Consider recycling equipment and packaging. Dispose of the product and packaging in
accordance with local and national legislation.
Rosemount 3051P5
IntroductionReference Manual
April 202000809-0700-4001
6Emerson.com/Rosemount
Reference ManualConfiguration
00809-0700-4001April 2020
2Configuration
2.1Safety messages
Procedures and instructions in this section may require special precautions to ensure the
safety of the personnel performing the operations.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with
the appropriate local, national, and international standards, codes, and practices.
Review the Product Certifications section of the Rosemount 3051P Product Data Sheet
for any restrictions associated with a safe installation.
Before connecting a handheld communicator in an explosive atmosphere, ensure that
the instruments in the loop are installed in accordance with intrinsically safe or nonincendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers
when power is applied to the unit.
WARNING
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads
can cause electrical shock.
WARNING
Process leaks could result in death or serious injury.
Install and tighten all four flange bolts before applying pressure.
Do not attempt to loosen or remove flange bolts while the transmitter is in service.
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare parts
could reduce the pressure retaining capabilities of the transmitter and may render the
instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts. Improper assembly of manifolds
to traditional flange can damage sensor module.
Rosemount 3051P7
ConfigurationReference Manual
April 202000809-0700-4001
WARNING
Improper assembly of manifolds to traditional flange can damage the device.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange
web (i.e., bolt hole) but must not contact sensor module housing.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or
misconfiguration of end users’ equipment. This could be intentional or unintentional and
needs to be protected against.
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access by unauthorized personnel to protect end
users’ assets. This is true for all systems used within the facility.
2.2System readiness
• If using HART® based control or asset management systems, confirm the HART
capability of such systems prior to commissioning and installation. Not all systems are
capable of communicating with HART Revision 7 devices.
• For instructions on how to change the HART revision of your transmitter, see Switching
HART® revision.
2.2.1
Table 2-1: Device Revisions and Files
Identify deviceFind device driver
Software
release
date
NAMUR
hardware
revision
Confirm correct device driver
Procedure
1. Verify the latest Device Driver (DD/DTM™) is loaded on your systems to ensure
proper communications.
2. Reference Emerson.com or FieldCommGroup.org for the latest DD.
3. Select desired product and download the DD.
a) Reference Table 2-1 for the correct DD.
files
®
HART
software
revision
(2)
HART
universal
revision
Device
revision
(1)
NAMUR
software
revision
(1)
Review instructionsReview
Manual document
(3)
number
functionality
Changes to software
August
2016
8Emerson.com/Rosemount
1.1.xx1.0.xx0371000809-0700-4001• HART Revision 5
and 7 selectable
Reference ManualConfiguration
00809-0700-4001April 2020
Table 2-1: Device Revisions and Files (continued)
Identify deviceFind device driver
files
59• Local operator
(1) NAMUR revision is located on the hardware tag of the device. Differences in level 3 changes, signified above by xx,
represent minor product changes as defined per NE53. Compatibility and functionality are preserved, and products can
be used interchangeably.
(2) HART software revision can be read using a HART capable configuration tool. Value shown is minimum revision that
could correspond to NAMUR revisions.
(3) Device driver file names use device and DD revision, e.g., 10_01. HART Protocol is designed to enable legacy device
driver revisions to continue to communicate with new HART devices. To access new functionality, the new device driver
must be downloaded. Emerson recommends downloading new device driver files to ensure full functionality.
Review instructionsReview
functionality
interface (LOI)
• Scaled variable
• Configurable
alarms
• Expanded
engineering units
• Updated
electronics
hardware design
• Intrinsic Safety
temperature
classification
change
Rosemount 3051P9
ConfigurationReference Manual
April 202000809-0700-4001
2.3HART® installation flowchart
10Emerson.com/Rosemount
Reference ManualConfiguration
00809-0700-4001April 2020
2.4Transmitter overview
The Rosemount 3051P In-Line Pressure Transmitter is offered for gage pressure (GP) and
absolute pressure (AP) measurements. The transmitter uses piezoresistive sensor
technology for AP and GP measurements.
The major components of the transmitter are the sensor module and the electronics
housing. The sensor module contains the oil-filled sensor system (isolating diaphragm, oil
fill system, and sensor). The electronics board is located within the electronics housing.
The electrical signals from the sensor module are transmitted to the electronics board
which contains the memory module and the analog to digital signal converter (A/D
converter). The signal is then converted to a 4–20mA analog output signal or HART
digital signal. The electronics housing contains the output electronics board, the optional
external configuration buttons, and the terminal block. The basic block diagram of the
transmitter is illustrated in Figure 2-2.
When pressure is applied to the isolating diaphragm, the oil deflects the sensor, which
then changes its capacitance or voltage signal. This signal is then changed to a digital
signal by the Signal Processing. The microprocessor then takes the signals from the Signal
Processing and calculates the correct output of the transmitter. This signal is then sent to
the D/A converter, which converts the signal back to the analog signal and then
superimposes the HART signal on the 4–20 mA output.
®
An optional LCD display can be ordered that connects directly to the interface board,
which maintains direct access to the signal terminals. The display indicates output and
abbreviated diagnostic messages. A glass display cover is provided. For 4-20 mA HART
output, the LCD display features a two-line display. The first line displays the actual
measured value; the second line of six characters displays the engineering units. The LCD
display can also display diagnostic messages.
Note
LCD display uses a 5x6 character display and can display output and diagnostic messages.
The local operator interface (LOI) display uses an 8x6 character display and can display
output and diagnostic messages as well as and LOI menu screens. The LOI display comes
with two buttons mounted on the front of the display board. See Figure 2-1.
Rosemount 3051P11
ConfigurationReference Manual
April 202000809-0700-4001
Figure 2-1: LCD/LOI display
LCD displayLOI display
12Emerson.com/Rosemount
Reference ManualConfiguration
00809-0700-4001April 2020
Figure 2-2: Block Diagram of Operation
A. Sensor module and electronics
B. 4-20 mA signal to control system
C. Field Communicator
D. Signal processing
E. Temperature sensor
F. Pressure sensor
G. Sensor module memory
H. Microprocessor
• Sensor linearization
• Rerange
• Damping
• Diagnostics
• Engineering units
• Communication
I. Memory
• Configuration
J. Digital-to-analog signal conversion
K. Digital communication
Rosemount 3051P13
ConfigurationReference Manual
April 202000809-0700-4001
2.5Configuration overview
This section contains information on commissioning and tasks that should be performed
on the bench prior to installation, as well as tasks performed after installation as described
in Performing transmitter tests.
Field Communicator, AMS Device Manager, and local operator interface (LOI) instructions
are given to perform configuration functions. For convenience, Field Communicator Fast
Key sequences are labeled “Fast Keys,” and abbreviated LOI menus are provided for each
function below.
Full Field Communicator menu trees and Fast Key sequences are available in Field
Communicator menu trees and Fast Keys. LOI menu trees are available in Local operator
interface (LOI).
2.6Configuration basics
CAUTION
2.6.1
Set all transmitter hardware adjustments during commissioning to avoid exposing the
transmitter electronics to the plant environment after installation.
You can configure the transmitter either before or after installation. Configuring the
transmitter on the bench using either a Field Communicator, AMS Device Manager, or LOI
ensures all transmitter components are in working order prior to installation. Verify that
the security switch is set in the unlock position ( ) to proceed with configuration. See
Figure 4-2 for switch location.
Configuring on the bench
To configure on the bench, you will need a power supply and a Field Communicator, AMS
Device Manager, or local operator interface (LOI), option M4.
Wire equipment as shown in Figure 2-3. To ensure successful HART® communication, a
resistance of at least 250 Ωs must be present between the transmitter and the power
supply; see Power supply for details. Connect the Field Communicator leads to the
terminals labeled “COMM” on the terminal block.
14Emerson.com/Rosemount
SAVE
1. Overview
2. Configure
3. Service Tools
3051 FT 45B
Online
Reference ManualConfiguration
00809-0700-4001April 2020
Figure 2-3: Wiring the Transmitter (4–20 mA HART)
A. Vdc supply
B. R L ≥ 250 (necessary for HART communication only)
2.6.2
Configuration tools
Configuring with a Field Communicator
There are two interfaces available with the Field Communicator: traditional and
dashboard.
This manual describes all steps using a Field Communicator using dashboard interfaces.
Figure 2-4 shows the Device Dashboard interface. As stated in System readiness, it is
critical that the latest device descriptors (DDs) are loaded into the Field Communicator.
Visit Emerson.com or FieldCommGroup.org to download the latest DD library.
Field Communicator menu trees and Fast Keys are available in Field Communicator menu
trees and Fast Keys.
Figure 2-4: Device Dashboard
Rosemount 3051P15
ConfigurationReference Manual
April 202000809-0700-4001
Configuring with AMS Device Manager
Full configuration capability with AMS Device Manager requires loading the most current
device descriptor (DD) for this device. Download the latest DD at Emerson.com or
FieldCommGroup.org.
Note
This manual describes all steps using AMS Device Manager version 11.5.
Configuring with a local operator interface (LOI)
To use the LOI, order the transmitter with option code M4. To activate the LOI push either
configuration button. Configuration buttons are located on the LCD display (must remove
housing cover to access), or underneath the top tag of the transmitter. See Table 2-2 for
configuration button functionality and Figure 2-5 for configuration button location.
When using the LOI for configuration, several features require multiple screens for a
successful configuration. Data entered will be saved on a screen-by-screen basis; the LOI
will indicate this by flashing SAVED on the LCD display each time.
LOI menu trees are available in Local operator interface (LOI).
Figure 2-5: LOI Configuration Buttons
A. Internal configuration buttons
B. External configuration buttons
16Emerson.com/Rosemount
Reference ManualConfiguration
00809-0700-4001April 2020
Table 2-2: LOI Button Operation
Button
LeftNoSCROLL
RightYesENTER
2.6.3Setting the loop to manual
Whenever sending or requesting data that would disrupt the loop or change the output of
the transmitter, set the process application loop to manual control.
The Field Communicator, AMS Device Manager, or local operator interface (LOI) will
prompt you to set the loop to manual when necessary. The prompt is only a reminder;
acknowledging this prompt does not set the loop to manual. You must set the loop to
manual control as a separate operation.
2.7Verifying configuration
Emerson recommends verifying various configuration parameters prior to installing them
into the process.
The various parameters are detailed out for each configuration tool. Depending on what
configuration tool(s) are available follow the steps listed relevant to each tool.
2.7.1
Verifying configuration with Field Communicator
Review configuration parameters listed in Table 2-3 prior to transmitter installation. A Full
list of configuration parameters that can be reviewed and configured using a Field
Communicator are located in Field Communicator menu trees and Fast Keys.
Fast Key sequences for the latest device descriptor (DD) are shown in Table 2-3. For Fast
Key sequences for legacy DDs, contact your local Emerson Representative.
