Rosemount 3051P In-Line Pressure Transmitter with HART Protocol Manuals & Guides

Rosemount™ 3051P In-Line Pressure Transmitter
with HART® Protocol
Reference Manual
00809-0700-4001, Rev AC
April 2020
2
Reference Manual Contents
00809-0700-4001 April 2020

Contents

Chapter 1 Introduction.............................................................................................................. 5
1.1 Using this manual........................................................................................................................ 5
1.2 Models covered........................................................................................................................... 5
1.3 Product recycling/disposal...........................................................................................................5
Chapter 2 Configuration............................................................................................................ 7
2.1 Safety messages.......................................................................................................................... 7
2.2 System readiness.........................................................................................................................8
2.3 HART® installation flowchart......................................................................................................10
2.4 Transmitter overview.................................................................................................................11
2.5 Configuration overview............................................................................................................. 14
2.6 Configuration basics.................................................................................................................. 14
2.7 Verifying configuration..............................................................................................................17
2.8 Basic setup of the transmitter.................................................................................................... 19
2.9 Configuring the LCD display.......................................................................................................24
2.10 Detailed transmitter setup.......................................................................................................25
2.11 Performing transmitter tests................................................................................................... 30
2.12 Configuring burst mode...........................................................................................................32
2.13 Establishing multidrop communication................................................................................... 34
Chapter 3 Hardware installation.............................................................................................. 37
3.1 Overview................................................................................................................................... 37
3.2 Safety messages........................................................................................................................ 37
3.3 Considerations...........................................................................................................................38
3.4 Installation procedures.............................................................................................................. 39
3.5 Rosemount 306 Manifold.......................................................................................................... 48
Chapter 4 Electrical installation................................................................................................49
4.1 Overview................................................................................................................................... 49
4.2 Safety messages........................................................................................................................ 49
4.3 Local Operating Interface (LOI)/LCD display...............................................................................50
4.4 Configuring transmitter security................................................................................................52
4.5 Set transmitter alarm.................................................................................................................55
4.6 Electrical considerations............................................................................................................ 55
Chapter 5 Operation and maintenance.....................................................................................63
5.1 Overview................................................................................................................................... 63
5.2 Safety messages........................................................................................................................ 63
5.3 Recommended calibration tasks................................................................................................64
5.4 Calibration overview..................................................................................................................65
Rosemount 3051P 3
Contents Reference Manual
April 2020 00809-0700-4001
5.5 Trimming the pressure signal.....................................................................................................68
5.6 Trimming the analog output......................................................................................................72
5.7 Switching HART® revision.......................................................................................................... 75
Chapter 6 Troubleshooting...................................................................................................... 77
6.1 Overview................................................................................................................................... 77
6.2 Safety messages........................................................................................................................ 77
6.3 Troubleshooting for 4-20 mA output......................................................................................... 78
6.4 Diagnostic messages................................................................................................................. 80
6.5 Disassembly procedures............................................................................................................ 86
6.6 Reassembly procedures.............................................................................................................88
6.7 Service support..........................................................................................................................88
Chapter 7 Safety instrumented systems requirements............................................................. 91
7.1 Safety instrumented systems (SIS) certification......................................................................... 91
7.2 Safety certified identification.....................................................................................................91
7.3 Installation in safety instrumented systems (SIS) applications....................................................91
7.4 Configuring in safety instrumented systems (SIS) applications...................................................92
7.5 Safety instrumented systems (SIS) operation and maintenance.................................................93
7.6 Inspection..................................................................................................................................95
Appendix A Reference data......................................................................................................... 97
A.1 Product certifications and installation drawings.........................................................................97
A.2 Ordering information, specifications, and dimensional drawings...............................................97
Appendix B Field Communicator menu trees and Fast Keys......................................................... 99
B.1 Menu trees................................................................................................................................ 99
B.2 Fast Keys..................................................................................................................................103
Appendix C Local operator interface (LOI)................................................................................. 105
C.1 Local operator interface (LOI) menu tree................................................................................. 105
C.2 Local operator interface (LOI) menu tree - extended menu......................................................106
C.3 Entering numbers....................................................................................................................107
C.4 Entering text............................................................................................................................108
4 Emerson.com/Rosemount
Reference Manual
00809-0700-4001 April 2020
Introduction

