Fast Key sequence for Set Output (Transfer Function).
2. Select Send.
2, 2, 1, 4
Set the Output on the AMS Device Manager
Procedure
1. Right click on the device and select Configure from the menu.
2. Select Manual Setup from the left window pane.
3. Select the Process Variables tab.
30 Emerson.com/RosemountEmerson.com/Rosemount
Loading...
+ 130 hidden pages