Rosemount 3051CFC Operating Manual

Reference Manual
00809-0100-4007, Rev BA
January 2017
Rosemount™ 3051 Pressure Transmitter
with 4–20 mA HART® Revision 5 and 7 Selectable Protocol
Reference Manual
00809-0100-4007, Rev BA
Contents
1Section 1: Introduction
2Section 2: Configuration
Contents
January 2017
1.1 Using this manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Models covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3 Product recycling/ disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.3 System readiness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3.1 Confirm correct Device Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.4 Configuration basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4.1 Configuring on the bench . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4.2 Configuration tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5 Setting the loop to manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.6 Verify configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.6.1 Verifying configuration with Field Communicator . . . . . . . . . . . . . . . . . . . . 8
2.6.2 Verifying configuration with AMS Device Manager . . . . . . . . . . . . . . . . . . . 8
2.6.3 Verifying configuration with LOI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.6.4 Verifying process variables configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.7 Basic setup of the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.7.1 Setting pressure units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.7.2 Setting transmitter output (transfer function) . . . . . . . . . . . . . . . . . . . . . . 10
2.7.3 Rerange the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.7.4 Damping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.8 Configuring the LCD display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.9 Detailed transmitter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.9.1 Configuring alarm and saturation levels. . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.9.2 Configuring process alerts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.9.3 Configuring scaled variable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.9.4 Re-mapping device variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.10Configuring transmitter diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.10.1Configuring power advisory diagnostic . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Contents
2.11Performing transmitter tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.11.1Verifying alarm level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.11.2Performing an analog loop test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.11.3Simulate device variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
iii
Contents
January 2017
Reference Manual
00809-0100-4007, Rev BA
2.12Configuring burst mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
2.13Establishing multidrop communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2.13.1Changing a transmitter address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2.13.2Communicating with a multidropped transmitter. . . . . . . . . . . . . . . . . . . 28
3Section 3: Hardware Installation
3.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.2 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.3 Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.3.1 Installation considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.3.2 Environmental considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.3.3 Mechanical considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.3.4 Draft range considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.4 Installation procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.4.1 Mount the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.4.2 Impulse piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.4.3 Process connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
3.4.4 Inline process connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.5 Rosemount 305, 306, and 304 Manifolds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
3.5.1 Rosemount 305 Integral Manifold installation procedure . . . . . . . . . . . . 44
3.5.2 Rosemount 306 Integral Manifold installation procedure . . . . . . . . . . . . 44
3.5.3 Rosemount 304 Conventional Manifold installation procedure . . . . . . . 44
3.5.4 Manifold operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4Section 4: Electrical Installation
4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4.2 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4.3 LCD display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
4.3.1 Rotating LOI/LCD display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
4.4 Configuring transmitter security. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
4.4.1 Setting security switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
4.4.2 Setting simulate switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
4.4.3 HART Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
4.4.4 Configuration button lock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
4.4.5 LOI password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
4.5 Setting transmitter alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
4.6 Electrical considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
4.6.1 Conduit installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
iv
Contents
Reference Manual
00809-0100-4007, Rev BA
5Section 5: Operation and Maintenance
Contents
January 2017
4.6.2 Power supply for 4–20 mA HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
4.6.3 Wiring the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
4.6.4 Signal wiring grounding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
5.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
5.2 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
5.3 Recommended calibration tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
5.3.1 Field installation tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
5.3.2 Bench calibration tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
5.4 Calibration overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
5.4.1 Determining necessary sensor trims . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
5.4.2 Determining calibration frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
5.4.3 Compensating for span line pressure effects (range 4 and 5) . . . . . . . . . 65
5.5 Trim the pressure signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
5.5.1 Sensor trim overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
5.5.2 Perform a sensor trim. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
5.5.3 Recall factory trim—sensor trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
5.6 Trim the analog output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
5.6.1 Performing Digital-to-Analog trim (4–20 mA output trim) . . . . . . . . . . . 70
5.6.2 Performing Digital-to-Analog trim (4–20 mA output trim)
using other scale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
5.6.3 Recalling factory trim—analog output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5.7 Switching HART Revision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
5.7.1 Switching HART revision with generic menu . . . . . . . . . . . . . . . . . . . . . . . . 72
5.7.2 Switching HART Revision with Field Communicator . . . . . . . . . . . . . . . . . 72
5.7.3 Switching HART Revision with AMS Device Manager. . . . . . . . . . . . . . . . . 72
5.7.4 Switching HART revision with LOI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
6Section 6: Troubleshooting
6.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
6.2 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Contents
6.3 Diagnostic messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
6.3.1 Diagnostic message: failed - fix now . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
6.3.2 Diagnostic message: maintenance - fix soon. . . . . . . . . . . . . . . . . . . . . . . . 76
6.3.3 Diagnostic message: advisory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
6.4 Disassembly procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
6.4.1 Removing from service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
v
Contents
January 2017
Reference Manual
00809-0100-4007, Rev BA
6.4.2 Removing terminal block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
6.4.3 Removing the electronics board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