1 Introduction

1.1 Using this manual

The sections in this manual provide information on installing, operating, and maintaining the Rosemount 3051P. The sections are organized as follows:
Configuration provides instruction on commissioning and operating Rosemount 3051P
Transmitters. It also includes information on software functions, configuration parameters, and online variables.
Hardware installation contains mechanical installation instructions and field upgrade
options.
Electrical installation contains electrical installation instructions, and field upgrade
options.
Operation and maintenance provides detailed information on calibrating and changing
HART® Revisions.
Troubleshooting provides troubleshooting techniques for the most common operating
problems.
Safety instrumented systems requirements provides identification, installation,
configuration, operation and maintenance, and inspection information for Safety Instrumented Systems.
Specifications and reference data provides information on how to access reference and
specification data, as well as ordering information.
Field Communicator menu trees and Fast Keys provides the menu trees and HART Fast
Keys used to operate the transmitter.
Local operator interface (LOI) provides menu trees and instructions on using the LOI.

1.2 Models covered

The following Rosemount Pressure Transmitters are covered by this manual:
Rosemount 3051P In-Line Gage Pressure Transmitter: Measures gage pressure up to
4,000 psig (275.8 BarG).
Rosemount 3051P In-Line Absolute Pressure Transmitter: Measures absolute pressure
up to 4,000 psig (275.8 BarG).

1.3 Product recycling/disposal

Consider recycling equipment and packaging. Dispose of the product and packaging in accordance with local and national legislation.
Rosemount 3051P 5
Introduction Reference Manual
April 2020 00809-0700-4001
6 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020

2 Configuration

2.1 Safety messages

Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the Product Certifications section of the Rosemount 3051P Product Data Sheet for any restrictions associated with a safe installation.
Before connecting a handheld communicator in an explosive atmosphere, ensure that the instruments in the loop are installed in accordance with intrinsically safe or non­incendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is applied to the unit.
WARNING
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
WARNING
Process leaks could result in death or serious injury.
Install and tighten all four flange bolts before applying pressure. Do not attempt to loosen or remove flange bolts while the transmitter is in service.
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts. Improper assembly of manifolds to traditional flange can damage sensor module.
Rosemount 3051P 7
Configuration Reference Manual
April 2020 00809-0700-4001
WARNING
Improper assembly of manifolds to traditional flange can damage the device.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e., bolt hole) but must not contact sensor module housing.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.

2.2 System readiness

If using HART® based control or asset management systems, confirm the HART
capability of such systems prior to commissioning and installation. Not all systems are capable of communicating with HART Revision 7 devices.
For instructions on how to change the HART revision of your transmitter, see Switching
HART® revision.
2.2.1
Table 2-1: Device Revisions and Files
Identify device Find device driver
Software release
date
NAMUR hardware revision

Confirm correct device driver

Procedure
1. Verify the latest Device Driver (DD/DTM™) is loaded on your systems to ensure
proper communications.
2. Reference Emerson.com or FieldCommGroup.org for the latest DD.
3. Select desired product and download the DD.
a) Reference Table 2-1 for the correct DD.
files
®
HART software revision
(2)
HART universal revision
Device revision
(1)
NAMUR software revision
(1)
Review instructions Review
Manual document
(3)
number
functionality
Changes to software
August 2016
8 Emerson.com/Rosemount
1.1.xx 1.0.xx 03 7 10 00809-0700-4001 HART Revision 5 and 7 selectable
Reference Manual Configuration
00809-0700-4001 April 2020
Table 2-1: Device Revisions and Files (continued)
Identify device Find device driver
files
5 9 Local operator
(1) NAMUR revision is located on the hardware tag of the device. Differences in level 3 changes, signified above by xx,
represent minor product changes as defined per NE53. Compatibility and functionality are preserved, and products can be used interchangeably.
(2) HART software revision can be read using a HART capable configuration tool. Value shown is minimum revision that
could correspond to NAMUR revisions.
(3) Device driver file names use device and DD revision, e.g., 10_01. HART Protocol is designed to enable legacy device
driver revisions to continue to communicate with new HART devices. To access new functionality, the new device driver must be downloaded. Emerson recommends downloading new device driver files to ensure full functionality.
Review instructions Review
functionality
interface (LOI)
Scaled variable
Configurable
alarms
Expanded
engineering units
Updated
electronics hardware design
Intrinsic Safety
temperature classification change
Rosemount 3051P 9
Configuration Reference Manual
April 2020 00809-0700-4001