Procedure
From the HOME screen, enter the Fast Key sequences listed
Table 2-3: Device Dashboard Fast Key Sequence
FunctionFast Key sequence
HART® 7HART 5
Alarm and saturation levels2, 2, 2, 52, 2, 2, 5
Rosemount 3051P17
ConfigurationReference Manual
April 202000809-0700-4001
Table 2-3: Device Dashboard Fast Key Sequence (continued)
FunctionFast Key sequence
HART® 7HART 5
Damping2, 2, 1, 1, 52, 2, 1, 1, 5
Primary variable2, 1, 1, 4, 12, 1, 1, 4, 1
Range values2, 1, 1, 42, 1, 1, 4
Tag2, 2, 7, 1, 12, 2, 7, 1, 1
Transfer function2, 2, 1, 1, 62, 2, 1, 1, 6
Units2, 2, 1, 1, 42, 2, 1, 1, 4
2.7.2Verifying configuration with AMS Device Manager
Procedure
1. Right click on the device and select Configuration Properties from the menu.
2. Navigate the tabs to review the transmitter configuration data.
2.7.3
Verifying configuration with local operator interface
(LOI)
Procedure
1. Press any configuration button to activate the LOI.
2. Select VIEW CONFIG to review the below parameters.
3. Use the configuration buttons to navigate through the menu.
Review the following pareameters prior to installation:
• Tag
• Units
• Transfer Function
• Alarm and Saturation Levels
• Primary Variable
• Range Values
• Damping
18Emerson.com/Rosemount
Reference ManualConfiguration
00809-0700-4001April 2020
2.7.4Verifying process variables configuration
This section describes how to verify that the correct process variables are selected.
Verifying process variables with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys3, 2, 1
Verifying process variables with AMS Device Manager
Procedure
1. Right click the device and select Overview from the menu.
2. Select the All Variables button to display the primary, secondary, tertiary, and
quaternary variables.
2.8Basic setup of the transmitter
This section provides the necessary steps for basic setup of a pressure transmitter.
When installing in DP level or DP flow applications, refer to Configuring scaled variable for
setup instructions.
2.8.1
Setting pressure units
The pressure unit command sets the unit of measure for the reported pressure.
Setting pressure units with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Setting pressure units with AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Select Manual Setup and select desired units from Pressure Units dropdown menu.
3. Select Send when complete.
2, 2, 1, 1, 4
Rosemount 3051P19
ConfigurationReference Manual
April 202000809-0700-4001
Setting pressure units with a local operator interface (LOI)
Procedure
1. Follow Figure 2-6 to select desired pressure and temperature units.
2. Use the SCROLL and ENTER buttons to select desired unit.
3. Save by selecting SAVE as indicated on the LCD display screen.
Example
Figure 2-6: Selecting Units with LOI
2.8.2Reranging the transmitter
The range values command sets each of the lower and upper range analog values to a
pressure. The lower range point represents 0 percent of range and the upper range point
represents 100 percent of range.
In practice, the transmitter range values may be changed as often as necessary to reflect
changing process requirements.
Select from one of the methods below to rerange the transmitter. Each method is unique;
examine all options closely before deciding which method works best for your process.
• Rerange by manually setting range points with a Field Communicator, AMS Device
Manager, or local operator interface (LOI).
• Rerange with a pressure input source and a Field Communicator, AMS Device Manager,
LOI, or local zero and span buttons.
Manually rerange the transmitter by entering range points
Entering range points with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 2, 1
20Emerson.com/Rosemount
Reference ManualConfiguration
00809-0700-4001April 2020
Entering range points with AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Select Manual Setup and select Analog Output.
3. Enter upper and lower range values in the Range Limits box and click Send.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
Entering range points with a local operator interface (LOI)
See Figure 2-7 to rerange the transmitter using the LOI.
Procedure
Enter values using SCROLL and ENTER buttons.
Figure 2-7: Rerange with LOI
Rerange the transmitter with applied pressure source
Reranging using an applied pressure source is a way of reranging the transmitter without
entering specific 4 and 20 mA points.
Rerange with an applied pressure source using a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Rerange with an applied pressure source using AMS Device Manager
Procedure
1. Right click the device; select Configure.
2. Select the Analog Output tab.
3. Select Range by Applying Pressure and follow the screen prompts range the
transmitter.
2, 2, 2, 2
Rosemount 3051P21
ConfigurationReference Manual
April 202000809-0700-4001
Rerange with an applied pressure source using local zero and span
buttons
If you order local zero and span buttons (option code D4), you can use them to rerange the
transmitter with an applied pressure. Refer to Figure 2-8 for analog zero and span button
location.
To rerange the transmitter using the span and zero buttons, perform the following
procedure:
Procedure
1. Loosen the screw holding the top tag of the transmitter housing. Rotate the label to
expose the zero and span buttons.
2. Confirm device has local zero and span buttons by verifying blue retainer under the
tag.
3. Apply transmitter pressure.
4. Rerange the transmitter.
a) To change the zero (4 mA) while maintaining the span: press and hold zero
button for at least two seconds then release.
b) To change the span (20 mA) while maintaining the zero point: press and hold
the span button for at least two seconds and then release.
Example
Note
4 mA and 20 mA points must maintain the minimum span defined in Specifications and
reference data.
Figure 2-8: Analog Zero and Span Buttons
A. Zero and span buttons
22Emerson.com/Rosemount
Reference ManualConfiguration
00809-0700-4001April 2020
Note
• If the transmitter security is on, you cannot make adjustments to the zero and span.
Refer to Configuring transmitter security for security information.
• The span is maintained when the 4 mA/1 V point is set. The span changes when the 20
mA/5 V point is set. If the lower range point is set to a value that causes the upper
range point to exceed the sensor limit, the upper range point is automatically set to the
sensor limit, and the span is adjusted accordingly.
• Regardless of the range points, the transmitter measures and reports all readings
within the digital limits of the sensor. For example, if the 4 and 20 mA points are set to
0 and 10 inH2O, and the transmitter detects a pressure of 25 inH2O, it digitally outputs
the 25 inH2O reading and a 250 percent of range reading.
2.8.3Damping
The damping command changes the response time of the transmitter; higher values can
smooth variations in output readings caused by rapid input changes.
Determine the appropriate damping setting based on the necessary response time, signal
stability, and other requirements of the loop dynamics within your system. The damping
command utilizes floating point configuration, allowing you to input any damping value
within 0.0–60.0 seconds.
Damping with a Field Communicator
Procedure
1. From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2. Enter desired damping value and select APPLY.
2, 2, 1, 1, 5
Damping with AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Select Manual Setup.
3. Within the Pressure Setup box, enter desired damping value and click Send.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
Damping with a local operator interface (LOI)
Procedure
Reference Figure 2-9 to enter damping values using an LOI.
Rosemount 3051P23
ConfigurationReference Manual
April 202000809-0700-4001
Figure 2-9: Damping with LOI
2.9Configuring the LCD display
The LCD display configuration command allows customization of the LCD display to suit
application requirements.
The LCD display will alternate between the selected items.
• Pressure Units
• % of Range
• Scaled Variable
• Sensor Temperature
• mA/Vdc Output
Use the following instructions to configure the LCD display to display configuration
information during the device startup. Select Review Parameters at start-up to enable or
disable this functionality.
See Table 2-2 for an image of the LCD display screen.
2.9.1
Configuring LCD display with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
24Emerson.com/Rosemount
2, 2, 4
Reference ManualConfiguration
00809-0700-4001April 2020
2.9.2Configuring LCD display with AMS Device Manager
Procedure
1. Right click on the device and select Configure.
2. Select Manual Setup; select the Display tab.
3. Select desired display options and click Send.
2.9.3Configuring LCD display with a local operator interface
(LOI)
Procedure
Refer to Figure 2-10 for LCD display configuration using an LOI.
Figure 2-10: Display with LOI
2.10Detailed transmitter setup
2.10.1Configuring alarm and saturation levels
In normal operation, the transmitter will drive the output in response to pressure from the
lower to upper saturation points. If the pressure goes outside the sensor limits, or if the
output would be beyond the saturation points, the output will be limited to the associated
saturation point.
The transmitter automatically and continuously performs self-diagnostic routines. If the
self-diagnostic routines detect a failure, the transmitter drives the output to configured
alarm and value based on the position of the alarm switch. See Set transmitter alarm.
Rosemount 3051P25
ConfigurationReference Manual
April 202000809-0700-4001
Table 2-4: Alarm and Saturation Values
Level4–20 mA saturation4–20 mA alarm
Low3.90 mA≤ 3.75 mA
High20.80 mA≥ 21.75 mA
Table 2-5: NAMUR-Compliant Alarm and Saturation Values
Level4–20 mA saturation4–20 mA alarm
Low3.80 mA≤ 3.60 mA
High20.50 mA≥22.50 mA
Table 2-6: Custom Alarm and Saturation Values
Level4–20 mA saturation4–20 mA alarm
Low3.50 mA– 3.90 mA3.40–3.80 mA
High20.10 mA –22.90 mA20.20 mA – 23.00 mA
You can configure failure mode alarm and saturation levels using a Field Communicator,
AMS Device Manager, or local operator interface (LOI). The following limitations exist for
custom levels:
• Low alarm level must be less than the low saturation level.
• High alarm level must be higher than the high saturation level.
• Alarm and saturation levels must be separated by at least 0.1 mA.
The configuration tool will provide an error message if the configuration rule is violated.
Note
Transmitters set to HART® multidrop mode send all saturation and alarm information
digitally; saturation and alarm conditions will not affect the analog output. See also
Establishing multidrop communication.
Configuring alarm and saturation levels using a Field
Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 2, 5
Configuring alarm and saturation levels with AMS Device
Manager
Procedure
1. Right click on the device and select Configure.
2. Select Configure Alarm and Saturation Levels.
26Emerson.com/Rosemount
Reference ManualConfiguration
00809-0700-4001April 2020
3. Follow screen prompts to configure alarm and saturation levels.
Configuring alarm and saturation levels using a local
operator interface (LOI)
Procedure
Refer to Figure 2-11 for instructions to configure alarm and saturation levels.
Figure 2-11: Configuring Alarm and Saturation with LOI
2.10.2Configuring scaled variable
With the scaled variable, you can create a relationship/conversion between the pressure
units and user-defined/custom units.
There are two use cases for scaled variable:
1. Allow custom units to be displayed on the transmitter's LCD/local operator interface
(LOI) display.
2. Allow custom units to drive the transmitters 4-20 mA output.
If the you want custom units to drive the 4–20 mA output, re-map the scaled variable as
the primary variable. Refer to Re-mapping device variables.
The scaled variable configuration defines the following items:
Scaled variable units
Scaled data options
Pressure value position 1
Scaled variable position 1
Pressure value position 2
Scaled variable position 2
Linear offset
Custom units to be displayed.
Defines the transfer function for the application.
Lower known value point with consideration of linear offset.
Custom unit equivalent to the lower known value point.
Upper known value point.
Custom unit equivalent to the upper known value point.
The value required to zero out pressures affecting the
desired pressure reading.
Rosemount 3051P27
ConfigurationReference Manual
April 202000809-0700-4001
Configuring a scaled variable using a Field Communicator
Procedure
1. From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys2, 1, 4, 7
2. Follow the screen prompts to configure scaled variable.
a) Select Linear under Select Scaled data options.
Configuring a scaled variable using AMS Device Manager
Procedure
1. Right click on the device and, select Configure.
2. Select the Scaled Variable tab and select the Scaled Variable button.
3. Follow screen prompts to configure scaled variable.
a) Select Linear under Select Scaled data options.
Configuring a scaled variable using a local operator interface
(LOI)
Procedure
Refer to Figure 2-12 for instructions to configure a scaled variable using an LOI.
