Beijing Rosemount Far East Instrument Co.,
Limited
No. 6 North Street,
Hepingli, Dong Cheng District
Beijing 100013, China
T (86) (10) 6428 2233
F (86) (10) 6422 8586
April 2005
IMPORTANT NOTICE
This installation guide provides basic guidelines for Rosemount 285 Annubar. It does not
provide instructions for configuration, diagnostics, maintenance, service, troubleshooting,
Explosion-proof, Flame-Proof, or instrinsically safe (I.S.) installations. Refer to the 285
Annubar reference manual (document number 00809-0100-4028) for more instruction.
This manual is also available electronically on www.rosemount.com.
WARNING
Process leaks may cause harm or result in death. To avoid process leaks, only use
gaskets designed to seal with the corresponding flange and o-rings to seal process
connections. Flowing medium may cause the 285 Annubar assembly to become hot and
could result in burns.
STEP 1: LOCATIONAND ORIENTATION
Correct location in the duct is important for accurate measurement. See Table 1 on page 3
for proper installation locations.
Straight-run Installations
The recommended straight-run duct lengths upstream are 7W or 7H; downstream, 2W or
2H. Installation across the longest dimension is preferred.
H
2W
W
7W
2
H
2H
W
7H
285/15-490024-901,
15-490025-901.eps
Page 3
Quick Installation Guide
1
1
00825-0100-4031, Rev AA
April 2005
Duct Mount 285 Annubar
Elbow Installations
The unit will measure accurately when installed 2 duct widths (height) downstream of a 90°
elbow in plane with the elbow.
H
W
2W
H
Special Installations
For unique duct configurations, consult the factory.
Table 1. Minimum straight duct requirements for the 285 Annubar
Upstream LengthDownstream Length
H
W
H
W
15W
7W
7W
2W
285/15-490028-901
2W
285/15-490029-901
H
2W
2H
W
7W2W
7W2W
15W2W
285/15-490026-901,
15-490027-901.eps
W
7W
2W
285/15-490030-90
H
7W2W
15W
W
2W
285/15-490031-90
3.864
15W2W
DAMPER
W
285/15-490032-901
3
Page 4
Quick Installation Guide
A
00825-0100-4031, Rev AA
Duct Mount 285 Annubar
April 2005
STEP 2: INSTALLATION PREPARATION
Operating Limitations
For the Annubar to produce accurate, repeatable flow measurement, the following must be
considered. The maximum allowed pressure and temperature limits are:
• Annubar Type D1 (duct mount without compression fitting): 10 psig @ -40°F to 850°F.
• Annubar Type D2 (duct mount with compression fitting): 10 psig @ -40°F to 300°F.
Annubar Installation Preparation
1. Make sure there is enough clearance to insert the Annubar into the duct.
2. Mark the mounting location of the Annubar, locating it along the center line of the
rectangular duct, or anywhere on the circumference of a round duct. Mark horizontal and
vertical center lines through the mounting location. For duct mount Annubars without
compression fitting (threaded stud welded to tip of sensor), extend the center line to the
opposite duct wall (or 180° around a circular duct), as shown in Figure 1.
Figure 1.
3. Measure and mark the locations of the mount screw holes and the opposite side support
285/15-490013-903,
hole (for Annubars with threaded stud welded to sensor tip) (see Table 2).
Duct-Mount without Compression Fitting (Annubar type D1)
1. Place the gasket over the end of the probe and push it up against the mounting flange.
Alternatively, a high-temperature gasket sealant may be used.
2. Insert the end of the Annubar through the mounting hole, and push it through the duct
until the threaded stud protrudes through the hole on the opposite side of the duct.
Figure 4.
GASKET OR SEALANT
5/16-18 STUD
FOR HIGH TEMPERATURE
5/16-18 STUD
GASKET OR SEALANT
FOR HIGH TEMPERATURE
285/15-490014-901,
15-490035-901.eps
ANNUBAR
NNUBAR
285/15-490015-901,
15-490036-901
5
Page 6
Quick Installation Guide
R
00825-0100-4031, Rev AA
Duct Mount 285 Annubar
3. Push the flange and gasket flush against the duct wall; align the flow arrow in the
direction of flow and fasten the flange to the duct using the #12 sheet metal screws
provided.