2.3 HART® installation flowchart

10 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020

2.4 Transmitter overview

The Rosemount 3051P In-Line Pressure Transmitter is offered for gage pressure (GP) and absolute pressure (AP) measurements. The transmitter uses piezoresistive sensor technology for AP and GP measurements.
The major components of the transmitter are the sensor module and the electronics housing. The sensor module contains the oil-filled sensor system (isolating diaphragm, oil fill system, and sensor). The electronics board is located within the electronics housing. The electrical signals from the sensor module are transmitted to the electronics board which contains the memory module and the analog to digital signal converter (A/D converter). The signal is then converted to a 4–20mA analog output signal or HART digital signal. The electronics housing contains the output electronics board, the optional external configuration buttons, and the terminal block. The basic block diagram of the transmitter is illustrated in Figure 2-2.
When pressure is applied to the isolating diaphragm, the oil deflects the sensor, which then changes its capacitance or voltage signal. This signal is then changed to a digital signal by the Signal Processing. The microprocessor then takes the signals from the Signal Processing and calculates the correct output of the transmitter. This signal is then sent to the D/A converter, which converts the signal back to the analog signal and then superimposes the HART signal on the 4–20 mA output.
®
An optional LCD display can be ordered that connects directly to the interface board, which maintains direct access to the signal terminals. The display indicates output and abbreviated diagnostic messages. A glass display cover is provided. For 4-20 mA HART output, the LCD display features a two-line display. The first line displays the actual measured value; the second line of six characters displays the engineering units. The LCD display can also display diagnostic messages.
Note
LCD display uses a 5x6 character display and can display output and diagnostic messages. The local operator interface (LOI) display uses an 8x6 character display and can display output and diagnostic messages as well as and LOI menu screens. The LOI display comes with two buttons mounted on the front of the display board. See Figure 2-1.
Rosemount 3051P 11
Configuration Reference Manual
April 2020 00809-0700-4001
Figure 2-1: LCD/LOI display
LCD display LOI display
12 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020
Figure 2-2: Block Diagram of Operation
A. Sensor module and electronics
B. 4-20 mA signal to control system C. Field Communicator D. Signal processing
E. Temperature sensor
F. Pressure sensor G. Sensor module memory H. Microprocessor
Sensor linearization
Rerange
Damping
Diagnostics
Engineering units
Communication
I. Memory
Configuration
J. Digital-to-analog signal conversion
K. Digital communication
Rosemount 3051P 13
Configuration Reference Manual
April 2020 00809-0700-4001

2.5 Configuration overview

This section contains information on commissioning and tasks that should be performed on the bench prior to installation, as well as tasks performed after installation as described in Performing transmitter tests.
Field Communicator, AMS Device Manager, and local operator interface (LOI) instructions are given to perform configuration functions. For convenience, Field Communicator Fast Key sequences are labeled “Fast Keys,” and abbreviated LOI menus are provided for each function below.
Full Field Communicator menu trees and Fast Key sequences are available in Field
Communicator menu trees and Fast Keys. LOI menu trees are available in Local operator interface (LOI).

2.6 Configuration basics

CAUTION
2.6.1
Set all transmitter hardware adjustments during commissioning to avoid exposing the transmitter electronics to the plant environment after installation.
You can configure the transmitter either before or after installation. Configuring the transmitter on the bench using either a Field Communicator, AMS Device Manager, or LOI ensures all transmitter components are in working order prior to installation. Verify that the security switch is set in the unlock position ( ) to proceed with configuration. See
Figure 4-2 for switch location.