Figure 2-12: Configuring Scaled Variable Using an LOI
28Emerson.com/Rosemount
Reference ManualConfiguration
00809-0700-4001April 2020
2.10.3Re-mapping device variables
The re-mapping function allows you to configure the transmitter primary, secondary,
tertiary, and quaternary variables (PV, 2V, 3V, and 4V) as desired.
You can re-map the PV with a Field Communicator, AMS Device Manager, or a local
operator interface (LOI). You can only re-map variables 2V, 3V, and 4V via Field
Communicator or AMS Device Manager.
Note
The variable assigned to the primary variable drives the 4–20 mA output. This value can be
selected as Pressure or Scaled Variable. The 2, 3, and 4 variables only apply if using HART
burst mode.
Re-map device variables using a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
®
Fast Keys
2, 1, 1, 3
Re-map device variables using AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Select Manual Setup and click on the HART tab.
3. Assign Primary, secondary, tertiary, and quaternary variables under Variable
Mapping.
4. Select Send.
5. Carefully read the warning and select Yes if it is safe to apply the changes.
Re-map device variables using local operator interface (LOI)
Procedure
Refer to Figure 2-13 for instructions on re-mapping the primary variable using an LOI.
Rosemount 3051P29
ConfigurationReference Manual
April 202000809-0700-4001
Figure 2-13: Re-mapping with LOI
2.11Performing transmitter tests
2.11.1Verifying alarm level
If the transmitter is repaired or replaced, verify the transmitter alarm level before
returning the transmitter to service.
This is useful in testing the reaction of the control system to a transmitter in an alarm
state. It ensures that the control system recognizes the alarm when activated. To verify the
transmitter alarm values, perform a loop test and set the transmitter output to the alarm
value (see Table 2-4, Table 2-5, and Table 2-6).
Note
Before returning transmitter to service, verify security switch is set to the correct position.
Refer to Verifying configuration.
2.11.2
Performing an analog loop test
The analog loop test command verifies the output of the transmitter, the integrity of the
loop, and the operations of any recorders or similar devices installed in the loop. Emerson
recommends testing the 4-20 mA points in addition to alarm levels when installing,
repairing, or replacing a transmitter.
The host system may provide a current measurement for the 4–20 mA HART® output. If it
does not, connect a reference meter to the transmitter by either connecting the meter to
30Emerson.com/Rosemount
Reference ManualConfiguration
00809-0700-4001April 2020
the test terminals on the terminal block, or shunting transmitter power through the meter
at some point in the loop.
Performing an analog loop test using a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys3, 5, 1
Performing an analog loop test using AMS Device Manager
Procedure
1. Right click on the device and hover the cursor over Diagnostics and Test in the
Methods dropdown menu. From the Diagnostics and Test dropdown menu, select
Loop Test.
2. Select Next after setting the control loop to manual.
3. Follow screen prompts to perform a loop test.
4. Select Finish to acknowledge the method is complete.
Performing an analog loop test using a local operator
interface (LOI)
To perform an analog loop test using the LOI, manually set the 4 mA, 20 mA, and custom
mA point.
Procedure
Reference Figure 2-14 for instructions on how to perform a transmitter loop test using an
LOI.
Figure 2-14: Performing an Analog Loop Test Using an LOI
Rosemount 3051P31
ConfigurationReference Manual
April 202000809-0700-4001
2.11.3Simulate device variables
You can temporarily set the pressure, sensor temperature, or scaled variable to a userdefined fixed value for testing purposes. Once the simulated variable method is left, the
process variable will be automatically returned to a live measurement.
You can only simulate device variables in HART® Revision 7 mode.
Simulate digital signal with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Simulate digital signal with AMS Device Manager
Procedure
1. Right click on the device and select Service Tools.
2. Select Simulate.
3. Under Device Variables select a digital value to simulate:
a. Pressure
b. Sensor temperature
c. Scaled variable
4. Follow the screen prompts to simulate selected digital value.
2.12Configuring burst mode
Burst mode is compatible with the analog signal. Because the HART® protocol features
simultaneous digital and analog data transmission, the analog value can drive other
equipment in the loop while the control system is receiving the digital information.
Burst mode applies only to the transmission of dynamic data (pressure and temperature in
engineering units, pressure in percent of range, scaled Vvariable, and/or analog output),
and does not affect the way other transmitter data is accessed. However, when activated,
burst mode can slow down communication of non-dynamic data to the host by 50
percent.
3, 5
Access to information other than dynamic transmitter data is obtained through the
normal poll/response method of HART communication. A Field Communicator, AMS
Device Manager, or the control system may request any of the information that is
normally available while the transmitter is in burst mode. Between each message sent by
the transmitter, a short pause allows the Field Communicator, AMS Device Manager, or a
control system to initiate a request.
Choosing burst mode options in HART 5
Message content options:
32Emerson.com/Rosemount
Reference ManualConfiguration
00809-0700-4001April 2020
• PV only
• Percent of Range
• PV, 2V, 3V, 4V
• Process Variables
• Device Status
Choosing burst mode options in HART 7
Message content options:
• PV only
• Percent of Range
• PV, 2V, 3V, 4V
• Process Variables and Status
• Process Variables
• Device Status
Choosing a HART 7 trigger mode
When in HART 7, you can select the following trigger modes:
• Continuous (same as HART 5 burst mode)
• Rising
• Falling
• Windowed
• On Change
Note
Consult your host system manufacturer for burst mode requirements.
2.12.1
Configuring burst mode using a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 5, 3
2.12.2Configuring burst mode using AMS Device Manager
Procedure
1. Right click on the device and select Configure.
2. Select the HART tab.
3. Enter the configuration in Burst Mode Configuration fields.
Rosemount 3051P33
ConfigurationReference Manual
April 202000809-0700-4001
2.13Establishing multidrop communication
Multidropping transmitters refers to the connection of several transmitters to a single
communications transmission line. Communication between the host and the
transmitters takes place digitally with the analog output of the transmitters deactivated.
Multidrop installation requires consideration of the update rate necessary from each
transmitter, the combination of transmitter models, and the length of the transmission
line. Use HART® modems and a host implementing HART protocol to communicate with
transmitters. Each transmitter is identified by a unique address and responds to the
commands defined in the HART protocol. Field Communicators and AMS Device Manager
can test, configure, and format a multidropped transmitter the same way as a transmitter
in a standard point-to-point installation.
Figure 2-15 shows a typical multidrop network. This figure is not intended as an
installation diagram.
Figure 2-15: Typical Multidrop Network (4–20 mA Only)
A. HART modem
B. Power supply
The Rosemount 3051P is set to address zero at the factory, which allows operation in the
standard point-to-point manner with a 4–20 mA output signal. To activate multidrop
communication, change the transmitter address to a number from 1 to 15 for HART
Revision 5, or 1 to 63 for HART Revision 7. This change deactivates the 4–20 mA analog
output, sending it to 4 mA . It also disables the failure mode alarm signal, which is
controlled by the upscale/downscale switch position. Failure signals in multidropped
transmitters are communicated through HART messages.
34Emerson.com/Rosemount
Reference ManualConfiguration
00809-0700-4001April 2020
2.13.1Changing a transmitter address
To activate multidrop communication, assign the transmitter poll address to a number
from 1 to 15 for HART® Revision 5, and 1 to 63 for HART Revision 7. Each transmitter in a
multidropped loop must have a unique poll address.
Changing transmitter address using a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Changing transmitter address using AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. In HART® Revision 5 mode:
a) Select Manual Setup and then select the HART tab.
2.13.2
b) In the Communication Settings box enter polling address in the Polling
Address box and then select Send.
3. In HART Revision 7 mode:
a) Select Manual Setup, select the HART tab, and select the Change Polling
Address button.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
Communicating with a multidropped transmitter
To communicate with a multidrop transmitter you must set up the Field Communicator or
AMS Device Manager for polling.
Communicating with a multidropped transmitter using a
Field Communicator
Procedure
1. Select Utility and Configure HART Application.
2. Select Polling Addresses.
3. Enter 0–63.
Rosemount 3051P35
ConfigurationReference Manual
April 202000809-0700-4001
Communicating with a multidropped transmitter using AMS
Device Manager
Procedure
Select the HART® modem icon and select Scan All Devices.
36Emerson.com/Rosemount
Reference ManualHardware installation
00809-0700-4001April 2020
3Hardware installation
3.1Overview
The information in this section covers installation considerations for the transmitter with
HART® protocol.
Emerson ships a Quick Start Guide with every transmitter to describe recommended pipefitting and wiring procedures for initial installation. Dimensional drawings for each
transmitter variation and mounting configuration are included in Mounting brackets.
Note
For transmitter disassembly and reassembly refer to Disassembly procedures, and
Reassembly procedures.
3.2Safety messages
Procedures and instructions in this section may require special precautions to ensure the
safety of the personnel performing the operations.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with
the appropriate local, national, and international standards, codes, and practices.
Review the Product Certifications section of the Rosemount 3051P Product Data Sheet
for any restrictions associated with a safe installation.
Before connecting a handheld communicator in an explosive atmosphere, ensure that
the instruments in the loop are installed in accordance with intrinsically safe or nonincendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers
when power is applied to the unit.
WARNING
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads
can cause electrical shock.
WARNING
Process leaks could result in death or serious injury.
Install and tighten all four flange bolts before applying pressure.
Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Rosemount 3051P37
Hardware installationReference Manual
April 202000809-0700-4001
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare parts
could reduce the pressure retaining capabilities of the transmitter and may render the
instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts. Improper assembly of manifolds
to traditional flange can damage sensor module.
WARNING
Improper assembly of manifolds to traditional flange can damage the device.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange
web (i.e., bolt hole) but must not contact sensor module housing.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or
misconfiguration of end users’ equipment. This could be intentional or unintentional and
needs to be protected against.
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access by unauthorized personnel to protect end
users’ assets. This is true for all systems used within the facility.
3.3Considerations
3.3.1Installation considerations
Measurement accuracy depends upon proper installation of the transmitter and impulse
piping. Mount the transmitter close to the process and use a minimum of piping to
achieve best accuracy.
Keep in mind the need for easy access, personnel safety, practical field calibration, and a
suitable transmitter environment. Install the transmitter to minimize vibration, shock, and
temperature fluctuation.
WARNING
Install the enclosed pipe plug (found in the box) in an unused housing conduit opening
with a minimum of five threads of engagement to comply with explosion-proof
requirements.
Always ensure a proper seal by installing the electronics housing cover(s) so that metal
contacts metal.
Use Rosemount O-rings.
38Emerson.com/Rosemount
Reference ManualHardware installation
00809-0700-4001April 2020
3.3.2Environmental considerations
Best practice is to mount the transmitter in an environment that has minimal ambient
temperature change. The transmitter electronics temperature operating limits are –40 to
185 °F (–40 to 85 °C).
Refer to the Rosemount 3051P Product Data Sheet for the sensing element operating
limits. Mount the transmitter so that it is not susceptible to vibration and mechanical
shock and does not have external contact with corrosive materials.
3.3.3Mechanical considerations
Steam service
For steam service or for applications with process temperatures greater than the limits of
the transmitter, do not blow down impulse piping through the transmitter. Flush lines
with the blocking valves closed and refill lines with water before resuming measurement.
Refer to Figure 3-3 through Figure 3-5 for correct mounting orientation.
3.4Installation procedures
3.4.1Mount the transmitter
The approximate weight of the transmitter is 2.44 lb. (1.11 kg).
