Rosemount 3051HT Hygienic Pressure Transmitter with Foundation Fieldbus Protocol Quick Start Guide

Page 1
Quick Start Guide
00825-0200-4091, Rev CA
June 2020
Rosemount™ 3051HT Hygienic Pressure Transmitter
with FOUNDATION™ Fieldbus Protocol
Page 2
Quick Start Guide June 2020
NOTICE
This guide provides basic guidelines for the Rosemount 3051HT Transmitter. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations.
WARNING
Explosions could result in death or serious injury.
Installation of device in an explosive environment must be in accordance with appropriate local, national, and international standards, codes, and practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is applied to the unit.
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
Process leaks could result in death or serious injury.
To avoid process leaks, only use the gasket designed to seal with the corresponding flange adapter.ph>
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
Conduit/cable entries
Unless otherwise marked, the conduit/cable entries in the housing enclosure use a ½–14 NPT form. Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries.
Contents
System readiness......................................................................................................................... 3
Transmitter installation................................................................................................................ 4
Product certifications................................................................................................................. 21
2 Emerson.com/Rosemount
Page 3
June 2020 Quick Start Guide

1 System readiness

Note
Before installing the transmitter, confirm that the correct device driver is loaded on the host systems.

1.1 Confirm correct device driver

Verify the latest device driver (DD/DTM™) is loaded on your systems to
ensure proper communications.
Download the latest device driver at Emerson.com or
FieldCommGroup.org.
Rosemount 3051 device revisions and drivers
Table 1-1 provides the information necessary to ensure you have the correct
device driver and documentation for your device.
Table 1-1: Rosemount 3051 Device Revision 8 and Drivers
FOUNDATION™ Fieldbus device revision can be read using a FOUNDATION Fieldbus capable configuration tool.
Host Device driver (DD)
All DD4: DD Rev 1 FieldCommGroup.org Emerson.com 00809-0100-47
All DD5: DD Rev 1 FieldCommGroup.org
Emerson AMS Device Manager V
10.5 or higher: DD Rev 2
Emerson AMS Device Manager V
8 to 10.5: DD Rev 1
Emerson 375/475: DD Rev 2 Easy Upgrade Utility
(1)
Obtain at Device driver
Emerson.com
Emerson.com
(DTM)
Manual document number
74, Rev CA or
newer
(1) Device driver file names use device and DD revision. To access functionality, the correct
device driver must be installed on your control and asset management hosts, and on your configuration tools.
Quick Start Guide 3
Page 4
Quick Start Guide June 2020

2 Transmitter installation

Figure 2-1: Installation Flowchart

2.1 Mount the transmitter

Place the transmitter to the desired orientation before mounting. Transmitter must not be securely mounted or clamped in place when changing transmitter orientation.
Conduit entry orientation
When installing a Rosemount 3051HT, it is recommended installing so a conduit entry faces downward or parallel to the ground to maximize drainability when cleaning.
Environmental seal for housing
Thread sealing (PTFE) tape or paste on male threads of conduit is required to provide a watertight/dustproof conduit seal and meets requirements of NEMA® Type 4X, IP66, IP68, and IP69K. Consult factory if other Ingress Protection ratings are required.
Note
IP69K rating only available on units with a SST housing and option code V9 in the model string.
For M20 threads, install conduit plugs to full thread engagement or until mechanical resistance is met.
In-line gauge transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage transmitter is located on the neck of the transmitter via a protected gage vent (See Figure 2-2).
Keep the vent path free from obstructions including but not limited to paint, dust, and viscous fluids by mounting the transmitter so the process can drain away.
4 Emerson.com/Rosemount
Page 5
June 2020 Quick Start Guide
Figure 2-2: In-line Protected Gage Vent Low Side Pressure Port
Aluminum Polished 316 SST
A. Low side pressure port (atmospheric reference)
Clamping
When installing clamp, follow recommended torque values provided by gasket manufacturer.
Note
To maintain performance, torquing a 1.5-in. Tri Clamp beyond 50 in-lb. is not recommended on pressure ranges below 20 psi.
Quick Start Guide 5
Page 6
A
Commissioning Tag
DEVICE ID:
001151AC00010001440-1216980917 25
DEVICE REVISION:
PHYSICAL DEVICE TAG
DEVICE ID:
001151AC00010001440-121698091725
DEVICE REVISION:
S / N :
PHYSICAL DEVICE TAG
Device Barcode
Quick Start Guide June 2020