6.4.4 Removing sensor module from the electronics housing . . . . . . . . . . . . . . 79
6.5 Reassembly procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
6.5.1 Attaching electronics board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
6.5.2 Installing terminal block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
6.5.3 Reassembling the Rosemount 3051C process flange . . . . . . . . . . . . . . . . 80
6.5.4 Installing drain/vent valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
6.6 Service support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
7Section 7: Safety Instrumented Systems (SIS) Requirements
7.1 Rosemount 3051 safety certified identification. . . . . . . . . . . . . . . . . . . . . . . . . . . 83
7.2 Installation in SIS applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
7.3 Configuring in SIS applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
7.3.1 Damping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
7.3.2 Alarm and saturation levels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
7.4 SIS operation and maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
7.4.1 Proof test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
7.4.2 Partial proof test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
7.4.3 Comprehensive proof test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
7.4.4 Calculation of average probability of failure on demand (PFDAVG) . . . . 86
7.5 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
AAppendix A: Specifications and Reference Data
A.1 Performance specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
A.1.1 Conformance to specification (±3 s [Sigma]) . . . . . . . . . . . . . . . . . . . . . . . 87
A.1.2 Reference accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
A.1.3 Flow performance - flow reference accuracy . . . . . . . . . . . . . . . . . . . . . . . . 88
A.1.4 Total performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
A.1.5 Long term stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
A.1.6 Dynamic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
A.1.7 Line pressure effect per 1000 psi (6.9 MPa) . . . . . . . . . . . . . . . . . . . . . . . . . 89
A.1.8 Ambient Temperature Effect per 50 °F (28 °C) . . . . . . . . . . . . . . . . . . . . . . 90
A.1.9 Mounting Position Effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
A.1.10Vibration effect. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
A.1.11Power supply effect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
A.1.12Electromagnetic compatibility (EMC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
A.1.13Transient protection (option code T1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
vi
Contents
Reference Manual
00809-0100-4007, Rev BA
Contents
January 2017
A.2 Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
A.2.1 Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
A.2.2 Range and sensor limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
A.3 4–20 mA (output code A). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
A.3.1 Overpressure Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
A.3.2 Static pressure limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
A.3.3 Burst pressure limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
A.3.4 Failure mode alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
A.3.5 Temperature limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
A.3.6 Humidity limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
A.3.7 Turn-on time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
A.3.8 Volumetric displacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
A.3.9 Damping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
A.4 Physical specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
A.4.1 Process connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
A.4.2 Rosemount 3051L process wetted parts . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
A.4.3 Non-wetted parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
A.4.4 Shipping weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
A.5 Dimensional drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
A.6 Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
A.6.1 Rosemount 3051C Coplanar Pressure Transmitter . . . . . . . . . . . . . . . . . 110
A.6.2 Rosemount 3051T In-Line Pressure Transmitter. . . . . . . . . . . . . . . . . . . . 117
A.6.3 Rosemount 3051CF Flowmeter Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
A.6.4 Rosemount 3051CFC Compact Flowmeter . . . . . . . . . . . . . . . . . . . . . . . . 129
A.6.5 Rosemount 3051CFP Integral Orifice Flowmeter . . . . . . . . . . . . . . . . . . . 134
A.6.6 Rosemount 3051L Level Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
A.7 Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
A.8 Spare parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
BAppendix B: Product Certifications
B.1 European Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
B.2 Ordinary Location Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
B.3 USA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
B.4 Europe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Contents
B.5 International . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
B.6 Brazil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
B.7 China. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
B.8 Japan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
vii
Contents
January 2017
Reference Manual
00809-0100-4007, Rev BA
B.9 Technical Regulations Customs Union (EAC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
B.10Combinations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
B.11Conduit Plugs and Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
B.12Additional Certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
B.13Pipe I.D. range codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
B.14Installation drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
B.14.1Factory mutual 03031-1019. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
B.14.2Canadian standards association (CSA) 03031-1024 . . . . . . . . . . . . . . . . 184
CAppendix C: Field Communicator Menu Trees and Fast Keys
C.1 Field Communicator menu trees. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
C.2 Field Communicator Fast Keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
DAppendix D: Local Operator Interface (LOI)
D.1 LOI menu tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
D.2 LOI menu tree - extended menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
D.3 Number entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
D.4 Text entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
viii
Contents
Reference Manual
NOTICE
00809-0100-4007, Rev BA
Rosemount™ 3051 Pressure Transmitter
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
For technical assistance, contacts are listed below:
Customer Central
Technical support, quoting, and order-related questions.
United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)
Asia Pacific- 65 777 8211
Europe/Middle East/Africa - 49 (8153) 9390
North American Response Center
Equipment service needs.
1-800-654-7768 (24 hours—includes Canada)
Outside of these areas, contact your local Emerson
representative.
Title Page
January 2017
The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Emerson Sales Representative.
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the approvals section of this manual for any restrictions associated with a safe installation.
Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments in the
loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is
applied to the unit.
Process leaks may cause harm or result in death.
Install and tighten process connectors before applying pressure.Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
Title Page
ix
Title Page
January 2017
Reference Manual
00809-0100-4007, Rev BA
Replacement equipment or spare parts not approved by Emerson for use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
Improper assembly of manifolds to traditional flange can damage sensor module.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e.,
bolt hole) but must not contact sensor module housing.
Severe changes in the electrical loop may inhibit HART values. Therefore, Rosemount cannot absolutely warrant or guarantee that the correct Failure alarm level (HIGH or LOW) can be read by the host system at the time of annunciation.
®
Communication or the ability to reach alarm
x
Title Page
Reference Manual
00809-0100-4007, Rev BA

