Rosemount 3051P In-Line Pressure Transmitter with HART Protocol Manuals & Guides

Rosemount™ 3051P In-Line Pressure Transmitter
with HART® Protocol
Reference Manual
00809-0700-4001, Rev AC
April 2020
2
Reference Manual Contents
00809-0700-4001 April 2020

Contents

Chapter 1 Introduction.............................................................................................................. 5
1.1 Using this manual........................................................................................................................ 5
1.2 Models covered........................................................................................................................... 5
1.3 Product recycling/disposal...........................................................................................................5
Chapter 2 Configuration............................................................................................................ 7
2.1 Safety messages.......................................................................................................................... 7
2.2 System readiness.........................................................................................................................8
2.3 HART® installation flowchart......................................................................................................10
2.4 Transmitter overview.................................................................................................................11
2.5 Configuration overview............................................................................................................. 14
2.6 Configuration basics.................................................................................................................. 14
2.7 Verifying configuration..............................................................................................................17
2.8 Basic setup of the transmitter.................................................................................................... 19
2.9 Configuring the LCD display.......................................................................................................24
2.10 Detailed transmitter setup.......................................................................................................25
2.11 Performing transmitter tests................................................................................................... 30
2.12 Configuring burst mode...........................................................................................................32
2.13 Establishing multidrop communication................................................................................... 34
Chapter 3 Hardware installation.............................................................................................. 37
3.1 Overview................................................................................................................................... 37
3.2 Safety messages........................................................................................................................ 37
3.3 Considerations...........................................................................................................................38
3.4 Installation procedures.............................................................................................................. 39
3.5 Rosemount 306 Manifold.......................................................................................................... 48
Chapter 4 Electrical installation................................................................................................49
4.1 Overview................................................................................................................................... 49
4.2 Safety messages........................................................................................................................ 49
4.3 Local Operating Interface (LOI)/LCD display...............................................................................50
4.4 Configuring transmitter security................................................................................................52
4.5 Set transmitter alarm.................................................................................................................55
4.6 Electrical considerations............................................................................................................ 55
Chapter 5 Operation and maintenance.....................................................................................63
5.1 Overview................................................................................................................................... 63
5.2 Safety messages........................................................................................................................ 63
5.3 Recommended calibration tasks................................................................................................64
5.4 Calibration overview..................................................................................................................65
Rosemount 3051P 3
Contents Reference Manual
April 2020 00809-0700-4001
5.5 Trimming the pressure signal.....................................................................................................68
5.6 Trimming the analog output......................................................................................................72
5.7 Switching HART® revision.......................................................................................................... 75
Chapter 6 Troubleshooting...................................................................................................... 77
6.1 Overview................................................................................................................................... 77
6.2 Safety messages........................................................................................................................ 77
6.3 Troubleshooting for 4-20 mA output......................................................................................... 78
6.4 Diagnostic messages................................................................................................................. 80
6.5 Disassembly procedures............................................................................................................ 86
6.6 Reassembly procedures.............................................................................................................88
6.7 Service support..........................................................................................................................88
Chapter 7 Safety instrumented systems requirements............................................................. 91
7.1 Safety instrumented systems (SIS) certification......................................................................... 91
7.2 Safety certified identification.....................................................................................................91
7.3 Installation in safety instrumented systems (SIS) applications....................................................91
7.4 Configuring in safety instrumented systems (SIS) applications...................................................92
7.5 Safety instrumented systems (SIS) operation and maintenance.................................................93
7.6 Inspection..................................................................................................................................95
Appendix A Reference data......................................................................................................... 97
A.1 Product certifications and installation drawings.........................................................................97
A.2 Ordering information, specifications, and dimensional drawings...............................................97
Appendix B Field Communicator menu trees and Fast Keys......................................................... 99
B.1 Menu trees................................................................................................................................ 99
B.2 Fast Keys..................................................................................................................................103
Appendix C Local operator interface (LOI)................................................................................. 105
C.1 Local operator interface (LOI) menu tree................................................................................. 105
C.2 Local operator interface (LOI) menu tree - extended menu......................................................106
C.3 Entering numbers....................................................................................................................107
C.4 Entering text............................................................................................................................108
4 Emerson.com/Rosemount
Reference Manual
00809-0700-4001 April 2020
Introduction

1 Introduction

1.1 Using this manual

The sections in this manual provide information on installing, operating, and maintaining the Rosemount 3051P. The sections are organized as follows:
Configuration provides instruction on commissioning and operating Rosemount 3051P
Transmitters. It also includes information on software functions, configuration parameters, and online variables.
Hardware installation contains mechanical installation instructions and field upgrade
options.
Electrical installation contains electrical installation instructions, and field upgrade
options.
Operation and maintenance provides detailed information on calibrating and changing
HART® Revisions.
Troubleshooting provides troubleshooting techniques for the most common operating
problems.
Safety instrumented systems requirements provides identification, installation,
configuration, operation and maintenance, and inspection information for Safety Instrumented Systems.
Specifications and reference data provides information on how to access reference and
specification data, as well as ordering information.
Field Communicator menu trees and Fast Keys provides the menu trees and HART Fast
Keys used to operate the transmitter.
Local operator interface (LOI) provides menu trees and instructions on using the LOI.

1.2 Models covered

The following Rosemount Pressure Transmitters are covered by this manual:
Rosemount 3051P In-Line Gage Pressure Transmitter: Measures gage pressure up to
4,000 psig (275.8 BarG).
Rosemount 3051P In-Line Absolute Pressure Transmitter: Measures absolute pressure
up to 4,000 psig (275.8 BarG).

1.3 Product recycling/disposal

Consider recycling equipment and packaging. Dispose of the product and packaging in accordance with local and national legislation.
Rosemount 3051P 5
Introduction Reference Manual
April 2020 00809-0700-4001
6 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020

2 Configuration

2.1 Safety messages

Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the Product Certifications section of the Rosemount 3051P Product Data Sheet for any restrictions associated with a safe installation.
Before connecting a handheld communicator in an explosive atmosphere, ensure that the instruments in the loop are installed in accordance with intrinsically safe or non­incendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is applied to the unit.
WARNING
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
WARNING
Process leaks could result in death or serious injury.
Install and tighten all four flange bolts before applying pressure. Do not attempt to loosen or remove flange bolts while the transmitter is in service.
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts. Improper assembly of manifolds to traditional flange can damage sensor module.
Rosemount 3051P 7
Configuration Reference Manual
April 2020 00809-0700-4001
WARNING
Improper assembly of manifolds to traditional flange can damage the device.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e., bolt hole) but must not contact sensor module housing.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.

2.2 System readiness

If using HART® based control or asset management systems, confirm the HART
capability of such systems prior to commissioning and installation. Not all systems are capable of communicating with HART Revision 7 devices.
For instructions on how to change the HART revision of your transmitter, see Switching
HART® revision.
2.2.1
Table 2-1: Device Revisions and Files
Identify device Find device driver
Software release
date
NAMUR hardware revision

Confirm correct device driver

Procedure
1. Verify the latest Device Driver (DD/DTM™) is loaded on your systems to ensure
proper communications.
2. Reference Emerson.com or FieldCommGroup.org for the latest DD.
3. Select desired product and download the DD.
a) Reference Table 2-1 for the correct DD.
files
®
HART software revision
(2)
HART universal revision
Device revision
(1)
NAMUR software revision
(1)
Review instructions Review
Manual document
(3)
number
functionality
Changes to software
August 2016
8 Emerson.com/Rosemount
1.1.xx 1.0.xx 03 7 10 00809-0700-4001 HART Revision 5 and 7 selectable
Reference Manual Configuration
00809-0700-4001 April 2020
Table 2-1: Device Revisions and Files (continued)
Identify device Find device driver
files
5 9 Local operator
(1) NAMUR revision is located on the hardware tag of the device. Differences in level 3 changes, signified above by xx,
represent minor product changes as defined per NE53. Compatibility and functionality are preserved, and products can be used interchangeably.
(2) HART software revision can be read using a HART capable configuration tool. Value shown is minimum revision that
could correspond to NAMUR revisions.
(3) Device driver file names use device and DD revision, e.g., 10_01. HART Protocol is designed to enable legacy device
driver revisions to continue to communicate with new HART devices. To access new functionality, the new device driver must be downloaded. Emerson recommends downloading new device driver files to ensure full functionality.
Review instructions Review
functionality
interface (LOI)
Scaled variable
Configurable
alarms
Expanded
engineering units
Updated
electronics hardware design
Intrinsic Safety
temperature classification change
Rosemount 3051P 9
Configuration Reference Manual
April 2020 00809-0700-4001

2.3 HART® installation flowchart

10 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020

2.4 Transmitter overview

The Rosemount 3051P In-Line Pressure Transmitter is offered for gage pressure (GP) and absolute pressure (AP) measurements. The transmitter uses piezoresistive sensor technology for AP and GP measurements.
The major components of the transmitter are the sensor module and the electronics housing. The sensor module contains the oil-filled sensor system (isolating diaphragm, oil fill system, and sensor). The electronics board is located within the electronics housing. The electrical signals from the sensor module are transmitted to the electronics board which contains the memory module and the analog to digital signal converter (A/D converter). The signal is then converted to a 4–20mA analog output signal or HART digital signal. The electronics housing contains the output electronics board, the optional external configuration buttons, and the terminal block. The basic block diagram of the transmitter is illustrated in Figure 2-2.
When pressure is applied to the isolating diaphragm, the oil deflects the sensor, which then changes its capacitance or voltage signal. This signal is then changed to a digital signal by the Signal Processing. The microprocessor then takes the signals from the Signal Processing and calculates the correct output of the transmitter. This signal is then sent to the D/A converter, which converts the signal back to the analog signal and then superimposes the HART signal on the 4–20 mA output.
®
An optional LCD display can be ordered that connects directly to the interface board, which maintains direct access to the signal terminals. The display indicates output and abbreviated diagnostic messages. A glass display cover is provided. For 4-20 mA HART output, the LCD display features a two-line display. The first line displays the actual measured value; the second line of six characters displays the engineering units. The LCD display can also display diagnostic messages.
Note
LCD display uses a 5x6 character display and can display output and diagnostic messages. The local operator interface (LOI) display uses an 8x6 character display and can display output and diagnostic messages as well as and LOI menu screens. The LOI display comes with two buttons mounted on the front of the display board. See Figure 2-1.
Rosemount 3051P 11
Configuration Reference Manual
April 2020 00809-0700-4001
Figure 2-1: LCD/LOI display
LCD display LOI display
12 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020
Figure 2-2: Block Diagram of Operation
A. Sensor module and electronics
B. 4-20 mA signal to control system C. Field Communicator D. Signal processing
E. Temperature sensor
F. Pressure sensor G. Sensor module memory H. Microprocessor
Sensor linearization
Rerange
Damping
Diagnostics
Engineering units
Communication
I. Memory
Configuration
J. Digital-to-analog signal conversion
K. Digital communication
Rosemount 3051P 13
Configuration Reference Manual
April 2020 00809-0700-4001

2.5 Configuration overview

This section contains information on commissioning and tasks that should be performed on the bench prior to installation, as well as tasks performed after installation as described in Performing transmitter tests.
Field Communicator, AMS Device Manager, and local operator interface (LOI) instructions are given to perform configuration functions. For convenience, Field Communicator Fast Key sequences are labeled “Fast Keys,” and abbreviated LOI menus are provided for each function below.
Full Field Communicator menu trees and Fast Key sequences are available in Field
Communicator menu trees and Fast Keys. LOI menu trees are available in Local operator interface (LOI).