2.2 Commissioning (paper) tag

To identify which device is at a particular location use the removable tag provided with the transmitter. Ensure the physical device tag (PD Tag field) is properly entered in both places on the removable commissioning tag and tear off the bottom portion for each transmitter.
Figure 2-3: Commissioning Tag
A. Device revision
Note
The device description loaded in the host system must be at the same revision as this device. The device description can be downloaded from the host system website, from Emerson.com/Rosemount, or from
FieldCommGroup.org.
6 Emerson.com/Rosemount
Page 7
A
B
June 2020 Quick Start Guide

2.3 The security and simulate switches

The security and simulate switches are located on the electronics.
Figure 2-4: Transmitter Electronics Board
Aluminum Polished 316 SST
A. Simulate switch B. Security switch

2.3.1 Setting the security switch

The security switch allows ( ) or prevents ( ) any configuration of the transmitter.
Note
Default security is off (
Setting the simulate switch
The security switch can be enabled or disabled in the software.
Procedure
1. If the transmitter is installed, secure the loop, and remove power.
2. Remove the housing cover opposite the field terminal side.
).
WARNING
Explosions could result in death or serious injury.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is applied to the unit.
Quick Start Guide 7
Page 8
Quick Start Guide June 2020
3. Slide the security switch into the preferred position.
4. Reattach the transmitter housing cover. Tighten the cover until there is no gap between the cover and
housing to comply with explosion proof requirements.

2.3.2 Setting the simulate switch

The simulate switch is used in conjunction with the transmitter simulate software to simulate process variables and/or alerts and alarms.
Note
The simulate switch enables or disables simulated alerts and simulated AI Block status and values. The default simulate switch position is enabled.
To simulate variables and/or alerts and alarms, the simulate switch must
be moved to the enable position and the software enabled through the host before installation of the transmitter.
To disable simulation, the switch must be in the disable position or the
software simulate parameter must be disabled through the host.
Procedure
1. If the transmitter is installed, secure the loop, and remove power.
2. Remove the housing cover opposite the field terminal side.
WARNING
Explosions could result in death or serious injury.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is applied to the unit.
3. Slide the simulate switch into the preferred position.
4. Reattach the transmitter housing cover. Tighten the cover until there is no gap between the cover and
housing to comply with explosion proof requirements.
2.4
8 Emerson.com/Rosemount

Connect the wiring and power up

Procedure to connect the wiring and power up the transmitter.
Prerequisites
Use copper wire of sufficient size to ensure the voltage across the
transmitter power terminals does not drop below 9 Vdc. A minimum of 12 Vdc under normal operating conditions is recommended. Shielded twisted pair Type A cable is recommended.
Page 9
June 2020 Quick Start Guide
Power supply voltage can be variable, especially under abnormal
conditions such as when operating on battery backup.
Procedure
1. To power the transmitter, connect the power leads to the terminals indicated on the terminal block label.
Note
The Rosemount 3051 power terminals are polarity insensitive, which means the electrical polarity of the power leads does not matter when connecting to the power terminals. If polarity sensitive devices are connected to the segment, terminal polarity should be followed. When wiring to the screw terminals, the use of crimped legs is recommended.
2. Ensure full contact with terminal block screw and washer. When using a direct wiring method, wrap wire clockwise to ensure it is in place when tightening the terminal block screw. No additional power is needed.
Note
The use of a pin or a ferrule wire terminal is not recommended as the connection may be more susceptible to loosening over time or under vibration.
3. Ensure proper grounding. It is important the instrument cable shield be:
a) Trimmed close and insulated from touching the transmitter
housing.
b) Connected to the next shield if cable is routed through a
junction box.
c) Connected to a good earth ground at the power supply end.
4. If transient protection is needed, refer to section Signal ground
wiring for grounding instructions.
5. Plug and seal unused conduit connections.
6. Reattach the transmitter covers.
a) The covers must only be capable of being released or
removed with the aid of a tool to comply with applicable ordinary locations requirements.
Figure 2-5: Wiring
Aluminum
Quick Start Guide 9
Polished 316 SST
Page 10
DP
A
B
D
E
C
DP
A
B
D
E
C
Quick Start Guide June 2020
A. Minimize distance B. Trim shield and insulate C. Protective grounding terminal (do not ground cable shield at the
transmitter)
D. Insulate shield
E. Connect shield back to the power supply ground