Figure 5.
STUD
April 2005
1/4" SHEET METAL SCREWS
STUD
1/4" SHEET
4. On the opposite side of the duct, place the 5/16-in. lock washer over the stud, screw on
5
the
/16 nut, and tighten. Depending on the pressure in the duct, it may be necessary to
METAL SCREWS
285/15-490016-901,
15-490017-901
285/15-490037-901,
15-490038-901
add some high temperature gasket sealant where the stud protrudes through the duct
wall.
DUCT
STUD
NUT
LOCK WASHER
ANNUBA
285/15-490018-901,
NUT
DUCT
STUD
LOCK WASHER
ANNUBAR
Duct Mount With Compression Fitting (Annubar type D2)
1. Place gasket against the mounting flange. Alternatively, a high-temperature gasket
sealant may be used.
2. Push the flange and gasket flush against the duct wall, and fasten the flange to the duct
using the #12 sheet metal screws provided.
/15-490039-901
6
Page 7
Quick Installation Guide
A
00825-0100-4031, Rev AA
April 2005
Figure 6.
GASKET OR SEALANT
FOR HIGH TEMPERATURE
1/4" SHEET
METAL SCREWS
3. Remove the packing gland from the Annubar, and thread it into the threaded coupling,
using teflon tape or pipe sealant.
Figure 7.
THREADED
COUPLING
PACKING GLAND
TEFLON TAPE OR
PIPE SEALANT
4. Remove the packing from the envelope and wrap it around the Annubar three full turns.
Insert the Annubar into the mounting until the packing is completely contained within the
glad, and the tip of the Annubar is contacting the opposite side of the duct wall. Place the
lock washers over the studs on the packing gland and hand tighten the nuts.
Figure 8.
(3) THREE FULL
TURNS
PACKING FROM
ENVELOPE
Duct Mount 285 Annubar
DUCT MOUNT PLATE
WITH THREADED
COUPLING
285/15-490022-901
285/ 15-490040-901
NNUBAR ASSEMBLY
285/ 15-490041-901
5. Align the flow arrow on the Annubar with the flow direction in the duct and tighten the
nuts on the packing.
NOTE
Do not over tighten the packing, as this can lead to deforming the opposite wall of the duct.
6. Observe the opposite side of the duct and ensure that the ducting has not deformed.
7
Page 8
Quick Installation Guide
00825-0100-4031, Rev AA
Duct Mount 285 Annubar
April 2005
STEP 4: MOUNTTHE TRANSMITTER
Transmitter Mounting, Direct Mount Head with Valves
It is not necessary to retract the Annubar when direct mounting a transmitter with valves.
1. Place Teflon® (PTFE) O-rings into grooves on the face of head.
2. Align the high side of the transmitter to the high side of the sensor (“Hi” is stamped on the
side of the head) and install.
3. Tighten the nuts in a cross pattern to 400 in•lb (45 N•m).
Transmitter Mounting, Direct Mount Head without Valves
1. Place Teflon (PTFE) O-rings into grooves on the face of head.
2. Orient the equalizer valve(s) so they are easily accessible. Install a manifold with the
smooth face mating to the face of the head. Tighten in cross pattern to a torque of 400
in•lb (45 N•m).
3. Place Teflon (PTFE) O-rings into grooves on the face of the manifold.
4. Align the high side of the transmitter to the high side of the sensor (“Hi” is stamped on the
side of the head) and install.
5. Tighten the nuts in a cross pattern to 400 in•lb (45 N•m).
Transmitter Mounting with Remote Mount Head
Temperatures in excess of 250 °F (121 °C)at the electronics will damage the transmitter.
Remote mounted electronics are connected to the sensor by means of impulse piping,
which allows service flow temperatures to decrease to a point where the electronics are no
longer vulnerable.