2.6 Configuration basics

CAUTION
2.6.1
Set all transmitter hardware adjustments during commissioning to avoid exposing the transmitter electronics to the plant environment after installation.
You can configure the transmitter either before or after installation. Configuring the transmitter on the bench using either a Field Communicator, AMS Device Manager, or LOI ensures all transmitter components are in working order prior to installation. Verify that the security switch is set in the unlock position ( ) to proceed with configuration. See
Figure 4-2 for switch location.

Configuring on the bench

To configure on the bench, you will need a power supply and a Field Communicator, AMS Device Manager, or local operator interface (LOI), option M4.
Wire equipment as shown in Figure 2-3. To ensure successful HART® communication, a resistance of at least 250 Ωs must be present between the transmitter and the power supply; see Power supply for details. Connect the Field Communicator leads to the terminals labeled “COMM” on the terminal block.
14 Emerson.com/Rosemount
SAVE
1. Overview
2. Configure
3. Service Tools
3051 FT 45B Online
Reference Manual Configuration
00809-0700-4001 April 2020
Figure 2-3: Wiring the Transmitter (4–20 mA HART)
A. Vdc supply
B. R L ≥ 250 (necessary for HART communication only)
2.6.2

Configuration tools

Configuring with a Field Communicator
There are two interfaces available with the Field Communicator: traditional and dashboard.
This manual describes all steps using a Field Communicator using dashboard interfaces.
Figure 2-4 shows the Device Dashboard interface. As stated in System readiness, it is
critical that the latest device descriptors (DDs) are loaded into the Field Communicator. Visit Emerson.com or FieldCommGroup.org to download the latest DD library.
Field Communicator menu trees and Fast Keys are available in Field Communicator menu
trees and Fast Keys.
Figure 2-4: Device Dashboard
Rosemount 3051P 15
Configuration Reference Manual
April 2020 00809-0700-4001
Configuring with AMS Device Manager
Full configuration capability with AMS Device Manager requires loading the most current device descriptor (DD) for this device. Download the latest DD at Emerson.com or
FieldCommGroup.org.
Note
This manual describes all steps using AMS Device Manager version 11.5.
Configuring with a local operator interface (LOI)
To use the LOI, order the transmitter with option code M4. To activate the LOI push either configuration button. Configuration buttons are located on the LCD display (must remove housing cover to access), or underneath the top tag of the transmitter. See Table 2-2 for configuration button functionality and Figure 2-5 for configuration button location.
When using the LOI for configuration, several features require multiple screens for a successful configuration. Data entered will be saved on a screen-by-screen basis; the LOI will indicate this by flashing SAVED on the LCD display each time.
LOI menu trees are available in Local operator interface (LOI).
Figure 2-5: LOI Configuration Buttons
A. Internal configuration buttons
B. External configuration buttons
16 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020
Table 2-2: LOI Button Operation
Button
Left No SCROLL
Right Yes ENTER

2.6.3 Setting the loop to manual

Whenever sending or requesting data that would disrupt the loop or change the output of the transmitter, set the process application loop to manual control.
The Field Communicator, AMS Device Manager, or local operator interface (LOI) will prompt you to set the loop to manual when necessary. The prompt is only a reminder; acknowledging this prompt does not set the loop to manual. You must set the loop to manual control as a separate operation.

2.7 Verifying configuration

Emerson recommends verifying various configuration parameters prior to installing them into the process.
The various parameters are detailed out for each configuration tool. Depending on what configuration tool(s) are available follow the steps listed relevant to each tool.
2.7.1

Verifying configuration with Field Communicator

Review configuration parameters listed in Table 2-3 prior to transmitter installation. A Full list of configuration parameters that can be reviewed and configured using a Field Communicator are located in Field Communicator menu trees and Fast Keys.
Fast Key sequences for the latest device descriptor (DD) are shown in Table 2-3. For Fast Key sequences for legacy DDs, contact your local Emerson Representative.
Procedure
From the HOME screen, enter the Fast Key sequences listed
Table 2-3: Device Dashboard Fast Key Sequence
Function Fast Key sequence
HART® 7 HART 5
Alarm and saturation levels 2, 2, 2, 5 2, 2, 2, 5
Rosemount 3051P 17
Configuration Reference Manual
April 2020 00809-0700-4001
Table 2-3: Device Dashboard Fast Key Sequence (continued)
Function Fast Key sequence
HART® 7 HART 5
Damping 2, 2, 1, 1, 5 2, 2, 1, 1, 5
Primary variable 2, 1, 1, 4, 1 2, 1, 1, 4, 1
Range values 2, 1, 1, 4 2, 1, 1, 4
Tag 2, 2, 7, 1, 1 2, 2, 7, 1, 1
Transfer function 2, 2, 1, 1, 6 2, 2, 1, 1, 6
Units 2, 2, 1, 1, 4 2, 2, 1, 1, 4

2.7.2 Verifying configuration with AMS Device Manager

Procedure
1. Right click on the device and select Configuration Properties from the menu.
2. Navigate the tabs to review the transmitter configuration data.
2.7.3

Verifying configuration with local operator interface (LOI)

Procedure
1. Press any configuration button to activate the LOI.
2. Select VIEW CONFIG to review the below parameters.
3. Use the configuration buttons to navigate through the menu.
Review the following pareameters prior to installation:
Tag
Units
Transfer Function
Alarm and Saturation Levels
Primary Variable
Range Values
Damping
18 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020

2.7.4 Verifying process variables configuration

This section describes how to verify that the correct process variables are selected.
Verifying process variables with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys 3, 2, 1
Verifying process variables with AMS Device Manager
Procedure
1. Right click the device and select Overview from the menu.
2. Select the All Variables button to display the primary, secondary, tertiary, and
quaternary variables.

2.8 Basic setup of the transmitter

This section provides the necessary steps for basic setup of a pressure transmitter.
When installing in DP level or DP flow applications, refer to Configuring scaled variable for setup instructions.
2.8.1

Setting pressure units

The pressure unit command sets the unit of measure for the reported pressure.
Setting pressure units with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Setting pressure units with AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Select Manual Setup and select desired units from Pressure Units dropdown menu.
3. Select Send when complete.
2, 2, 1, 1, 4
Rosemount 3051P 19
Configuration Reference Manual
April 2020 00809-0700-4001
Setting pressure units with a local operator interface (LOI)
Procedure
1. Follow Figure 2-6 to select desired pressure and temperature units.
2. Use the SCROLL and ENTER buttons to select desired unit.
3. Save by selecting SAVE as indicated on the LCD display screen.
Example
Figure 2-6: Selecting Units with LOI

2.8.2 Reranging the transmitter

The range values command sets each of the lower and upper range analog values to a pressure. The lower range point represents 0 percent of range and the upper range point represents 100 percent of range.
In practice, the transmitter range values may be changed as often as necessary to reflect changing process requirements.
Select from one of the methods below to rerange the transmitter. Each method is unique; examine all options closely before deciding which method works best for your process.
Rerange by manually setting range points with a Field Communicator, AMS Device
Manager, or local operator interface (LOI).
Rerange with a pressure input source and a Field Communicator, AMS Device Manager,
LOI, or local zero and span buttons.
Manually rerange the transmitter by entering range points
Entering range points with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 2, 1
20 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020
Entering range points with AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Select Manual Setup and select Analog Output.
3. Enter upper and lower range values in the Range Limits box and click Send.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
Entering range points with a local operator interface (LOI)
See Figure 2-7 to rerange the transmitter using the LOI.
Procedure
Enter values using SCROLL and ENTER buttons.
Figure 2-7: Rerange with LOI
Rerange the transmitter with applied pressure source
Reranging using an applied pressure source is a way of reranging the transmitter without entering specific 4 and 20 mA points.
Rerange with an applied pressure source using a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Rerange with an applied pressure source using AMS Device Manager
Procedure
1. Right click the device; select Configure.
2. Select the Analog Output tab.
3. Select Range by Applying Pressure and follow the screen prompts range the
transmitter.
2, 2, 2, 2
Rosemount 3051P 21
Configuration Reference Manual
April 2020 00809-0700-4001
Rerange with an applied pressure source using local zero and span buttons
If you order local zero and span buttons (option code D4), you can use them to rerange the transmitter with an applied pressure. Refer to Figure 2-8 for analog zero and span button location.
To rerange the transmitter using the span and zero buttons, perform the following procedure:
Procedure
1. Loosen the screw holding the top tag of the transmitter housing. Rotate the label to
expose the zero and span buttons.
2. Confirm device has local zero and span buttons by verifying blue retainer under the
tag.
3. Apply transmitter pressure.
4. Rerange the transmitter.
a) To change the zero (4 mA) while maintaining the span: press and hold zero
button for at least two seconds then release.
b) To change the span (20 mA) while maintaining the zero point: press and hold
the span button for at least two seconds and then release.
Example
Note
4 mA and 20 mA points must maintain the minimum span defined in Specifications and
reference data.
Figure 2-8: Analog Zero and Span Buttons
A. Zero and span buttons
22 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020
Note
If the transmitter security is on, you cannot make adjustments to the zero and span.
Refer to Configuring transmitter security for security information.
The span is maintained when the 4 mA/1 V point is set. The span changes when the 20
mA/5 V point is set. If the lower range point is set to a value that causes the upper range point to exceed the sensor limit, the upper range point is automatically set to the sensor limit, and the span is adjusted accordingly.
Regardless of the range points, the transmitter measures and reports all readings
within the digital limits of the sensor. For example, if the 4 and 20 mA points are set to 0 and 10 inH2O, and the transmitter detects a pressure of 25 inH2O, it digitally outputs the 25 inH2O reading and a 250 percent of range reading.

2.8.3 Damping

The damping command changes the response time of the transmitter; higher values can smooth variations in output readings caused by rapid input changes.
Determine the appropriate damping setting based on the necessary response time, signal stability, and other requirements of the loop dynamics within your system. The damping command utilizes floating point configuration, allowing you to input any damping value within 0.0–60.0 seconds.
Damping with a Field Communicator
Procedure
1. From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2. Enter desired damping value and select APPLY.
2, 2, 1, 1, 5
Damping with AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Select Manual Setup.
3. Within the Pressure Setup box, enter desired damping value and click Send.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
Damping with a local operator interface (LOI)
Procedure
Reference Figure 2-9 to enter damping values using an LOI.
Rosemount 3051P 23
Configuration Reference Manual
April 2020 00809-0700-4001
Figure 2-9: Damping with LOI

2.9 Configuring the LCD display

The LCD display configuration command allows customization of the LCD display to suit application requirements.
The LCD display will alternate between the selected items.
Pressure Units
% of Range
Scaled Variable
Sensor Temperature
mA/Vdc Output
Use the following instructions to configure the LCD display to display configuration information during the device startup. Select Review Parameters at start-up to enable or disable this functionality.
See Table 2-2 for an image of the LCD display screen.
2.9.1

Configuring LCD display with a Field Communicator

Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
24 Emerson.com/Rosemount
2, 2, 4
Reference Manual Configuration
00809-0700-4001 April 2020

2.9.2 Configuring LCD display with AMS Device Manager

Procedure
1. Right click on the device and select Configure.
2. Select Manual Setup; select the Display tab.
3. Select desired display options and click Send.

