Read this manual before working with the product. For personal and system safety, and for optimum
product performance, make sure you thoroughly understand the contents before installing, using, or
maintaining this product.
For technical assistance, contacts are listed below:
Customer Central
Technical support, quoting, and order-related questions.
United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)
Asia Pacific- 65 777 8211
Europe/Middle East/Africa - 49 (8153) 9390
North American Response Center
Equipment service needs.
1-800-654-7768 (24 hours—includes Canada)
Outside of these areas, contact your local Emerson
™
representative.
Title Page
January 2017
The products described in this document are NOT designed for nuclear-qualified applications. Using
non-nuclear qualified products in applications that require nuclear-qualified hardware or products may
cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Emerson Sales
Representative.
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate
local, national, and international standards, codes, and practices. Review the approvals section of this
manual for any restrictions associated with a safe installation.
Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments in the
loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is
applied to the unit.
Process leaks may cause harm or result in death.
Install and tighten process connectors before applying pressure.
Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
Title Page
ix
Title Page
January 2017
Reference Manual
00809-0100-4007, Rev BA
Replacement equipment or spare parts not approved by Emerson for use as spare parts could
reduce the pressure retaining capabilities of the transmitter and may render the instrument
dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
Improper assembly of manifolds to traditional flange can damage sensor module.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e.,
bolt hole) but must not contact sensor module housing.
Severe changes in the electrical loop may inhibit HART
values. Therefore, Rosemount cannot absolutely warrant or guarantee that the correct Failure alarm
level (HIGH or LOW) can be read by the host system at the time of annunciation.
®
Communication or the ability to reach alarm
x
Title Page
Reference Manual
00809-0100-4007, Rev BA
Section 1Introduction
1.1Using this manual
The sections in this manual provide information on installing, operating, and maintaining the
Rosemount
Section 2: Configuration provides instruction on commissioning and operating Rosemount 3051
Transmitters. Information on software functions, configuration parameters, and online variables is also
included.
Section 3: Hardware Installation contains mechanical installation instructions and field upgrade options.
Section 4: Electrical Installation contains electrical installation instructions and field upgrade options.
Section 5: Operation and Maintenance provides detailed information on calibrating and changing HART
revisions.
Section 6: Troubleshooting provides troubleshooting techniques for the most common operating
problems.
™
3051 Pressure Transmitter. The sections are organized as follows:
Introduction
January 2017
Section 7: Safety Instrumented Systems (SIS) Requirements provides identification, installation,
configuration, operation and maintenance, and inspection information for Safety Instrumented
Systems.
Appendix A: Specifications and Reference Data supplies reference and specification data, as well as
This section contains information on commissioning and tasks that should be performed on the bench
prior to installation, as well as tasks performed after installation as described in “Configuring transmitter
diagnostics” on page 21.
Field Communicator, AMS
perform configuration functions. For convenience, Field Communicator Fast Key sequences are labeled
“Fast Keys,” and abbreviated LOI menus are provided for each function below.
Full Field Communicator menu trees and Fast Key sequences are available in Appendix C: Field
Communicator Menu Trees and Fast Keys. LOI menu trees are available in Appendix D: Local Operator
Interface (LOI).
™
Device Manager, and Local Operator Interface (LOI) instructions are given to
2.2Safety messages
Procedures and instructions in this section may require special precautions to ensure the safety of the
personnel performing the operations. Information that raises potential safety issues is indicated by a
warning symbol (). Refer to the following safety messages before performing an operation preceded
by this symbol.
Config uration
3
Configuration
January 2017
Reference Manual
00809-0100-4007, Rev BA
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate
local, national, and international standards, codes, and practices. Review the approvals section of this
manual for any restrictions associated with a safe installation.
Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments in the
loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is
applied to the unit.
Process leaks may cause harm or result in death.
Install and tighten process connectors before applying pressure.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
Replacement equipment or spare parts not approved by Emerson for use as spare parts could
reduce the pressure retaining capabilities of the transmitter and may render the instrument
dangerous.
Use only bolts supplied or sold by Emerson
Improper assembly of manifolds to traditional flange can damage sensor module.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e.,
bolt hole) but must not contact sensor module housing.