Section 1 Introduction

1.1 Using this manual

The sections in this manual provide information on installing, operating, and maintaining the Rosemount
Section 2: Configuration provides instruction on commissioning and operating Rosemount 3051
Transmitters. Information on software functions, configuration parameters, and online variables is also included.
Section 3: Hardware Installation contains mechanical installation instructions and field upgrade options.
Section 4: Electrical Installation contains electrical installation instructions and field upgrade options.
Section 5: Operation and Maintenance provides detailed information on calibrating and changing HART
revisions.
Section 6: Troubleshooting provides troubleshooting techniques for the most common operating
problems.
3051 Pressure Transmitter. The sections are organized as follows:
Introduction
January 2017
Section 7: Safety Instrumented Systems (SIS) Requirements provides identification, installation,
configuration, operation and maintenance, and inspection information for Safety Instrumented Systems.
Appendix A: Specifications and Reference Data supplies reference and specification data, as well as
ordering information.
Appendix B: Product Certifications contains intrinsic safety approval information, European ATEX
directive information, and approval drawings.
Appendix C: Field Communicator Menu Trees and Fast Keys provides full menu trees and abbreviated Fast
Key sequences for commissioning tasks.
Appendix D: Local Operator Interface (LOI) provides detailed LOI menu trees.

1.2 Models covered

The following transmitters are covered by this manual:
Rosemount 3051C Coplanar™ Pressure Transmitter
Measures differential and gage pressure up to 2000 psi (137,9 bar).
Measures absolute pressure up to 4000 psia (275,8 bar).
Rosemount 3051T In-Line Pressure Transmitter
Measures absolute pressure up to 20000 psi (1378,95 bar)
Introduction
Rosemount 3051L Liquid Level Transmitter
Measures level and specific gravity up to 300 psi (20,7 bar).
Rosemount 3051CF Series Flowmeter
Measures flow in line sizes from 1/2-in. (15mm) to 96-in. (2400 mm).
1
Introduction
January 2017
Reference Manual
00809-0100-4007, Rev BA
Note
For transmitter with F For transmitter with PROFIBUS® PA, see Rosemount 3051 Reference Manual.
OUNDATION
Fieldbus, see Rosemount 3051 Reference Manual.

1.3 Product recycling/ disposal

Recycling of equipment and packaging should be taken into consideration and disposed of in accordance with local and national legislation/regulations.
2
Introduction
Reference Manual
00809-0100-4007, Rev BA

Section 2 Configuration

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
System readiness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Configuration basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5
Verify configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7
Basic setup of the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 9
Configuring the LCD display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 14
Detailed transmitter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 15
Configuring transmitter diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 21
Configuring burst mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 26
Establishing multidrop communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 27

2.1 Overview

Configuration
January 2017
This section contains information on commissioning and tasks that should be performed on the bench prior to installation, as well as tasks performed after installation as described in “Configuring transmitter
diagnostics” on page 21.
Field Communicator, AMS perform configuration functions. For convenience, Field Communicator Fast Key sequences are labeled “Fast Keys,” and abbreviated LOI menus are provided for each function below.
Full Field Communicator menu trees and Fast Key sequences are available in Appendix C: Field
Communicator Menu Trees and Fast Keys. LOI menu trees are available in Appendix D: Local Operator Interface (LOI).
Device Manager, and Local Operator Interface (LOI) instructions are given to

2.2 Safety messages

Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that raises potential safety issues is indicated by a
warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.
Config uration
3
Configuration
January 2017
Reference Manual
00809-0100-4007, Rev BA
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the approvals section of this manual for any restrictions associated with a safe installation.
Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments in the
loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is
applied to the unit.
Process leaks may cause harm or result in death.
Install and tighten process connectors before applying pressure.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
Replacement equipment or spare parts not approved by Emerson for use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous.
Use only bolts supplied or sold by Emerson
Improper assembly of manifolds to traditional flange can damage sensor module.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e.,
bolt hole) but must not contact sensor module housing.
Severe changes in the electrical loop may inhibit HART
values. Therefore, Rosemount cannot absolutely warrant or guarantee that the correct Failure alarm level (HIGH or LOW) can be read by the host system at the time of annunciation.
as spare parts.
®
Communication or the ability to reach alarm