2.9.3 Configuring LCD display with a local operator interface (LOI)

Procedure
Refer to Figure 2-10 for LCD display configuration using an LOI.
Figure 2-10: Display with LOI

2.10 Detailed transmitter setup

2.10.1 Configuring alarm and saturation levels

In normal operation, the transmitter will drive the output in response to pressure from the lower to upper saturation points. If the pressure goes outside the sensor limits, or if the output would be beyond the saturation points, the output will be limited to the associated saturation point.
The transmitter automatically and continuously performs self-diagnostic routines. If the self-diagnostic routines detect a failure, the transmitter drives the output to configured alarm and value based on the position of the alarm switch. See Set transmitter alarm.
Rosemount 3051P 25
Configuration Reference Manual
April 2020 00809-0700-4001
Table 2-4: Alarm and Saturation Values
Level 4–20 mA saturation 4–20 mA alarm
Low 3.90 mA ≤ 3.75 mA
High 20.80 mA ≥ 21.75 mA
Table 2-5: NAMUR-Compliant Alarm and Saturation Values
Level 4–20 mA saturation 4–20 mA alarm
Low 3.80 mA ≤ 3.60 mA
High 20.50 mA ≥22.50 mA
Table 2-6: Custom Alarm and Saturation Values
Level 4–20 mA saturation 4–20 mA alarm
Low 3.50 mA– 3.90 mA 3.40–3.80 mA
High 20.10 mA –22.90 mA 20.20 mA – 23.00 mA
You can configure failure mode alarm and saturation levels using a Field Communicator, AMS Device Manager, or local operator interface (LOI). The following limitations exist for custom levels:
Low alarm level must be less than the low saturation level.
High alarm level must be higher than the high saturation level.
Alarm and saturation levels must be separated by at least 0.1 mA.
The configuration tool will provide an error message if the configuration rule is violated.
Note
Transmitters set to HART® multidrop mode send all saturation and alarm information digitally; saturation and alarm conditions will not affect the analog output. See also
Establishing multidrop communication.
Configuring alarm and saturation levels using a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 2, 5
Configuring alarm and saturation levels with AMS Device Manager
Procedure
1. Right click on the device and select Configure.
2. Select Configure Alarm and Saturation Levels.
26 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020
3. Follow screen prompts to configure alarm and saturation levels.
Configuring alarm and saturation levels using a local operator interface (LOI)
Procedure
Refer to Figure 2-11 for instructions to configure alarm and saturation levels.
Figure 2-11: Configuring Alarm and Saturation with LOI

2.10.2 Configuring scaled variable

With the scaled variable, you can create a relationship/conversion between the pressure units and user-defined/custom units.
There are two use cases for scaled variable:
1. Allow custom units to be displayed on the transmitter's LCD/local operator interface (LOI) display.
2. Allow custom units to drive the transmitters 4-20 mA output.
If the you want custom units to drive the 4–20 mA output, re-map the scaled variable as the primary variable. Refer to Re-mapping device variables.
The scaled variable configuration defines the following items:
Scaled variable units
Scaled data options
Pressure value position 1
Scaled variable position 1
Pressure value position 2
Scaled variable position 2
Linear offset
Custom units to be displayed.
Defines the transfer function for the application.
Lower known value point with consideration of linear offset.
Custom unit equivalent to the lower known value point.
Upper known value point.
Custom unit equivalent to the upper known value point.
The value required to zero out pressures affecting the desired pressure reading.
Rosemount 3051P 27
Configuration Reference Manual
April 2020 00809-0700-4001
Configuring a scaled variable using a Field Communicator
Procedure
1. From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys 2, 1, 4, 7
2. Follow the screen prompts to configure scaled variable.
a) Select Linear under Select Scaled data options.
Configuring a scaled variable using AMS Device Manager
Procedure
1. Right click on the device and, select Configure.
2. Select the Scaled Variable tab and select the Scaled Variable button.
3. Follow screen prompts to configure scaled variable.
a) Select Linear under Select Scaled data options.
Configuring a scaled variable using a local operator interface (LOI)
Procedure
Refer to Figure 2-12 for instructions to configure a scaled variable using an LOI.
Figure 2-12: Configuring Scaled Variable Using an LOI
28 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020

2.10.3 Re-mapping device variables

The re-mapping function allows you to configure the transmitter primary, secondary, tertiary, and quaternary variables (PV, 2V, 3V, and 4V) as desired.
You can re-map the PV with a Field Communicator, AMS Device Manager, or a local operator interface (LOI). You can only re-map variables 2V, 3V, and 4V via Field Communicator or AMS Device Manager.
Note
The variable assigned to the primary variable drives the 4–20 mA output. This value can be selected as Pressure or Scaled Variable. The 2, 3, and 4 variables only apply if using HART burst mode.
Re-map device variables using a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
®
Fast Keys
2, 1, 1, 3
Re-map device variables using AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Select Manual Setup and click on the HART tab.
3. Assign Primary, secondary, tertiary, and quaternary variables under Variable Mapping.
4. Select Send.
5. Carefully read the warning and select Yes if it is safe to apply the changes.
Re-map device variables using local operator interface (LOI)
Procedure
Refer to Figure 2-13 for instructions on re-mapping the primary variable using an LOI.
Rosemount 3051P 29
Configuration Reference Manual
April 2020 00809-0700-4001
Figure 2-13: Re-mapping with LOI

2.11 Performing transmitter tests

2.11.1 Verifying alarm level

If the transmitter is repaired or replaced, verify the transmitter alarm level before returning the transmitter to service.
This is useful in testing the reaction of the control system to a transmitter in an alarm state. It ensures that the control system recognizes the alarm when activated. To verify the transmitter alarm values, perform a loop test and set the transmitter output to the alarm value (see Table 2-4, Table 2-5, and Table 2-6).
Note
Before returning transmitter to service, verify security switch is set to the correct position. Refer to Verifying configuration.
2.11.2

Performing an analog loop test

The analog loop test command verifies the output of the transmitter, the integrity of the loop, and the operations of any recorders or similar devices installed in the loop. Emerson recommends testing the 4-20 mA points in addition to alarm levels when installing, repairing, or replacing a transmitter.
The host system may provide a current measurement for the 4–20 mA HART® output. If it does not, connect a reference meter to the transmitter by either connecting the meter to
30 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020
the test terminals on the terminal block, or shunting transmitter power through the meter at some point in the loop.
Performing an analog loop test using a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys 3, 5, 1
Performing an analog loop test using AMS Device Manager
Procedure
1. Right click on the device and hover the cursor over Diagnostics and Test in the Methods dropdown menu. From the Diagnostics and Test dropdown menu, select Loop Test.
2. Select Next after setting the control loop to manual.
3. Follow screen prompts to perform a loop test.
4. Select Finish to acknowledge the method is complete.
Performing an analog loop test using a local operator interface (LOI)
To perform an analog loop test using the LOI, manually set the 4 mA, 20 mA, and custom mA point.
Procedure
Reference Figure 2-14 for instructions on how to perform a transmitter loop test using an LOI.
Figure 2-14: Performing an Analog Loop Test Using an LOI
Rosemount 3051P 31
Configuration Reference Manual
April 2020 00809-0700-4001

2.11.3 Simulate device variables

You can temporarily set the pressure, sensor temperature, or scaled variable to a user­defined fixed value for testing purposes. Once the simulated variable method is left, the process variable will be automatically returned to a live measurement.
You can only simulate device variables in HART® Revision 7 mode.
Simulate digital signal with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Simulate digital signal with AMS Device Manager
Procedure
1. Right click on the device and select Service Tools.
2. Select Simulate.
3. Under Device Variables select a digital value to simulate:
a. Pressure
b. Sensor temperature
c. Scaled variable
4. Follow the screen prompts to simulate selected digital value.

2.12 Configuring burst mode

Burst mode is compatible with the analog signal. Because the HART® protocol features simultaneous digital and analog data transmission, the analog value can drive other equipment in the loop while the control system is receiving the digital information.
Burst mode applies only to the transmission of dynamic data (pressure and temperature in engineering units, pressure in percent of range, scaled Vvariable, and/or analog output), and does not affect the way other transmitter data is accessed. However, when activated, burst mode can slow down communication of non-dynamic data to the host by 50 percent.
3, 5
Access to information other than dynamic transmitter data is obtained through the normal poll/response method of HART communication. A Field Communicator, AMS Device Manager, or the control system may request any of the information that is normally available while the transmitter is in burst mode. Between each message sent by the transmitter, a short pause allows the Field Communicator, AMS Device Manager, or a control system to initiate a request.
Choosing burst mode options in HART 5
Message content options:
32 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020
PV only
Percent of Range
PV, 2V, 3V, 4V
Process Variables
Device Status
Choosing burst mode options in HART 7
Message content options:
PV only
Percent of Range
PV, 2V, 3V, 4V
Process Variables and Status
Process Variables
Device Status
Choosing a HART 7 trigger mode
When in HART 7, you can select the following trigger modes:
Continuous (same as HART 5 burst mode)
Rising
Falling
Windowed
On Change
Note
Consult your host system manufacturer for burst mode requirements.
2.12.1

Configuring burst mode using a Field Communicator

Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 5, 3

2.12.2 Configuring burst mode using AMS Device Manager

Procedure
1. Right click on the device and select Configure.
2. Select the HART tab.
3. Enter the configuration in Burst Mode Configuration fields.
Rosemount 3051P 33
Configuration Reference Manual
April 2020 00809-0700-4001

2.13 Establishing multidrop communication

Multidropping transmitters refers to the connection of several transmitters to a single communications transmission line. Communication between the host and the transmitters takes place digitally with the analog output of the transmitters deactivated.
Multidrop installation requires consideration of the update rate necessary from each transmitter, the combination of transmitter models, and the length of the transmission line. Use HART® modems and a host implementing HART protocol to communicate with transmitters. Each transmitter is identified by a unique address and responds to the commands defined in the HART protocol. Field Communicators and AMS Device Manager can test, configure, and format a multidropped transmitter the same way as a transmitter in a standard point-to-point installation.
Figure 2-15 shows a typical multidrop network. This figure is not intended as an
installation diagram.
Figure 2-15: Typical Multidrop Network (4–20 mA Only)
A. HART modem
B. Power supply
The Rosemount 3051P is set to address zero at the factory, which allows operation in the standard point-to-point manner with a 4–20 mA output signal. To activate multidrop communication, change the transmitter address to a number from 1 to 15 for HART Revision 5, or 1 to 63 for HART Revision 7. This change deactivates the 4–20 mA analog output, sending it to 4 mA . It also disables the failure mode alarm signal, which is controlled by the upscale/downscale switch position. Failure signals in multidropped transmitters are communicated through HART messages.
34 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020

2.13.1 Changing a transmitter address

To activate multidrop communication, assign the transmitter poll address to a number from 1 to 15 for HART® Revision 5, and 1 to 63 for HART Revision 7. Each transmitter in a multidropped loop must have a unique poll address.
Changing transmitter address using a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
HART® Revision 5 HART Revision 7
Device Dashboard Fast Keys 2, 2, 5, 2, 1 2, 2, 5, 2, 2
Changing transmitter address using AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. In HART® Revision 5 mode:
a) Select Manual Setup and then select the HART tab.
2.13.2
b) In the Communication Settings box enter polling address in the Polling
Address box and then select Send.
3. In HART Revision 7 mode:
a) Select Manual Setup, select the HART tab, and select the Change Polling
Address button.
4. Carefully read the warning and click Yes if it is safe to apply the changes.

Communicating with a multidropped transmitter

To communicate with a multidrop transmitter you must set up the Field Communicator or AMS Device Manager for polling.
Communicating with a multidropped transmitter using a Field Communicator
Procedure
1. Select Utility and Configure HART Application.
2. Select Polling Addresses.
3. Enter 0–63.
Rosemount 3051P 35
Configuration Reference Manual
April 2020 00809-0700-4001
Communicating with a multidropped transmitter using AMS Device Manager
Procedure
Select the HART® modem icon and select Scan All Devices.
36 Emerson.com/Rosemount
Reference Manual Hardware installation
00809-0700-4001 April 2020

3 Hardware installation

3.1 Overview

The information in this section covers installation considerations for the transmitter with HART® protocol.
Emerson ships a Quick Start Guide with every transmitter to describe recommended pipe­fitting and wiring procedures for initial installation. Dimensional drawings for each transmitter variation and mounting configuration are included in Mounting brackets.
Note
For transmitter disassembly and reassembly refer to Disassembly procedures, and
Reassembly procedures.