Severe changes in the electrical loop may inhibit HART
values. Therefore, Rosemount cannot absolutely warrant or guarantee that the correct Failure alarm
level (HIGH or LOW) can be read by the host system at the time of annunciation.
™
as spare parts.
®
Communication or the ability to reach alarm
2.3 System readiness
If using HART-based control or asset management systems, confirm the HART capability of such
systems prior to commissioning and installation. Not all systems are capable of communicating with
HART revision 7 devices.
For instructions on how to change the HART revision of your transmitter, see “Switching HART
Revision” on page 72.
2.3.1Confirm correct Device Driver
1. Verify the latest Device Driver (DD/DTM) is loaded on your systems to ensure proper
communications.
2. Download the latest DD at Emerson.com
3. In the Browse by Member dropdown menu, select Rosemount
4. Select desired Product
a. Within Table 2-1 on page 5, use the HART Universal Revision and Device Revision numbers to find
the correct Device Driver
4
or FieldCommGroup.org.
™
business unit of Emerson.
Configuration
Reference Manual
00809-0100-4007, Rev BA
Table 2-1. Rosemount 3051 Device Revisions and Files
Configuration
January 2017
Device identification
NAMUR
Release date
April 20121.0.xx1.0.xx01
January 1998N/AN/A1785300809-0100-4001
1. NAMUR Revision is located on the hardware tag of the device. Differences in level 3 changes, signified above by xx, represent minor product changes as defined per
NE53. Compatibility and functionality are preserved and product can be used interchangeably.
2. HART Software Revision can be read using a HART capable configuration tool. Value shown is minimum revision that could correspond to NAMUR Revisions.
3. Device Driver file names use Device and DD Revision, e.g. 10_01. HART Protocol is designed to enable legacy device driver revisions to continue to communicate with
new HART devices. To access new functionality, the new Device Driver must be downloaded. It is recommended to download new Device Driver files to ensure full
functionality.
4. HART Revision 5 and 7 selectable, power diagnostics, safety certified, LOI, process alerts, scaled variable, configurable alarms, expanded engineering units.
software
revision
(1)
NAMUR
hardware
revision
(1)
HART
software
revision
(2)
Device driver
identification
HART
Universal
Revision
710
5
Device
revision
9
(3)
Review instructions
Manual document
number
00809-0100-4007
Review
functionality
Change
description
(4)
N/A
2.4Configuration basics
Set all transmitter hardware adjustments during commissioning to avoid exposing the transmitter
electronics to the plant environment after installation.
The Rosemount 3051 can be configured either before or after installation. Configuring the transmitter
on the bench using either a Field Communicator, AMS Device Manager, or LOI ensures all transmitter
components are in working order prior to installation. Verify the security switch is set in the unlock
position () in order to proceed with configuration. See Figure 4-2 on page 53 for switch location.
2.4.1Configuring on the bench
To configure on the bench, required equipment includes a power supply, and a Field Communicator,
AMS Device Manager, or LOI (option M4). Wire equipment as shown in Figure 2-1 below. To ensure
successful HART Communication, a resistance of at least 250 Ω must be present between the
transmitter and the power supply, see“Power supply for 4–20 mA HART” on page 56for details.
Connect the Field Communicator leads to the terminals labeled “COMM” on the terminal block.
Config uration
5
Configuration
SAVE
1. Overview
2. Configure
3. Service Tools
3051 FT 45B
Online
January 2017
Figure 2-1. Wiring the Transmitter
A. Vdc supply
B. R
≥ 250 (necessary for HART Communication only)
L
2.4.2Configuration tools
Configuring with a Field Communicator
Reference Manual
00809-0100-4007, Rev BA
A.
B.
There are two interfaces available with the Field Communicator: Traditional and Dashboard interfaces.
All steps using a Field Communicator will be described using Dashboard interfaces. Figure 2-2 on page 6
shows the Device Dashboard interface. As stated in System readiness , it is critical that the latest DD’s are
loaded into the Field Communicator. Visit Emerson.com/Rosemount/Device-Install-Kits
FieldCommGroup.org
Field Communicator menu trees and Fast Keys are available in Appendix C: Field Communicator Menu
Trees and Fast Keys.