In many cases its compact size and light weight makes it possible to mount directly to the
respective apparatus without using an additional mounting bracket. When this is not
desirable, mount directly to a wall, panel, or 2-in. (50.8 mm) pipe using the optional
mounting bracket (see Mounting brackets).
For dimensional drawing information refer to the Rosemount 3051P Product Data Sheet.
Note
Most transmitters are calibrated in the upright position. Mounting the transmitter in any
other position will shift the zero point to the equivalent amount of liquid head pressure
caused by the varied mounting position. To reset zero point, refer to Sensor trim overview.
Electronics housing clearance
Mount the transmitter so the terminal side is accessible. Clearance of 0.75 in. (19 mm) is
required for cover removal.
Use a conduit plug in the unused conduit opening. 3 in. (76.2 mm) of clearance is required
for cover removal if a meter is installed.
Environmental seal for housing
Thread sealing (PTFE) tape or paste on male threads of conduit is required to provide a
water/dust tight conduit seal and meets requirements of NEMA® Type 4X, IP66, and IP68.
Consult factory if other Ingress Protection ratings are required.
Rosemount 3051P39
Hardware installationReference Manual
April 202000809-0700-4001
For M20 threads, install conduit plugs to full thread engagement or until mechanical
resistance is met.
40Emerson.com/Rosemount
Reference ManualHardware installation
00809-0700-4001April 2020
Mounting brackets
You can panel mount or pipe mount the transmitter via an optional mounting bracket
(option code B4).
See Figure 3-1 and for dimensional and mounting configuration information.
Figure 3-1: Mounting Bracket Option Code B4
Dimensions are in inches (millimeters).
Pipe mountingPanel mounting
A. 2-in. (50.8 mm) U-bolt for pipe mounting (clamp shown)
B. ¼ x 1¼ bolts for transmitter mounting (not supplied)
C. ¼ x 1¼ bolts for transmitter mounting (not supplied)
D. 5/16 x 1½ bolts for panel mounting (not supplied)
Rosemount 3051P41
Hardware installationReference Manual
April 202000809-0700-4001
Figure 3-2: Head Markings
3.4.2
A. Carbon steel (CS) head markings
B. The last digit in the F593_ head marking may be any letter between A and M.
C. Stainless steel (SST) head markings
D. Alloy K-500 head marking
Impulse piping
Mounting requirements
Impulse piping configurations depend on specific measurement conditions.
Refer to Figure 3-3 through Figure 3-5 for examples of the following mounting
configurations:
Liquid measurement
• Place taps to the side of the line to prevent sediment deposits on the transmitter’s
process isolator.
• Mount the transmitter beside or below the taps so gases can vent into the process line.
• Mount drain/vent valve upward to allow gases to vent.
42Emerson.com/Rosemount
Reference ManualHardware installation
00809-0700-4001April 2020
Figure 3-3: Liquid Applications Installation Example
Gas measurement
• Place tap in the top or side of the line.
• Mount the transmitter beside or above the tap so liquid will drain into the process line.
Rosemount 3051P43
Hardware installationReference Manual
April 202000809-0700-4001
Figure 3-4: Gas Applications Installation Example
Steam measurement
• Place tap to the side of the line.
• Mount the transmitter below the taps to ensure the impulse piping will stay filled with
condensate.
• In steam service above 250 °F (121 °C), fill impulse line with water to prevent steam
from contacting the transmitter directly and to ensure accurate measurement start-up.
44Emerson.com/Rosemount
Reference ManualHardware installation
00809-0700-4001April 2020
Figure 3-5: Steam Applications Installation Example
CAUTION
For steam or other elevated temperature services, it is important that temperatures at the
process connection do not exceed the transmitter’s process temperature limits.
Best practices
The piping between the process and the transmitter must accurately transfer the pressure
to obtain accurate measurements.
There are six possible sources of error:
1. Pressure transfer
2. Leaks
3. Friction loss (particularly if purging is used)
4. Trapped gas in a liquid line
5. Liquid in a gas line
6. Density variations between the legs
The best location for the transmitter in relation to the process pipe is dependent on the
process. Use the following guidelines to determine transmitter location and placement of
impulse piping:
Rosemount 3051P45
Hardware installationReference Manual
April 202000809-0700-4001
• Keep impulse piping as short as possible.
• For liquid service, slope the impulse piping at least 1 in./ft (8 cm/m) upward from the
transmitter toward the process connection.
• For gas service, slope the impulse piping at least 1 in./ft (8 cm/m) downward from the
transmitter toward the process connection.
• Avoid high points in liquid lines and low points in gas lines.
• Use impulse piping large enough to avoid friction effects and blockage.
• Vent all gas from liquid piping legs.
• When purging, make the purge connection close to the process taps and purge
through equal lengths of the same size pipe. Avoid purging through the transmitter.
• Keep corrosive or hot (above 250 °F [121 °C]) process material out of direct contact
with the sensor module and flanges.
• Prevent sediment deposits in the impulse piping.
• Avoid conditions that might allow process fluid to freeze within the process flange.
3.4.3
In-line process connection
In-line gage transmitter orientation
CAUTION
Interfering or blocking the atmospheric reference port will cause the transmitter to output
erroneous pressure values.
The low side pressure port on the inline gage transmitter is located in the neck of the
transmitter, behind the housing. The vent path is 360 degrees around the transmitter
between the housing and sensor (See Figure 3-6).
Keep the vent path free of any obstruction, such as paint, dust, and lubrication by
mounting the transmitter so the process can drain away.
46Emerson.com/Rosemount
Reference ManualHardware installation
00809-0700-4001April 2020
Figure 3-6: In-Line Gage Low Side Pressure Port
A. Low side pressure port (atmospheric reference)
CAUTION
Rotation between the sensor module and the process connection can damage the
electronics.
Do not apply torque directly to the sensor module.
To avoid damage, apply torque only to the hex-shaped process connection.
Rosemount 3051P47
Hardware installationReference Manual
April 202000809-0700-4001
3.5Rosemount 306 Manifold
The Rosemount 306 Integral Manifold is used with the Rosemount 3051P In-Line
Transmitter to provide block-and-bleed valve capabilities of up to 10,000 psi (690 bar).
Figure 3-7: Rosemount 3051P and 306 In-line Manifold
3.5.1Rosemount 306 Integral Manifold installation procedure
Assemble the Rosemount 306 Manifold to the Rosemount 3051P In-Line Transmitter with
a thread sealant.
48Emerson.com/Rosemount
Reference ManualElectrical installation
00809-0700-4001April 2020
4Electrical installation
4.1Overview
The information in this section covers installation considerations for the Rosemount
3051P.
Emerson ships a Quick Start Guide with every transmitter to describe pipe-fitting, wiring
procedures, and basic configuration for initial installation.
Note
For transmitter disassembly and reassembly refer to sections Disassembly procedures, and
Reassembly procedures.
4.2Safety messages
Procedures and instructions in this section may require special precautions to ensure the
safety of the personnel performing the operations.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with
the appropriate local, national, and international standards, codes, and practices.
Review the Product Certifications section of the Rosemount 3051P Product Data Sheet
for any restrictions associated with a safe installation.
Before connecting a handheld communicator in an explosive atmosphere, ensure that
the instruments in the loop are installed in accordance with intrinsically safe or nonincendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers
when power is applied to the unit.
WARNING
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads
can cause electrical shock.
WARNING
Process leaks could result in death or serious injury.
Install and tighten all four flange bolts before applying pressure.
Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Rosemount 3051P49
Electrical installationReference Manual
April 202000809-0700-4001
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare parts
could reduce the pressure retaining capabilities of the transmitter and may render the
instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts. Improper assembly of manifolds
to traditional flange can damage sensor module.
WARNING
Improper assembly of manifolds to traditional flange can damage the device.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange
web (i.e., bolt hole) but must not contact sensor module housing.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or
misconfiguration of end users’ equipment. This could be intentional or unintentional and
needs to be protected against.
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access by unauthorized personnel to protect end
users’ assets. This is true for all systems used within the facility.
4.3Local Operating Interface (LOI)/LCD display
Emerson ships transmitters ordered with the LCD display option (M5) or LOI option (M4)
with the display installed.
Installing the display on an existing transmitter requires a small instrument screwdriver.
Carefully align the desired display connector with the electronics board connector. If
connectors don't align, the display and electronics board are not compatible.
50Emerson.com/Rosemount
Reference ManualElectrical installation
00809-0700-4001April 2020
Figure 4-1: LOI Display Assembly
4.3.1
A. LCD/LOI display
B. Extended cover
C. Captive screws
Rotate LCD/local operator interface (LOI) display
Procedure
1. Secure the loop to manual control and remove power to transmitter.
2. Remove transmitter housing cover.
3. Remove screws form the LCD/LOI display and rotate to desired orientation.
a) Insert 10-pin connector into the display board for the correct orientation.
Carefully align pins for insertion into the output board.
4. Re-insert screws.
5. Reattach transmitter housing cover.
WARNING
Explosions
Cover must be fully engaged to comply with explosion proof requirements.
6. Reattach power and return loop to automatic control.
Rosemount 3051P51
Electrical installationReference Manual
April 202000809-0700-4001
4.4Configuring transmitter security
The transmitter has four security methods.
• Security switch
• HART® Lock
• Configuration buttons lock
• Local operator interface (LOI) password
Figure 4-2: 4–20 mA Electronics Board
Without LCD display meterWith LCD display /LOI display
4.4.1
A. Alarm
B. Security
Set security switch
The security switch is used to prevent changes to the transmitter configuration data. If the
security switch is set to the locked location ( ), any transmitter configuration requests
sent via HART®, local operator interface (LOI), or local configuration buttons will be
rejected by the transmitter, and the transmitter configuration data will not be modified.
See Figure 4-2 for the location of the security switch. Follow the steps below to enable the
security switch.
Procedure
1. Set loop to manual and remove power.
2. Remove transmitter housing cover.
3. Use a small screwdriver to slide the switch to the lock (
4. Replace transmitter housing cover.
) position.
52Emerson.com/Rosemount
Reference ManualElectrical installation
00809-0700-4001April 2020
WARNING
Cover must be fully engaged to comply with explosion proof requirements.
4.4.2HART® Lock
The HART Lock prevents changes to the transmitter configuration from all sources; all
changes requested via HART, local operator interface (LOI), and local configuration
buttons will be rejected.
You can only set the HART Lock via HART communication, and it is only available in HART
Revision 7 mode. Enable or disable the HART lock with a Field Communicator or AMS
Device Manager.
Configure HART® Lock using Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
4.4.3
Device Dashboard Fast Keys
2, 2, 6, 4
Configure HART® Lock using AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Under Manual Setup, select the Security tab.
3. Select Lock/Unlock button under HART Lock (Software) and follow the screen
prompts.
Configuration button lock
The configuration button lock disables all local button functionality. Changes to the
transmitter configuration from the local operator interface (LOI) and local buttons will be
rejected.
You can only lock local external keys via HART® communication.
Configure button lock using the Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Rosemount 3051P53
2, 2, 6, 3
Electrical installationReference Manual
April 202000809-0700-4001
Configure button lock using AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Under Manual Setup select the Security tab.
3. Fron the Configuration Buttons dropdown menu, select Disabled to lock external
local keys.
4. Select Send.
5. Confirm service reason and click Yes.
4.4.4Local operator interface (LOI) password
You can enter and enable an LOI password to prevent review and modification of device
configuration via the LOI.