3.2 Safety messages

Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the Product Certifications section of the Rosemount 3051P Product Data Sheet for any restrictions associated with a safe installation.
Before connecting a handheld communicator in an explosive atmosphere, ensure that the instruments in the loop are installed in accordance with intrinsically safe or non­incendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is applied to the unit.
WARNING
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
WARNING
Process leaks could result in death or serious injury.
Install and tighten all four flange bolts before applying pressure. Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Rosemount 3051P 37
Hardware installation Reference Manual
April 2020 00809-0700-4001
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts. Improper assembly of manifolds to traditional flange can damage sensor module.
WARNING
Improper assembly of manifolds to traditional flange can damage the device.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e., bolt hole) but must not contact sensor module housing.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.

3.3 Considerations

3.3.1 Installation considerations

Measurement accuracy depends upon proper installation of the transmitter and impulse piping. Mount the transmitter close to the process and use a minimum of piping to achieve best accuracy.
Keep in mind the need for easy access, personnel safety, practical field calibration, and a suitable transmitter environment. Install the transmitter to minimize vibration, shock, and temperature fluctuation.
WARNING
Install the enclosed pipe plug (found in the box) in an unused housing conduit opening with a minimum of five threads of engagement to comply with explosion-proof requirements.
Always ensure a proper seal by installing the electronics housing cover(s) so that metal contacts metal.
Use Rosemount O-rings.
38 Emerson.com/Rosemount
Reference Manual Hardware installation
00809-0700-4001 April 2020

3.3.2 Environmental considerations

Best practice is to mount the transmitter in an environment that has minimal ambient temperature change. The transmitter electronics temperature operating limits are –40 to 185 °F (–40 to 85 °C).
Refer to the Rosemount 3051P Product Data Sheet for the sensing element operating limits. Mount the transmitter so that it is not susceptible to vibration and mechanical shock and does not have external contact with corrosive materials.

3.3.3 Mechanical considerations

Steam service
For steam service or for applications with process temperatures greater than the limits of the transmitter, do not blow down impulse piping through the transmitter. Flush lines with the blocking valves closed and refill lines with water before resuming measurement.
Refer to Figure 3-3 through Figure 3-5 for correct mounting orientation.

3.4 Installation procedures

3.4.1 Mount the transmitter

The approximate weight of the transmitter is 2.44 lb. (1.11 kg).
In many cases its compact size and light weight makes it possible to mount directly to the respective apparatus without using an additional mounting bracket. When this is not desirable, mount directly to a wall, panel, or 2-in. (50.8 mm) pipe using the optional mounting bracket (see Mounting brackets).
For dimensional drawing information refer to the Rosemount 3051P Product Data Sheet.
Note
Most transmitters are calibrated in the upright position. Mounting the transmitter in any other position will shift the zero point to the equivalent amount of liquid head pressure caused by the varied mounting position. To reset zero point, refer to Sensor trim overview.
Electronics housing clearance
Mount the transmitter so the terminal side is accessible. Clearance of 0.75 in. (19 mm) is required for cover removal.
Use a conduit plug in the unused conduit opening. 3 in. (76.2 mm) of clearance is required for cover removal if a meter is installed.
Environmental seal for housing
Thread sealing (PTFE) tape or paste on male threads of conduit is required to provide a water/dust tight conduit seal and meets requirements of NEMA® Type 4X, IP66, and IP68.
Consult factory if other Ingress Protection ratings are required.
Rosemount 3051P 39
Hardware installation Reference Manual
April 2020 00809-0700-4001
For M20 threads, install conduit plugs to full thread engagement or until mechanical resistance is met.
40 Emerson.com/Rosemount
Reference Manual Hardware installation
00809-0700-4001 April 2020
Mounting brackets
You can panel mount or pipe mount the transmitter via an optional mounting bracket (option code B4).
See Figure 3-1 and for dimensional and mounting configuration information.
Figure 3-1: Mounting Bracket Option Code B4
Dimensions are in inches (millimeters).
Pipe mounting Panel mounting
A. 2-in. (50.8 mm) U-bolt for pipe mounting (clamp shown)
B. ¼ x 1¼ bolts for transmitter mounting (not supplied) C. ¼ x 1¼ bolts for transmitter mounting (not supplied) D. 5/16 x 1½ bolts for panel mounting (not supplied)
Rosemount 3051P 41
Hardware installation Reference Manual
April 2020 00809-0700-4001
Figure 3-2: Head Markings
3.4.2
A. Carbon steel (CS) head markings
B. The last digit in the F593_ head marking may be any letter between A and M. C. Stainless steel (SST) head markings D. Alloy K-500 head marking

Impulse piping

Mounting requirements
Impulse piping configurations depend on specific measurement conditions.
Refer to Figure 3-3 through Figure 3-5 for examples of the following mounting configurations:
Liquid measurement
Place taps to the side of the line to prevent sediment deposits on the transmitter’s
process isolator.
Mount the transmitter beside or below the taps so gases can vent into the process line.
Mount drain/vent valve upward to allow gases to vent.
42 Emerson.com/Rosemount
Reference Manual Hardware installation
00809-0700-4001 April 2020
Figure 3-3: Liquid Applications Installation Example
Gas measurement
Place tap in the top or side of the line.
Mount the transmitter beside or above the tap so liquid will drain into the process line.
Rosemount 3051P 43
Hardware installation Reference Manual
April 2020 00809-0700-4001
Figure 3-4: Gas Applications Installation Example
Steam measurement
Place tap to the side of the line.
Mount the transmitter below the taps to ensure the impulse piping will stay filled with
condensate.
In steam service above 250 °F (121 °C), fill impulse line with water to prevent steam
from contacting the transmitter directly and to ensure accurate measurement start-up.
44 Emerson.com/Rosemount
Reference Manual Hardware installation
00809-0700-4001 April 2020
Figure 3-5: Steam Applications Installation Example
CAUTION
For steam or other elevated temperature services, it is important that temperatures at the process connection do not exceed the transmitter’s process temperature limits.
Best practices
The piping between the process and the transmitter must accurately transfer the pressure to obtain accurate measurements.
There are six possible sources of error:
1. Pressure transfer
2. Leaks
3. Friction loss (particularly if purging is used)
4. Trapped gas in a liquid line
5. Liquid in a gas line
6. Density variations between the legs
The best location for the transmitter in relation to the process pipe is dependent on the process. Use the following guidelines to determine transmitter location and placement of impulse piping:
Rosemount 3051P 45
Hardware installation Reference Manual
April 2020 00809-0700-4001
Keep impulse piping as short as possible.
For liquid service, slope the impulse piping at least 1 in./ft (8 cm/m) upward from the
transmitter toward the process connection.
For gas service, slope the impulse piping at least 1 in./ft (8 cm/m) downward from the
transmitter toward the process connection.
Avoid high points in liquid lines and low points in gas lines.
Use impulse piping large enough to avoid friction effects and blockage.
Vent all gas from liquid piping legs.
When purging, make the purge connection close to the process taps and purge
through equal lengths of the same size pipe. Avoid purging through the transmitter.
Keep corrosive or hot (above 250 °F [121 °C]) process material out of direct contact
with the sensor module and flanges.
Prevent sediment deposits in the impulse piping.
Avoid conditions that might allow process fluid to freeze within the process flange.
3.4.3

In-line process connection

In-line gage transmitter orientation
CAUTION
Interfering or blocking the atmospheric reference port will cause the transmitter to output erroneous pressure values.
The low side pressure port on the inline gage transmitter is located in the neck of the transmitter, behind the housing. The vent path is 360 degrees around the transmitter between the housing and sensor (See Figure 3-6).
Keep the vent path free of any obstruction, such as paint, dust, and lubrication by mounting the transmitter so the process can drain away.
46 Emerson.com/Rosemount
Reference Manual Hardware installation
00809-0700-4001 April 2020
Figure 3-6: In-Line Gage Low Side Pressure Port
A. Low side pressure port (atmospheric reference)
CAUTION
Rotation between the sensor module and the process connection can damage the electronics.
Do not apply torque directly to the sensor module. To avoid damage, apply torque only to the hex-shaped process connection.
Rosemount 3051P 47
Hardware installation Reference Manual
April 2020 00809-0700-4001

3.5 Rosemount 306 Manifold

The Rosemount 306 Integral Manifold is used with the Rosemount 3051P In-Line Transmitter to provide block-and-bleed valve capabilities of up to 10,000 psi (690 bar).
Figure 3-7: Rosemount 3051P and 306 In-line Manifold

3.5.1 Rosemount 306 Integral Manifold installation procedure

Assemble the Rosemount 306 Manifold to the Rosemount 3051P In-Line Transmitter with a thread sealant.
48 Emerson.com/Rosemount
Reference Manual Electrical installation
00809-0700-4001 April 2020

4 Electrical installation

4.1 Overview

The information in this section covers installation considerations for the Rosemount 3051P.
Emerson ships a Quick Start Guide with every transmitter to describe pipe-fitting, wiring procedures, and basic configuration for initial installation.
Note
For transmitter disassembly and reassembly refer to sections Disassembly procedures, and
Reassembly procedures.

4.2 Safety messages

Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the Product Certifications section of the Rosemount 3051P Product Data Sheet for any restrictions associated with a safe installation.
Before connecting a handheld communicator in an explosive atmosphere, ensure that the instruments in the loop are installed in accordance with intrinsically safe or non­incendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is applied to the unit.
WARNING
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
WARNING
Process leaks could result in death or serious injury.
Install and tighten all four flange bolts before applying pressure. Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Rosemount 3051P 49
Electrical installation Reference Manual
April 2020 00809-0700-4001
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts. Improper assembly of manifolds to traditional flange can damage sensor module.
WARNING
Improper assembly of manifolds to traditional flange can damage the device.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e., bolt hole) but must not contact sensor module housing.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.

4.3 Local Operating Interface (LOI)/LCD display

Emerson ships transmitters ordered with the LCD display option (M5) or LOI option (M4) with the display installed.
Installing the display on an existing transmitter requires a small instrument screwdriver. Carefully align the desired display connector with the electronics board connector. If connectors don't align, the display and electronics board are not compatible.
50 Emerson.com/Rosemount
Reference Manual Electrical installation
00809-0700-4001 April 2020
Figure 4-1: LOI Display Assembly
4.3.1
A. LCD/LOI display
B. Extended cover
C. Captive screws

Rotate LCD/local operator interface (LOI) display

Procedure
1. Secure the loop to manual control and remove power to transmitter.
2. Remove transmitter housing cover.
3. Remove screws form the LCD/LOI display and rotate to desired orientation.
a) Insert 10-pin connector into the display board for the correct orientation.
Carefully align pins for insertion into the output board.
4. Re-insert screws.
5. Reattach transmitter housing cover.
WARNING
Explosions
Cover must be fully engaged to comply with explosion proof requirements.
6. Reattach power and return loop to automatic control.
Rosemount 3051P 51
Electrical installation Reference Manual
April 2020 00809-0700-4001

4.4 Configuring transmitter security

The transmitter has four security methods.
Security switch
HART® Lock
Configuration buttons lock
Local operator interface (LOI) password
Figure 4-2: 4–20 mA Electronics Board
Without LCD display meter With LCD display /LOI display
4.4.1
A. Alarm
B. Security

Set security switch

The security switch is used to prevent changes to the transmitter configuration data. If the security switch is set to the locked location ( ), any transmitter configuration requests
sent via HART®, local operator interface (LOI), or local configuration buttons will be rejected by the transmitter, and the transmitter configuration data will not be modified.
See Figure 4-2 for the location of the security switch. Follow the steps below to enable the security switch.
Procedure
1. Set loop to manual and remove power.
2. Remove transmitter housing cover.
3. Use a small screwdriver to slide the switch to the lock (
4. Replace transmitter housing cover.
) position.
52 Emerson.com/Rosemount
Reference Manual Electrical installation
00809-0700-4001 April 2020
WARNING
Cover must be fully engaged to comply with explosion proof requirements.