Configuring on the bench

To configure on the bench, you will need a power supply and a Field Communicator, AMS Device Manager, or local operator interface (LOI), option M4.
Wire equipment as shown in Figure 2-3. To ensure successful HART® communication, a resistance of at least 250 Ωs must be present between the transmitter and the power supply; see Power supply for details. Connect the Field Communicator leads to the terminals labeled “COMM” on the terminal block.
14 Emerson.com/Rosemount
SAVE
1. Overview
2. Configure
3. Service Tools
3051 FT 45B Online
Reference Manual Configuration
00809-0700-4001 April 2020
Figure 2-3: Wiring the Transmitter (4–20 mA HART)
A. Vdc supply
B. R L ≥ 250 (necessary for HART communication only)
2.6.2

Configuration tools

Configuring with a Field Communicator
There are two interfaces available with the Field Communicator: traditional and dashboard.
This manual describes all steps using a Field Communicator using dashboard interfaces.
Figure 2-4 shows the Device Dashboard interface. As stated in System readiness, it is
critical that the latest device descriptors (DDs) are loaded into the Field Communicator. Visit Emerson.com or FieldCommGroup.org to download the latest DD library.
Field Communicator menu trees and Fast Keys are available in Field Communicator menu
trees and Fast Keys.
Figure 2-4: Device Dashboard
Rosemount 3051P 15
Configuration Reference Manual
April 2020 00809-0700-4001
Configuring with AMS Device Manager
Full configuration capability with AMS Device Manager requires loading the most current device descriptor (DD) for this device. Download the latest DD at Emerson.com or
FieldCommGroup.org.
Note
This manual describes all steps using AMS Device Manager version 11.5.
Configuring with a local operator interface (LOI)
To use the LOI, order the transmitter with option code M4. To activate the LOI push either configuration button. Configuration buttons are located on the LCD display (must remove housing cover to access), or underneath the top tag of the transmitter. See Table 2-2 for configuration button functionality and Figure 2-5 for configuration button location.
When using the LOI for configuration, several features require multiple screens for a successful configuration. Data entered will be saved on a screen-by-screen basis; the LOI will indicate this by flashing SAVED on the LCD display each time.
LOI menu trees are available in Local operator interface (LOI).
Figure 2-5: LOI Configuration Buttons
A. Internal configuration buttons
B. External configuration buttons
16 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020
Table 2-2: LOI Button Operation
Button
Left No SCROLL
Right Yes ENTER

2.6.3 Setting the loop to manual

Whenever sending or requesting data that would disrupt the loop or change the output of the transmitter, set the process application loop to manual control.
The Field Communicator, AMS Device Manager, or local operator interface (LOI) will prompt you to set the loop to manual when necessary. The prompt is only a reminder; acknowledging this prompt does not set the loop to manual. You must set the loop to manual control as a separate operation.

2.7 Verifying configuration

Emerson recommends verifying various configuration parameters prior to installing them into the process.
The various parameters are detailed out for each configuration tool. Depending on what configuration tool(s) are available follow the steps listed relevant to each tool.
2.7.1

Verifying configuration with Field Communicator

Review configuration parameters listed in Table 2-3 prior to transmitter installation. A Full list of configuration parameters that can be reviewed and configured using a Field Communicator are located in Field Communicator menu trees and Fast Keys.
Fast Key sequences for the latest device descriptor (DD) are shown in Table 2-3. For Fast Key sequences for legacy DDs, contact your local Emerson Representative.
Procedure
From the HOME screen, enter the Fast Key sequences listed
Table 2-3: Device Dashboard Fast Key Sequence
Function Fast Key sequence
HART® 7 HART 5
Alarm and saturation levels 2, 2, 2, 5 2, 2, 2, 5
Rosemount 3051P 17
Configuration Reference Manual
April 2020 00809-0700-4001
Table 2-3: Device Dashboard Fast Key Sequence (continued)
Function Fast Key sequence
HART® 7 HART 5
Damping 2, 2, 1, 1, 5 2, 2, 1, 1, 5
Primary variable 2, 1, 1, 4, 1 2, 1, 1, 4, 1
Range values 2, 1, 1, 4 2, 1, 1, 4
Tag 2, 2, 7, 1, 1 2, 2, 7, 1, 1
Transfer function 2, 2, 1, 1, 6 2, 2, 1, 1, 6
Units 2, 2, 1, 1, 4 2, 2, 1, 1, 4

2.7.2 Verifying configuration with AMS Device Manager

Procedure
1. Right click on the device and select Configuration Properties from the menu.
2. Navigate the tabs to review the transmitter configuration data.
2.7.3

Verifying configuration with local operator interface (LOI)

Procedure
1. Press any configuration button to activate the LOI.
2. Select VIEW CONFIG to review the below parameters.
3. Use the configuration buttons to navigate through the menu.
Review the following pareameters prior to installation:
Tag
Units
Transfer Function
Alarm and Saturation Levels
Primary Variable
Range Values
Damping
18 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020

2.7.4 Verifying process variables configuration

This section describes how to verify that the correct process variables are selected.
Verifying process variables with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys 3, 2, 1
Verifying process variables with AMS Device Manager
Procedure
1. Right click the device and select Overview from the menu.
2. Select the All Variables button to display the primary, secondary, tertiary, and
quaternary variables.