This does not prevent configuration from HART® or external keys (analog zero and span;
digital zero trim). The LOI password is a four digit code that is to be set by the user. If the
password is lost or forgotten the master password is 9307.
You can figure and enable or disable the LOI password with HART® communication via a
Field Communicator, AMS Device Manager, or the LOI.
Configure local operator interface (LOI) password with Field
Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 6, 5, 2
Configure local operator interface (LOI) password with AMS
Device Manager
Procedure
1. Right click the device and select Configure.
2. Under Manual Setup select the Security tab.
3. Within the LOI, select the Configure Password button and follow the screen
prompts.
54Emerson.com/Rosemount
Reference ManualElectrical installation
00809-0700-4001April 2020
Configure local operator interface (LOI) password using LOI
Figure 4-3: LOI Password
4.5Set transmitter alarm
On the electronics board is an alarm switch; see Figure 4-2 for switch location. Follow the
steps below to change the alarm switch location.
Procedure
1. Set loop to manual and remove power.
2. Remove transmitter housing cover.
3. Use a small screwdriver to slide switch to desired position.
4. Replace transmitter cover.
WARNING
Cover must be fully engaged to comply with explosion proof requirements.
4.6Electrical considerations
WARNING
Make sure all electrical installation is in accordance with national and local code
requirements.
Do not run signal wiring in conduit or open trays with power wiring or near heavy
electrical equipment.
Rosemount 3051P55
Electrical installationReference Manual
April 202000809-0700-4001
4.6.1Conduit installation
CAUTION
If all connections are not sealed, excess moisture accumulation can damage the
transmitter.
Make sure to mount the transmitter with the electrical housing positioned downward
for drainage.
To avoid moisture accumulation in the housing, install wiring with a drip loop, and
ensure the bottom of the drip loop is mounted lower than the conduit connections of
the transmitter housing.
Transmitter operates on 10.5–42.4 Vdc at the terminal of the transmitter. The dc power
supply should provide power with less than two percent ripple. A minimum of 16.6 V is
required for loops with a 250 Ω resistance.
Note
A minimum loop resistance of 250 Ω is required to communicate with a Field
Communicator. If a single power supply is used to power more than one transmitter, the
power supply used, and circuitry common to the transmitters, should not have more that
20 Ω of impedance at 1200 Hz.
56Emerson.com/Rosemount
Reference ManualElectrical installation
00809-0700-4001April 2020
Figure 4-5: Load Limitation
4.6.3
Maximum loop resistance = 43.5 x (Power supply voltage – 10.5)
The total resistance load is the sum of the resistance of the signal leads and the load
resistance of the controller, indicator,intrinsically safe (I.S.) barriers, and related pieces. If
intrinsic safety barriers are used, the resistance and voltage drop must be included.
Wiring the transmitter
CAUTION
Incorrect wiring can damage test circuits.
Do not connect the power signal wiring to the test terminals.
Note
Use shielded twisted pairs to yield best results. To ensure proper communication, use 24
AWG or larger wire and do not exceed 5,000 ft. (1500 m).
Rosemount 3051P57
Electrical installationReference Manual
April 202000809-0700-4001
Figure 4-6: 4–20 mA HART
A. DC power supply
B. R L ≥ 250 (necessary for HART communication only)
Perform the following procedure to make wiring connections:
Procedure
1. Remove the housing cover on terminal compartment side.
®
WARNING
Signal wiring supplies all power to the transmitter. Do not remove the cover in
explosive atmospheres when the circuit is live.
2. For 4–20 mA HART output, connect the positive lead to the terminal marked (pwr/
comm+) and the negative lead to the terminal marked (pwr/comm–).
CAUTION
Power could damage the test diode.
Do not connect the powered signal wiring to the test terminals.
3. Ensure full contact with terminal block screw and washer. When using a direct
wiring method, wrap wire clockwise to ensure it is in place when tightening the
terminal block screw.
CAUTION
The connection may be susceptible fo loosening over time or under vibration.
Emerson does not recommend using a pin or ferrule wire.
58Emerson.com/Rosemount
Reference ManualElectrical installation
00809-0700-4001April 2020
4. Plug and seal unused conduit connection on the transmitter housing to avoid
moisture accumulation in the terminal side.
4.6.4Grounding the transmitter
Ground signal cable shield
Figure 4-7 summarizes signal cable shield grounding. Trim and insulate the signal cable
shield and unused shield drain wire to ensure that the signal cable shield and drain wire do
not come in contact with the transmitter.
See Transmitter case grounding for instructions on grounding the transmitter case. Follow
the steps below to correctly ground the signal cable shield.
Procedure
1. Remove the field terminals housing cover.
2. Connect the signal wire pair at the field terminals as indicated in Figure 4-6.
3. At the field terminals, trim the cable shield and shield drain wire close and insulate
them from transmitter housing.
4. Reattach the field terminals housing cover.
WARNING
Cover must be fully engaged to comply with explosion proof requirements.
5. At terminations outside the transmitter housing, ensure that the cable shield drain
wire is continuously connected.
a) Prior to the termination point, insulate any exposed shield drain wire as
shown in Figure 4-7 (B).
6. Properly terminate the signal cable shield drain wire to an earth ground at or near
the power supply.
Rosemount 3051P59
DP
A
B
C
Electrical installationReference Manual
April 202000809-0700-4001
Figure 4-7: Wiring Pair and Ground
A. Insulate shield and shield drain wire.
B. Insulate exposed shield drain wire.
C. Terminate cable shield drain wire to earth ground.
Transmitter case grounding
The most effective transmitter case grounding method is a direct connection to earth
ground with minimal impedance.
WARNING
Always ground the transmitter case in accordance with national and local electrical codes.
Methods for grounding the transmitter case include:
• Internal ground connection: the internal ground connection screw is inside the FIELD
TERMINALS side of the electronics housing. This screw is identified by a ground symbol
( ). The ground connection screw is standard on all Rosemount 3051P Transmitters.
Refer to Figure 4-8.
60Emerson.com/Rosemount
Reference ManualElectrical installation
00809-0700-4001April 2020
Figure 4-8: Internal Ground Connection
A. Internal ground location
B. External ground location
C. Positive
D. Negative
E. Test
• External ground connection: The external ground connection is located on the exterior
of the transmitter housing. Refer to Figure 4-8. This connection is only available with
option T1.
WARNING
Grounding the transmitter case via threaded conduit connection may not provide
sufficient ground continuity.
Transient protection terminal block grounding
The transmitter can withstand electrical transients of the energy level usually encountered
in static discharges or induced switching transients. However, high-energy transients,
such as those induced in wiring from nearby lightning strikes, can damage the transmitter.
You can order the transient protection terminal block as an installed option (option code
T1) or as a spare part to retrofit existing Rosemount 3051P Transmitters in the field. See
the Rosemount 3051P Product Data Sheet for part numbers. The lightning bolt symbol
shown in Figure 4-9 identifies the transient protection terminal block.
Rosemount 3051P61
Electrical installationReference Manual
April 202000809-0700-4001
Figure 4-9: Transient Protection Terminal Block
A. Lightning bolt location
Note
The transient protection terminal block does not provide transient protection unless the
transmitter case is properly grounded. Use the guidelines to ground the transmitter case.
Refer to Figure 4-8.
62Emerson.com/Rosemount
Reference ManualOperation and maintenance
00809-0700-4001April 2020
5Operation and maintenance
5.1Overview
This section contains information on calibrating Rosemount 3051P Pressure Transmitters.
This section gives instructions on using the Field Communicator, AMS Device Manager and
Local Operator Interface (LOI) to calibrate the transmitter.
5.2Safety messages
Procedures and instructions in this section may require special precautions to ensure the
safety of the personnel performing the operations.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with
the appropriate local, national, and international standards, codes, and practices.
Review the Product Certifications section of the Rosemount 3051P Product Data Sheet
for any restrictions associated with a safe installation.
Before connecting a handheld communicator in an explosive atmosphere, ensure that
the instruments in the loop are installed in accordance with intrinsically safe or nonincendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers
when power is applied to the unit.
WARNING
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads
can cause electrical shock.
WARNING
Process leaks could result in death or serious injury.
Install and tighten all four flange bolts before applying pressure.
Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Rosemount 3051P63
Operation and maintenanceReference Manual
April 202000809-0700-4001
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare parts
could reduce the pressure retaining capabilities of the transmitter and may render the
instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts. Improper assembly of manifolds
to traditional flange can damage sensor module.
WARNING
Improper assembly of manifolds to traditional flange can damage the device.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange
web (i.e., bolt hole) but must not contact sensor module housing.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or
misconfiguration of end users’ equipment. This could be intentional or unintentional and
needs to be protected against.
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access by unauthorized personnel to protect end
users’ assets. This is true for all systems used within the facility.
5.3Recommended calibration tasks
CAUTION
Emerson calibrates absolute pressure transmitters at the factory.
Trimming adjusts the position of the factory calibration curve. If you trim the transmitter
improperly or with inaccurate equipment, you may degrade the transmitter's
performance.
5.3.1Calibrate in the field
Procedure
1. Perform sensor zero/lower trim: Compensate for mounting pressure effects
Refer to Rosemount 306 Manifold for manifold operation instructions to properly
drain/vent valves.
2. Set/check basic configuration parameters
a. Output units
64Emerson.com/Rosemount
Reference ManualOperation and maintenance
00809-0700-4001April 2020
b. Range points
c. Output type
d. Damping value
5.3.2Calibrate on the bench
Procedure
1. Perform optional 4–20 mA output trim.
2. Perform a sensor trim.
a) Zero/lower trim using line pressure effect correction.
Reference Hardware installation for manifold drain/vent valve operation
instructions.
b) Perform an optional full scale trim, which sets the span of the device and
requires accurate calibration equipment.
c) Set/check basic configuration parameters.
5.4Calibration overview
Emerson fully calibrates the Rosemount 3051P at the factory to ensure accuracy. You can
also calibrate the transmitter in the field to meet plant requirements or industry
standards. Complete calibration of the transmitter can be split into two halves: sensor
calibration and analog output calibration.
With sensor calibration, you can adjust the pressure (digital value) reported by the
transmitter to be equal to a pressure standard. The sensor calibration can adjust the
pressure offset to correct for mounting conditions or line pressure effects. Emerson
recommends making this correction. The calibration of the pressure range (pressure span
or gain correction) requires accurate pressure standards (sources) to provide a full
calibration.
Like the sensor calibration, you can calibrate the analog output to match the user
measurement system. The analog output trim (4–20 mA) will calibrate the loop at the 4 m
and 20 mA points.
The sensor calibration and the analog output calibration combine to match the
transmitter’s measurement system to the plant standard.
Calibrate the sensor
• Performing a sensor trim
• Perform a digital zero trim (option DZ)
Calibrate the 4–20 mA output
• Performing digital-to-analog trim (4–20mA output trim)
• Performing digital-to-analog trim (4–20mA output trim) using other scale
Rosemount 3051P65
Operation and maintenanceReference Manual
April 202000809-0700-4001
5.4.1Determine necessary sensor trims
Bench calibrations allow for calibrating the instrument for its desired range of operation.
Straight forward connections to pressure source allow for a full calibration at the planned
operating points. Exercising the transmitter over the desired pressure range allows for
verification of the analog output.
Trimming the pressure signal outlines how the trim operations change the calibration. It is
possible to degrade the performance of the transmitter if a trim is done improperly or with
inaccurate equipment. To set the transmitter back to factory settings, see Recall factory
trim—sensor trim. Determine the necessary trims with the following steps.