4.4.2 HART® Lock

The HART Lock prevents changes to the transmitter configuration from all sources; all changes requested via HART, local operator interface (LOI), and local configuration buttons will be rejected.
You can only set the HART Lock via HART communication, and it is only available in HART Revision 7 mode. Enable or disable the HART lock with a Field Communicator or AMS Device Manager.
Configure HART® Lock using Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
4.4.3
Device Dashboard Fast Keys
2, 2, 6, 4
Configure HART® Lock using AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Under Manual Setup, select the Security tab.
3. Select Lock/Unlock button under HART Lock (Software) and follow the screen
prompts.

Configuration button lock

The configuration button lock disables all local button functionality. Changes to the transmitter configuration from the local operator interface (LOI) and local buttons will be rejected.
You can only lock local external keys via HART® communication.
Configure button lock using the Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Rosemount 3051P 53
2, 2, 6, 3
Electrical installation Reference Manual
April 2020 00809-0700-4001
Configure button lock using AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Under Manual Setup select the Security tab.
3. Fron the Configuration Buttons dropdown menu, select Disabled to lock external
local keys.
4. Select Send.
5. Confirm service reason and click Yes.

4.4.4 Local operator interface (LOI) password

You can enter and enable an LOI password to prevent review and modification of device configuration via the LOI.
This does not prevent configuration from HART® or external keys (analog zero and span; digital zero trim). The LOI password is a four digit code that is to be set by the user. If the password is lost or forgotten the master password is 9307.
You can figure and enable or disable the LOI password with HART® communication via a Field Communicator, AMS Device Manager, or the LOI.
Configure local operator interface (LOI) password with Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 6, 5, 2
Configure local operator interface (LOI) password with AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Under Manual Setup select the Security tab.
3. Within the LOI, select the Configure Password button and follow the screen
prompts.
54 Emerson.com/Rosemount
Reference Manual Electrical installation
00809-0700-4001 April 2020
Configure local operator interface (LOI) password using LOI
Figure 4-3: LOI Password

4.5 Set transmitter alarm

On the electronics board is an alarm switch; see Figure 4-2 for switch location. Follow the steps below to change the alarm switch location.
Procedure
1. Set loop to manual and remove power.
2. Remove transmitter housing cover.
3. Use a small screwdriver to slide switch to desired position.
4. Replace transmitter cover.
WARNING
Cover must be fully engaged to comply with explosion proof requirements.

4.6 Electrical considerations

WARNING
Make sure all electrical installation is in accordance with national and local code requirements.
Do not run signal wiring in conduit or open trays with power wiring or near heavy electrical equipment.
Rosemount 3051P 55
Electrical installation Reference Manual
April 2020 00809-0700-4001

4.6.1 Conduit installation

CAUTION
If all connections are not sealed, excess moisture accumulation can damage the transmitter.
Make sure to mount the transmitter with the electrical housing positioned downward for drainage.
To avoid moisture accumulation in the housing, install wiring with a drip loop, and ensure the bottom of the drip loop is mounted lower than the conduit connections of the transmitter housing.
Figure 4-4: Recommended Conduit Installation Diagrams
4.6.2
A. Possible conduit line positions
B. Sealing compound

Power supply

4–20 mA HART® (option code A)
Transmitter operates on 10.5–42.4 Vdc at the terminal of the transmitter. The dc power supply should provide power with less than two percent ripple. A minimum of 16.6 V is required for loops with a 250 Ω resistance.
Note
A minimum loop resistance of 250 Ω is required to communicate with a Field Communicator. If a single power supply is used to power more than one transmitter, the power supply used, and circuitry common to the transmitters, should not have more that 20 Ω of impedance at 1200 Hz.
56 Emerson.com/Rosemount
Reference Manual Electrical installation
00809-0700-4001 April 2020
Figure 4-5: Load Limitation
4.6.3
Maximum loop resistance = 43.5 x (Power supply voltage – 10.5)
The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator,intrinsically safe (I.S.) barriers, and related pieces. If intrinsic safety barriers are used, the resistance and voltage drop must be included.

Wiring the transmitter

CAUTION
Incorrect wiring can damage test circuits.
Do not connect the power signal wiring to the test terminals.
Note
Use shielded twisted pairs to yield best results. To ensure proper communication, use 24 AWG or larger wire and do not exceed 5,000 ft. (1500 m).
Rosemount 3051P 57
Electrical installation Reference Manual
April 2020 00809-0700-4001
Figure 4-6: 4–20 mA HART
A. DC power supply
B. R L ≥ 250 (necessary for HART communication only)
Perform the following procedure to make wiring connections:
Procedure
1. Remove the housing cover on terminal compartment side.
®
WARNING
Signal wiring supplies all power to the transmitter. Do not remove the cover in explosive atmospheres when the circuit is live.
2. For 4–20 mA HART output, connect the positive lead to the terminal marked (pwr/
comm+) and the negative lead to the terminal marked (pwr/comm–).
CAUTION
Power could damage the test diode.
Do not connect the powered signal wiring to the test terminals.
3. Ensure full contact with terminal block screw and washer. When using a direct
wiring method, wrap wire clockwise to ensure it is in place when tightening the terminal block screw.
CAUTION
The connection may be susceptible fo loosening over time or under vibration.
Emerson does not recommend using a pin or ferrule wire.
58 Emerson.com/Rosemount
Reference Manual Electrical installation
00809-0700-4001 April 2020
4. Plug and seal unused conduit connection on the transmitter housing to avoid
moisture accumulation in the terminal side.

4.6.4 Grounding the transmitter

Ground signal cable shield
Figure 4-7 summarizes signal cable shield grounding. Trim and insulate the signal cable
shield and unused shield drain wire to ensure that the signal cable shield and drain wire do not come in contact with the transmitter.
See Transmitter case grounding for instructions on grounding the transmitter case. Follow the steps below to correctly ground the signal cable shield.
Procedure
1. Remove the field terminals housing cover.
2. Connect the signal wire pair at the field terminals as indicated in Figure 4-6.
3. At the field terminals, trim the cable shield and shield drain wire close and insulate
them from transmitter housing.
4. Reattach the field terminals housing cover.
WARNING
Cover must be fully engaged to comply with explosion proof requirements.
5. At terminations outside the transmitter housing, ensure that the cable shield drain
wire is continuously connected.
a) Prior to the termination point, insulate any exposed shield drain wire as
shown in Figure 4-7 (B).
6. Properly terminate the signal cable shield drain wire to an earth ground at or near
the power supply.
Rosemount 3051P 59
DP
A
B
C
Electrical installation Reference Manual
April 2020 00809-0700-4001
Figure 4-7: Wiring Pair and Ground
A. Insulate shield and shield drain wire.
B. Insulate exposed shield drain wire.
C. Terminate cable shield drain wire to earth ground.
Transmitter case grounding
The most effective transmitter case grounding method is a direct connection to earth ground with minimal impedance.
WARNING
Always ground the transmitter case in accordance with national and local electrical codes.
Methods for grounding the transmitter case include:
Internal ground connection: the internal ground connection screw is inside the FIELD
TERMINALS side of the electronics housing. This screw is identified by a ground symbol ( ). The ground connection screw is standard on all Rosemount 3051P Transmitters. Refer to Figure 4-8.
60 Emerson.com/Rosemount
Reference Manual Electrical installation
00809-0700-4001 April 2020
Figure 4-8: Internal Ground Connection
A. Internal ground location
B. External ground location
C. Positive
D. Negative
E. Test
External ground connection: The external ground connection is located on the exterior
of the transmitter housing. Refer to Figure 4-8. This connection is only available with option T1.
WARNING
Grounding the transmitter case via threaded conduit connection may not provide sufficient ground continuity.
Transient protection terminal block grounding
The transmitter can withstand electrical transients of the energy level usually encountered in static discharges or induced switching transients. However, high-energy transients, such as those induced in wiring from nearby lightning strikes, can damage the transmitter.
You can order the transient protection terminal block as an installed option (option code T1) or as a spare part to retrofit existing Rosemount 3051P Transmitters in the field. See the Rosemount 3051P Product Data Sheet for part numbers. The lightning bolt symbol shown in Figure 4-9 identifies the transient protection terminal block.
Rosemount 3051P 61
Electrical installation Reference Manual
April 2020 00809-0700-4001
Figure 4-9: Transient Protection Terminal Block
A. Lightning bolt location
Note
The transient protection terminal block does not provide transient protection unless the transmitter case is properly grounded. Use the guidelines to ground the transmitter case. Refer to Figure 4-8.
62 Emerson.com/Rosemount
Reference Manual Operation and maintenance
00809-0700-4001 April 2020

5 Operation and maintenance

5.1 Overview

This section contains information on calibrating Rosemount 3051P Pressure Transmitters.
This section gives instructions on using the Field Communicator, AMS Device Manager and Local Operator Interface (LOI) to calibrate the transmitter.

5.2 Safety messages

Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the Product Certifications section of the Rosemount 3051P Product Data Sheet for any restrictions associated with a safe installation.
Before connecting a handheld communicator in an explosive atmosphere, ensure that the instruments in the loop are installed in accordance with intrinsically safe or non­incendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is applied to the unit.
WARNING
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
WARNING
Process leaks could result in death or serious injury.
Install and tighten all four flange bolts before applying pressure. Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Rosemount 3051P 63
Operation and maintenance Reference Manual
April 2020 00809-0700-4001
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts. Improper assembly of manifolds to traditional flange can damage sensor module.
WARNING
Improper assembly of manifolds to traditional flange can damage the device.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e., bolt hole) but must not contact sensor module housing.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.

5.3 Recommended calibration tasks

CAUTION
Emerson calibrates absolute pressure transmitters at the factory.
Trimming adjusts the position of the factory calibration curve. If you trim the transmitter improperly or with inaccurate equipment, you may degrade the transmitter's performance.

5.3.1 Calibrate in the field

Procedure
1. Perform sensor zero/lower trim: Compensate for mounting pressure effects
Refer to Rosemount 306 Manifold for manifold operation instructions to properly drain/vent valves.
2. Set/check basic configuration parameters
a. Output units
64 Emerson.com/Rosemount
Reference Manual Operation and maintenance
00809-0700-4001 April 2020
b. Range points
c. Output type
d. Damping value

5.3.2 Calibrate on the bench

Procedure
1. Perform optional 4–20 mA output trim.
2. Perform a sensor trim.
a) Zero/lower trim using line pressure effect correction.
Reference Hardware installation for manifold drain/vent valve operation instructions.
b) Perform an optional full scale trim, which sets the span of the device and
requires accurate calibration equipment.
c) Set/check basic configuration parameters.

