Rosemount 214C Operating Manual

Rosemount™ 214C Sensor
Quick Start Guide
00825-0400-2654, Rev AF
August 2017
August 2017
NOTICE
This guide provides basic guidelines for Rosemount 214C Sensor models.
If the sensor was ordered assembled to a temperature thermowell or transmitter, see the appropriate product literature for information on configuration and hazardous locations certifications.
Explosions could result in death or serious injury.
Installation of this sensor in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices.
Conduit/cable entries
Unless marked, the conduit/cable entries in the transmitter housing use a
marked “M20” are M20 1.5 thread form. On devices with multiple conduit entries, all conduit entries will have the same thread form.
When installing in a hazardous location, use only appropriately listed or Ex certified flameproof/dust plugs,
adapters, or glands in cable/conduit entries.
Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries.
1
/2–14 NPT thread form. Entries
Contents
Wiring diagram for RTDs . . . . . . . . . . . . . . . . 3
Wiring diagram for thermocouples . . . . . . 4
2
Product certifications . . . . . . . . . . . . . . . . . . . 5
Installation drawings. . . . . . . . . . . . . . . . . . .10
August 2017
Red Red
White
White
Red
Red
White
Red
Red
White
Black Black
Yellow
Quick Start Guide

1.0 Wiring diagram for RTDs

Figure 1. RTD Lead Wire Configuration per IEC 60751
Single element, 3-wire Single element, 4-wire Dual element, 3-wire
Note
To configure a single element, 4-wire RTD as a 3-wire system, connect only one white lead. Insulate or terminate the unused white lead in a manner that prevents shorting to the ground. To configure a single element, 4-wire RTD as a 2-wire system, connect matching colored wires first and then connect the paired wires to the terminal.
3
(
)

2.0 Wiring diagram for thermocouples

Figure 2. Thermocouple Lead Wire Configuration
Single thermocouple, 2-wire Dual thermocouple, 4-wire
August 2017
( – )
( + )
( – )
( + )
( – )
+
IEC 60584 thermocouple colors ASTM E- 230 thermocouple colors
Typ e POS (+) NEG (-) POS (+) NEG (-)
J Black White White Red
K Green White Yell ow Red
T Brown White Blue Red
Note
Dual thermocouple sensors are shipped with one pair of the wires shrink wrapped together.
4
August 2017
Quick Start Guide

3.0 Product certifications

Rev 1.12

3.1 European Directive information

A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at
Emerson.com/Rosemount

3.2 Ordinary Location Certification

The Rosemount 214C has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).

