Rosemount 2130 Specifications

Page 1
Rosemount™ 2130 Level Switch
Vibrating Fork
Product Data Sheet
March 2017
00813-0100-4130, Rev EE
Designed for operation in process temperatures of –94 to 500 °F (–70 to 260 °C)
Electronic self-checking and condition monitoring – ‘Heartbeat’ LED gives status and instrument health
information
Increased safety, SIL2-certified to IEC 61508 as required by IEC 61511
Adjustable switching delay for turbulent or splashing applications
General area, explosion-proof/flameproof, and intrinsically safe options
Page 2
Rosemount 2130
‘Fast drip’ forks
There is a variety of plug-in electronics options, with
each having an adjustable mode and switching delay
(see “Electrical” on page 11)
The Quick Release kit is a new optional set of accessories.
It makes inspection, proof-testing, and servicing easier
than ever (see Table 2 on page 7 for accessories)
Overview of the Rosemount 2130
Measurement principle
The Rosemount 2130 is designed using the principle of a tuning fork. A piezo-electric crystal oscillates the forks at their natural frequency. Changes to this frequency are continuously monitored. The frequency of the vibrating fork sensor changes depending on the medium in which it is immersed. The denser the liquid, the lower the frequency.
When used as a low level alarm, the liquid in the tank or pipe drains down past the fork, causing a change of natural frequency that is detected by the electronics and switches the output state.
When the 2130 is used as a high level alarm, the liquid rises in the tank or pipe, making contact with the fork which then causes the output state to switch.
Key features and benefits
Virtually unaffected by turbulence, foam, vibration, solids
content, coating products, and liquid properties
The mid-range temperature Rosemount 2130 is designed for
operation in process temperatures from –40 to 356 °F (–40 to 180 °C)
The high temperature Rosemount 2130 is designed for
operation in process temperatures from –94 to 500 °F (–70 to 260 °C). It has a stainless steel thermal tube to move the electronics away from the process
Electronic self-checking and condition monitoring. The
‘heartbeat’ LED gives status and health information on the Rosemount 2130
Adjustable switching delay prevents false switching in
turbulent or splashing applications
‘Fast drip’ fork design gives quicker response time when
mounted horizontally, especially with viscous liquids
Rapid wet-to-dry time for highly responsive switchingFork shape is optimized for hand polishing to meet hygienic
requirements
No moving parts or crevices for virtually no maintenance
March 2017

Contents

Overview of the Rosemount 2130 . . . . . . . . . . . . . page 2
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . page 4
Spare Parts and Accessories . . . . . . . . . . . . . . . . . . . page 7
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 9
Product Certifications . . . . . . . . . . . . . . . . . . . . . . . page 12
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . page 14
Emerson.com/Rosemount
Page 3
March 2017
R
o
s
e
m
o
u
n
t
T
a
n
k
R
a
d
a
r
F
B
M
2
1
8
0
Ext. pwr
RS-232
USB
Tx
Rx
L
o
-
G
A
I
N
-
H
i
O
n
-
T
E
R
M
-
O
f
f
In tank gauging systems, a Rosemount 2130 high level alarm switch can be used as an alternative to a second radar level gauge (see the Rosemount Tank Gauging Product
Data Sheet)
Point level alarm
Rosemount
2130
Rosemount
5900S
Level
High level alarm: two separate and configurable relay outputs
High and low level alarm
High temperature applications
Pump control / limit detection
Wireless applications using a
Rosemount 702 Wireless Discrete Transmitter
Superior diagnostics
Built-in diagnostics continuously check electronic and
mechanical health
Fork conditions detected including internal and external
damage, coated or blocked, and extreme corrosion
Ideal for critical alarm duties
Fit and forget
Once installed, the Rosemount 2130 is ready to go.
It needs no calibration and requires minimum installation
The ‘heartbeat’ LED gives an instant visual indication that the
unit is operational
Functional testing of the instrument and system is easy with a
magnetic test point
You can install, and forget it
Extended high and low temperature performance
Rosemount 2130
The high temperature Rosemount 2130 enables standardization of Rosemount vibrating fork switches across a wide range of process environments, and is ideally suited for harsh conditions where high reliability is essential Applications
Overfill protectionHigh and low level alarmsPump control or limit detectionRun dry or pump protectionHygienic applicationsHigh temperature applicationsWireless applications
Emerson.com/Rosemount
3
Page 4
Rosemount 2130
March 2017