Procedure
1. Apply pressure.
2. Check digital pressure; if the digital pressure does not match the applied pressure,
perform a digital trim.
See Performing a sensor trim .
3. Check reported analog output against the live analog output. If they do not match,
perform an analog output trim.
See Performing digital-to-analog trim (4–20mA output trim).
Trim with configuration buttons
Local configuration buttons are external buttons located underneath the top tag of the
transmitter. There are two possible sets of local configuration buttons you can order with
the transmitter and use to perform trim operations: Digital zero trim and LOI.
Procedure
To access the buttons, loosen screw and rotate top tag until buttons are visible.
• LOI (M4): Can perform both digital sensor trim and the 4–20 mA output trim (analog
output trim). Follow the same procedures listed in trimming with Field Communicator
or AMS Device Manager listed below.
• Analog zero and span (D4): Used to rerange the transmitter with an applied pressure.
• Digital zero trim (DZ): Used for performing a sensor zero trim. See Determine
calibration frequency for trim instructions.
Monitor all configuration changes either on the display or by measuring the loop output..
Figure 5-1 shows the physical differences between the two sets of buttons.
66Emerson.com/Rosemount
Reference ManualOperation and maintenance
00809-0700-4001April 2020
Figure 5-1: Local Configuration Button Options
A. Analog zero and span (D4)- green retainer
B. Digital zero trim (DZ)- blue retainer
5.4.2
Determine calibration frequency
Calibration frequency can vary greatly depending on the application, performance
requirements, and process conditions. Use the following procedure to determine
calibration frequency that meets the needs of your application.
Procedure
1. Determine the performance required for your application.
Example
Required Performance:
2. Determine the operating conditions.
Example
Transmitter
Calibrated span30 psi (2.1 bar)
Ambient temperature
change
3. Calculate the total probable error (TPE).
Example
Rosemount 3051P, Range 1 [URL = 30 psi (2.1 bar)]
±50 °F (28 °C)
0.50 percent of span
TPE
Where:
Reference accuracy
Ambient temperature
effect
Static pressure effect0 percent (does not apply to in-line products)
Rosemount 3051P67
± 0.040 percent of span
±(0.05 percent URL + 0.25 percent of span) per 50 °F
(28 °C) = ±0.3 percent of span
= 0.303 percent of span
Operation and maintenanceReference Manual
April 202000809-0700-4001
4. Calculate the stability per month.
Example
Stability
5. Calculate the calibration frequency.
Example
Calibration frequency
5.5Trimming the pressure signal
5.5.1Sensor trim overview
A sensor trim corrects the pressure offset and pressure range to match a pressure
standard. The upper sensor trim corrects the pressure range, and the lower sensor trim
(zero trim) corrects the pressure offset. An accurate pressure standard is required for full
calibration. You can perform a zero trim if the process is vented.
Zero trim is a single-point offset adjustment. It is useful for compensating for mounting
position effects and is most effective when performed with the transmitter installed in its
final mounting position. Since this correction maintains the slope of the characterization
curve, do not use it in place of a sensor trim over the full sensor range.
Note
Do not perform a zero trim on Rosemount 3051P Absolute Pressure Transmitters. Zero
trim is zero based, and absolute pressure transmitters reference absolute zero. To correct
mounting position effects on an absolute pressure transmitter, perform a low trim within
the sensor trim function. The low trim function provides an offset correction similar to the
zero trim function, but it does not require zero-based input.
Upper and lower sensor trim is a two-point sensor calibration where two end-point
pressures are applied and all output is linearized between them; this trim requires an
accurate pressure source. Always adjust the low trim value first to establish the correct
offset. Adjustment of the high trim value provides a slope correction to the
characterization curve based on the low trim value. The trim values help optimize
performance over a specific measurement range.
68Emerson.com/Rosemount
Reference ManualOperation and maintenance
00809-0700-4001April 2020
Figure 5-2: Sensor Trim Example
A. Before trim
B. After trim
5.5.2
Performing a sensor trim
When performing a sensor trim, you can trim both the upper and lower limits. If doing
both upper and lower trims, perform the lower trim before the upper time.
Note
Use a pressure input source that is at least four times more accurate than the transmitter
and allow the input pressure to stabilize for 10 seconds before entering any values.
Perform a sensor trim with a Field Communicator
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field
Communicator to complete the sensor trim.
Device Dashboard Fast Keys
To calibrate the sensor with a Field Communicator using the sensor trim function:
Procedure
1. Select 2: Lower Sensor Trim.
Note
Select pressure points so that lower and upper values are equal to or outside the
expected process operation range. To do this, see Reranging the transmitter.
2. Follow the commands provided by the Field Communicator to complete the
adjustment of the lower value.
3. Select 3: Upper Sensor Trim.
4. Follow the commands provided by the Field Communicator to complete the
adjustment of the upper value.
3, 4, 1
Rosemount 3051P69
Operation and maintenanceReference Manual
April 202000809-0700-4001
Perform a sensor trim with AMS Device Manager
Procedure
1. Right click the device and, under the Method drop down menu, move the cursor
over Calibrate.
2. Under Sensor Trim, select Lower Sensor Trim.
3. Follow the screen prompts to perform a sensor trim using AMS Device Manager.
4. If desired, repeat Step 1.
5. Under Sensor Trim, select Upper Sensor Trim.
Perform a sensor trim using local operator interface (LOI)
Procedure
See Figure 5-3 to perform an upper and lower sensor trim.
Figure 5-3: Sensor Trim with LOI
Perform a digital zero trim (option DZ)
A digital zero trim (option DZ) provides the same function as a zero/lower sensor trim, but
you can complete it in hazardous areas at any given time by pushing the Zero Trim button
when the transmitter is at zero pressure.
If the transmitter is not close enough to zero when the button is pushed, the command
may fail due to excess correction. If ordered, you can use external configuration buttons
located underneath the top tag of the transmitter to perform a digital zero trim. See
Figure 5-1 for DZ button location.
Procedure
1. Loosen the top tag of the transmitter to expose buttons.
2. Press and hold the digital zero button for at least two seconds; then release to
perform a digital zero trim.
70Emerson.com/Rosemount
Reference ManualOperation and maintenance
00809-0700-4001April 2020
5.5.3Recall factory trim—sensor trim
The recall factory trim-sensor trim command allows the restoration of the as-shipped
factory settings of the sensor trim. You can use this command to recover from an
inadvertent zero trim of an absolute pressure unit or inaccurate pressure source.
Recall factory trim with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field
Communicator to complete the sensor trim.
Device Dashboard Fast Keys3, 4, 3
Recall factory trim with AMS Device Manager
Procedure
1. Right click on the device and, under the Method dropdown menu, move cursor over
Calibrate and select Restore Factory Calibration.
2. Set the control loop to manual.
3. Select Next.
4. Select Sensor Trim under Trim to recall and click Next.
5. Follow the screen prompts to recall Sensor Trim.
Recall factory trim with local operator interface (LOI)
Procedure
Refer to Figure 5-4 to recall factory sensor trim.
Figure 5-4: Recall Factory Trim with LOI
Rosemount 3051P71
Operation and maintenanceReference Manual
April 202000809-0700-4001
5.6Trimming the analog output
The Analog Output Trim commands allow you to adjust the transmitter's current output at
the 4 and 20 mA points to match the plant standards.
Perform this trim after the digital to analog conversion, so only the 4–20 mA analog signal
will be affected. Figure 5-5 graphically shows the two ways the characterization curve is
affected when an analog output trim is performed.
Figure 5-5: Analog Output Trim Example
5.6.1
A. Before trim
B. After trim
Performing digital-to-analog trim (4–20mA output trim)
Note
If adding a resistor to the loop, ensure that the power supply is sufficient to power the
transmitter to a 20 mA output with additional loop resistance. Refer to Power supply.
Perform a 4–20 mA output trim with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field
Communicator to complete the 4–20 mA output trim.
Device Dashboard Fast Keys
Perform a 4–20 mA output trim with AMS Device Manager
Procedure
1. Right click the device and, under the Method drop down menu, move the cursor
over Calibrate and select Analog Calibration.
2. Select Digital to Analog Trim.
3. Follow the screen prompts to perform a 4–20 mA output trim.
3, 4, 2, 1
72Emerson.com/Rosemount
Reference ManualOperation and maintenance
00809-0700-4001April 2020
Perform a 4–20 mA output trim using local operator
interface (LOI)
Figure 5-6: 4–20mA Output Trim using LOI
5.6.2Performing digital-to-analog trim (4–20mA output trim)
using other scale
The scaled 4–20 mA output trim command matches the 4 and 20 mA points to a user
selectable reference scale other than 4 and 20 mA (e.g., 2 to 10 volts if measuring across a
500 Ω load, or 0 to 100 percent if measuring from a Distributed Control System [DCS]). To
perform a scaled 4–20 mA output trim, connect an accurate reference meter to the
transmitter and trim the output signal to scale, as outlined in the output trim procedure.
Perform a 4–20 mA output trim using other scale with a Field
Communicator
Procedure
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field
Communicator to complete the 4–20 mA output trim using other scale.
Device Dashboard Fast Keys
Perform a 4–20 mA output trim using other scale with AMS
Device Manager
Procedure
1. Right click the device and, under the Method dropdown menu, move the cursor over
Calibrate and select Analog Calibration.
2. Select Scaled Digital to Analog Trim.
3. Follow screen prompts to perform a 4–20mA output trim.
3, 4, 2, 2
Rosemount 3051P73
Operation and maintenanceReference Manual
April 202000809-0700-4001
5.6.3Recalling factory trim—analog output
The Recall Factory Trim—Analog Output command allows the restoration of the asshipped factory settings of the analog output trim.
This command can be useful for recovering from an inadvertent trim, incorrect plant
standard or faulty meter.
Recall factory trim - analog output with a Field
Communicator
Procedure
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field
Communicator to complete the digital to analog trim using other scale.
Device Dashboard Fast Keys
3, 4, 3
Recall factory trim - analog output with AMS Device
Manager
Procedure
1. Right click the device and, under the Method drop down menu, move the cursor
over Calibrate and select Restore Factory Calibration.
2. Select Next to set the control loop to manual.
3. Select Analog Output Trim under Select Trim to recall and click Next.
4. Follow screen prompts to recall analog output trim.
Recall factory trim - analog output with local operator
interface (LOI)
Procedure
Reference Figure 5-7 for LOI instructions.
Figure 5-7: Recall Factory Trim – Analog Output with LOI
74Emerson.com/Rosemount
Reference ManualOperation and maintenance
00809-0700-4001April 2020
5.7Switching HART® revision
Some systems are not capable of communicating with HART Revision 7 devices. The
following procedures list how to change HART revisions between HART Revision 7 and
HART Revision 5.
5.7.1Switch HART® revision with generic menu
If the HART configuration tool is not capable of communicating with a HART Revision 7
device, it should load a generic menu with limited capability. The following procedures
allow for switching between HART Revision 7 and HART Revision 5 from a generic menu.
Procedure
1. To change to HART Revision 5, enter HART5 in the Message field.
2. To change to HART Revision 7, enter HART7 in the Message field.
5.7.2
Switch HART® revision with Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence and follow steps within the Field
Communicator to complete the HART revision change.