3.3 North America

The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.
E5 Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate: 70044744 Standards: FM 3600:2011, FM 3615:2006, UL 50E:2007, UL 61010-1:2010, ANSI/ISA
60529:2004
Markings: XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T6 (–50 °C ≤ T
+80 °C), T5 (–50 °C ≤ T drawing 00214-1030; Type 4X
Special Conditions for Safe Use (X):
1. Flameproof joints are not intended for repair.
2. Cable entries must be used which maintain the ingress protection of the enclosure. Unused cable entries must be filled with suitable blanking plugs.
N5 Division 2 (NI)
Certificate: 70044744 Standards: FM 3600:2011, FM 3611:2004, UL 50E:2007, UL 61010-1:2010, ANSI/ISA
60529:2004
Markings: NI CL I, DIV 2, GP A, B, C, D; T6 (–50 °C ≤ T
T5 (–50 °C ≤ T 4X
E6 Explosionproof and Dust-Ignitionproof
Certificate: 70044744 Standards: CAN/CSA C22.2 No. 0:2010, CAN/CSA No. 25-1966,
CAN/CSA C22.2 No. 30-M1986, CAN/CSA C22.2 No. 94-M1991, CAN/CSA C22.2 No. 61010-1:2012
Markings: Explosionproof CL I, DIV 1, GP B, C, D; Dust-Ignitionproof CL II, DIV 1,
GP E, F, G; CL III; T6 (–50 °C ≤ T Seal not required; installed per Rosemount drawing 00214-1030; Type 4X V
.
a
35 VDC, 750 mW
max
3 5VDC, 750 mW
max
; V
+95 °C); Seal not required; installed per Rosemount
a
; V
35 VDC, 750 mW
max
+80 °C),
a
max
≤ +95 °C); installed per Rosemount drawing 00214-1030; Type
max
+80 °C), T5 (–50 °C Ta +95 °C);
a
max
a
;
5
Special Conditions for Safe Use (X):
1. Flameproof joints are not intended for repair.
2. Cable entries must be used which maintain the ingress protection of the enclosure. Unused cable entries must be filled with suitable blanking plugs.
N6 Division 2
Certificate: 70044744 Standards: CAN/CSA C22.2 No. 0:2010, CAN/CSA C22.2 No. 94-M1991, CAN/CSA No.
213-M1987, CAN/CSA C22.2 No. 61010-1:2012
Markings: CL I, DIV 2, GP A, B, C, D; T6; (–50 °C ≤ T
installed per Rosemount drawing 00214-1030; Type 4X 750 mW
max
Spring loaded indicator has reduced ingress and dust ratings. Spring loaded sensors must be
+80 °C), T5 (–50 °C Ta +95 °C);
a
; V
max
installed in a thermowell to maintain dust and ingress ratings. Un-painted aluminum enclosures are Type 4 rated.

3.4 Europe

E1 Flameproof
Certificate: DEMKO 16 ATEX 1677X Standards: EN 60079-0:2012+A11 2013, EN 60079-1:2014 Markings: II 2 G Ex db IIC T6…T1 Gb
Installation Instructions:
1. Use field wiring suitable for both the minimum and maximum service temperatures.
2. These devices are provided without cable glands/conduit sealing devices/blanking elements. Proper selection of suitable cable glands/conduit sealing/blanking elements should occur in the field.
3. Unused apertures shall be closed with suitable blanking elements.
4. The enclosures may be provided with up to three entries, with location of the entries specified in the installation instructions document.
Special Conditions for Safe Use (X):
1. Refer to certificate for details regarding process and ambient temperature limits.
2. When the Rosemount 214C sensor is provided with an enclosure with a display cover, the maximum ambient shall be 95 °C.
3. The non-metallic label on the device may store an electrostatic charge and become a source of ignition in Group III atmospheres. Care shall be taken to reduce electrostatic build-up. For example, the non-metallic label may be rubbed with a damp cloth.