Ordering Information

Specification and selection of product materials, options, or components must be made by the purchaser of the equipment. See page 9 for more information on material selection.
Table 1. Rosemount 2130 Ordering Information
The starred options () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Model Product description
2130 Enhanced Vibrating Fork Liquid Level Switch
Output
L Direct Load Switching (Mains 2-wire) 20 to 264 Vac, 50/60 Hz, 20 to 60 Vdc, Self-checking P PNP/PLC Low Voltage (3-wire) 20 to 60 Vdc, Self-checking
D
Relay (DPCO), 20 to 264 Vac, 50/60 Hz, 20 to 60 Vdc, Self-checking
(Fault and Alarm Relays version is available by selecting D and adding “R2264” to end of model number)
N NAMUR, 8 Vdc, Self-checking M 8/16 mA, Self-checking
Housing material
A Aluminum S Stainless Steel
Conduit entry / cable threads
9
3
/4-in. ANPT NA, E5, E6, G5, G6, I1, I2, I3, I5, I6, I7
Product certifications
2 M20 NA, E1, E2, E3, E7, I1, I2, I3, I5, I6, I7
Operating temperature
M Mid-Range: –40 °F (–40 °C) ... 356 °F (180 °C) E High: –94 °F (–70 °C) ... 500 °F (260 °C)
Materials of construction: process connection / fork
S 316/316L Stainless Steel (1.4401/1.4404)
(2)(3)(4)
F
(5)
H
Process connection size
9 1 1 -in. / 25 mm (DN25) 2 2 -in. / 50 mm (DN50) 5 11/2 -in. / 40 mm (DN40) 3 3 -in. / 80 mm (DN80) 4 4 -in. / 100 mm (DN100) 7 21/2 -in. / 65 mm (DN65)
Process connection rating
AA ASME B16.5 Class 150 flange AB ASME B16.5 Class 300 flange AC ASME B16.5 Class 600 flange DA EN1092-1 PN 10/16 flange DB EN1092-1 PN 25/40 flange DC EN1092-1 PN 63 flange
ECTFE Copolymer, Coated 316/316L Stainless Steel (1.4401/1.4404) Alloy C (UNS N10002), Alloy C-276 (UNS N10276), solid
(6)
3
/4 -in. / 19 mm
(6)
(1)
4
Emerson.com/Rosemount
Page 5
March 2017
Rosemount 2130
Table 1. Rosemount 2130 Ordering Information
The starred options () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
DD EN1092-1 PN 100 flange NN For use with non-flange process connection type
Process connection type
(6)
R Raised Face (RF) Flange B BSPT (R) Thread G BSPP (G) Thread N NPT Thread P BSPP (G) O-ring C Tri-Clover Clamp
Fork length
Process connection
A Standard length 1.7-in. (44 mm) All except flanged models
(3)
H
(7)
E
(7)
M
Standard length flange 4.0-in. (102 mm) All flanged models Extended, customer specified length in tenths of inches All except connection 1-NN-P Extended, customer specified length in millimeters All except connection 1-NN-P
Specific extended fork length
0000 Factory default length (only if Fork Length A or H is selected)
(7)
XXXX
Surface finish
Specific customer specified length in tenths of inches, or millimeters (XXX.X inches or XXXX mm)
Process connection
1 Standard surface finish All
(8)(9)
2
Hand polished (Ra < 0.4 μm) P or C
Product certifications
Output Conduit entry/cable threads
(10)
NA G5 G6
No Hazardous Locations Certifications All models All models
(11)
FM Ordinary Locations (unclassified, safe area) All models
(12)(13)
CSA Ordinary Locations (unclassified, safe area) All models
3
/4-in. ANPT models only
3
/4-in. ANPT models only E1 ATEX Flameproof All models M20 models only E2 INMETRO Flameproof All except Fault Relays M20 models only E3 NEPSI Explosion-proof All models M20 models only E5 E6
(11)
(12)(13)
FM Explosion-proof All models CSA Explosion-proof All models
3
/4-in. ANPT models only
3
/4-in. ANPT models only E7 IECEx Explosion-proof All models M20 models only EM Technical Regulation Customs Union (EAC) Flameproof
All models All models I1 ATEX Intrinsic Safety NAMUR or 8/16 mA All models I2 INMETRO Intrinsic Safety NAMUR or 8/16 mA All models I3 NEPSI Intrinsic Safety NAMUR or 8/16 mA All models I5 FM Intrinsic Safety NAMUR or 8/16 mA All models
(13)
I6