5.4 Calibration overview

Emerson fully calibrates the Rosemount 3051P at the factory to ensure accuracy. You can also calibrate the transmitter in the field to meet plant requirements or industry standards. Complete calibration of the transmitter can be split into two halves: sensor calibration and analog output calibration.
With sensor calibration, you can adjust the pressure (digital value) reported by the transmitter to be equal to a pressure standard. The sensor calibration can adjust the pressure offset to correct for mounting conditions or line pressure effects. Emerson recommends making this correction. The calibration of the pressure range (pressure span or gain correction) requires accurate pressure standards (sources) to provide a full calibration.
Like the sensor calibration, you can calibrate the analog output to match the user measurement system. The analog output trim (4–20 mA) will calibrate the loop at the 4 m and 20 mA points.
The sensor calibration and the analog output calibration combine to match the transmitter’s measurement system to the plant standard.
Calibrate the sensor
Performing a sensor trim
Perform a digital zero trim (option DZ)
Calibrate the 4–20 mA output
Performing digital-to-analog trim (4–20mA output trim)
Performing digital-to-analog trim (4–20mA output trim) using other scale
Rosemount 3051P 65
Operation and maintenance Reference Manual
April 2020 00809-0700-4001

5.4.1 Determine necessary sensor trims

Bench calibrations allow for calibrating the instrument for its desired range of operation. Straight forward connections to pressure source allow for a full calibration at the planned operating points. Exercising the transmitter over the desired pressure range allows for verification of the analog output.
Trimming the pressure signal outlines how the trim operations change the calibration. It is
possible to degrade the performance of the transmitter if a trim is done improperly or with inaccurate equipment. To set the transmitter back to factory settings, see Recall factory
trim—sensor trim. Determine the necessary trims with the following steps.
Procedure
1. Apply pressure.
2. Check digital pressure; if the digital pressure does not match the applied pressure,
perform a digital trim. See Performing a sensor trim .
3. Check reported analog output against the live analog output. If they do not match,
perform an analog output trim. See Performing digital-to-analog trim (4–20mA output trim).
Trim with configuration buttons
Local configuration buttons are external buttons located underneath the top tag of the transmitter. There are two possible sets of local configuration buttons you can order with the transmitter and use to perform trim operations: Digital zero trim and LOI.
Procedure
To access the buttons, loosen screw and rotate top tag until buttons are visible.
LOI (M4): Can perform both digital sensor trim and the 4–20 mA output trim (analog
output trim). Follow the same procedures listed in trimming with Field Communicator or AMS Device Manager listed below.
Analog zero and span (D4): Used to rerange the transmitter with an applied pressure.
Digital zero trim (DZ): Used for performing a sensor zero trim. See Determine
calibration frequency for trim instructions.
Monitor all configuration changes either on the display or by measuring the loop output..
Figure 5-1 shows the physical differences between the two sets of buttons.
66 Emerson.com/Rosemount
Reference Manual Operation and maintenance
00809-0700-4001 April 2020
Figure 5-1: Local Configuration Button Options
A. Analog zero and span (D4)- green retainer
B. Digital zero trim (DZ)- blue retainer
5.4.2

Determine calibration frequency

Calibration frequency can vary greatly depending on the application, performance requirements, and process conditions. Use the following procedure to determine calibration frequency that meets the needs of your application.
Procedure
1. Determine the performance required for your application.
Example
Required Performance:
2. Determine the operating conditions.
Example
Transmitter
Calibrated span 30 psi (2.1 bar)
Ambient temperature change
3. Calculate the total probable error (TPE).
Example
Rosemount 3051P, Range 1 [URL = 30 psi (2.1 bar)]
±50 °F (28 °C)
0.50 percent of span
TPE
Where:
Reference accuracy
Ambient temperature effect
Static pressure effect 0 percent (does not apply to in-line products)
Rosemount 3051P 67
± 0.040 percent of span
±(0.05 percent URL + 0.25 percent of span) per 50 °F (28 °C) = ±0.3 percent of span
= 0.303 percent of span
Operation and maintenance Reference Manual
April 2020 00809-0700-4001
4. Calculate the stability per month.
Example
Stability
5. Calculate the calibration frequency.
Example
Calibration frequency

5.5 Trimming the pressure signal

5.5.1 Sensor trim overview

A sensor trim corrects the pressure offset and pressure range to match a pressure standard. The upper sensor trim corrects the pressure range, and the lower sensor trim (zero trim) corrects the pressure offset. An accurate pressure standard is required for full calibration. You can perform a zero trim if the process is vented.
Zero trim is a single-point offset adjustment. It is useful for compensating for mounting position effects and is most effective when performed with the transmitter installed in its final mounting position. Since this correction maintains the slope of the characterization curve, do not use it in place of a sensor trim over the full sensor range.
Note
Do not perform a zero trim on Rosemount 3051P Absolute Pressure Transmitters. Zero trim is zero based, and absolute pressure transmitters reference absolute zero. To correct mounting position effects on an absolute pressure transmitter, perform a low trim within the sensor trim function. The low trim function provides an offset correction similar to the zero trim function, but it does not require zero-based input.
Upper and lower sensor trim is a two-point sensor calibration where two end-point pressures are applied and all output is linearized between them; this trim requires an accurate pressure source. Always adjust the low trim value first to establish the correct offset. Adjustment of the high trim value provides a slope correction to the characterization curve based on the low trim value. The trim values help optimize performance over a specific measurement range.
68 Emerson.com/Rosemount
Reference Manual Operation and maintenance
00809-0700-4001 April 2020
Figure 5-2: Sensor Trim Example
A. Before trim
B. After trim
5.5.2

Performing a sensor trim

When performing a sensor trim, you can trim both the upper and lower limits. If doing both upper and lower trims, perform the lower trim before the upper time.
Note
Use a pressure input source that is at least four times more accurate than the transmitter and allow the input pressure to stabilize for 10 seconds before entering any values.
Perform a sensor trim with a Field Communicator
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field Communicator to complete the sensor trim.
Device Dashboard Fast Keys
To calibrate the sensor with a Field Communicator using the sensor trim function:
Procedure
1. Select 2: Lower Sensor Trim.
Note
Select pressure points so that lower and upper values are equal to or outside the expected process operation range. To do this, see Reranging the transmitter.
2. Follow the commands provided by the Field Communicator to complete the
adjustment of the lower value.
3. Select 3: Upper Sensor Trim.
4. Follow the commands provided by the Field Communicator to complete the
adjustment of the upper value.
3, 4, 1
Rosemount 3051P 69
Operation and maintenance Reference Manual
April 2020 00809-0700-4001
Perform a sensor trim with AMS Device Manager
Procedure
1. Right click the device and, under the Method drop down menu, move the cursor
over Calibrate.
2. Under Sensor Trim, select Lower Sensor Trim.
3. Follow the screen prompts to perform a sensor trim using AMS Device Manager.
4. If desired, repeat Step 1.
5. Under Sensor Trim, select Upper Sensor Trim.
Perform a sensor trim using local operator interface (LOI)
Procedure
See Figure 5-3 to perform an upper and lower sensor trim.
Figure 5-3: Sensor Trim with LOI
Perform a digital zero trim (option DZ)
A digital zero trim (option DZ) provides the same function as a zero/lower sensor trim, but you can complete it in hazardous areas at any given time by pushing the Zero Trim button when the transmitter is at zero pressure.
If the transmitter is not close enough to zero when the button is pushed, the command may fail due to excess correction. If ordered, you can use external configuration buttons located underneath the top tag of the transmitter to perform a digital zero trim. See
Figure 5-1 for DZ button location.
Procedure
1. Loosen the top tag of the transmitter to expose buttons.
2. Press and hold the digital zero button for at least two seconds; then release to
perform a digital zero trim.
70 Emerson.com/Rosemount
Reference Manual Operation and maintenance
00809-0700-4001 April 2020

5.5.3 Recall factory trim—sensor trim

The recall factory trim-sensor trim command allows the restoration of the as-shipped factory settings of the sensor trim. You can use this command to recover from an inadvertent zero trim of an absolute pressure unit or inaccurate pressure source.
Recall factory trim with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field Communicator to complete the sensor trim.
Device Dashboard Fast Keys 3, 4, 3
Recall factory trim with AMS Device Manager
Procedure
1. Right click on the device and, under the Method dropdown menu, move cursor over
Calibrate and select Restore Factory Calibration.
2. Set the control loop to manual.
3. Select Next.
4. Select Sensor Trim under Trim to recall and click Next.
5. Follow the screen prompts to recall Sensor Trim.
Recall factory trim with local operator interface (LOI)
Procedure
Refer to Figure 5-4 to recall factory sensor trim.
Figure 5-4: Recall Factory Trim with LOI
Rosemount 3051P 71
Operation and maintenance Reference Manual
April 2020 00809-0700-4001

5.6 Trimming the analog output

The Analog Output Trim commands allow you to adjust the transmitter's current output at the 4 and 20 mA points to match the plant standards.
Perform this trim after the digital to analog conversion, so only the 4–20 mA analog signal will be affected. Figure 5-5 graphically shows the two ways the characterization curve is affected when an analog output trim is performed.
Figure 5-5: Analog Output Trim Example
5.6.1
A. Before trim
B. After trim

Performing digital-to-analog trim (4–20mA output trim)

Note
If adding a resistor to the loop, ensure that the power supply is sufficient to power the transmitter to a 20 mA output with additional loop resistance. Refer to Power supply.
Perform a 4–20 mA output trim with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field Communicator to complete the 4–20 mA output trim.
Device Dashboard Fast Keys
Perform a 4–20 mA output trim with AMS Device Manager
Procedure
1. Right click the device and, under the Method drop down menu, move the cursor
over Calibrate and select Analog Calibration.
2. Select Digital to Analog Trim.
3. Follow the screen prompts to perform a 4–20 mA output trim.
3, 4, 2, 1
72 Emerson.com/Rosemount
Reference Manual Operation and maintenance
00809-0700-4001 April 2020
Perform a 4–20 mA output trim using local operator interface (LOI)
Figure 5-6: 4–20mA Output Trim using LOI

5.6.2 Performing digital-to-analog trim (4–20mA output trim) using other scale

The scaled 4–20 mA output trim command matches the 4 and 20 mA points to a user selectable reference scale other than 4 and 20 mA (e.g., 2 to 10 volts if measuring across a 500 Ω load, or 0 to 100 percent if measuring from a Distributed Control System [DCS]). To perform a scaled 4–20 mA output trim, connect an accurate reference meter to the transmitter and trim the output signal to scale, as outlined in the output trim procedure.
Perform a 4–20 mA output trim using other scale with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field Communicator to complete the 4–20 mA output trim using other scale.
Device Dashboard Fast Keys
Perform a 4–20 mA output trim using other scale with AMS Device Manager
Procedure
1. Right click the device and, under the Method dropdown menu, move the cursor over Calibrate and select Analog Calibration.
2. Select Scaled Digital to Analog Trim.
3. Follow screen prompts to perform a 4–20mA output trim.
3, 4, 2, 2
Rosemount 3051P 73
Operation and maintenance Reference Manual
April 2020 00809-0700-4001

5.6.3 Recalling factory trim—analog output

The Recall Factory Trim—Analog Output command allows the restoration of the as­shipped factory settings of the analog output trim.
This command can be useful for recovering from an inadvertent trim, incorrect plant standard or faulty meter.
Recall factory trim - analog output with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field Communicator to complete the digital to analog trim using other scale.
Device Dashboard Fast Keys
3, 4, 3
Recall factory trim - analog output with AMS Device Manager
Procedure
1. Right click the device and, under the Method drop down menu, move the cursor over Calibrate and select Restore Factory Calibration.
2. Select Next to set the control loop to manual.
3. Select Analog Output Trim under Select Trim to recall and click Next.
4. Follow screen prompts to recall analog output trim.
Recall factory trim - analog output with local operator interface (LOI)
Procedure
Reference Figure 5-7 for LOI instructions.
Figure 5-7: Recall Factory Trim – Analog Output with LOI
74 Emerson.com/Rosemount
Reference Manual Operation and maintenance
00809-0700-4001 April 2020

5.7 Switching HART® revision

Some systems are not capable of communicating with HART Revision 7 devices. The following procedures list how to change HART revisions between HART Revision 7 and HART Revision 5.