2.3 System readiness

If using HART-based control or asset management systems, confirm the HART capability of such
systems prior to commissioning and installation. Not all systems are capable of communicating with HART revision 7 devices.
For instructions on how to change the HART revision of your transmitter, see “Switching HART
Revision” on page 72.
2.3.1 Confirm correct Device Driver
1. Verify the latest Device Driver (DD/DTM) is loaded on your systems to ensure proper communications.
2. Download the latest DD at Emerson.com
3. In the Browse by Member dropdown menu, select Rosemount
4. Select desired Product a. Within Table 2-1 on page 5, use the HART Universal Revision and Device Revision numbers to find
the correct Device Driver
4
or FieldCommGroup.org.
business unit of Emerson.
Configuration
Reference Manual
00809-0100-4007, Rev BA
Table 2-1. Rosemount 3051 Device Revisions and Files
Configuration
January 2017
Device identification
NAMUR
Release date
April 2012 1.0.xx 1.0.xx 01
January 1998 N/A N/A 178 5 3 00809-0100-4001
1. NAMUR Revision is located on the hardware tag of the device. Differences in level 3 changes, signified above by xx, represent minor product changes as defined per NE53. Compatibility and functionality are preserved and product can be used interchangeably.
2. HART Software Revision can be read using a HART capable configuration tool. Value shown is minimum revision that could correspond to NAMUR Revisions.
3. Device Driver file names use Device and DD Revision, e.g. 10_01. HART Protocol is designed to enable legacy device driver revisions to continue to communicate with new HART devices. To access new functionality, the new Device Driver must be downloaded. It is recommended to download new Device Driver files to ensure full functionality.
4. HART Revision 5 and 7 selectable, power diagnostics, safety certified, LOI, process alerts, scaled variable, configurable alarms, expanded engineering units.
software
revision
(1)
NAMUR hardware revision
(1)
HART
software
revision
(2)
Device driver
identification
HART
Universal
Revision
7 10
5
Device
revision
9
(3)
Review instructions
Manual document
number
00809-0100-4007
Review
functionality
Change
description
(4)
N/A

2.4 Configuration basics

Set all transmitter hardware adjustments during commissioning to avoid exposing the transmitter electronics to the plant environment after installation.
The Rosemount 3051 can be configured either before or after installation. Configuring the transmitter on the bench using either a Field Communicator, AMS Device Manager, or LOI ensures all transmitter components are in working order prior to installation. Verify the security switch is set in the unlock position ( ) in order to proceed with configuration. See Figure 4-2 on page 53 for switch location.
2.4.1 Configuring on the bench
To configure on the bench, required equipment includes a power supply, and a Field Communicator, AMS Device Manager, or LOI (option M4). Wire equipment as shown in Figure 2-1 below. To ensure successful HART Communication, a resistance of at least 250 Ω must be present between the transmitter and the power supply, see “Power supply for 4–20 mA HART” on page 56 for details. Connect the Field Communicator leads to the terminals labeled “COMM” on the terminal block.
Config uration
5
Configuration
SAVE
1. Overview
2. Configure
3. Service Tools
3051 FT 45B Online
January 2017
Figure 2-1. Wiring the Transmitter
A. Vdc supply B. R
250 (necessary for HART Communication only)
L
2.4.2 Configuration tools
Configuring with a Field Communicator
Reference Manual
00809-0100-4007, Rev BA
A.
B.
There are two interfaces available with the Field Communicator: Traditional and Dashboard interfaces. All steps using a Field Communicator will be described using Dashboard interfaces. Figure 2-2 on page 6 shows the Device Dashboard interface. As stated in System readiness , it is critical that the latest DD’s are loaded into the Field Communicator. Visit Emerson.com/Rosemount/Device-Install-Kits
FieldCommGroup.org
Field Communicator menu trees and Fast Keys are available in Appendix C: Field Communicator Menu
Trees and Fast Keys.
Figure 2-2. Device Dashboard
to download latest DD library.
or
6
Configuring with AMS Device Manager
Full configuration capability with AMS Device Manager requires loading the most current Device Descriptor (DD) for this device. Download the latest DD at
Emerson.com/Rosemount/Device-Install-Kits
Note
All steps using AMS Device Manager will be described using version 11.5.
or FieldCommGroup.org.
Configuration
Reference Manual
00809-0100-4007, Rev BA
Configuring with a LOI
The LOI requires option code M4 to be ordered. To activate the LOI push either configuration button. Configuration buttons are located on the LCD display (must remove housing cover to access), or underneath the top tag of the transmitter. See Ta b le 2 - 2 for configuration button functionality and
Figure 2-3 for configuration button location. When using the LOI for configuration, several features
require multiple screens for a successful configuration. Data entered will be saved on a screen-by-screen basis; the LOI will indicate this by flashing “SAVED” on the LCD display each time.
LOI menu trees are available in Appendix D: Local Operator Interface (LOI).
Figure 2-3. LOI Configuration Buttons
Configuration
January 2017
B
A
A. Internal configuration buttons B. External configuration buttons
Table 2-2. LOI Button Operation
Button
Left No SCROLL Right Yes ENTER

2.5 Setting the loop to manual

Whenever sending or requesting data that would disrupt the loop or change the output of the transmitter, set the process application loop to manual control. The Field Communicator, AMS Device Manager, or the LOI will prompt you to set the loop to manual when necessary. The prompt is only a reminder; acknowledging this prompt does not set the loop to manual. It is necessary to set the loop to manual control as a separate operation.