4. The display covers were impacted at 4 J according to a low risk of mechanical danger. Guard the display covers against impact energies greater than 4 J.
5. Flameproof joints are not intended for repair.
6. The stand-alone Rosemount 214C sensors without an enclosure must be assembled to a suitable Ex certified enclosure of a volume no greater than 0.55 L to maintain the types of protection “db” and “tb”.
7. The spring loaded sensors and DIN sensors must be installed in a thermowell to maintain IP6X ratings.
8. Contact indicating sensors do not meet requirements for protection type “tb” and therefore are not “tb” rated.
V
max
= 45 Vdc, P
= 750 mW
max
1
/2–14 NPT, 3/4–14 NPT, or M20 x 1.5
August 2017
35 VDC,
6
August 2017
Quick Start Guide
I1 ATE X In tri nsi c Sa fet y
Certificate: Baseefa16ATEX0101X Standards: EN 60079-0:2012+A11:2013, EN 60079-11:2012 Markings: II 1 G Ex ia IIC T5/T6 Ga (SEE CERTIFICATE FOR SCHEDULE)
Thermocouples; Pi = 500 mW T6 60 °C Ta +70 °C
RTDs; Pi = 192 mW T6 60 °C Ta +70 °C
RTDs; Pi = 290 mW
T6 60 °C Ta +60 °C
T5 60 °C Ta +70 °C
Special Condition of Use (X):
1. The equipment must be installed in an enclosure which affords it a degree of ingress
protection of at least IP20.
N1 ATEX Type n – with enclosure
Certificate: BAS00ATEX3145 Standards: EN 60079-0:2012+A11:2013, EN 60079-15:2010 Markings: II 3 G Ex nA IIC T5 Gc T5(-40 °C
T
70 °C)
a
ND Dust
Certificate: DEMKO 16 ATEX 1677X Standards: EN 60079-0:2012+A11 2013, EN 60079-31:2014 Markings: II 2 D Ex tb IIIC T 130 °C Db
V
= 45 Vdc, P
max
= 750 mW
max
Installation Instructions:
1. Use field wiring suitable for both the minimum and maximum service temperatures.
2. These devices are provided without cable glands/conduit sealing devices/blanking elements. Proper selection of suitable cable glands/conduit sealing/blanking elements should occur in the field.
3. Unused apertures shall be closed with suitable blanking elements.
4. The enclosures may be provided with up to (3)
1
/2–14 NPT, 3/4–14 NPT, or M20 ⫻ 1.5
entries, with location of the entries specified in the installation instructions document.
Special Conditions for Safe Use (X):
1. Refer to certificate for details regarding process and ambient temperature limits.
2. When the Rosemount 214C sensor is provided with an enclosure with a display cover, the maximum ambient shall be 95 °C.
3. The non-metallic label on the device may store an electrostatic charge and become a source of ignition in Group III atmospheres. Care shall be taken to reduce electrostatic build-up. For example, the non-metallic label may be rubbed with a damp cloth.
4. The display covers were impacted at 4 J according to a low risk of mechanical danger. Guard the display covers against impact energies greater than 4J.
5. Flameproof joints are not intended for repair.
6. The stand-alone Rosemount 214C sensors without an enclosure must be assembled to a suitable Ex certified enclosure of a volume no greater than 0.55 L to maintain the types of protection “db” and “tb”.
7. The spring loaded sensors and DIN sensors must be installed in a thermowell to maintain IP6X ratings.
8. Contact indicating sensors do not meet requirements for protection type “tb” and therefore are not “tb” rated.
7