2.4.1 Signal ground wiring

Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. Grounding terminations are provided on the outside of the electronics housing and inside the Terminal Compartment. These grounds are used when transient protect terminal blocks are installed or to fulfill local regulations.
Procedure
1. Remove the field terminals housing cover.
2. Connect the wiring pair and ground as indicated in Figure 2-5 a) Trim the cable shield as short as practical and insulate from
touching the transmitter housing.
Note
Do NOT ground the cable shield at the transmitter; if the cable shield touches the transmitter housing, it can create ground loops and interfere with communications.
b) Continuously connect the cable shields to the power supply
ground.
c) Connect the cable shields for the entire segment to a single
10 Emerson.com/Rosemount
good earth ground at the power supply.
Page 11
June 2020 Quick Start Guide
Note
Improper grounding is the most frequent cause of poor segment communications.
3. Replace the housing cover. It is recommended that the cover be tightened until there is no gap between the cover and the housing.
4. Plug and seal unused conduit connections.
Note
The Rosemount 3051HT polished 316 SST housing only provides ground termination inside the terminal compartment.
Power supply
The transmitter requires between 9 and 32 Vdc (9 and 30 Vdc for intrinsic safety) to operate and provide complete functionality.
Power conditioner
A Fieldbus segment requires a power conditioner to isolate the power supply, filter, and decouple the segment from other segments attached to the same power supply.
Grounding
Signal wiring of the Fieldbus segment can not be grounded. Grounding out one of the signal wires will shut down the entire Fieldbus segment.
Shield wire ground
To protect the Fieldbus segment from noise, grounding techniques for shield wire require a single grounding point for shield wire to avoid creating a ground loop. Connect the cable shields for the entire segment to a single good earth ground at the power supply.
Signal termination
For every Fieldbus segment a terminator should be installed at the beginning and at the end of each segment.
Locating devices
Devices are frequently installed, configured, and commissioned over time by different personnel. A “Locate Device” capability uses the LCD display (when installed) to assist personnel in finding the desired device.
From the device Overview screen, select the Locate Device button. This will launch a method allowing the user to display a “Find me” message or enter a custom message to display on the device LCD display. When the user exits the “Locate Device” method, the device LCD display automatically returns to normal operation.
Quick Start Guide 11
Page 12
Quick Start Guide June 2020
Note
Some hosts do not support “Locate Device” in the DD.

2.5 Configure

Each FOUNDATION™ Fieldbus host or configuration tool has a different way of displaying and performing configurations. Some use device descriptions (DD) or DD methods for configuration and to display data consistently across platforms. There is no requirement that a host or configuration tool support these features. Use the following block examples to do basic configuration to the transmitter. For more advanced configurations, see the Rosemount 3051 FOUNDATION Fieldbus Reference Manual.
Note
DeltaV™ users should use DeltaV Explorer for the resource and transducer blocks and Control Studio for the function blocks.

2.5.1 Configure the AI block

Navigation instructions for each step are provided in the Figure 2-7. In addition, the screens used for each step are shown in the Figure 2-6.
12 Emerson.com/Rosemount
Page 13
(Overview) Pressure Calibration Device Information
Locate Device Scale Gauges
(Calibration) Primary Value Sensor Trim Sensor Limits
Restore Factory Calibration
Last Calibration Points Calibration Details
(Device Information) Identification
( 1)
Revisions Materials of Construction Security & Simulation
(Materials of Construction) Sensor Sensor Range Flange Remote Seal
(Configure) Guided Setup Manual Setup Alert Setup
(Manual Setup) Process Variable Materials of Construction Display
( )
Display Options Advanced Configuration
(Classic View)( 9 ) View All Parameters Mode Summary AI Blocks Channel Mapping
Master Reset
(Process Variable ) Pressure Pressure Damping Sensor Temperature Change Damping (7, 9)
(Security & Simulation)
Write Lock Setup
(Guided Setup)
Zero Trim Change Damping
Local Display Setup Configure Analog Input Blocks (3, 4, 5, 9)
(8, 9)
(8, 9)
(7, 9)
Cl
as
s
i
c
Vi
e
w
Display
(2, 10)
June 2020 Quick Start Guide
Figure 2-6: Basic Configuration Menu Tree
Standard Text – Navigation selections available
(Text) – Name of selection used on parent menu screen to access this
screen
Bold Text – Automated methods
Underlined Text – Configuration task numbers from configuration flow
chart