2.6 Verify configuration

It is recommended that various configuration parameters are verified prior to installation into the process. The various parameters are detailed out for each configuration tool. Depending on what configuration tool(s) are available follow the steps listed relevant to each tool.
Config uration
7
Configuration
January 2017
2.6.1 Verifying configuration with Field Communicator
Configuration parameters listed in Ta b le 2 - 3 are to be reviewed prior to transmitter installation. A Full list of configuration parameters that can be reviewed and configured using a Field Communicator are located in Appendix C: Field Communicator Menu Trees and Fast Keys.
Fast key sequences for the latest DD are shown in Ta bl e 2 - 3. For Fast Key sequences for legacy DD's contact your local Emerson Representative.
From the HOME screen, enter the Fast Key sequences listed.
Table 2-3. Rosemount 3051 Device Dashboard Fast Key Sequence
Fast Key sequence
Function
HART 7 HART 5
Alarm and saturation levels 2, 2, 2, 5 2, 2, 2, 5
Damping 2, 2, 1, 1, 5 2, 2, 1, 1, 5
Primary variable 2, 1, 1, 4, 1 2, 1, 1, 4, 1
Range values 2, 1, 1, 4 2, 1, 1, 4
Ta g 2, 2, 7, 1, 1 2, 2, 7, 1, 1
Tra nsfer func tion 2, 2, 1, 1, 6 2, 2, 1, 1, 6
Reference Manual
00809-0100-4007, Rev BA
Units 2, 2, 1, 1, 4 2, 2, 1, 1, 4
2.6.2 Verifying configuration with AMS Device Manager
Right click on the device and select Configuration Properties from the menu. Navigate the tabs to review the transmitter configuration data.
2.6.3 Verifying configuration with LOI
Press any configuration button to activate the LOI. Select VIEW CONFIG to review the below parameters. Use the configuration buttons to navigate through the menu. installation include:
Ta g Primary Variable
Units Range Values
Transfer Func tion Damping
Alarm and Saturation Levels
The parameters to be reviewed prior to
2.6.4 Verifying process variables configuration
This section describes how to verify the correct process variables are selected.
Verifying process variables with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
8
3, 2, 1
Configuration
Reference Manual
UNITS
PRESS UNITS
PRESS UNITS
TEMP UNITS BACK TO MENU EXIT MENU
PRESS UNITS
INH2O MMHG CMHG0C MHG0C PSI PSF ATM TORR PA KPA ...
VIEW CONFIG ZERO TRIM
UNITS
UNITS
RERANGE LOOP TEST DISPLAY EXTENDED MENU EXIT MENU
00809-0100-4007, Rev BA
Verifying process variables with AMS Device Manager
1. Right click on the device and select Overview from the menu.
2. Select the All Variables button to display the primary, secondary, tertiary and quaternary variables.