5.7.1 Switch HART® revision with generic menu

If the HART configuration tool is not capable of communicating with a HART Revision 7 device, it should load a generic menu with limited capability. The following procedures allow for switching between HART Revision 7 and HART Revision 5 from a generic menu.
Procedure
1. To change to HART Revision 5, enter HART5 in the Message field.
2. To change to HART Revision 7, enter HART7 in the Message field.
5.7.2

Switch HART® revision with Field Communicator

Procedure
From the HOME screen, enter the Fast Key sequence and follow steps within the Field Communicator to complete the HART revision change.
HART5
Device Dashboard Fast Keys 2, 2, 5, 2, 4 2, 2, 5, 2, 3
HART7

5.7.3 Switch HART® revision with AMS Device Manager

Procedure
1. Select Manual Setup and select HART.
2. Select Change HART Revision; then follow the on screen prompts.
Note
AMS Device Manager versions 10.5 or greater are compatible with HART Revision 7.
5.7.4

Switch HART® revision with local operator interface (LOI)

Procedure
Navigate to HART REV within the extended menu and select either HART REV 5 or HART REV 7. Use Figure 5-8 to change HART Revision.
Rosemount 3051P 75
Operation and maintenance Reference Manual
April 2020 00809-0700-4001
Figure 5-8: Change HART Revision with LOI
76 Emerson.com/Rosemount
Reference Manual Troubleshooting
00809-0700-4001 April 2020

6 Troubleshooting

6.1 Overview

This section provides summarized maintenance and troubleshooting suggestions for the most common operating problems.
If you suspect malfunction despite the absence of any diagnostic messages on the Field Communicator display, consider using Diagnostic messages to identify any potential problem.

6.2 Safety messages

Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the Product Certifications section of the Rosemount 3051P Product Data Sheet for any restrictions associated with a safe installation.
Before connecting a handheld communicator in an explosive atmosphere, ensure that the instruments in the loop are installed in accordance with intrinsically safe or non­incendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is applied to the unit.
WARNING
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
WARNING
Process leaks could result in death or serious injury.
Install and tighten all four flange bolts before applying pressure. Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Rosemount 3051P 77
Troubleshooting Reference Manual
April 2020 00809-0700-4001
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts. Improper assembly of manifolds to traditional flange can damage sensor module.
WARNING
Improper assembly of manifolds to traditional flange can damage the device.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e., bolt hole) but must not contact sensor module housing.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.

6.3 Troubleshooting for 4-20 mA output

6.3.1 Transmitter milliamp reading is zero

Recommended actions
1. Verify terminal voltage is 10.5 to 42.4 Vdc at signal terminals.
2. Check power wires for reversed polarity.
3. Check that power wires are connected to signal terminals.
4. Check for open diode across test terminal.
6.3.2

Transmitter not communicating with Field Communicator

Recommended actions
1. Verify terminal voltage is 10.5 to 42.2 Vdc.
2. Check loop resistance, 250 Ω minimum (PS voltage - transmitter voltage/loop current).
78 Emerson.com/Rosemount
Reference Manual Troubleshooting
00809-0700-4001 April 2020
3. Check that power wires are connected to signal terminals and not test terminals.
4. Verify clean DC power to transmitter (maximum AC noise 0.2 volts peak to peak).
5. Verify the output is between 4 and 20 mA or saturation levels.
6. Have Field Communicator poll for all addresses.

6.3.3 Transmitter milliamp reading is low or high

Recommended actions
1. Verify applied pressure.
2. Verify 4 and 20 mA range points.
3. Verify output is not in alarm condition.
4. Perform analog trim.
5. Check that power wires are connected to the correct signal terminals (positive to positive, negative to negative) and not the test terminal.
6.3.4
6.3.5

Transmitter will not respond to changes in applied pressure

Recommended actions
1. Check impulse piping or manifold for blockage.
2. Verify applied pressure is between 4 and 20 mA points.
3. Verify the output is not in alarm condition.
4. Verify transmitter is not in loop test mode.
5. Verify transmitter is not in multidrop mode.
6. Check test equipment.

Digital pressure variable reading is low or high

Recommended actions
1. Check impulse piping for blockage or low fill in wet leg.
2. Verify transmitter is calibrated properly.
3. Check test equipment (verify accuracy).
4. Verify pressure calculations for application.
6.3.6
Rosemount 3051P 79

Digital pressure variable reading is erratic

Recommended actions
1. Check application for faulty equipment in pressure line.
2. Verify transmitter is not reacting directly to equipment turning on/off.
Troubleshooting Reference Manual
April 2020 00809-0700-4001
3. Verify damping is set properly for application.

6.3.7 Milliamp reading is erratic

Recommended actions
1. Verify power source to transmitter has adequate voltage and current.
2. Check for external electrical interference.
3. Verify transmitter is properly grounded.
4. Verify shield for twisted pair is only grounded at one end.

6.4 Diagnostic messages

The following are possible messages that will appear on either the LCD/LOI display, a Field Communicator, or an AMS Device Manager system.
Good
Failed – fix now
6.4.1
Maintenance – fix soon
Advisory

Status: Failed - Fix Now

No pressure updates
LCD display screen
Local operator interface (LOI) screen
There are no pressure updates from the sensor to the electronics.
Recommended actions
1. Ensure the sensor cable connection to the electronics is tight.
2. Replace the transmitter.
Electronics board failure
LCD display screen
NO P UPDATE
NO PRESS UPDATE
FAIL BOARD
Local operator interface (LOI) screen
A failure has been detected in the electronics circuit board.
80 Emerson.com/Rosemount
FAIL BOARD
Reference Manual Troubleshooting
00809-0700-4001 April 2020
Recommended action
Replace the pressure transmitter.
Critical sensor data error
LCD display screen
Local operator interface (LOI) screen
A user-written parameter does not match the expected value.
Recommended actions
1. Confirm and correct all parameters listed in Device Information.
2. Perform a device reset.
3. Replace pressure transmitter.
MEMRY ERROR
MEMORY ERROR
Critical electronics data error
LCD display screen
Local operator interface (LOI) screen
A user-written parameter does not match the expected value.
Recommended actions
MEMRY ERROR
MEMORY ERROR
1. Confirm and correct all parameters listed in Device Information.
2. Perform a device reset.
3. Replace pressure transmitter.
Sensor failure
LCD display screen
Local operator interface (LOI) screen
A failure has been detected in the pressure sensor.
Recommended action
Replace pressure transmitter.
Rosemount 3051P 81
FAIL SENSOR
FAIL SENSOR
Troubleshooting Reference Manual
April 2020 00809-0700-4001
Incompatible electronics and sensor
6.4.2
LCD display screen
Local operator interface (LOI) screen
The pressure sensor is incompatible with the attached electronics.
Recommended action
Replace the pressure transmitter.
XMTR MSMTCH
XMTR MSMTCH

Status: Maintenance - Fix Soon

No temperature updates
LCD display screen
Local operator interface (LOI) screen
There are no temperature updates from the sensor to the electronics.
Recommended actions
NO T UPDATE
NO TEMP UPDATE
1. Ensure the sensor cable connection to the electronics is tight.
2. Replace the pressure transmitter.
Pressure out of limits
LCD display screen
Local operator interface (LOI) screen
The pressure is either above or below the sensor limits.
Recommended actions
1. Check the transmitter pressure connection to ensure it is not plugged and the
2. Replace the pressure transmitter.
NO T UPDATE
PRES OUT LIMITS
isolating diaphragms are not damaged.
Sensor temperature beyond limits
LOI display screen
TEMP LIMITS
82 Emerson.com/Rosemount
Reference Manual Troubleshooting
00809-0700-4001 April 2020
Local operator interface (LOI) screen
The sensor temperature has exceeded its safe operating range.
Recommended actions
1. Check the process and ambient conditions are within -85 to 194 °F (-65 to 90
2. Replace the pressure transmitter.
TEMP OUT LIMITS
°C).
Electronics temperature beyond limits
LCD display screen
Local operator interface (LOI) screen
The temperature of the electronics has exceeded its safe operating range.
Recommended actions
1. Confirm electronics temperature is within limits of -85 to 194 °F (-65 to 90 °C).
2. Replace the pressure transmitter.
TEMP LIMITS
TEMP OUT LIMITS
Electronics board parameter error
LCD display screen
Local operator interface (LOI) screen
A device parameter does not match the expected value. The error does not affect transmitter operation or analog output.
Recommended action
Replace the pressure transmitter.
MEMRY WARN (also in advisory)
MEMORY WARN (also in advisory)
Configuration buttons operator error
LCD display screen
Local operator interface (LOI) screen
Device is not responding to button presses.
STUCK BUTTON
STUCK BUTTON
Rosemount 3051P 83
Troubleshooting Reference Manual
April 2020 00809-0700-4001
Recommended actions
1. Check configuration buttons are not stuck.
2. Replace the pressure transmitter.

6.4.3 Status: Advisory

Non-critical user data warning
LCD display screen
Local operator interface (LOI) screen
A user-written parameter does not match expected value.
Recommended actions
1. Confirm and correct all parameters listed in Device Information.
2. Perform a Device Reset.
3. Replace the pressure transmitter.
MEMRY WARN
MEMORY WARN
Sensor parameter warning
LCD display screen
Local operator interface (LOI) screen
A user-written parameter does not match expected value.
Recommended actions
MEMRY WARN
MEMORY WARN
1. Confirm and correct all parameters listed in Device Information.
2. Perform a Device Reset.
3. Replace pressure transmitter.
LCD display update failure
LCD display screen
Local operator interface (LOI) screen
The LCD display is not receiving updates from the pressure sensor.
84 Emerson.com/Rosemount
(Not updating)
(Not updating)
Reference Manual Troubleshooting
00809-0700-4001 April 2020
Recommended actions
1. Check the connection between the LCD and the circuit board.
2. Replace the LCD display.
3. Replace the electronics board.
4. Replace the pressure transmitter.
Configuration changed
LCD display screen
Local operator interface (LOI) screen
A recent change has been made to the device by a secondary HART® master, such as a handheld device.
Recommended actions
1. Verify that the configuration change of the device was intended and expected.
2. Clear this alert by selecting Clear Configuration Changed Status.
3. Connect a HART master, such as AMS or similar, which will autmatically clear
(None)
(None)
the alert.
Analog output fixed
LCD display screen
Local operator interface (LOI) screen
ANLOG FIXED
ANALOG FIXED
The analog output is fixed and does not represent the process measurement.
This may be caused by other conditions in the device or because the device has been set to loop test or multidrop mode.
Recommended actions
1. Take action on any other notifications from the device.
2. If the device is in a loop test and should no longer be, disable or momentarily remove power.
3. If the device is in multidrop mode and should not be, re-enable loop current by setting the polling address to 0.
Simulation active
LCD display screen
Rosemount 3051P 85
(None)
Troubleshooting Reference Manual
April 2020 00809-0700-4001
Local operator interface (LOI) screen
The device is in simulation mode and may not be reporting actual information.
Recommended actions
1. Verify that simulation is no longer required.
2. Disable simulation mode in service tools.
3. Perform a Device Reset.
(None)
Analog output saturated
LCD display screen
Local operator interface (LOI) screen
The analog output is saturated either high or low due to the pressure either above or below the range values.
Recommended actions
1. Check the pressure applied to ensure it is between the 4 and 20 mA points.
2. Check the transmitter pressure connection to ensure it is not plugged and the
3. Replace the pressure transmitter.
ANLOG SAT
ANALOG SAT
isolating diaphragms are not damaged.