2.5.2 Before you begin configuration

Before beginning configuration, you may need to verify the device tag or deactivate hardware and software write protection on the transmitter.
Use this procedure to verify the device tag and the software write lock switch.
Quick Start Guide 13
Page 14
Quick Start Guide June 2020
Procedure
1. To verify the device tag, from the Overview screen, select Device Information.
2. To disable the software write lock (devices ship from the factory with the software write lock disabled):
Note
The software write lock switch must be in the unlocked position if the switch has been enabled in the software.
a) From the Overview screen, select Device Information and
then select the Security and Simulation tab.
b) To disable the software write lock, perform write lock setup.
Note
Place the control loop in Manual mode before beginning analog input block configuration.

2.5.3 Guided setup of the AI Block Configuration

This procedure is for the guided setup of the AI Block Configuration.
Prerequisites
Navigate to Configure Guided Setup.
Procedure
1. Select AI Block Unit Setup.
2. Select the signal conditioning L_TYPE from the menu.
Select Direct for pressure measurements using the device default
units.
Select Indirect for other pressure or level units.
3. Set the XD_SCALE to the 0% and 100% scale points (the transmitter range).
a) Select the XD_SCALE_UNITS from the menu.
b) Enter the XD_SCALE 0% point.
This may be elevated or suppressed for level applications.
c) Enter the XD_SCALE 100% point.
This may be elevated or suppressed for level applications.
d) If the L_TYPE is Direct, guided setup automatically places the
AI block into AUTO mode to return the device to service.
14 Emerson.com/Rosemount
Page 15
June 2020 Quick Start Guide
4. If the L_TYPE selected is Indirect or Indirect Square Root, set OUT_SCALE to change engineering units.
a) Select OUT_SCALE UNITS from the menu.
b) Set the OUT_SCALE low value.
This may be elevated or suppressed for level applications.
c) Set the OUT_SCALE high value.
This may be elevated or suppressed for level applications.
d) If the L_TYPE selected is Indirect, guided setup automatically
places the AI block into AUTO mode to return the device to service.
5. To change damping, select Change Damping
Note
Guided setup will automatically go through each step in the proper order.
6. Enter the desired damping value in seconds. The permitted range of values is 0.4 to 60 seconds.
7. To configure the LCD display (if installed).
8. Select Local Display Setup.
9. Check the box next to each parameter to be displayed to a maximum of four parameters. The LCD display will continuously scroll through the selected parameters.
10. To review the transmitter configuration, navigate using the manual setup navigation sequences for “AI Block Unit Setup”, “Change Damping”, and “Set up LCD Display”.
11. Change any values as necessary.
12. Return to the Overview screen.
13. If mode is “Not in Service”, click Change, and then select Return All to Service.
Note
If hardware or software write protection is not needed, Step 14 can be skipped.
14. Set switches and software write lock.
a) Check switches (see Figure 2-4).
Quick Start Guide 15
Page 16
Start
Device Configuration
here
1. Verify device tag: PD_TAG
7. Set damping:
PRIMARY_VALUE_
DAMPING
8. Set up LCD display
6. Set low cutoff: LOW_CUT
9. Review transmitter configuration
3. Set signal
conditioning:
L_TYPE
5. Set scaling OUT_SCALE
2. Check switches and software write lock
Done
10. Set switches and software write lock
4. Set scaling XD_SCALE
Quick Start Guide June 2020
Note
The write lock switch can be left in the locked or unlocked position. The simulate enable/disable switch may be in either position for normal device operation.