2.8 Basic setup of the transmitter

This section provides the necessary steps for basic setup of a pressure transmitter.
When installing in DP level or DP flow applications, refer to Configuring scaled variable for setup instructions.
2.8.1

Setting pressure units

The pressure unit command sets the unit of measure for the reported pressure.
Setting pressure units with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Setting pressure units with AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Select Manual Setup and select desired units from Pressure Units dropdown menu.
3. Select Send when complete.
2, 2, 1, 1, 4
Rosemount 3051P 19
Configuration Reference Manual
April 2020 00809-0700-4001
Setting pressure units with a local operator interface (LOI)
Procedure
1. Follow Figure 2-6 to select desired pressure and temperature units.
2. Use the SCROLL and ENTER buttons to select desired unit.
3. Save by selecting SAVE as indicated on the LCD display screen.
Example
Figure 2-6: Selecting Units with LOI

2.8.2 Reranging the transmitter

The range values command sets each of the lower and upper range analog values to a pressure. The lower range point represents 0 percent of range and the upper range point represents 100 percent of range.
In practice, the transmitter range values may be changed as often as necessary to reflect changing process requirements.
Select from one of the methods below to rerange the transmitter. Each method is unique; examine all options closely before deciding which method works best for your process.
Rerange by manually setting range points with a Field Communicator, AMS Device
Manager, or local operator interface (LOI).
Rerange with a pressure input source and a Field Communicator, AMS Device Manager,
LOI, or local zero and span buttons.
Manually rerange the transmitter by entering range points
Entering range points with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 2, 1
20 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020
Entering range points with AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Select Manual Setup and select Analog Output.
3. Enter upper and lower range values in the Range Limits box and click Send.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
Entering range points with a local operator interface (LOI)
See Figure 2-7 to rerange the transmitter using the LOI.
Procedure
Enter values using SCROLL and ENTER buttons.
Figure 2-7: Rerange with LOI
Rerange the transmitter with applied pressure source
Reranging using an applied pressure source is a way of reranging the transmitter without entering specific 4 and 20 mA points.
Rerange with an applied pressure source using a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Rerange with an applied pressure source using AMS Device Manager
Procedure
1. Right click the device; select Configure.
2. Select the Analog Output tab.
3. Select Range by Applying Pressure and follow the screen prompts range the
transmitter.
2, 2, 2, 2
Rosemount 3051P 21
Configuration Reference Manual
April 2020 00809-0700-4001
Rerange with an applied pressure source using local zero and span buttons
If you order local zero and span buttons (option code D4), you can use them to rerange the transmitter with an applied pressure. Refer to Figure 2-8 for analog zero and span button location.
To rerange the transmitter using the span and zero buttons, perform the following procedure:
Procedure
1. Loosen the screw holding the top tag of the transmitter housing. Rotate the label to
expose the zero and span buttons.
2. Confirm device has local zero and span buttons by verifying blue retainer under the
tag.
3. Apply transmitter pressure.
4. Rerange the transmitter.
a) To change the zero (4 mA) while maintaining the span: press and hold zero
button for at least two seconds then release.
b) To change the span (20 mA) while maintaining the zero point: press and hold
the span button for at least two seconds and then release.
Example
Note
4 mA and 20 mA points must maintain the minimum span defined in Specifications and
reference data.
Figure 2-8: Analog Zero and Span Buttons
A. Zero and span buttons
22 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020
Note
If the transmitter security is on, you cannot make adjustments to the zero and span.
Refer to Configuring transmitter security for security information.
The span is maintained when the 4 mA/1 V point is set. The span changes when the 20
mA/5 V point is set. If the lower range point is set to a value that causes the upper range point to exceed the sensor limit, the upper range point is automatically set to the sensor limit, and the span is adjusted accordingly.
Regardless of the range points, the transmitter measures and reports all readings
within the digital limits of the sensor. For example, if the 4 and 20 mA points are set to 0 and 10 inH2O, and the transmitter detects a pressure of 25 inH2O, it digitally outputs the 25 inH2O reading and a 250 percent of range reading.