3.5 International

E7 Flameproof
Certificate: IECEx UL 16.0048X Standards: IEC 60079-0:2011, IEC 60079-1:2014 Markings: Ex db IIC T6…T1 Gb
V
= 45 Vdc, P
max
Installation Instructions:
1. Use field wiring suitable for both the minimum and maximum service temperatures.
2. These devices are provided without cable glands/conduit sealing devices/blanking elements. Proper selection of suitable cable glands/conduit sealing/blanking elements should occur in the field.
3. Unused apertures shall be closed with suitable blanking elements.
4. The enclosures may be provided with up to three entries, with location of the entries specified in the installation instructions document.
Special Conditions for Safe Use (X):
1. Refer to certificate for details regarding process and ambient temperature limits.
2. When the Rosemount 214C sensor is provided with an enclosure with a display cover, the maximum ambient shall be 95 °C.
3. The non-metallic label on the device may store an electrostatic charge and become a source of ignition in Group III atmospheres. Care shall be taken to reduce electrostatic build-up. For example, the non-metallic label may be rubbed with a damp cloth.
4. The display covers were impacted at 4 J according to a low risk of mechanical danger. Guard the display covers against impact energies greater than 4J.
5. Flameproof joints are not intended for repair.
6. The stand-alone Rosemount 214C sensors without an enclosure must be assembled to a suitable Ex certified enclosure of a volume no greater than 0.55 L to maintain the types of protection “db” and “tb”.
7. The spring loaded sensors and DIN sensors must be installed in a thermowell to maintain IP6X ratings.
8. Contact indicating sensors do not meet requirements for protection type “tb” and therefore are not “tb” rated.
I7 IECEx Intrinsic Safety
Certificate: IECEx BAS 16.0077X Standards: EN 60079-0:2012+A11:2013, EN 60079-11:2012 Markings: Ex ia IIC T5/T6 Ga (SEE CERTIFICATE FOR SCHEDULE)
= 750 mW
max
1
/2–14 NPT, 3/4–14 NPT, or M20 1.5
August 2017
Thermocouples; Pi = 500 mW T6 60 °C Ta +70 °C
RTDs; Pi = 192 mW T6 60 °C Ta +70 °C
RTDs; Pi = 290 mW
T6 60 °C Ta +60 °C
T5 60 °C Ta +70 °C
Special Condition of Use (X):
1. The equipment must be installed in an enclosure which affords it a degree of ingress
protection of at least IP20.
N7 IECEx Type n – with enclosure
Certificate: IECEx BAS 07.0055 Standards: IEC 60079-0:2011, IEC 60079-15:2010 Markings: Ex nA IIC T5 Gc; T5(–40 °C ≤ T
+70 °C)
a
8
August 2017
Quick Start Guide
NK Dust
Certificate: IECEx UL 16.0048X Standards: IEC 60079-0:2011, IEC 60079-31:2013 Markings: Ex tb IIIC T 130 °C Db
V
= 45 Vdc, P
max
= 750 mW
max
Installation Instructions:
1. Use field wiring suitable for both the minimum and maximum service temperatures.
2. These devices are provided without cable glands/conduit sealing devices/blanking elements. Proper selection of suitable cable glands/conduit sealing/blanking elements should occur in the field.
3. Unused apertures shall be closed with suitable blanking elements.
4. The enclosures may be provided with up to three
1
/2–14 NPT, 3/4–14 NPT, or M20 1.5
entries, with location of the entries specified in the installation instructions document.
Special Conditions for Safe Use (X):
1. Refer to certificate for details regarding process and ambient temperature limits.
2. When the Rosemount 214C sensor is provided with an enclosure with a display cover, the maximum ambient shall be 95 °C.
3. The non-metallic label on the device may store an electrostatic charge and become a source of ignition in Group III atmospheres. Care shall be taken to reduce electrostatic build-up. For example, the non-metallic label may be rubbed with a damp cloth.
4. The display covers were impacted at 4 J according to a low risk of mechanical danger. Guard the display covers against impact energies greater than 4J.
5. Flameproof joints are not intended for repair.
6. The stand-alone Rosemount 214C sensors without an enclosure must be assembled to a suitable Ex certified enclosure of a volume no greater than 0.55 L to maintain the types of protection “db” and “tb”.
7. The spring loaded sensors and DIN sensors must be installed in a thermowell to maintain IP6X ratings.
8. Contact indicating sensors do not meet requirements for protection type “tb” and therefore are not “tb” rated.

3.6 Combinations

KA Combination of E1 and E6 KB Combination of E5 and E6 KC Combination of E1 and E5 KD Combination of E1, E5, and E6 KN Combination of N1, N5, N6, and N7s
9