Figure 2-2. Device Dashboard
to download latest DD library.
or
6
Configuring with AMS Device Manager
Full configuration capability with AMS Device Manager requires loading the most current Device
Descriptor (DD) for this device. Download the latest DD at
Emerson.com/Rosemount/Device-Install-Kits
Note
All steps using AMS Device Manager will be described using version 11.5.
or FieldCommGroup.org.
Configuration
Reference Manual
00809-0100-4007, Rev BA
Configuring with a LOI
The LOI requires option code M4 to be ordered. To activate the LOI push either configuration button.
Configuration buttons are located on the LCD display (must remove housing cover to access), or
underneath the top tag of the transmitter. See Ta b le 2 - 2 for configuration button functionality and
Figure 2-3 for configuration button location. When using the LOI for configuration, several features
require multiple screens for a successful configuration. Data entered will be saved on a screen-by-screen
basis; the LOI will indicate this by flashing “SAVED” on the LCD display each time.
LOI menu trees are available in Appendix D: Local Operator Interface (LOI).
Figure 2-3. LOI Configuration Buttons
Configuration
January 2017
B
A
A. Internal configuration buttons
B. External configuration buttons
Table 2-2. LOI Button Operation
Button
LeftNoSCROLL
RightYesENTER
2.5Setting the loop to manual
Whenever sending or requesting data that would disrupt the loop or change the output of the
transmitter, set the process application loop to manual control. The Field Communicator, AMS Device
Manager, or the LOI will prompt you to set the loop to manual when necessary. The prompt is only a
reminder; acknowledging this prompt does not set the loop to manual. It is necessary to set the loop to
manual control as a separate operation.
2.6Verify configuration
It is recommended that various configuration parameters are verified prior to installation into the
process. The various parameters are detailed out for each configuration tool. Depending on what
configuration tool(s) are available follow the steps listed relevant to each tool.
Config uration
7
Configuration
January 2017
2.6.1Verifying configuration with Field Communicator
Configuration parameters listed in Ta b le 2 - 3 are to be reviewed prior to transmitter installation. A Full list
of configuration parameters that can be reviewed and configured using a Field Communicator are
located in Appendix C: Field Communicator Menu Trees and Fast Keys.
Fast key sequences for the latest DD are shown in Ta bl e 2 - 3. For Fast Key sequences for legacy DD's
contact your local Emerson Representative.
From the HOME screen, enter the Fast Key sequences listed.
Table 2-3. Rosemount 3051 Device Dashboard Fast Key Sequence
Fast Key sequence
Function
HART 7HART 5
Alarm and saturation levels2, 2, 2, 52, 2, 2, 5
Damping2, 2, 1, 1, 52, 2, 1, 1, 5
Primary variable2, 1, 1, 4, 12, 1, 1, 4, 1
Range values 2, 1, 1, 42, 1, 1, 4
Ta g2, 2, 7, 1, 12, 2, 7, 1, 1
Tra nsfer func tion2, 2, 1, 1, 62, 2, 1, 1, 6
Reference Manual
00809-0100-4007, Rev BA
Units2, 2, 1, 1, 42, 2, 1, 1, 4
2.6.2Verifying configuration with AMS Device Manager
Right click on the device and select Configuration Properties from the menu. Navigate the tabs to
review the transmitter configuration data.
2.6.3Verifying configuration with LOI
Press any configuration button to activate the LOI. Select VIEW CONFIG to review the below parameters.
Use the configuration buttons to navigate through the menu.
installation include:
Ta g Primary Variable
Units Range Values
Transfer Func tion Damping
Alarm and Saturation Levels
The parameters to be reviewed prior to
2.6.4Verifying process variables configuration
This section describes how to verify the correct process variables are selected.
Verifying process variables with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Verifying process variables with AMS Device Manager
1. Right click on the device and select Overview from the menu.
2. Select the All Variables button to display the primary, secondary, tertiary and quaternary variables.
2.7Basic setup of the transmitter
This section goes through the necessary steps for basic setup of a pressure transmitter. When installing
in DP level or DP flow applications, refer to“Configuring scaled variable” on page 17 for setup
instructions.