CSA Intrinsic Safety NAMUR or 8/16 mA All models I7 IECEx Intrinsic Safety NAMUR or 8/16 mA All models IM Technical Regulation Customs Union (EAC) Intrinsic Safety
NAMUR or 8/16 mA All models
Typical Model Number: 2130 L A 2 E S 9 NN B A 0000 1 NA
Emerson.com/Rosemount
5
Page 6
Rosemount 2130
March 2017
Table 1. Rosemount 2130 Ordering Information
The starred options () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Options (include with the selected model number)
Calibration data certification
Q4 Certificate of functional test
Material traceability certification
(2)(3)
Q8 Material traceability certification per EN 10204 3.1
Material certification
(2)(3)
Q15 NACE MR0175 / ISO 15156 Q25 NACE MR0103
Safety certifications
(14)
QS Prior-use certificate of FMEDA Data QT Safety certificate to IEC61508
Special procedures
(15)
P1 Hydrostatic testing with certificate
Low liquid density range
LD Low density liquids – minimum density is 31.2 lb/ft3 (500 kg/m3)
Example of options included with the model number: 2130 L A 2 E S 9 NN B A 0000 1 NA Q8
1. Flanges are dual certified 316 and 316L Stainless Steel (1.4401 and 1.4404).
2. Only available for wetted parts.
3. Option is not available for hand polished wet side as standard.
4. Only available for a flanged Rosemount 2130; the Operating Temperature code M must be selected (mid-range) and the process temperature must be below 302 °F (150 °C).
5. Only available for BSPT and NPT threaded process connection codes 9-NN-B, 9-NN-N, 1-NN-B, and 1-NN-N as standard, other upon request.
6. Other process connections available upon request.
7. Example Fork Length code E1181 is 118.1 inches. Code M4000 is 4000 millimeters. See “Extended lengths” on page 9 for minimum and maximum exte nded lengths.
8. Not available with Material of Construction Process / Fork option code H.
9. Hand-polished for hygienic connections to better than 0.4 μm Ra such that there are no pits, folds, crevices or cracks discernible to the naked eye (i.e. no features larger than 75 micrometers based on resolving 1/60 degree at a distance of 250 mm).
10. Includes the Technical Regulation Customs Union (EAC) ordinary location mark.
11. See “Product Certifications” on page -12. E5 includes G5 requirements. G5 is for use in unclassified, safe area locations only.
12. See “Product Certifications” on page -12. E6 includes G6 requirements. G6 is for use in unclassified, safe area locations only.
13. The requirements of CRN are met when a Rosemount 2130 CSA approved vibrating fork level switch (with Product Certifications code G6, E6, or I6) is configured with stainless steel wetted parts and either NPT threaded or ASME B16.5 2-in. to 4-in. flanged process connections.
14. Not available for Direct Load switching electronics.
15. Option limited to units with extended lengths up to 59.1-in. (1500 mm). Option is not available for ECTFE coating.
Safety Integrity Level (SIL) certification option
The Rosemount 2130 is SIL2-certified.The Rosemount 2130 has been independently certified to IEC 61508 as required by IEC 61511. Certification was conducted by
Exida. If required, add “QT” to the end of the model number. For example, 2130 L A 2 E S 9 NN B A 0000 1 NA Q8 QT (Note that you can have one or more OPTIONS codes at the end of the model number).
Visit the Rosemount 2130 web page for additional information.
6
Emerson.com/Rosemount
Page 7
March 2017
Rosemount 2130
Overfill approval option
The Rosemount 2130 has been TÜV-tested and approved for overfill protection according to the German DIBt/WHG regulations.
This option is not selectable in the ordering information table. If required, add “R2259” to the end of the model number. For example, 2130 L A 2 E S 9 NN B A 0000 1 NA Q8 R2259 (Note that you can have one or more OPTIONS codes added at the end of the model number).