5.7.3Switch HART® revision with AMS Device Manager
Procedure
1. Select Manual Setup and select HART.
2. Select Change HART Revision; then follow the on screen prompts.
Note
AMS Device Manager versions 10.5 or greater are compatible with HART Revision 7.
5.7.4
Switch HART® revision with local operator interface (LOI)
Procedure
Navigate to HART REV within the extended menu and select either HART REV 5 or HART
REV 7. Use Figure 5-8 to change HART Revision.
Rosemount 3051P75
Operation and maintenanceReference Manual
April 202000809-0700-4001
Figure 5-8: Change HART Revision with LOI
76Emerson.com/Rosemount
Reference ManualTroubleshooting
00809-0700-4001April 2020
6Troubleshooting
6.1Overview
This section provides summarized maintenance and troubleshooting suggestions for the
most common operating problems.
If you suspect malfunction despite the absence of any diagnostic messages on the Field
Communicator display, consider using Diagnostic messages to identify any potential
problem.
6.2Safety messages
Procedures and instructions in this section may require special precautions to ensure the
safety of the personnel performing the operations.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with
the appropriate local, national, and international standards, codes, and practices.
Review the Product Certifications section of the Rosemount 3051P Product Data Sheet
for any restrictions associated with a safe installation.
Before connecting a handheld communicator in an explosive atmosphere, ensure that
the instruments in the loop are installed in accordance with intrinsically safe or nonincendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers
when power is applied to the unit.
WARNING
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads
can cause electrical shock.
WARNING
Process leaks could result in death or serious injury.
Install and tighten all four flange bolts before applying pressure.
Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Rosemount 3051P77
TroubleshootingReference Manual
April 202000809-0700-4001
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare parts
could reduce the pressure retaining capabilities of the transmitter and may render the
instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts. Improper assembly of manifolds
to traditional flange can damage sensor module.
WARNING
Improper assembly of manifolds to traditional flange can damage the device.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange
web (i.e., bolt hole) but must not contact sensor module housing.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or
misconfiguration of end users’ equipment. This could be intentional or unintentional and
needs to be protected against.
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access by unauthorized personnel to protect end
users’ assets. This is true for all systems used within the facility.
6.3Troubleshooting for 4-20 mA output
6.3.1Transmitter milliamp reading is zero
Recommended actions
1. Verify terminal voltage is 10.5 to 42.4 Vdc at signal terminals.
2. Check power wires for reversed polarity.
3. Check that power wires are connected to signal terminals.
4. Check for open diode across test terminal.
6.3.2
Transmitter not communicating with Field
Communicator
3. Check that power wires are connected to signal terminals and not test
terminals.
4. Verify clean DC power to transmitter (maximum AC noise 0.2 volts peak to
peak).
5. Verify the output is between 4 and 20 mA or saturation levels.
6. Have Field Communicator poll for all addresses.
6.3.3Transmitter milliamp reading is low or high
Recommended actions
1. Verify applied pressure.
2. Verify 4 and 20 mA range points.
3. Verify output is not in alarm condition.
4. Perform analog trim.
5. Check that power wires are connected to the correct signal terminals (positive
to positive, negative to negative) and not the test terminal.
6.3.4
6.3.5
Transmitter will not respond to changes in applied
pressure
Recommended actions
1. Check impulse piping or manifold for blockage.
2. Verify applied pressure is between 4 and 20 mA points.
3. Verify the output is not in alarm condition.
4. Verify transmitter is not in loop test mode.
5. Verify transmitter is not in multidrop mode.
6. Check test equipment.
Digital pressure variable reading is low or high
Recommended actions
1. Check impulse piping for blockage or low fill in wet leg.
2. Verify transmitter is calibrated properly.
3. Check test equipment (verify accuracy).
4. Verify pressure calculations for application.
6.3.6
Rosemount 3051P79
Digital pressure variable reading is erratic
Recommended actions
1. Check application for faulty equipment in pressure line.
2. Verify transmitter is not reacting directly to equipment turning on/off.
TroubleshootingReference Manual
April 202000809-0700-4001
3. Verify damping is set properly for application.
6.3.7Milliamp reading is erratic
Recommended actions
1. Verify power source to transmitter has adequate voltage and current.
2. Check for external electrical interference.
3. Verify transmitter is properly grounded.
4. Verify shield for twisted pair is only grounded at one end.
6.4Diagnostic messages
The following are possible messages that will appear on either the LCD/LOI display, a Field
Communicator, or an AMS Device Manager system.
• Good
• Failed – fix now
6.4.1
• Maintenance – fix soon
• Advisory
Status: Failed - Fix Now
No pressure updates
LCD display
screen
Local operator
interface (LOI)
screen
There are no pressure updates from the sensor to the electronics.
Recommended actions
1. Ensure the sensor cable connection to the electronics is tight.
2. Replace the transmitter.
Electronics board failure
LCD display
screen
NO P UPDATE
NO PRESS UPDATE
FAIL BOARD
Local operator
interface (LOI)
screen
A failure has been detected in the electronics circuit board.
80Emerson.com/Rosemount
FAIL BOARD
Reference ManualTroubleshooting
00809-0700-4001April 2020
Recommended action
Replace the pressure transmitter.
Critical sensor data error
LCD display
screen
Local operator
interface (LOI)
screen
A user-written parameter does not match the expected value.
Recommended actions
1. Confirm and correct all parameters listed in Device Information.
2. Perform a device reset.
3. Replace pressure transmitter.
MEMRY ERROR
MEMORY ERROR
Critical electronics data error
LCD display
screen
Local operator
interface (LOI)
screen
A user-written parameter does not match the expected value.
Recommended actions
MEMRY ERROR
MEMORY ERROR
1. Confirm and correct all parameters listed in Device Information.
2. Perform a device reset.
3. Replace pressure transmitter.
Sensor failure
LCD display
screen
Local operator
interface (LOI)
screen
A failure has been detected in the pressure sensor.
Recommended action
Replace pressure transmitter.
Rosemount 3051P81
FAIL SENSOR
FAIL SENSOR
TroubleshootingReference Manual
April 202000809-0700-4001
Incompatible electronics and sensor
6.4.2
LCD display
screen
Local operator
interface (LOI)
screen
The pressure sensor is incompatible with the attached electronics.
Recommended action
Replace the pressure transmitter.
XMTR MSMTCH
XMTR MSMTCH
Status: Maintenance - Fix Soon
No temperature updates
LCD display
screen
Local operator
interface (LOI)
screen
There are no temperature updates from the sensor to the electronics.
Recommended actions
NO T UPDATE
NO TEMP UPDATE
1. Ensure the sensor cable connection to the electronics is tight.
2. Replace the pressure transmitter.
Pressure out of limits
LCD display
screen
Local operator
interface (LOI)
screen
The pressure is either above or below the sensor limits.
Recommended actions
1. Check the transmitter pressure connection to ensure it is not plugged and the
2. Replace the pressure transmitter.
NO T UPDATE
PRES OUT LIMITS
isolating diaphragms are not damaged.
Sensor temperature beyond limits
LOI display
screen
TEMP LIMITS
82Emerson.com/Rosemount
Reference ManualTroubleshooting
00809-0700-4001April 2020
Local operator
interface (LOI)
screen
The sensor temperature has exceeded its safe operating range.
Recommended actions
1. Check the process and ambient conditions are within -85 to 194 °F (-65 to 90
2. Replace the pressure transmitter.
TEMP OUT LIMITS
°C).
Electronics temperature beyond limits
LCD display
screen
Local operator
interface (LOI)
screen
The temperature of the electronics has exceeded its safe operating range.
Recommended actions
1. Confirm electronics temperature is within limits of -85 to 194 °F (-65 to 90 °C).
2. Replace the pressure transmitter.
TEMP LIMITS
TEMP OUT LIMITS
Electronics board parameter error
LCD display
screen
Local operator
interface (LOI)
screen
A device parameter does not match the expected value. The error does not affect
transmitter operation or analog output.
Recommended action
Replace the pressure transmitter.
MEMRY WARN (also in advisory)
MEMORY WARN (also in advisory)
Configuration buttons operator error
LCD display
screen
Local operator
interface (LOI)
screen
Device is not responding to button presses.
STUCK BUTTON
STUCK BUTTON
Rosemount 3051P83
TroubleshootingReference Manual
April 202000809-0700-4001
Recommended actions
1. Check configuration buttons are not stuck.
2. Replace the pressure transmitter.
6.4.3Status: Advisory
Non-critical user data warning
LCD display
screen
Local operator
interface (LOI)
screen
A user-written parameter does not match expected value.
Recommended actions
1. Confirm and correct all parameters listed in Device Information.
2. Perform a Device Reset.
3. Replace the pressure transmitter.
MEMRY WARN
MEMORY WARN
Sensor parameter warning
LCD display
screen
Local operator
interface (LOI)
screen
A user-written parameter does not match expected value.
Recommended actions
MEMRY WARN
MEMORY WARN
1. Confirm and correct all parameters listed in Device Information.
2. Perform a Device Reset.
3. Replace pressure transmitter.
LCD display update failure
LCD display
screen
Local operator
interface (LOI)
screen
The LCD display is not receiving updates from the pressure sensor.
84Emerson.com/Rosemount
(Not updating)
(Not updating)
Reference ManualTroubleshooting
00809-0700-4001April 2020
Recommended actions
1. Check the connection between the LCD and the circuit board.
2. Replace the LCD display.
3. Replace the electronics board.
4. Replace the pressure transmitter.
Configuration changed
LCD display
screen
Local operator
interface (LOI)
screen
A recent change has been made to the device by a secondary HART® master, such as a
handheld device.
Recommended actions
1. Verify that the configuration change of the device was intended and expected.
2. Clear this alert by selecting Clear Configuration Changed Status.
3. Connect a HART master, such as AMS or similar, which will autmatically clear
(None)
(None)
the alert.
Analog output fixed
LCD display
screen
Local operator
interface (LOI)
screen
ANLOG FIXED
ANALOG FIXED
The analog output is fixed and does not represent the process measurement.
This may be caused by other conditions in the device or because the device has been set to
loop test or multidrop mode.
Recommended actions
1. Take action on any other notifications from the device.
2. If the device is in a loop test and should no longer be, disable or momentarily
remove power.
3. If the device is in multidrop mode and should not be, re-enable loop current by
setting the polling address to 0.
Simulation active
LCD display
screen
Rosemount 3051P85
(None)
TroubleshootingReference Manual
April 202000809-0700-4001
Local operator
interface (LOI)
screen
The device is in simulation mode and may not be reporting actual information.
Recommended actions
1. Verify that simulation is no longer required.
2. Disable simulation mode in service tools.
3. Perform a Device Reset.
(None)
Analog output saturated
LCD display
screen
Local operator
interface (LOI)
screen
The analog output is saturated either high or low due to the pressure either above or
below the range values.
Recommended actions
1. Check the pressure applied to ensure it is between the 4 and 20 mA points.
2. Check the transmitter pressure connection to ensure it is not plugged and the
3. Replace the pressure transmitter.
ANLOG SAT
ANALOG SAT
isolating diaphragms are not damaged.
6.5Disassembly procedures
WARNING
Do not remove cover in explosive atmospheres when the circuit is live.
6.5.1Remove from service
WARNING
Follow all plant safety rules and procedures.
Procedure
1. Power down transmitter.
2. Isolate and vent the process from the transmitter before removing the transmitter
from service.