4.0 Installation drawings

Figure 3. Rosemount 214C Hazardous Location (00214-1030)
August 2017
10
August 2017
EU Declaration of Conformity
No: RMD 1109 Rev. C
Page 1 of 2
We,
Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
declare under our sole responsibility that the product,
Rosemount™ 214C Temperature Sensor
manufactured by,
Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
to which this declaration relates, is in conformity with the provisions of the European Union Directives, including the latest amendments, as shown in the attached schedule.
Assumption of conformity is based on the application of the harmonized standards and, when applicable or required, a European Union notified body certification, as shown in the attached schedule.
Vice President of Global Quality
Chris LaPoint
31-July-2017
Figure 4. Rosemount 214C Declaration of Conformity
Quick Start Guide
(signature)
(name)
(function)
(date of issue)
11
EU Declaration of Conformity
No: RMD 1109 Rev. C
Page 2 of 2
ATEX Directive (2014/34/EU)
DEMKO 16ATEX1677X - Flameproof Certificate
Equipment Group II Category 2 G (Ex db IIC T6…T1 Gb) Harmonized Standards:
EN 60079-0:2012+A11:2013, EN 60079-1:2014
DEMKO 16ATEX1677X - Dust Certificate
Equipment Group II Category 2 D (Ex tb IIIC T130°C Db) Harmonized Standards:
EN 60079-0:2012+A11:2013, EN 60079-31:2009
BAS00ATEX3145 - Type n Certificate
Equipment Group II Category 3 G (Ex nA IIC T5 Gc) Harmonized Standards:
EN60079-0:2012+A11:2013, EN60079-15:2010
Baseefa16ATEX0101X – Intrinsic Safety Certificate
Equipment Group II Category 1 G (Ex ia IIC T5/T6) Harmonized Standards:
EN 60079-0:2012+A11:2013, EN 60079-11:2012
RoHS Directive (2011/65/EU)
Harmonized Standard: EN 50581:2012
ATEX Notified Bodies
UL International Demko A/S [Notified Body Number: 0539]
Borupvang 5A 2750 Ballerup Denmark
SGS Baseefa Limited [Notified Body Number: 1180] Rockhead Business Park Staden Lane Buxton Derbyshire SK17 9RZ United Kingdom
ATEX Notified Body for Quality Assurance
SGS Baseefa Limited [Notified Body Number: 1180]
Rockhead Business Park Staden Lane SK17 9RZ Buxton United Kingdom
August 2017
12
August 2017
China RoHS
㇑᧗⢙䍘䎵䗷ᴰབྷ⎃ᓖ䲀٬Ⲵ䜘Ԧරࡇ㺘
Rosemount 214
List of Rosemount 214 Parts with China RoHS Concentration above MCVs
䜘Ԧ〠
Part Name
ᴹᇣ⢙䍘Hazardous Substances
䫵
Lead (Pb)
⊎
Mercury
(Hg)
䭹
Cadmium
(Cd)
ޝԧ䬜
Hexavalent Chromium
(Cr +6)
ཊⓤ㚄㤟
Polybrominated
biphenyls
(PBB)
ཊⓤ㚄㤟䟊
Polybrominated diphenyl ethers
(PBDE)
⭥ᆀ㓴Ԧ
Electronics
Assembly
O O O O O
O
༣փ㓴Ԧ
Housing
Assembly
O O O O O
O
Րᝏಘ㓴Ԧ
Sensor
Assembly
O O O O O
O
ᵜ㺘Ṭ㌫׍ᦞ
SJ/T11364
Ⲵ㿴ᇊ㘼ࡦ֌
This table is proposed in accordance with the provision of SJ/T11364.
O:
᜿Ѫ䈕䜘ԦⲴᡰᴹ൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿൷վҾ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572.
X:
᜿Ѫ൘䈕䜘Ԧᡰ֯⭘Ⲵᡰᴹ൷䍘ᶀᯉ䟼ˈ㠣ቁᴹа㊫൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿儈Ҿ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.
Quick Start Guide
13
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com
North America Regional Office
Emerson Automation Solutions
8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com
Latin America Regional Office
Emerson Automation Solutions
1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
Europe Regional Office
Emerson Automation Solutions
Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office
Emerson Automation Solutions
1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions
Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emi rates
+971 4 8118100 +971 4 8865465
RFQ.RMTMEA@Emerson.com
*00825-0400-2654*
Quick Start Guide
00825-0400-2654, Rev AF
Linkedin.com/company/Emerson-Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/us er/RosemountMeasur ement
Google.com/+RosemountMeasurement
Standard Terms and Conditions of Sale can be found on the Term s
and Conditions of Sale page.
The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and Rosemount logotype are trademarks of Emerson. National Electrical Code is a registered trademark of National Fire Protection Association, Inc. All other marks are the property of their respective owners. © 2017 Emerson. All rights reserved.
August 2017