2.5.4 Manual setup of the AI block configuration

This procedure describes the manual setup of the AI Block Configuration.
Prerequisites
Navigate to Configure Manual Setup Process Variable.
Note
When using manual setup perform the steps in the order described in Figure
2-7
Figure 2-7: Configuration Flowchart
Note
For convenience, AI block 1 is pre-linked to the transmitter primary variable and should be used for this purpose. AI block 2 is pre-linked to the transmitter sensor temperature. The channel must be selected for AI blocks 3 and 4.
Channel 1 is the primary variable.
16 Emerson.com/Rosemount
Channel 2 is the sensor temperature.
If the FOUNDATION™ Fieldbus Diagnostics Suite Option Code D01 is enabled, these additional channels are available.
Channel 12 is the SPM mean.
Channel 13 is the SPM standard deviation.
Page 17
June 2020 Quick Start Guide
To configure SPM, refer to the Rosemount 3051 FOUNDATION Fieldbus
Reference Manual.
Procedure
1. Select AI Block Unit Setup.
2. Place the AI Block in Out of Service mode.
3. Select the signal conditioning L_TYPE from the menu.
Select Direct for pressure measurements using the device default
units.
Select Indirect for other pressure or level units.
4. Set the XD_SCALE to the 0% and 100% scale points (the transmitter range).
a) Select the XD_SCALE_UNITS from the menu.
b) Enter the XD_SCALE 0% point.
This may be elevated or suppressed for level applications.
c) Enter the XD_SCALE 100% point.
This may be elevated or suppressed for level applications.
5. If the L_TYPE selected is Direct, the AI block may be placed in AUTO mode to return the device to service.
6. If the L_TYPE selected is Indirect or Indirect Square Root, set OUT_SCALE to change engineering units.
a) Select OUT_SCALE UNITS from the menu.
b) Set the OUT_SCALE low value.
This may be elevated or suppressed for level applications.
c) Set the OUT_SCALE high value.
This may be elevated or suppressed for level applications.
d) If the L_TYPE selected is Indirect, the AI Block may be placed
in AUTO mode to return the device to service.
7. To change damping, select Change Damping.
8. Enter the desired damping value in seconds. The permitted range of values is 0.4 to 60 seconds.
9. To configure the LCD display (if installed).
10. Select Local Display Setup.
11. Check the box next to each parameter to be displayed to a maximum of four parameters.
Quick Start Guide 17
Page 18
Quick Start Guide June 2020
The LCD display will continuously scroll through the selected parameters.
12. To review the transmitter configuration, navigate using the manual setup navigation sequences for “AI Block Unit Setup”, “Change Damping”, and “Set up LCD Display”.
13. Change any values as necessary.
14. Return to the Overview screen.
15. If mode is “Not in Service”, click Change, and then select Return All to Service.
Note
If hardware or software write protection is not needed, Step 16 can be skipped.
16. Set switches and software write lock.
a) Check switches (see Figure 2-4).
Note
The write lock switch can be left in the locked or unlocked position. The simulate enable/disable switch may be in either position for normal device operation.

2.5.5 Enable software write lock

Procedure
1. Navigate from the Overview screen. a) Select Device Information.
b) Select the Security and Simulation tab.
2. Perform Write Lock Setup to enable software write lock.
18 Emerson.com/Rosemount
Page 19
June 2020 Quick Start Guide

2.5.6 AI block configuration parameters

Use the pressure example for a guide.
Parameters Enter data
Channel 1 = Pressure, 2 = Sensor temp, 12 = SPM mean, 13 = SPM standard
L_Type Direct, indirect, or square root
XD_Scale Scale and engineering units
Out_Scale Scale and engineering units
(1) Select only the units that are supported by the device.
Table 2-1: Pressure example
deviation
(1)
Pa bar torr at 0 °C ft H2O at 4 °C m H2O at 4 °C
kPa mbar kg/cm
mPa psf kg/cm
hPa Atm in H2O at 4 °C mm H2O at 4 °C in Hg at 0 °C
°C psi in H2O at 60 °F mm H2O at 68 °C in Hg at 0 °C
°F g/cm22in H2O at 68 °F cm H2O at 4 °C
2
2
ft H2O at 60 °F mm Hg at 0 °C
ft H2O at 68 °F cm Hg at 0 °C
Parameters Enter data
Channel 1
L_Type Direct
XD_Scale See list of supported engineering
Out_Scale Set values outside operating range.
(1) Select only the units that are supported by the device.
units
(1)
.