Different impulse piping arrangements are used depending on the process fluid and must be
rated for continuous operation at the pipeline design pressure and temperature. A minimum
1
of
/2 in. (12 mm) outer diameter stainless steel tubing with a wall thickness of at least 0.035
in. (1 mm) is recommended. Threaded pipe fittings are not recommended because they
create voids where air can become entrapped and create leakage points.
The following restrictions and recommendations apply to impulse piping location:
1. Impulse piping that runs horizontally must slope at least one inch per foot (83 mm/m).
• Slope downward (toward the electronics) for liquid and steam applications
• Slope upward (toward the electronics) for gas applications.
2. For applications with temperature below 250 °F (121 °C), impulse piping should be as
short as possible to minimize temperature changes. Insulation may be required.
3. For applications above 250 °F (121 °C), impulse piping should have a minimum length of
one foot (0.3048 m) for every 100 °F (38°C) temperature increase over 250 °F (121 °C).
Impulse piping must be non-insulated to reduce fluid temperature. Any threaded
connections should be checked after the system reaches the intended temperature
because connections may come loose with contraction and expansion caused by
temperature change.
4. Outdoor installations for liquid, saturated gas, or steam may require insulation and heat
tracing to prevent freezing.
5. When impulse piping is longer than six feet (1.8 m) the high and low impulse lines must
be positioned together to maintain equal temperature. They must be supported to
prevent sagging and vibration.
8
Page 9
Quick Installation Guide
00825-0100-4031, Rev AA
April 2005
6. Impulse lines should be positioned in protected areas or against walls or ceilings. Use
appropriate pipe sealing compound rated for the service temperature on all threaded
connections. Do not place the impulse piping near high temperature piping or equipment.
An instrument manifold is recommended for all installations. Manifolds allow an operator to
equalize the pressures prior to zeroing and isolates the process fluid from the electronics.
Figure 9. Valve Identification for 5-valve and 3-Valve Manifolds
5-Valve Manifold3-Valve Manifold
To P HTo PL
Duct Mount 285 Annubar
To P HTo P L
MV
MH
Table 5. Description of Impulse Valves and Components
Drains (for gas service) or vents (for liquid or steam service) the DP
(2)
electronics chambers
(1)
(2)
Isolates high side or low side pressure from the process
(1)
Allows high and low pressure side access to the vent valve, or for
(2)
isolating the process fluid
MEManifold EqualizerAllows high and low side pressure to equalize
MVManifold Vent ValveVents process fluid
(1) High Pressure
(2) Low Pressure
ME
ML
DVLDVH
9
Page 10
Quick Installation Guide
00825-0100-4031, Rev AA
Duct Mount 285 Annubar
April 2005
STEP 4 CONTINUED...
Recommended Installations
Gas Service
Secure the electronics above the sensor to prevent condensable liquids from collecting in
the impulse piping and the DP cell.
Liquid Service (up to 250 °F (121 °C))
Secure the electronics below the sensor to ensure that air will not be introduced into the
impulse piping or the electronics.
Figure 10. GasFigure 11. Liquid
Steam or Liquid Service (above 250 °F (121 °C))
Mount the electronics below the process piping, adjust 10 to 15 degree above direct vertical
down. Route the impulse piping down to the electronics and fill the system with cool water
through the two tee fittings.
Figure 12. Horizontal LineFigure 13. Vertical Line
10
Page 11
Quick Installation Guide
00825-0100-4031, Rev AA
April 2005
Duct Mount 285 Annubar
PRODUCT CERTIFICATIONS
Approved Manufacturing Locations
Rosemount Inc. — Chanhassen, Minnesota USA
European Directive Information
The EC declaration of conformity for all applicable European directives for this product can
be found on the Rosemount website at www.rosemount.com. A hard copy may be obtained
by contacting our local sales office.
European Pressure Equipment Directive (PED) (97/23/EC)
Rosemount 285 Annubar — Refer to EC declaration of conformity for conformity
assessment
Pressure Transmitter — See appropriate Pressure Transmitter QIG
11
Page 12
Duct Mount 285 Annubar
Quick Installation Guide
00825-0100-4031, Rev AA
April 2005
12
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.