2.7 Basic setup of the transmitter

This section goes through the necessary steps for basic setup of a pressure transmitter. When installing in DP level or DP flow applications, refer to“Configuring scaled variable” on page 17 for setup instructions.
2.7.1 Setting pressure units
The pressure unit command sets the unit of measure for the reported pressure.
Setting pressure units with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Configuration
January 2017
Device Dashboard Fast Keys
2, 2, 1, 1, 4
Setting pressure units with AMS Device Manager
1. Right click on the device and select Configure.
2. Select Manual Setup and select desired units from Pressure Units dropdown menu.
3. Select Send when complete.
Setting pressure units with a LOI
Follow Figure 2-4 on page 9 to select desired pressure and temperature units. Use the SCROLL and ENTER buttons to select desired unit. Save by selecting SAVE as indicated on the LCD display screen.
Figure 2-4. Selecting Units with LOI
Config uration
9
Configuration
EXTENDED MENU
CALIBRAT DAMPING
TRANSFER FUNCT
TRANSFER FUNCT
SCALED VARIAB ASSIGN PV TAG ALARM SAT VALUES PASSWORD SIMLATE HART REV BACK TO MENU EXIT MENU
TRANSFER FUNCT
LINEAR TRANSFER FUNCTION SQR ROOT TRANSFER FUNCTION BACK TO MENU EXIT MENU
VIEW CONFIG ZERO TRIM UNITS RERANGE LOOP TEST DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
January 2017
2.7.2 Setting transmitter output (transfer function)
The Rosemount 3051 has two output settings: Linear and Square root. As shown in Figure 2-6 on
page 11, activating the square root options makes analog output proportional to flow, and includes a
fixed Low Flow Cutoff at 5 percent.
However, for Differential Pressure (DP) Flow and DP Level applications it is recommended to use scaled variable. Refer to “Configuring scaled variable” on page 17 for setup instructions.
Setting transmitter output with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Reference Manual
00809-0100-4007, Rev BA
Device Dashboard Fast Keys
2, 2, 1, 1, 6
Setting transmitter output with AMS Device Manager
1. Right click on the device and select Configure.
2. Select Manual Setup and select output type from Analog Output Transfer Function and click Send.
3. Carefully read the warning and select Ye s if it is safe to apply the changes.
Setting transmitter output with a LOI
Reference Figure 2-5 on page 10 to select either linear or square root transfer function using the LOI.
Figure 2-5. Set Output with LOI
10
Configuration
Reference Manual
A
B
C
0.5 1
% Pressure Input
0
0 102030405060708090100
4 mA
20mA
% Pressure Input
B
A
4 mA
00809-0100-4007, Rev BA
Figure 2-6. 4-20 mA HART Square Root Output Transition Point
A. Square root curve B. 5% transition point C. 4% transition point
Configuration
January 2017
2.7.3 Rerange the transmitter
The range values command sets each of the lower and upper range analog values (4 and 20 mA points) to a pressure. The lower range point represents 0% of range and the upper range point represents 100% of range. In practice, the transmitter range values may be changed as often as necessary to reflect changing process requirements. For a complete listing of range and sensor limits, refer to “Range and sensor limits” on page 91.
Select from one of the methods below to rerange the transmitter. Each method is unique; examine all options closely before deciding which method works best for your process.
Rerange by manually setting range points with a Field Communicator, AMS Device Manager, or LOI. Rerange with a pressure input source and a Field Communicator, AMS Device Manager, LOI, or local
zero and span buttons
Manually rerange the transmitter by entering range points
Entering range points with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Entering range points with AMS Device Manager
1. Right click on the device and select Configure:
2. Select Manual Setup and select Analog Output.
2, 2, 2, 1
Config uration
3. Enter upper and lower range values in the Range Limits box and select Send.
4. Carefully read the warning and select Ye s if it is safe to apply the changes.
11
Configuration
RERANGE
ENTER VALUES
ENTER VALUES
APPLY VALUES BACK TO MENU EXIT MENU
ENTER VALUES
LRV URV BACK TO MENU EXIT MENU
VIEW CONFIG ZERO TRIM UNITS
RERANGE
RERANGE
LOOP TEST DISPLAY EXTENDED MENU EXIT MENU
RERANGE
ENTER VALUES
APPLY VALUES
APPLY VALUES
BACK TO MENU EXIT MENU
APPLY VALUES
LRV URV BACK TO MENU EXIT MENU
VIEW CONFIG ZERO TRIM UNITS
RERANGE
RERANGE
LOOP TEST DISPLAY EXTENDED MENU EXIT MENU
January 2017
Reference Manual
00809-0100-4007, Rev BA
Entering range points with LOI
Reference Figure 2-7 on page 12 to rerange the transmitter using the LOI. Enter values using SCROLL and ENTER buttons.
Figure 2-7. Rerange with LOI
Rerange the transmitter with applied pressure source
Reranging using an applied pressure source is a way of reranging the transmitter without entering specific 4 and 20 mA points.
Rerange with an applied pressure source using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 2, 2
Rerange with an applied pressure source using AMS Device Manager
1. Right click on the device, select Configure.
2. Select the Analog Output tab.
3. Select Range by Applying Pressure button and follow the screen prompts range the transmitter.
Rerange with an applied pressure source using a Field Communicator
Use Figure 2-8 to manually rerange the device using an applied pressure source with an LOI.
Figure 2-8. Rerange with Applied Pressure Using LOI
12
Configuration
Reference Manual
00809-0100-4007, Rev BA
Rerange with an applied pressure source using local zero and span buttons
If ordered, local zero and span buttons (option code D4) can be used to rerange the transmitter with an applied pressure. Refer to Figure 2-9 on page 13 for analog zero and span button location.
To rerange the transmitter using the span and zero buttons, perform the following procedure:
1. Loosen the screw holding the top tag of the transmitter housing. Rotate the label to expose the zero and span buttons.
2. Confirm device has local zero and span buttons by verifying blue retainer under the tag.
3. Apply transmitter pressure.
4. Rerange the transmitter. a. To change the zero (4 mA point) while maintaining the span: press and hold zero button for at
b. To change the span (20 mA point) while maintaining the zero point: press and hold the span
Note
4 and 20 mA points must maintain the minimum span defined in Functional specifications .
Configuration
January 2017
least two seconds then release.
button for at least two seconds and then release.
Figure 2-9. Analog Zero and Span Buttons
A
A. Zero and span buttons
If the transmitter security is on, adjustments to the zero and span will not be able to be made. Refer
to “Configuring transmitter security” on page 53 for security information.
The span is maintained when the 4 mA point is set. The span changes when the
20 mA point is set. If the lower range point is set to a value that causes the upper range point to exceed the sensor limit, the upper range point is automatically set to the sensor limit, and the span is adjusted accordingly.
Regardless of the range points, the Rosemount 3051 will measure and report all readings within the
digital limits of the sensor. For example, if the 4 and 20 mA points are set to 0 and 10 inH transmitter detects a pressure of 25 inH
O, it digitally outputs the 25 inH2O reading and a 250% of
2
range reading.
O, and the
2
Config uration
13
Configuration
EXTENDED MENU
CALIBRAT
DAMPING
DAMPING
TRANSFER FUNCT SCALED VARIAB ASSIGN PV TAG ALARM SAT VALUES PASSWORD SIMLATE HART REV BACK TO MENU EXIT MENU
VIEW CONFIG ZERO TRIM UNITS RERANGE LOOP TEST DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
January 2017
2.7.4 Damping
The damping command changes the response time of the transmitter; higher values can smooth variations in output readings caused by rapid input changes. Determine the appropriate damping setting based on the necessary response time, signal stability, and other requirements of the loop dynamics within your system. The damping command utilizes floating point configuration allowing the user to input any damping value within 0–60 seconds.
Damping with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Reference Manual
00809-0100-4007, Rev BA
Device Dashboard Fast Keys
2, 2, 1, 1, 5
Enter desired Damping Value and select APPLY.
Damping with AMS Device Manager
1. Right click on the device and select Configure.
2. Select Manual Setup.
3. Within the Pressure Setup box, enter desired damping value and click Send.
4. Carefully read the warning and click Ye s if it is safe to apply the changes.
Damping with a LOI
Reference Figure 2-10 to enter damping values using an LOI.
Figure 2-10. Damping with LOI