Spare Parts and Accessories

Specification and selection of product materials, options, or components must be made by the purchaser of the equipment. See page 9 for more information on Material Selection.
Table 2. Rosemount 2130 Spare Parts and Accessories
The starred options () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Spares and accessories
(1)(2)
02100-1000-0001 Seal for 1-in. BSPP (G1A). Material: Non-asbestos BS7531 grade X carbon fiber with rubber binder
02100-1040-0001 Seal for 3/4-in. BSPP (G3/4A). Material: Non-asbestos BS7531 grade X carbon fiber with rubber binder
02100-1010-0001 Hygienic adaptor boss 1-in. BSPP. Material: 316 SS fitting. FPM/FKM ‘O’ ring
02100-1020-0001 2-in. (51 mm) Tri Clamp kit (vessel fitting, clamp ring, and seal). Material: 316 SST NBR Nitrile
02100-1030-0001 Telescopic test magnet
02120-2000-0001
02120-2000-0002
02130-7000-0001
02130-7000-0002
02130-7000-0003
02130-7000-0004
02130-7000-0005
02130-7000-0006
02130-7000-0007
02130-7000-0008
02130-7000-0009
02130-7000-0010
02130-7000-0011
02130-7000-0012
02100-1060-0001
(3)
316 SST adjustable clamp gland for 1-in. threaded extended length. 11/2-in. BSPP male connection
(3)
316 SST adjustable clamp gland for 1-in. threaded extended length. 11/2-in. NPT male connection
(4)
Replacement Cassette: Direct load switching (Red)
(5)
Replacement Cassette: PNP/PLC low voltage (Yellow)
(6)
Replacement Cassette: NAMUR current switching (Light Blue)
(7)
Replacement Cassette: DPCO Relay (Dark Green)
(8)
Replacement Cassette: Direct load switching, low density range selection (Red)
(9)
Replacement Cassette: PNP/PLC low voltage, low density range selection (Yellow)
(10)
Replacement Cassette: NAMUR current switching, low density range selection (Light Blue)
(11)
Replacement Cassette: DPCO Relay, low density range selection (Dark Green)
(12)
Replacement Cassette: 8/16 mA, (Dark Blue)
(13)
Replacement Cassette: 8/16 mA, low density range selection (Dark Blue)
(14)
Replacement Cassette: Fault and Alarm Relays (2 x SPCO) (Light Green)
(15)
Same as replacement cassette 02130-7000-011 but with Low density range selection
(16)
Quick Release kit (contains 2-in. Tri Clamp, seal, and quick release device for 2-in. NPT process connection)
1. Intrinsically Safe (IS) approved cassettes can only be replaced with the same type of IS cassette. Non-IS cassette types can be interchanged with other non -IS cassettes, but the new label must be fitted and the original part number transferred to the new label.
2. When ordering a replacement cassette, check the Product Certification section in Table 1 on page 4 for availability conditions.
3. The adjustable clamp gland is not explosion-proof. It has a silicone rubber seal. Maximum pressure is 1.3 barg. Maximum temperature is 257 °F (125 °C).
4. Available for units with Direct Load electronics (Output code L). Not available for units with Options code LD is included in the model number.
5. Available for units with PNP/PLC electronics (Output code P). Not available for units with Options code LD is included in the model number.
6. Available for units with NAMUR electronics (Output code N). Not available for units with Options code LD is included in the model number.
7. Available for units with DCPO Relay electronics (Output code D). Not available for units with Options code LD is included in the model number.
8. Available for units with Direct Load electronics (Output code L) and Options code LD included in the model number.
Emerson.com/Rosemount
7
Page 8
Rosemount 2130
9. Available for units with PNP/PLC electronics (Output code P) and Options code LD included in the model number.
10. Available for units with NAMUR electronics (Output code N) and Options code LD included in the model number.
11. Available for units with DCPO Relay electronics (Output code D) and Options code LD included in the model number.
12. Available for units with 8/16 mA electronics (Output code M). Not available for units with Options code LD is included in the model number.
13. Available for units with 8/16 mA electronics (Output code M) and Options code LD included in the model number.
14. Available for units with Fault and Alarm Relay electronics (Option code F) only. Not available for units with Options code LD is included in the model number.
15. Available for units with Fault and Alarm Relay electronics (Option code F) and Options code LD included in the model number.
16. The Quick Release kit is a set of accessories requiring a Rosemount 2130 with the 2-in. Tri Clamp option and an existing 2-in. NPT process connection on the vessel. For additional information, see Rosemount 2120 Quick Release kit – Quick Start Guide
.
March 2017
8
Emerson.com/Rosemount
Page 9
March 2017