2.5.7 Display pressure on the LCD display

Select the Pressure check box on the Display Configuration screen.
2.6
Quick Start Guide 19

Zero trim the transmitter

Procedure to zero trim the transmitter, which is a single-point adjustment used for compensating mounting position and line pressure effects.
Prerequisites
When performing a zero trim, ensure that the equalizing valve is open and all wet legs are filled to the correct level.
Page 20
Quick Start Guide June 2020
Note
Transmitters are shipped fully calibrated per request or by the factory default of full scale (span = upper range limit).
The transmitter will only allow 3–5 percent URL Zero error to be trimmed.
For greater zero errors, compensate for the offset by using the XD_Scaling, Out_Scaling and Indirect L_Type which are part of the AI Block Configure.
Procedure
Guided Setup
1. Navigate to Configure Guided Setup.
2. Select Zero Trim.
The method will execute the zero trim.
Manual Setup
3. Navigate to Overview Calibration Sensor Trim.
4. Select Zero Trim.
The method will execute the zero trim.
20 Emerson.com/Rosemount
Page 21
June 2020 Quick Start Guide

3 Product certifications

Rev. 1.6

3.1 European Directive Information

A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com.

3.2 Ordinary Location Certification

As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
Altitude Pollution degree
5000 m max 4 (metallic enclosure)
2 (non-metallic enclosure)

3.3 Installing Equipment in North America

The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.
3.4

USA

I5 Intrinsic Safety; Nonincendive
Certificate:
Standards:
Markings:
1053834
FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 – 2004, FM Class 3810 – 2005
IS CL I, DIV 1, GP A, B, C, D when connected per Rosemount drawing 03031-1024, CL I ZONE 0 AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D T5; T4 (–20 °C ≤ Ta ≤ +70 °C) [HART]; T4(–20 °C ≤ Ta ≤ +60 °C) [Fieldbus]; Type 4x

3.5 Canada

I6 Intrinsic Safety
Certificate:
Quick Start Guide 21
1053834
Page 22
Quick Start Guide June 2020
Standards:
Markings:

3.6 Europe

I1 ATEX Intrinsic Safety
Certificate:
Standards:
Markings:
Table 3-1: Input Parameters
Parameter HART Fieldbus/
Voltage U
Current I
Power P
Capacitance Ci0.012 µF 0 µF
Inductance Li0 mH 0 mH
ANSI/ISA 12.27.01-2003, CSA Std. C22.2 No.142-M1987, CSA Std. C22.2. No.157-92, CSA Std. C22.2 No. 213 - M1987
Intrinsically Safe Class I, Division 1 Groups A, B, C, D when connected in accordance with Rosemount drawing 03031-1024, Temperature Code T4; Suitable for Class I, Zone 0; Type 4X; Factory Sealed; Single Seal (See drawing 03031-1053)
BAS97ATEX1089X
EN 60079-0:2012 + A11:2013, EN 60079-11:2012
HART™: II 1 G Ex ia IIC T5/T4 Ga, T5(–20 °C ≤ Ta ≤ +40 °C), T4(–20 °C ≤ Ta ≤ +70 °C) Fieldbus: II 1 G Ex ia IIC Ga T4(–20 °C ≤ Ta ≤ +60 °C)
PROFIBUS
30 V 30 V
i
i
i
200 mA 300 mA
0.9 W 1.3 W
®
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation
test required by clause 6.3.12 of EN60079-11:2012. This must be taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however care should be taken to protect it from impact or abrasion if located in Zone 0.
3.7

International

I7 IECEx Intrinsic Safety
Certificate:
Standards:
22 Emerson.com/Rosemount
IECEx BAS 09.0076X
IEC 60079-0:2011, IEC 60079-11:2011
Page 23
June 2020 Quick Start Guide
Markings:
Parameter PROFIBUS
Voltage U
Current I
Power P
Capacitance Ci0 µF
Inductance Li0 mH
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation
2. The enclosure may be made of aluminum alloy and given a protective