2.7.1Setting pressure units
The pressure unit command sets the unit of measure for the reported pressure.
Setting pressure units with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Configuration
January 2017
Device Dashboard Fast Keys
2, 2, 1, 1, 4
Setting pressure units with AMS Device Manager
1. Right click on the device and select Configure.
2. Select Manual Setup and select desired units from Pressure Units dropdown menu.
3. Select Send when complete.
Setting pressure units with a LOI
Follow Figure 2-4 on page 9 to select desired pressure and temperature units. Use the SCROLL and
ENTER buttons to select desired unit. Save by selecting SAVE as indicated on the LCD display screen.
Figure 2-4. Selecting Units with LOI
Config uration
9
Configuration
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT
VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
TRANSFER FUNCT
LINEAR TRANSFER
FUNCTION
SQR ROOT TRANSFER
FUNCTION
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
The Rosemount 3051 has two output settings: Linear and Square root. As shown in Figure 2-6 on
page 11, activating the square root options makes analog output proportional to flow, and includes a
fixed Low Flow Cutoff at 5 percent.
However, for Differential Pressure (DP) Flow and DP Level applications it is recommended to use scaled
variable. Refer to “Configuring scaled variable” on page 17 for setup instructions.
Setting transmitter output with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Reference Manual
00809-0100-4007, Rev BA
Device Dashboard Fast Keys
2, 2, 1, 1, 6
Setting transmitter output with AMS Device Manager
1. Right click on the device and select Configure.
2. Select Manual Setup and select output type from Analog Output Transfer Function and click Send.
3. Carefully read the warning and select Ye s if it is safe to apply the changes.
Setting transmitter output with a LOI
Reference Figure 2-5 on page 10 to select either linear or square root transfer function using the LOI.
Figure 2-5. Set Output with LOI
10
Configuration
Reference Manual
A
B
C
0.51
% Pressure Input
0
0 102030405060708090100
4 mA
20mA
% Pressure Input
B
A
4 mA
00809-0100-4007, Rev BA
Figure 2-6. 4-20 mA HART Square Root Output Transition Point
A. Square root curve
B. 5% transition point
C. 4% transition point
Configuration
January 2017
2.7.3Rerange the transmitter
The range values command sets each of the lower and upper range analog values (4 and
20 mA points) to a pressure. The lower range point represents 0% of range and the upper range point
represents 100% of range. In practice, the transmitter range values may be changed as often as
necessary to reflect changing process requirements. For a complete listing of range and sensor limits,
refer to “Range and sensor limits” on page 91.
Select from one of the methods below to rerange the transmitter. Each method is unique; examine all
options closely before deciding which method works best for your process.
Rerange by manually setting range points with a Field Communicator, AMS Device Manager, or LOI.
Rerange with a pressure input source and a Field Communicator, AMS Device Manager, LOI, or local
zero and span buttons
Manually rerange the transmitter by entering range points
Entering range points with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Entering range points with AMS Device Manager
1. Right click on the device and select Configure:
2. Select Manual Setup and select Analog Output.
2, 2, 2, 1
Config uration
3. Enter upper and lower range values in the Range Limits box and select Send.
4. Carefully read the warning and select Ye s if it is safe to apply the changes.
11
Configuration
RERANGE
ENTER VALUES
ENTER VALUES
APPLY VALUES
BACK TO MENU
EXIT MENU
ENTER VALUES
LRV
URV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
RERANGE
ENTER VALUES
APPLY VALUES
APPLY VALUES
BACK TO MENU
EXIT MENU
APPLY VALUES
LRV
URV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
January 2017
Reference Manual
00809-0100-4007, Rev BA
Entering range points with LOI
Reference Figure 2-7 on page 12 to rerange the transmitter using the LOI. Enter values using SCROLL and
ENTER buttons.
Figure 2-7. Rerange with LOI
Rerange the transmitter with applied pressure source
Reranging using an applied pressure source is a way of reranging the transmitter without entering
specific 4 and 20 mA points.