Specifications

Rosemount 2130

General

Product
Rosemount 2130 Level Switch
Measuring principle
Vibrating Fork.
Applications
Most liquids including coating liquids, aerated liquids, and slurries

Mechanical

Housing / Enclosure
Table 3. Housing / Enclosure Specification
Housing code
Housing material
Rotational No No No No Housing paint Polyurethane paint Not applicable LED window None None
Conduit entry M20
Ingress protection
Connections
Threaded, Tri Clamp, and flanged process connections. See Table 1 on page 4 for a complete list.
Extended lengths
Table 4. Minimum Extended Lengths
Process connection Minimum extended length
3
/4–in. threaded 3.8 -in. (95 mm) 1–in. threaded 3.7 -in. (94 mm) Flanged 3.5 -in. (89 mm) Tri Clamp 4.1 -in. (105 mm)
A-2 A-9 S-2 S-9
Aluminum Alloy
ASTM B85 A360.0
3
/4-in.
ANPT
IP66/67 to EN60529,
®
4X
NEMA
316C12
Stainless Steel
M20
IP66/67 to EN60529,
NEMA 4X
3
/4-in.
ANPT
Material selection
Emerson™ provides a variety of Rosemount product with various product options and configurations including materials of construction that can be expected to perform well in a wide range of applications. The Rosemount product information presented is intended as a guide for the purchaser to make an appropriate selection for the application. It is the purchaser’s sole responsibility to make a careful analysis of all process parameters (such as all chemical components, temperature, pressure, flow rate, abrasives, contaminants, etc.), when specifying product, materials, options and components for the particular application.
Emerson is not in a position to evaluate or guarantee the compatibility of the process fluid or other process parameters with the product, options, configuration or materials of construction selected.
Process connection materials
316/316L Stainless Steel (1.4401/1.4404 dual certified). Alloy C (UNS N10002) and Alloy C-276 (UNS N10276) – available for flanged, and BSPT and NPT threaded process connections
3
(
/4-in. and 1-in. BSPT (R), and 3/4-in. and 1-in. NPT).
ECTFE co-polymer coated 316/316L Stainless Steel (1.4401/1.4404 dual certified) – only available for a flanged 2130. Hand-polished to better than 0.4 m option for hygienic connections Gasket material for
Grade X carbon fiber with rubber binder.
3
/4-in. and 1-in. BSPP (G) is non-asbestos BS7531

Functional

Maximum operating altitude
6562 ft. (2000 m)
Maximum operating pressure
The final rating depends on the type of process connection.
Threaded connection: see Figure 3 for operating pressures.
Clamp glands 02120-2000-0001 and 02120-2000-0002 limit the maximum pressure to 18.85 psig (1.3 bar g).
Tri Clamp connection: 435 psig (30 bar g)Flanged Connection: See Figure 3 or Table 1 (whichever gives the
lowest pressure).
The maximum extended length is 157.5-in. (4000 mm) except for the ECTFE co-polymer coating and polished process connection options which have a maximum length of 59.1-in. (1500 mm) and 39.4-in. (1000 mm) respectively.
Emerson.com/Rosemount
9
Page 10
Rosemount 2130
1450 (100)
885 (61)
-14.5 (-1.0)
-94
(-70)
68
(20)
500
(260)
Process Temperature °F (°C)
Process Pressure psig (bar g)
0 (0)
32 (0)
2130***E
1450 (100)
1073 (74)
-14.5 (-1.0)
-40
(-40)
68
(20)
356
(180)
Process Temperature °F (°C)
Process Pressure psig (bar g)
0 (0)
32 (0)
2130***M
176 (80)
176 (80)
-40 (-40)
-94
(-70)
500
(260)
Process Temperature °F (°C)
Ambient Temperature °F (°C)
149 (65)
32 (0)
32 (0)
2130***E
176 (80)
176 (80)
-40 (-40)
-40
(-40)
356
(180)
Process Temperature °F (°C)
Ambient Temperature °F (°C)
122 (50)
32 (0)
32
(0)
2130***M
March 2017
Figure 1. Process Pressure
Figure 2. Operating Temperatures
Table 5. Maximum flange pressure rating
1. At 100 °F (38 °C), the pressure rating decreases with an increasing process
2. At 122 °F (50 °C), the pressure rating decreases with an increasing process
Minimum and maximum operating temperatures
See Figure 2 for operating temperatures.Clamp glands 02120-2000-0001 and 02120-2000-0002 (page 7)
The ambient temperature for a 8/16 mA cassette is limited to 158 °F (70 °C) in dust applications.
10
Standard Class/Rating
Stainless steel flanges
ASME B16.5 Class 150 275 psig
ASME B16.5 Class 300 720 psig
ASME B16.5 Class 600 1,440 psig
EN1092-1 PN 10/16 16 barg
EN1092-1 PN 25/40 40 barg
EN1092-1 PN 63 63 barg
EN1092-1 PN 100 100 barg
limit the maximum temperature to 257 °F (125 °C).
temperature.
temperature.
(2)
(2)
(2)
(1)
(1)