2.8.3 Damping

The damping command changes the response time of the transmitter; higher values can smooth variations in output readings caused by rapid input changes.
Determine the appropriate damping setting based on the necessary response time, signal stability, and other requirements of the loop dynamics within your system. The damping command utilizes floating point configuration, allowing you to input any damping value within 0.0–60.0 seconds.
Damping with a Field Communicator
Procedure
1. From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2. Enter desired damping value and select APPLY.
2, 2, 1, 1, 5
Damping with AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Select Manual Setup.
3. Within the Pressure Setup box, enter desired damping value and click Send.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
Damping with a local operator interface (LOI)
Procedure
Reference Figure 2-9 to enter damping values using an LOI.
Rosemount 3051P 23
Configuration Reference Manual
April 2020 00809-0700-4001
Figure 2-9: Damping with LOI

2.9 Configuring the LCD display

The LCD display configuration command allows customization of the LCD display to suit application requirements.
The LCD display will alternate between the selected items.
Pressure Units
% of Range
Scaled Variable
Sensor Temperature
mA/Vdc Output
Use the following instructions to configure the LCD display to display configuration information during the device startup. Select Review Parameters at start-up to enable or disable this functionality.
See Table 2-2 for an image of the LCD display screen.
2.9.1

Configuring LCD display with a Field Communicator

Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
24 Emerson.com/Rosemount
2, 2, 4
Reference Manual Configuration
00809-0700-4001 April 2020

2.9.2 Configuring LCD display with AMS Device Manager

Procedure
1. Right click on the device and select Configure.
2. Select Manual Setup; select the Display tab.
3. Select desired display options and click Send.

2.9.3 Configuring LCD display with a local operator interface (LOI)

Procedure
Refer to Figure 2-10 for LCD display configuration using an LOI.
Figure 2-10: Display with LOI

2.10 Detailed transmitter setup

2.10.1 Configuring alarm and saturation levels

In normal operation, the transmitter will drive the output in response to pressure from the lower to upper saturation points. If the pressure goes outside the sensor limits, or if the output would be beyond the saturation points, the output will be limited to the associated saturation point.
The transmitter automatically and continuously performs self-diagnostic routines. If the self-diagnostic routines detect a failure, the transmitter drives the output to configured alarm and value based on the position of the alarm switch. See Set transmitter alarm.
Rosemount 3051P 25
Configuration Reference Manual
April 2020 00809-0700-4001
Table 2-4: Alarm and Saturation Values
Level 4–20 mA saturation 4–20 mA alarm
Low 3.90 mA ≤ 3.75 mA
High 20.80 mA ≥ 21.75 mA
Table 2-5: NAMUR-Compliant Alarm and Saturation Values
Level 4–20 mA saturation 4–20 mA alarm
Low 3.80 mA ≤ 3.60 mA
High 20.50 mA ≥22.50 mA
Table 2-6: Custom Alarm and Saturation Values
Level 4–20 mA saturation 4–20 mA alarm
Low 3.50 mA– 3.90 mA 3.40–3.80 mA
High 20.10 mA –22.90 mA 20.20 mA – 23.00 mA
You can configure failure mode alarm and saturation levels using a Field Communicator, AMS Device Manager, or local operator interface (LOI). The following limitations exist for custom levels:
Low alarm level must be less than the low saturation level.
High alarm level must be higher than the high saturation level.
Alarm and saturation levels must be separated by at least 0.1 mA.
The configuration tool will provide an error message if the configuration rule is violated.
Note
Transmitters set to HART® multidrop mode send all saturation and alarm information digitally; saturation and alarm conditions will not affect the analog output. See also
Establishing multidrop communication.
Configuring alarm and saturation levels using a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 2, 5
Configuring alarm and saturation levels with AMS Device Manager
Procedure
1. Right click on the device and select Configure.
2. Select Configure Alarm and Saturation Levels.
26 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020
3. Follow screen prompts to configure alarm and saturation levels.
Configuring alarm and saturation levels using a local operator interface (LOI)
Procedure
Refer to Figure 2-11 for instructions to configure alarm and saturation levels.
Figure 2-11: Configuring Alarm and Saturation with LOI