3.8 Brazil

I2 INMETRO Intrinsic Safety
HART™: Ex ia IIC T5/T4 Ga, T5(–20 °C ≤ Ta ≤ +40 °C), T4(–20 °C ≤ Ta ≤ +70 °C)
PROFIBUS®: Ex ia IIC T4 (–20 °C ≤ Ta ≤ +60 °C)
30 V
i
i
i
300 mA
1.3 W
test required by clause 6.3.12 of EN60079-11:2012. This must be taken into account when installing the apparatus.
polyurethane paint finish; however care should be taken to protect it from impact or abrasion if located in Zone 0.
Certificate:
Standards:
UL-BR 13.0584X
ABNT NBR IEC60079-0:2008 + Errata 1:2011, ABNT NBR IEC60079-11:2009
Markings:
HART™: Ex ia IIC T5/T4 Ga, T5(–20 °C ≤ Ta ≤ +40 °C), T4(–20 °C ≤ Ta ≤ +70 °C) Fieldbus: Ex ia IIC T4 Ga (–20 °C ≤ Ta ≤ +60 °C)
HART PROFIBUS
Voltage U
Current I
Power P
Capacitance Ci0.012 µF 0 µF
Inductance L
i
i
i
30 V 30 V
200 mA 300 mA
0.9 W 1.3 W
0 mH 0 mH
i
®
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90 V transient suppressor, it is not capable of withstanding the 500 V insulation test required by
Quick Start Guide 23
Page 24
Quick Start Guide June 2020
ABNT NBR IRC 60079-11. This must be taken into account when installing the equipment.
2. The enclosure may be made of aluminum alloy and given protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if equipment requires EPL Ga.

3.9 Additional certifications

®
3-A
All Rosemount 3051HT transmitters with the following connections are 3-A approved and labeled:
T32: 1½-in. Tri Clamp
T42: 2-in. Tri Clamp
If process connection B11 is selected, see reference the ordering table of the Rosemount 1199 Diaphragm Seal PDS (00813-0100-4016) for availability of 3-A certifications.
A 3-A certificate of compliance is available by selecting option code QA.
EHEDG
All Rosemount 3051HT transmitters with the following connections are EHEDG approved and labeled:
T32: 1½-in. Tri Clamp
T42: 2-in. Tri Clamp
If process connection B11 is selected, see reference the ordering table of the Rosemount 1199 Diaphragm Seal PDS (00813-0100-4016) for availability of EHEDG certifications.
An EHEDG certificate of compliance is available by selecting option code QE.
Ensure gasket selected for installation is approved to meet both application and EHEDG certification requirements.
ASME-BPE
All Rosemount 3051HT Transmitters with option F2 and the following connections are designed to ASME-BPE SF4 standards
(1)
:
T32: 1½-in. Tri Clamp
T42: 2-in. Tri Clamp
A self-certified certificate of compliance to ASME-BPE is also available (option QB)
(1)
Per Clause SD-2.4.4.2 (m), suitability of painted aluminum housings to be determined by end user.
24 Emerson.com/Rosemount
Page 25
June 2020 Quick Start Guide
Figure 3-1: Rosemount 3051HT Declaration of Conformity
Quick Start Guide 25
Page 26
Quick Start Guide June 2020
Figure 3-2: Rosemount 3051HT Declaration of Conformity
26 Emerson.com/Rosemount
Page 27
June 2020 Quick Start Guide
Figure 3-3: Rosemount 3051HT Declaration of Conformity
Quick Start Guide 27
Page 28
Quick Start Guide June 2020
China RoHS
28 Emerson.com/Rosemount
Page 29
June 2020 Quick Start Guide
Quick Start Guide 29
Page 30
Quick Start Guide June 2020
30 Emerson.com/Rosemount
Page 31
June 2020 Quick Start Guide
Quick Start Guide 31
Page 32
*00825-0200-4091*
00825-0200-4091, Rev. CA
Quick Start Guide
June 2020
Global Headquarters
Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 204 8889 RFQ.RMD-RCC@Emerson.com
Latin America Regional Office
Emerson Automation Solutions 1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office
Emerson Automation Solutions 1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com
North America Regional Office
Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 204 8889 RMT-NA.RCCRFQ@Emerson.com
Europe Regional Office
Emerson Automation Solutions Europe GmbH Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465 RFQ.RMTMEA@Emerson.com
Linkedin.com/company/Emerson-
Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/
RosemountMeasurement
©
2020 Emerson. All rights reserved.
Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners.
Loading...