2.8 Configuring the LCD display

14
The LCD display configuration command allows customization of the LCD display to suit application requirements. The LCD display will alternate between the selected items.
Pressure units Sensor temperature
% of range mA output
Scaled variable
Configuration
Reference Manual
DISPLAY
PRESS (on/off) SCALED (on/off) TEMP (on/off) %RANGE (on/off) ANALOG (on/off) STRTUP (on/off) BACK TO MENU EXIT MENU
VIEW CONFIG ZERO TRIM UNITS RERANGE LOOP TEST
DISPLAY
DISPLAY
EXTENDED MENU EXIT MENU
00809-0100-4007, Rev BA
In the following instructions, the LCD display can also be configured to display configuration information during the device startup. Select Review Parameters at Startup to enable or disable this functionality.
Configuring LCD display with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Configuration
January 2017
Device Dashboard Fast Keys
2, 2, 4
Configuring LCD display with AMS Device Manager
1. Right click on the device and select Configure.
2. Click Manual Setup, select the Display tab.
3. Select desired display options and select Send.
Configuring LCD display with a LOI
Refer to Figure 2-11 for LCD display configuration using a LOI.
Figure 2-11. Display with LOI

2.9 Detailed transmitter setup

2.9.1 Configuring alarm and saturation levels
Config uration
In normal operation, the transmitter will drive the output in response to pressure from the lower to upper saturation points. If the pressure goes outside the sensor limits, or if the output would be beyond the saturation points, the output will be limited to the associated saturation point.
The Rosemount 3051 Transmitter automatically and continuously performs self-diagnostic routines. If the self-diagnostic routines detect a failure, the transmitter drives the output to configured alarm and value based on the position of the alarm switch. See “Setting transmitter alarm” on page 55.
Table 2-4. Rosemount Alarm and Saturation Value
Level 4–20 mA saturation 4–20 mA alarm
Low 3.9 mA 3.75 mA
High 20.8 mA 21.75 mA
15
Configuration
January 2017
Reference Manual
00809-0100-4007, Rev BA
Table 2-5. NAMUR-Compliant Alarm And Saturation Values
Level 4–20 mA saturation 4–20 mA alarm
Low 3.8 mA 3.6 mA
High 20.5 mA 22.5 mA
Table 2-6. Custom Alarm and Saturation Values
Level 4–20 mA saturation 4–20 mA alarm
Low 3.7–3.9 mA 3.6–3.8 mA
High 20.1–22.9 mA 20.2–23.0 mA
Failure mode alarm and saturation levels can be configured using a Field Communicator, AMS Device Manager, and the LOI. The following limitations exist for custom levels:
Low alarm level must be less than the low saturation level High alarm level must be higher than the high saturation level Alarm and saturation levels must be separated by at least 0.1 mA
The configuration tool will provide an error message if the configuration rule is violated.
Note
Transmitters set to HART multidrop mode send all saturation and alarm information digitally; saturation and alarm conditions will not affect the analog output. See also “Establishing multidrop
communication” on page 27.
Configuring alarm and saturation levels using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 2, 5, 6
Configuring alarm and saturation levels with AMS Device Manager
1. Right click on the device, and select Configure.
2. Select Configure Alarm and Saturation Levels button.
3. Follow screen prompts to configure Alarm and Saturation Levels.
Configuring alarm and saturation levels using LOI
Refer to Figure 2-12 for instructions to configure alarm and saturation levels.
16
Configuration
Reference Manual
EXTENDED MENU
CALIBRAT DAMPING TRANSFER FUNCT SCALED VARIAB ASSIGN PV TAG
ALARM SAT VALUES
ALARM SAT VALUES
PASSWORD SIMULATE HART REV BACK TO MENU EXIT MENU
ALARM SAT VALUES
ROSEMOUNT VALUES NAMUR VALUES OTHER VALUES BACK TO MENU EXIT MENU
VIEW CONFIG ZERO TRIM UNITS RERANGE LOOP TEST DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
00809-0100-4007, Rev BA
Figure 2-12. Configuring Alarm and Saturation with LOI
2.9.2 Configuring process alerts
Process alerts allow the transmitter to indicate when the configured data point is exceeded. Process alerts can be set for pressure, temperature, or both. An alert will be displayed on a Field Communicator, AMS Device Manager status screen or in the error section of the LOI/LCD display. The alert will reset once the value returns within range.
Configuration
January 2017
2.9.3 Configuring scaled variable
Config uration
Note
HI alert value must be higher than the LO alert value. Both alert values must be within the pressure or temperature sensor limits.
Configuring process alerts using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 3
1. Select either Pressure Alert or Temperature Alert and press ENTER.
2. Select Configure Alert.
3. Follow screen prompts to configure process alerts.
Configuring process alerts using AMS Device Manager
Right click on the device and select Configure.
1. Select Guided Setup.
2. Select the Process Alerts button.
3. Follow screen prompts to configure Process Alerts.
The scaled variable configuration allows the user to create a relationship/conversion between the pressure units and user-defined/custom units. There are two use cases for scaled variable. The first use case is to allow custom units to be displayed on the transmitter's LOI/LCD display. The second use case is to allow custom units to drive the transmitter's 4–20 mA output.