2.10.2 Configuring scaled variable

With the scaled variable, you can create a relationship/conversion between the pressure units and user-defined/custom units.
There are two use cases for scaled variable:
1. Allow custom units to be displayed on the transmitter's LCD/local operator interface (LOI) display.
2. Allow custom units to drive the transmitters 4-20 mA output.
If the you want custom units to drive the 4–20 mA output, re-map the scaled variable as the primary variable. Refer to Re-mapping device variables.
The scaled variable configuration defines the following items:
Scaled variable units
Scaled data options
Pressure value position 1
Scaled variable position 1
Pressure value position 2
Scaled variable position 2
Linear offset
Custom units to be displayed.
Defines the transfer function for the application.
Lower known value point with consideration of linear offset.
Custom unit equivalent to the lower known value point.
Upper known value point.
Custom unit equivalent to the upper known value point.
The value required to zero out pressures affecting the desired pressure reading.
Rosemount 3051P 27
Configuration Reference Manual
April 2020 00809-0700-4001
Configuring a scaled variable using a Field Communicator
Procedure
1. From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys 2, 1, 4, 7
2. Follow the screen prompts to configure scaled variable.
a) Select Linear under Select Scaled data options.
Configuring a scaled variable using AMS Device Manager
Procedure
1. Right click on the device and, select Configure.
2. Select the Scaled Variable tab and select the Scaled Variable button.
3. Follow screen prompts to configure scaled variable.
a) Select Linear under Select Scaled data options.
Configuring a scaled variable using a local operator interface (LOI)
Procedure
Refer to Figure 2-12 for instructions to configure a scaled variable using an LOI.
Figure 2-12: Configuring Scaled Variable Using an LOI
28 Emerson.com/Rosemount
Reference Manual Configuration
00809-0700-4001 April 2020

2.10.3 Re-mapping device variables

The re-mapping function allows you to configure the transmitter primary, secondary, tertiary, and quaternary variables (PV, 2V, 3V, and 4V) as desired.
You can re-map the PV with a Field Communicator, AMS Device Manager, or a local operator interface (LOI). You can only re-map variables 2V, 3V, and 4V via Field Communicator or AMS Device Manager.
Note
The variable assigned to the primary variable drives the 4–20 mA output. This value can be selected as Pressure or Scaled Variable. The 2, 3, and 4 variables only apply if using HART burst mode.
Re-map device variables using a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
®
Fast Keys
2, 1, 1, 3
Re-map device variables using AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Select Manual Setup and click on the HART tab.
3. Assign Primary, secondary, tertiary, and quaternary variables under Variable Mapping.
4. Select Send.
5. Carefully read the warning and select Yes if it is safe to apply the changes.
Re-map device variables using local operator interface (LOI)
Procedure
Refer to Figure 2-13 for instructions on re-mapping the primary variable using an LOI.
Rosemount 3051P 29
Configuration Reference Manual
April 2020 00809-0700-4001
Figure 2-13: Re-mapping with LOI

2.11 Performing transmitter tests

2.11.1 Verifying alarm level

If the transmitter is repaired or replaced, verify the transmitter alarm level before returning the transmitter to service.
This is useful in testing the reaction of the control system to a transmitter in an alarm state. It ensures that the control system recognizes the alarm when activated. To verify the transmitter alarm values, perform a loop test and set the transmitter output to the alarm value (see Table 2-4, Table 2-5, and Table 2-6).
Note
Before returning transmitter to service, verify security switch is set to the correct position. Refer to Verifying configuration.
2.11.2

Performing an analog loop test

The analog loop test command verifies the output of the transmitter, the integrity of the loop, and the operations of any recorders or similar devices installed in the loop. Emerson recommends testing the 4-20 mA points in addition to alarm levels when installing, repairing, or replacing a transmitter.
The host system may provide a current measurement for the 4–20 mA HART® output. If it does not, connect a reference meter to the transmitter by either connecting the meter to
30 Emerson.com/Rosemount
Loading...
+ 80 hidden pages