6.5 Disassembly procedures

WARNING
Do not remove cover in explosive atmospheres when the circuit is live.

6.5.1 Remove from service

WARNING
Follow all plant safety rules and procedures.
Procedure
1. Power down transmitter.
2. Isolate and vent the process from the transmitter before removing the transmitter from service.
3. Remove all electrical leads and disconnect conduit.
86 Emerson.com/Rosemount
Reference Manual Troubleshooting
00809-0700-4001 April 2020
4. Remove the transmitter from the process connection.
a) The transmitter is attached to the process by a single hex nut process
connection. Loosen the hex nut to separate the transmitter from the process.
CAUTION
Do not wrench on neck of transmitter. See warning in In-line process connection.
5. Do not scratch, puncture, or depress the isolating diaphragms.
6. Clean isolating diaphragms with a soft rag and a mild cleaning solution and rinse with clear water.

6.5.2 Remove terminal block

Electrical connections are located on the terminal block in the compartment labeled FIELD TERMINALS.
Procedure
6.5.3
1. Remove the housing cover from the field terminal side.
2. Loosen the two small screws located on the assembly in the 9 and 5 o’clock positions relative to the top of the transmitter.
3. Pull the entire terminal block out to remove it.

Remove the local operator interface (LOI) or LCD display

Rosemount 3051P transmitters with M4 or M5 option codes have an LOI or LCD display. The transmitter LOI/LCD display is located in the compartment opposite the terminal side. To remove and/or replace the LOI/LCD display, perform the following procedures:
Procedure
1. Remove the housing cover opposite the field terminal side.
2. Loosen the two captive screws that are visible. See Figure 4-2 for screw locations. The two screws anchor the LOI/LCD display to
the electronics board and the electronics board to the housing. See Safety
messages.
3. After the loosening the screws, pull the LOI/LCD display off of the electronics board and out of the housing.
CAUTION
Make sure to pull directly backwards to avoid bending or damaging the connection pins on the electronics board.
Rosemount 3051P 87
Troubleshooting Reference Manual
April 2020 00809-0700-4001
CAUTION
Do not attempt to pull out the electronics board from the housing, as this could permanently damage the transmitter.

6.6 Reassembly procedures

6.6.1 Install the local operator interface (LOI) or LCD display

Procedure
1. While aligning the captive screws with the respective holes on the electronics board, connect the LCD/LOI display to the electronics board by pressing down firmly.
2. Make sure the connecting pins on the back of the LCD fully connect to the front of the electronics board.
3. Fully tighten down the captive screws.
4. Replace the housing cover.
WARNING
Ensure the transmitter is fully engaged to meet Explosion-Proof requirement.

6.7 Service support

Within the United States, call the Emerson Instrument and Valve Response Center using the 1-800-654-RSMT (7768) toll-free number. This center, available 24 hours a day, will assist you with any needed information or materials.
The center will ask for product model and serial numbers, and will provide a Return Material Authorization (RMA) number. The center will also ask for the process material to which the product was last exposed.
For inquiries outside of the United States, contact the nearest Emerson representative for RMA instructions.
To expedite the return process outside of the United States, contact the nearest Emerson representative.
WARNING
Individuals who handle products exposed to a hazardous substance can avoid injury if they are informed of and understand the hazard. The product being returned will require a copy of the required Material Safety Data Sheet (MSDS) for each substance must be included with the returned goods.
88 Emerson.com/Rosemount
Reference Manual Troubleshooting
00809-0700-4001 April 2020
Emerson Instrument and Valve Response Center representatives will explain the additional information and procedures necessary to return goods exposed to hazardous substances.
Rosemount 3051P 89
Troubleshooting Reference Manual
April 2020 00809-0700-4001
90 Emerson.com/Rosemount

Reference Manual Safety instrumented systems requirements

00809-0700-4001 April 2020
7 Safety instrumented systems
requirements

7.1 Safety instrumented systems (SIS) certification

The safety-critical output of the Rosemount 3051P is provided through a two-wire, 4 - 20 mA signal representing pressure. The Rosemount 3051P safety certified pressure transmitter is certified to: Low Demand; Type B. SIL 2 for random integrity @ HFT=0 SIL 3 for random integrity @ HFT=1 SIL 3 for systematic integrity

7.2 Safety certified identification

All Rosemount 3051P Transmitters must be identified as safety certified before installing into SIS systems.
To identify a safety certified Rosemount 3051P:
Procedure
1. Check Namur Software Revision located on the metal device tag. "SW _._._".
Example
Namur Software Revision Number
SW
Note
Namur Software Revision: Located on the metal device tag.
2. Verify that option code QT is included in the transmitter model code.
1.0.x - 1.4.x

7.3 Installation in safety instrumented systems (SIS) applications

Only qualified personnel should install the transmitter in SIS applications. No special installation is required in addition to the standard installation practices outlined in this document.
WARNING
Always ensure a proper seal by installing the electronics housing cover(s) so that metal contacts metal.
Environmental and operational limits are available in the Rosemount 3051P Product Data
Sheet.
Rosemount 3051P 91
Safety instrumented systems requirements Reference Manual
April 2020 00809-0700-4001
Design the loop so that the terminal voltage does not drop below 10.5 Vdc when the transmitter output is set to 23 mA. For more information see the Rosemount 3051P
Product Data Sheet.
Position the security switch to the ( ) position to prevent accidental or deliberate change of configuration data during normal operation.

7.4 Configuring in safety instrumented systems (SIS) applications

Use any HART® capable configuration tool to communicate with and verify configuration of the Rosemount 3051P.
Note
Transmitter output is not safety-rated during the following: configuration changes, multidrop, and loop test. Use alternative means to ensure process safety during transmitter configuration and maintenance activities.
7.4.1

Damping

User-selected damping will affect the transmitters ability to respond to changes in the applied process. The damping value and response time must not exceed the loop requirements.
Reference Damping to change damping value.
92 Emerson.com/Rosemount
Reference Manual Safety instrumented systems requirements
00809-0700-4001 April 2020

7.4.2 Alarm and saturation levels

Configure DCS or safety logic solver to match transmitter configuration. Figure 7-1 identifies the three alarm levels available and their operation values.
Figure 7-1: Alarm Levels
Rosemount alarm level
Namur alarm level
Custom alarm level
A. Transmitter failure, hardware or software alarm in LO position.
B. Transmitter failure, hardware or software alarm in HI position.

7.5 Safety instrumented systems (SIS) operation and maintenance

7.5.1 Proof tests

Emerson recommends the following proof tests. Ensure that only qualified personnel perform proof tests.
Use Fast Keys to perform a loop test, analog output trim, or sensor trim. Place the security switch in the (
after execution.
) position during proof test execution and reposition it in the ( ) position
Rosemount 3051P 93
Safety instrumented systems requirements Reference Manual
April 2020 00809-0700-4001

7.5.2 Partial proof test

The partial suggested proof test consists of a power cycle plus reasonability checks of the transmitter output. Reference the FMEDA Report for percent of possible DU failures in the device.
See the FMEDA Report.
Prerequisites
Required tools: Field Communicator and mA meter.
Procedure
1. Bypass the safety function and take appropriate action to avoid a false trip.
2. Use HART® communications to retrieve any diagnostics and take appropriate action.
3. Send a HART command to the transmitter to go to the high alarm current output and verify that the analog current reaches that value.
Note
This tests for compliance voltage problems such as a low loop power supply voltage or increased wiring distance. This also tests for other possible failures.
7.5.3
See Verifying alarm level.
4. Send a HART command to the transmitter to go to the low alarm current output and verify that the analog current reaches that value.
Note
This tests for possible quiescent current related failures.
5. Inspect the device for any leaks, visible damage, or contamination.
6. Remove the bypass and otherwise restore the normal operation.
7. Place the Security switch in the (
) position.

Comprehensive proof test

The comprehensive proof test consists of performing the same steps as the partial proof test but with a two point calibration of the pressure sensor in place of the reasonability check. Reference the FMEDA Report for percent of possible DU failures in the device.
Prerequisites
Required tools: Field Communicator and pressure calibration equipment.
Procedure
1. Bypass the safety function and take appropriate action to avoid a false trip.
2. Use HART® communications to retrieve any diagnostics and take appropriate action.
3. Send a HART command to the transmitter to go to the high alarm current output and verify that the analog current reaches that value.
94 Emerson.com/Rosemount
Reference Manual Safety instrumented systems requirements
00809-0700-4001 April 2020
Note
This tests for compliance voltage problems such as a low loop power supply voltage or increased wiring distance. This also tests for other possible failures.
See Verifying alarm level.
4. Send a HART command to the transmitter to go to the low alarm current output and verify that the analog current reaches that value.
Note
This tests for possible quiescent current related failures.
5. Inspect the device for any leaks, visible damage or contamination.
6. Perform a two-point calibration of the sensor (see Trimming the pressure signal) over the full working range and verify the current output at each point.
7. Remove the bypass and otherwise restore the normal operation.
8. Place the Security switch in the ( ) position.
Note
The user determines the proof test requirements for impulse piping.
Automatic diagnostics are defined for the corrected % DU: The tests performed
internally by the device during runtime without requiring enabling or programming by the user.

7.6 Inspection

7.6.1 Visual inspection

Not required.
7.6.2
7.6.3

Special tools

Not required.

Product repair

The transmitter is repairable with limited replacement options.
Report all failures detected by the transmitter diagnostics or by the proof test. Submit feedback electronically at Emerson.com/Rosemount/Report-A-Failure
Only qualified personnel should repair the product and replace parts.
Rosemount 3051P 95
Safety instrumented systems requirements Reference Manual
April 2020 00809-0700-4001

7.6.4 Safety instrumented systems (SIS) reference

Operate the transmitter in accordance to the functional and performance specifications provided in the Rosemount 3051P Product Data Sheet.

7.6.5 Failure rate data

The FMEDA Report includes failure rates.

7.6.6 Failure values

Safety Deviation (defines what is dangerous in an FMEDA): ±2.0% of analog output span Transmitter response time: provided in Dynamic performance. Self-diagnostics Test Interval: At least once every 60 minutes.
7.6.7

Product life

50 years: based on worst case component wear-out mechanisms, not based on wear-out of process wetted materials.
96 Emerson.com/Rosemount
Reference Manual Reference data
00809-0700-4001 April 2020

A Reference data

A.1 Product certifications and installation
drawings
To view current Rosemount 3051P product certifications and installation drawings, follow these steps:
1. Go to Emerson.com/Rosemount-3051P.
2. Scroll as needed to the green menu bar and click Documents and Drawings.
3. Click Certificates & Approvals.
A.2 Ordering information, specifications, and
dimensional drawings
To view current Rosemount 3051P ordering information, specifications, and dimensional drawings, follow these steps:
1. Go to Emerson.com/Rosemount-3051P.
2. Scroll as needed to the green menu bar and click Documents and Drawings.
3. Click Data Sheets & Bulletins.
4. Select the appropriate Product Data Sheet.
Rosemount 3051P 97
Reference data Reference Manual
April 2020 00809-0700-4001
98 Emerson.com/Rosemount
Reference Manual Field Communicator menu trees and Fast Keys
00809-0700-4001 April 2020
B Field Communicator menu trees and
Fast Keys

B.1 Menu trees

Figure B-1: Overview
Rosemount 3051P 99
Field Communicator menu trees and Fast Keys Reference Manual
April 2020 00809-0700-4001
Note
Selections with black circle are only available in HART® Revision 7 mode. Selection will not appear in the HART Revision 5 device descriptor (DD).
Figure B-2: Configure: Guided Setup
Note
Selections with black circle are only available in HART Revision 7 mode. Selection will not appear in the HART Revision 5 DD.
100 Emerson.com/Rosemount
Loading...