17
Configuration
January 2017
Reference Manual
00809-0100-4007, Rev BA
If the user desires custom units to drive the 4–20 mA output, scaled variable must be re-mapped as the primary variable. Refer to “Re-mapping device variables” on page 20.
The scaled variable configuration defines the following items:
Scaled variable units - Custom units to be displayed. Scaled data options - Defines the transfer function for the application
LinearSquare root
Pressure value position 1 - Lower known value point with consideration of linear offset. Scaled variable value position 1 - Custom unit equivalent to the lower known value point. Pressure value position 2 - Upper known value point Scaled variable value position 2 - Custom unit equivalent to the upper known value point Linear offset - The value required to zero out pressures effecting the desired pressure reading. Low flow cutoff - Point at which output is driven to zero to prevent problems caused by process
noise. It is highly recommended to use the low flow cutoff function in order to have a stable output and avoid problems due to process noise at a low flow or no flow condition. A low flow cutoff value that is practical for the flow element in the application should be entered.
Configuring Scaled Variable using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 1, 5, 7
1. Follow the screen prompts to configure Scaled Variable. a. When configuring for level, select Linear under Select Scaled data options. b. When configuring for flow, select Square Root under Select Scaled data options.
Configuring Scaled Variable using AMS Device Manager
1. Right click on the device and, select Configure.
2. Select Scaled Variable tab and select Scaled Variable button.
3. Follow screen prompts to configure Scaled Variable a. When configuring for level applications, select Linear under Select Scaled data options. b. When configuring for flow applications, select Square Root under Select Scaled data options.
Configuring Scaled Variable using a LOI
Refer to Figure 2-13 on page 19 for instructions to configure Scaled Variable using a LOI.
18
Configuration
Reference Manual
EXTENDED MENU
CALIBRAT DAMPING TRANSFER FUNCT
SCALED VARIAB
SCALED VARIAB
ASSIGN PV TAG ALARM SAT VALUES PASSWORD SIMLATE HART REV BACK TO MENU EXIT MENU
SCALED VARIAB
VIEW SCALED
CONFIG SCALED
CONFIG SCALED
BACK TO MENU EXIT MENU
VIEW CONFIG ZERO TRIM UNITS RERANGE LOOP TEST DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
H
L
230-in.
200-in.
12-in.
0.94 sg
00809-0100-4007, Rev BA
Figure 2-13. Configuring Scaled Variable Using a LOI
DP Level example
Figure 2-14. Example Tank
Configuration
January 2017
Config uration
A differential transmitter is used in a level application. Once installed on an empty tank and taps vented, the process variable reading is –209.4 inH
O. The process variable reading is the head pressure created
2
by fill fluid in the capillary. Based on Table 2-7 on page 20, the scaled variable configuration would be as follows:
19
Configuration
January 2017
Reference Manual
00809-0100-4007, Rev BA
Table 2-7. Scaled Variable Configuration for Tank Application
Scaled Variable units
Scaled data options
Pressure value position 1
Scaled Variable position 1
Pressure value position 2
Scaled Variable position 2
Linear offset
inch
linear
0 inH2O
12-in.
188 inH2O
212-in.
–209.4 inH2O
DP Flow example
A differential pressure transmitter is used in conjunction with an orifice plate in a flow application where the differential pressure at full scale flow is 125 inH
scale flow is 20,000 gallons of water per hour. It is highly recommended to use the low flow cutoff function in order to have a stable output and avoid problems due to process noise at a low flow or no flow condition. A low flow cutoff value that is practical for the flow element in the application should be entered. In this particular example, the low flow cutoff value is 1000 gallons of water per hour. Based on this information, the Scaled Variable configuration would be as follows:
Table 2-8. Scaled Variable Configuration for Flow Application
Scaled Variable units
gal/h
O. In this particular application, the flow rate at full
2
Scaled data options
Pressure value position 2
Scaled Variable position 2
Low Flow Cutoff
square root
125 inH2O
20,000 gal/h
1000 gal/h
Note
Pressure value position 1 and Scaled Variable position 1 are always set to zero for a flow application. No configuration of these values is required.
2.9.4 Re-mapping device variables
The re-mapping function allows the transmitter primary, secondary, tertiary, and quaternary variables (PV, 2V, 3V, and 4V) to be configured as desired. The PV can be remapped with a Field Communicator, AMS Device Manager, or a LOI. Variables (2V, 3V, and 4V) can only be re-mapped via Field Communicator or AMS Device Manager.
Note
The variable assigned to the primary variable drives the 4–20 mA output. This value can be selected as Pressure or Scaled Variable. The 2, 3, and 4 variables only apply if HART burst mode is being used.
20
Configuration
Loading...
+ 186 hidden pages