Rerange with an applied pressure source using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 2, 2
Rerange with an applied pressure source using AMS Device Manager
1. Right click on the device, select Configure.
2. Select the Analog Output tab.
3. Select Range by Applying Pressure button and follow the screen prompts range the transmitter.
Rerange with an applied pressure source using a Field Communicator
Use Figure 2-8 to manually rerange the device using an applied pressure source with an LOI.
Figure 2-8. Rerange with Applied Pressure Using LOI
12
Configuration
Reference Manual
00809-0100-4007, Rev BA
Rerange with an applied pressure source using local zero and span buttons
If ordered, local zero and span buttons (option code D4) can be used to rerange the transmitter with an
applied pressure. Refer to Figure 2-9 on page 13 for analog zero and span button location.
To rerange the transmitter using the span and zero buttons, perform the following procedure:
1. Loosen the screw holding the top tag of the transmitter housing. Rotate the label to expose the zero
and span buttons.
2. Confirm device has local zero and span buttons by verifying blue retainer under the tag.
3. Apply transmitter pressure.
4. Rerange the transmitter.
a. To change the zero (4 mA point) while maintaining the span: press and hold zero button for at
b. To change the span (20 mA point) while maintaining the zero point: press and hold the span
Note
4 and 20 mA points must maintain the minimum span defined in Functional specifications .
Configuration
January 2017
least two seconds then release.
button for at least two seconds and then release.
Figure 2-9. Analog Zero and Span Buttons
A
A. Zero and span buttons
If the transmitter security is on, adjustments to the zero and span will not be able to be made. Refer
to “Configuring transmitter security” on page 53 for security information.
The span is maintained when the 4 mA point is set. The span changes when the
20 mA point is set. If the lower range point is set to a value that causes the upper range point to
exceed the sensor limit, the upper range point is automatically set to the sensor limit, and the span is
adjusted accordingly.
Regardless of the range points, the Rosemount 3051 will measure and report all readings within the
digital limits of the sensor. For example, if the 4 and 20 mA points are set to 0 and 10 inH
transmitter detects a pressure of 25 inH
O, it digitally outputs the 25 inH2O reading and a 250% of
2
range reading.
O, and the
2
Config uration
13
Configuration
EXTENDED MENU
CALIBRAT
DAMPING
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
January 2017
2.7.4Damping
The damping command changes the response time of the transmitter; higher values can smooth
variations in output readings caused by rapid input changes. Determine the appropriate damping setting
based on the necessary response time, signal stability, and other requirements of the loop dynamics
within your system. The damping command utilizes floating point configuration allowing the user to
input any damping value within 0–60 seconds.
Damping with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Reference Manual
00809-0100-4007, Rev BA
Device Dashboard Fast Keys
2, 2, 1, 1, 5
Enter desired Damping Value and select APPLY.
Damping with AMS Device Manager
1. Right click on the device and select Configure.
2. Select Manual Setup.
3. Within the Pressure Setup box, enter desired damping value and click Send.
4. Carefully read the warning and click Ye s if it is safe to apply the changes.
Damping with a LOI
Reference Figure 2-10 to enter damping values using an LOI.
Figure 2-10. Damping with LOI
2.8Configuring the LCD display
14
The LCD display configuration command allows customization of the LCD display to suit application
requirements. The LCD display will alternate between the selected items.
Pressure units Sensor temperature
% of range mA output
Scaled variable
Configuration
Reference Manual
DISPLAY
PRESS (on/off)
SCALED (on/off)
TEMP (on/off)
%RANGE (on/off)
ANALOG (on/off)
STRTUP (on/off)
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
DISPLAY
EXTENDED MENU
EXIT MENU
00809-0100-4007, Rev BA
In the following instructions, the LCD display can also be configured to display configuration information
during the device startup. Select Review Parameters at Startup to enable or disable this functionality.
Configuring LCD display with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Configuration
January 2017
Device Dashboard Fast Keys
2, 2, 4
Configuring LCD display with AMS Device Manager
1. Right click on the device and select Configure.
2. Click Manual Setup, select the Display tab.
3. Select desired display options and select Send.
Configuring LCD display with a LOI
Refer to Figure 2-11 for LCD display configuration using a LOI.