3. Remove all electrical leads and disconnect conduit.
86Emerson.com/Rosemount
Reference ManualTroubleshooting
00809-0700-4001April 2020
4. Remove the transmitter from the process connection.
a) The transmitter is attached to the process by a single hex nut process
connection. Loosen the hex nut to separate the transmitter from the process.
CAUTION
Do not wrench on neck of transmitter. See warning in In-line process connection.
5. Do not scratch, puncture, or depress the isolating diaphragms.
6. Clean isolating diaphragms with a soft rag and a mild cleaning solution and rinse
with clear water.
6.5.2Remove terminal block
Electrical connections are located on the terminal block in the compartment labeled FIELDTERMINALS.
Procedure
6.5.3
1. Remove the housing cover from the field terminal side.
2. Loosen the two small screws located on the assembly in the 9 and 5 o’clock
positions relative to the top of the transmitter.
3. Pull the entire terminal block out to remove it.
Remove the local operator interface (LOI) or LCD display
Rosemount 3051P transmitters with M4 or M5 option codes have an LOI or LCD display.
The transmitter LOI/LCD display is located in the compartment opposite the terminal side.
To remove and/or replace the LOI/LCD display, perform the following procedures:
Procedure
1. Remove the housing cover opposite the field terminal side.
2. Loosen the two captive screws that are visible.
See Figure 4-2 for screw locations. The two screws anchor the LOI/LCD display to
the electronics board and the electronics board to the housing. See Safety
messages.
3. After the loosening the screws, pull the LOI/LCD display off of the electronics board
and out of the housing.
CAUTION
Make sure to pull directly backwards to avoid bending or damaging the connection
pins on the electronics board.
Rosemount 3051P87
TroubleshootingReference Manual
April 202000809-0700-4001
CAUTION
Do not attempt to pull out the electronics board from the housing, as this could
permanently damage the transmitter.
6.6Reassembly procedures
6.6.1Install the local operator interface (LOI) or LCD display
Procedure
1. While aligning the captive screws with the respective holes on the electronics
board, connect the LCD/LOI display to the electronics board by pressing down
firmly.
2. Make sure the connecting pins on the back of the LCD fully connect to the front of
the electronics board.
3. Fully tighten down the captive screws.
4. Replace the housing cover.
WARNING
Ensure the transmitter is fully engaged to meet Explosion-Proof requirement.
6.7Service support
Within the United States, call the Emerson Instrument and Valve Response Center using
the 1-800-654-RSMT (7768) toll-free number. This center, available 24 hours a day, will
assist you with any needed information or materials.
The center will ask for product model and serial numbers, and will provide a Return
Material Authorization (RMA) number. The center will also ask for the process material to
which the product was last exposed.
For inquiries outside of the United States, contact the nearest Emerson representative for
RMA instructions.
To expedite the return process outside of the United States, contact the nearest Emerson
representative.
WARNING
Individuals who handle products exposed to a hazardous substance can avoid injury if they
are informed of and understand the hazard. The product being returned will require a copy
of the required Material Safety Data Sheet (MSDS) for each substance must be included
with the returned goods.
88Emerson.com/Rosemount
Reference ManualTroubleshooting
00809-0700-4001April 2020
Emerson Instrument and Valve Response Center representatives will explain the additional
information and procedures necessary to return goods exposed to hazardous substances.
Rosemount 3051P89
TroubleshootingReference Manual
April 202000809-0700-4001
90Emerson.com/Rosemount
Reference ManualSafety instrumented systems requirements
00809-0700-4001April 2020
7Safety instrumented systems
requirements
7.1Safety instrumented systems (SIS) certification
The safety-critical output of the Rosemount 3051P is provided through a two-wire, 4 - 20
mA signal representing pressure. The Rosemount 3051P safety certified pressure
transmitter is certified to: Low Demand; Type B. SIL 2 for random integrity @ HFT=0 SIL 3
for random integrity @ HFT=1 SIL 3 for systematic integrity
7.2Safety certified identification
All Rosemount 3051P Transmitters must be identified as safety certified before installing
into SIS systems.
To identify a safety certified Rosemount 3051P:
Procedure
1. Check Namur Software Revision located on the metal device tag. "SW _._._".
Example
Namur Software Revision Number
SW
Note
Namur Software Revision: Located on the metal device tag.
2. Verify that option code QT is included in the transmitter model code.
1.0.x - 1.4.x
7.3Installation in safety instrumented systems
(SIS) applications
Only qualified personnel should install the transmitter in SIS applications. No special
installation is required in addition to the standard installation practices outlined in this
document.
WARNING
Always ensure a proper seal by installing the electronics housing cover(s) so that metal
contacts metal.
Environmental and operational limits are available in the Rosemount 3051P Product Data
Sheet.
Rosemount 3051P91
Safety instrumented systems requirementsReference Manual
April 202000809-0700-4001
Design the loop so that the terminal voltage does not drop below 10.5 Vdc when the
transmitter output is set to 23 mA. For more information see the Rosemount 3051P
Product Data Sheet.
Position the security switch to the ( ) position to prevent accidental or deliberate change
of configuration data during normal operation.
7.4Configuring in safety instrumented systems
(SIS) applications
Use any HART® capable configuration tool to communicate with and verify configuration
of the Rosemount 3051P.
Note
Transmitter output is not safety-rated during the following: configuration changes,
multidrop, and loop test. Use alternative means to ensure process safety during
transmitter configuration and maintenance activities.
7.4.1
Damping
User-selected damping will affect the transmitters ability to respond to changes in the
applied process. The damping value and response time must not exceed the loop
requirements.
Reference Damping to change damping value.
92Emerson.com/Rosemount
Reference ManualSafety instrumented systems requirements
00809-0700-4001April 2020
7.4.2Alarm and saturation levels
Configure DCS or safety logic solver to match transmitter configuration. Figure 7-1
identifies the three alarm levels available and their operation values.
Figure 7-1: Alarm Levels
Rosemount alarm level
Namur alarm level
Custom alarm level
A. Transmitter failure, hardware or software alarm in LO position.
B. Transmitter failure, hardware or software alarm in HI position.
7.5Safety instrumented systems (SIS) operation
and maintenance
7.5.1Proof tests
Emerson recommends the following proof tests. Ensure that only qualified personnel
perform proof tests.
Use Fast Keys to perform a loop test, analog output trim, or sensor trim. Place the security
switch in the (
after execution.
) position during proof test execution and reposition it in the ( ) position
Rosemount 3051P93
Safety instrumented systems requirementsReference Manual
April 202000809-0700-4001
7.5.2Partial proof test
The partial suggested proof test consists of a power cycle plus reasonability checks of the
transmitter output. Reference the FMEDA Report for percent of possible DU failures in the
device.
See the FMEDA Report.
Prerequisites
Required tools: Field Communicator and mA meter.
Procedure
1. Bypass the safety function and take appropriate action to avoid a false trip.
2. Use HART® communications to retrieve any diagnostics and take appropriate
action.
3. Send a HART command to the transmitter to go to the high alarm current output
and verify that the analog current reaches that value.
Note
This tests for compliance voltage problems such as a low loop power supply voltage
or increased wiring distance. This also tests for other possible failures.
7.5.3
See Verifying alarm level.
4. Send a HART command to the transmitter to go to the low alarm current output
and verify that the analog current reaches that value.
Note
This tests for possible quiescent current related failures.
5. Inspect the device for any leaks, visible damage, or contamination.
6. Remove the bypass and otherwise restore the normal operation.
7. Place the Security switch in the (
) position.
Comprehensive proof test
The comprehensive proof test consists of performing the same steps as the partial proof
test but with a two point calibration of the pressure sensor in place of the reasonability
check. Reference the FMEDA Report for percent of possible DU failures in the device.
Prerequisites
Required tools: Field Communicator and pressure calibration equipment.
Procedure
1. Bypass the safety function and take appropriate action to avoid a false trip.
2. Use HART® communications to retrieve any diagnostics and take appropriate
action.
3. Send a HART command to the transmitter to go to the high alarm current output
and verify that the analog current reaches that value.
94Emerson.com/Rosemount
Reference ManualSafety instrumented systems requirements
00809-0700-4001April 2020
Note
This tests for compliance voltage problems such as a low loop power supply voltage
or increased wiring distance. This also tests for other possible failures.
See Verifying alarm level.
4. Send a HART command to the transmitter to go to the low alarm current output
and verify that the analog current reaches that value.
Note
This tests for possible quiescent current related failures.
5. Inspect the device for any leaks, visible damage or contamination.
6. Perform a two-point calibration of the sensor (see Trimming the pressure signal)
over the full working range and verify the current output at each point.
7. Remove the bypass and otherwise restore the normal operation.
8. Place the Security switch in the ( ) position.
Note
• The user determines the proof test requirements for impulse piping.
• Automatic diagnostics are defined for the corrected % DU: The tests performed
internally by the device during runtime without requiring enabling or
programming by the user.
7.6Inspection
7.6.1Visual inspection
Not required.
7.6.2
7.6.3
Special tools
Not required.
Product repair
The transmitter is repairable with limited replacement options.
Report all failures detected by the transmitter diagnostics or by the proof test. Submit
feedback electronically at Emerson.com/Rosemount/Report-A-Failure
Only qualified personnel should repair the product and replace parts.
Rosemount 3051P95
Safety instrumented systems requirementsReference Manual
April 202000809-0700-4001
7.6.4Safety instrumented systems (SIS) reference
Operate the transmitter in accordance to the functional and performance specifications
provided in the Rosemount 3051P Product Data Sheet.
7.6.5Failure rate data
The FMEDA Report includes failure rates.
7.6.6Failure values
Safety Deviation (defines what is dangerous in an FMEDA): ±2.0% of analog output span
Transmitter response time: provided in Dynamic performance. Self-diagnostics Test
Interval: At least once every 60 minutes.
7.6.7
Product life
50 years: based on worst case component wear-out mechanisms, not based on wear-out
of process wetted materials.
96Emerson.com/Rosemount
Reference ManualReference data
00809-0700-4001April 2020
AReference data
A.1Product certifications and installation
drawings
To view current Rosemount 3051P product certifications and installation drawings, follow
these steps:
1. Go to Emerson.com/Rosemount-3051P.
2. Scroll as needed to the green menu bar and click Documents and Drawings.
3. Click Certificates & Approvals.
A.2Ordering information, specifications, and
dimensional drawings
To view current Rosemount 3051P ordering information, specifications, and dimensional
drawings, follow these steps:
1. Go to Emerson.com/Rosemount-3051P.
2. Scroll as needed to the green menu bar and click Documents and Drawings.
3. Click Data Sheets & Bulletins.
4. Select the appropriate Product Data Sheet.
Rosemount 3051P97
Reference dataReference Manual
April 202000809-0700-4001
98Emerson.com/Rosemount
Reference ManualField Communicator menu trees and Fast Keys
00809-0700-4001April 2020
BField Communicator menu trees and
Fast Keys
B.1Menu trees
Figure B-1: Overview
Rosemount 3051P99
Field Communicator menu trees and Fast KeysReference Manual
April 202000809-0700-4001
Note
Selections with black circle are only available in HART® Revision 7 mode. Selection will not
appear in the HART Revision 5 device descriptor (DD).
Figure B-2: Configure: Guided Setup
Note
Selections with black circle are only available in HART Revision 7 mode. Selection will not
appear in the HART Revision 5 DD.
100Emerson.com/Rosemount
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.