Figure 2-11. Display with LOI
2.9Detailed transmitter setup
2.9.1Configuring alarm and saturation levels
Config uration
In normal operation, the transmitter will drive the output in response to pressure from the lower to
upper saturation points. If the pressure goes outside the sensor limits, or if the output would be beyond
the saturation points, the output will be limited to the associated saturation point.
The Rosemount 3051 Transmitter automatically and continuously performs self-diagnostic routines. If
the self-diagnostic routines detect a failure, the transmitter drives the output to configured alarm and
value based on the position of the alarm switch. See “Setting transmitter alarm” on page 55.
Table 2-4. Rosemount Alarm and Saturation Value
Level4–20 mA saturation4–20 mA alarm
Low3.9 mA≤ 3.75 mA
High20.8 mA≥ 21.75 mA
15
Configuration
January 2017
Reference Manual
00809-0100-4007, Rev BA
Table 2-5. NAMUR-Compliant Alarm And Saturation Values
Level4–20 mA saturation4–20 mA alarm
Low3.8 mA≤ 3.6 mA
High20.5 mA≥22.5 mA
Table 2-6. Custom Alarm and Saturation Values
Level4–20 mA saturation4–20 mA alarm
Low3.7–3.9 mA3.6–3.8 mA
High20.1–22.9 mA20.2–23.0 mA
Failure mode alarm and saturation levels can be configured using a Field Communicator, AMS Device
Manager, and the LOI. The following limitations exist for custom levels:
Low alarm level must be less than the low saturation level
High alarm level must be higher than the high saturation level
Alarm and saturation levels must be separated by at least 0.1 mA
The configuration tool will provide an error message if the configuration rule is violated.
Note
Transmitters set to HART multidrop mode send all saturation and alarm information digitally; saturation
and alarm conditions will not affect the analog output. See also “Establishing multidrop
communication” on page 27.
Configuring alarm and saturation levels using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 2, 5, 6
Configuring alarm and saturation levels with AMS Device Manager
1. Right click on the device, and select Configure.
2. Select Configure Alarm and Saturation Levels button.
3. Follow screen prompts to configure Alarm and Saturation Levels.
Configuring alarm and saturation levels using LOI
Refer to Figure 2-12 for instructions to configure alarm and saturation levels.
16
Configuration
Reference Manual
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
ALARM SAT VALUES
ROSEMOUNT VALUES
NAMUR VALUES
OTHER VALUES
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
00809-0100-4007, Rev BA
Figure 2-12. Configuring Alarm and Saturation with LOI
2.9.2Configuring process alerts
Process alerts allow the transmitter to indicate when the configured data point is exceeded. Process
alerts can be set for pressure, temperature, or both. An alert will be displayed on a Field Communicator,
AMS Device Manager status screen or in the error section of the LOI/LCD display. The alert will reset once
the value returns within range.
Configuration
January 2017
2.9.3Configuring scaled variable
Config uration
Note
HI alert value must be higher than the LO alert value. Both alert values must be within the pressure or
temperature sensor limits.
Configuring process alerts using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 3
1. Select either Pressure Alert or Temperature Alert and press ENTER.
2. Select Configure Alert.
3. Follow screen prompts to configure process alerts.
Configuring process alerts using AMS Device Manager
Right click on the device and select Configure.
1. Select Guided Setup.
2. Select the Process Alerts button.
3. Follow screen prompts to configure Process Alerts.
The scaled variable configuration allows the user to create a relationship/conversion between the
pressure units and user-defined/custom units. There are two use cases for scaled variable. The first use
case is to allow custom units to be displayed on the transmitter's LOI/LCD display. The second use case is
to allow custom units to drive the transmitter's 4–20 mA output.
17
Configuration
January 2017
Reference Manual
00809-0100-4007, Rev BA
If the user desires custom units to drive the 4–20 mA output, scaled variable must be re-mapped as the
primary variable. Refer to “Re-mapping device variables” on page 20.
The scaled variable configuration defines the following items:
Scaled variable units - Custom units to be displayed.
Scaled data options - Defines the transfer function for the application
– Linear
– Square root
Pressure value position 1 - Lower known value point with consideration of linear offset.
Scaled variable value position 1 - Custom unit equivalent to the lower known value point.
Pressure value position 2 - Upper known value point
Scaled variable value position 2 - Custom unit equivalent to the upper known value point
Linear offset - The value required to zero out pressures effecting the desired pressure reading.
Low flow cutoff - Point at which output is driven to zero to prevent problems caused by process
noise. It is highly recommended to use the low flow cutoff function in order to have a stable output
and avoid problems due to process noise at a low flow or no flow condition. A low flow cutoff value
that is practical for the flow element in the application should be entered.
Configuring Scaled Variable using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 1, 5, 7
1. Follow the screen prompts to configure Scaled Variable.
a. When configuring for level, select Linear under Select Scaled data options.
b. When configuring for flow, select Square Root under Select Scaled data options.
Configuring Scaled Variable using AMS Device Manager
1. Right click on the device and, select Configure.
2. Select Scaled Variable tab and select Scaled Variable button.
3. Follow screen prompts to configure Scaled Variable
a. When configuring for level applications, select Linear under Select Scaled data options.
b. When configuring for flow applications, select Square Root under Select Scaled data options.
Configuring Scaled Variable using a LOI
Refer to Figure 2-13 on page 19 for instructions to configure Scaled Variable using a LOI.
18
Configuration
Reference Manual
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
SCALED VARIAB
VIEW SCALED
CONFIG SCALED
CONFIG SCALED
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
H
L
230-in.
200-in.
12-in.
0.94 sg
00809-0100-4007, Rev BA
Figure 2-13. Configuring Scaled Variable Using a LOI
DP Level example
Figure 2-14. Example Tank
Configuration
January 2017
Config uration
A differential transmitter is used in a level application. Once installed on an empty tank and taps vented,
the process variable reading is –209.4 inH
O. The process variable reading is the head pressure created
2
by fill fluid in the capillary. Based on Table 2-7 on page 20, the scaled variable configuration would be as
follows:
19
Configuration
January 2017
Reference Manual
00809-0100-4007, Rev BA
Table 2-7. Scaled Variable Configuration for Tank Application
Scaled Variable units
Scaled data options
Pressure value position 1
Scaled Variable position 1
Pressure value position 2
Scaled Variable position 2
Linear offset
inch
linear
0 inH2O
12-in.
188 inH2O
212-in.
–209.4 inH2O
DP Flow example
A differential pressure transmitter is used in conjunction with an orifice plate in a flow application where
the differential pressure at full scale flow is 125 inH
scale flow is 20,000 gallons of water per hour. It is highly recommended to use the low flow cutoff
function in order to have a stable output and avoid problems due to process noise at a low flow or no flow
condition. A low flow cutoff value that is practical for the flow element in the application should be
entered. In this particular example, the low flow cutoff value is 1000 gallons of water per hour. Based on
this information, the Scaled Variable configuration would be as follows:
Table 2-8. Scaled Variable Configuration for Flow Application
Scaled Variable units
gal/h
O. In this particular application, the flow rate at full
2
Scaled data options
Pressure value position 2
Scaled Variable position 2
Low Flow Cutoff
square root
125 inH2O
20,000 gal/h
1000 gal/h
Note
Pressure value position 1 and Scaled Variable position 1 are always set to zero for a flow application. No
configuration of these values is required.
2.9.4Re-mapping device variables
The re-mapping function allows the transmitter primary, secondary, tertiary, and quaternary variables
(PV, 2V, 3V, and 4V) to be configured as desired. The PV can be remapped with a Field Communicator,
AMS Device Manager, or a LOI. Variables (2V, 3V, and 4V) can only be re-mapped via Field Communicator
or AMS Device Manager.
Note
The variable assigned to the primary variable drives the 4–20 mA output. This value can be selected as
Pressure or Scaled Variable. The 2, 3, and 4 variables only apply if HART burst mode is being used.
20
Configuration
Loading...
+ 186 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.