Performance

Hysteresis (water)
0.1-in. (2.5 mm).
Switching point (water)
(1)
(2)
0.5-in. (13 mm) from tip of fork (if vertical installation) or from edge of fork (if horizontal installation) – this will vary with different liquid densities
Liquid density requirement
Minimum standard density is 37.5 lb/ft3 (600 kg/m3).
Minimum density is 31.2 lb/ft3 (500 kg/m3) when ordered with the Low Density Range option.
Liquid viscosity range
Up to 10000 cP (centiPoise) when operating in the Normal mode.
Up to 1000 cP (centiPoise) when operating in Self-check mode.
Solids content and coating
The maximum recommended diameter of solid particles in the liquid is 0.2-in. (5 mm) when used in normal mode only.
For coating products, avoid bridging of forks.
Emerson.com/Rosemount
Page 11
March 2017
Rosemount 2130
Switching delay
There is a user-selectable 0.3, 1, 3, 10, 30 seconds delay for dry-to-wet and wet-to-dry switching.
CIP (Clean In Place) and SIP (Steam In Place) cleaning
Withstands cleaning routines up to 275 °F (135 °C).
NACE
NACE compliance to MR0175 / ISO 15156 or MR0103, depending on the option code selected for the model number.
Operating modes
Table 6. Operating Modes
Fault conditions detected
PCB Control Circuit Corruption Yes Yes External Damage to Fork No Yes Internal Damage to Sensor No Yes Excessive Corrosion No Yes Over-temperature No Yes
Normal
mode
Self-check
mode

Electrical

Grounding
The Rosemount 2130 should always be grounded, either through the terminals or using the external ground connection provided.
Switching mode
User-selectable switching mode (Dry = on or Wet = on)
Protection
Polarity insensitive
On Direct Load and Relay electronics
Over-current protection
On Direct Load and PNP/PLC electronics
Short-circuit protection
On Direct Load and PNP/PLC electronics
Load-missing protection
On Direct Load and PNP/PLC electronics
Surge protection (to IEC61326)
Available on all versions of the Rosemount 2130
Magnetic test point
A magnetic test point is located on the side of the housing, allowing a functional test of the Rosemount 2130 and a system connected to it. By holding a magnet to the target, the output changes state for as long as the magnet is held there.
Terminal connection (wire diameter)
Minimum 26 AWG and maximum 14 AWG (0.13 to 2.5 mm2). Note national regulations.
Conduit plugs/cable gland
Conduit entries for explosion-proof areas are shipped with one Exd plug (loose in bag) and two dust caps fitted. Use suitably rated cable glands. Unused conduit entries must be sealed with a suitably rated blanking plug. Local codes and regulations must be complied with.
Emerson.com/Rosemount
11
Page 12
Rosemount 2130

Product Certifications

March 2017

European directive information

The EC declaration of conformity for all applicable European directives for this product can be found at
Emerson.com/Rosemount
.

NAMUR approval

NAMUR NE95 type test report is available upon request. Complies with NAMUR NE21.

Overfill approval

Certificate number: Z-65.11-519. TÜV-tested and approved for overfill protection according to the
German DIBt/WHG regulations. Certified under safety devices for tanks and piping related to
water pollution control.

Marine approvals

ABS American Bureau of Shipping GL Germanischer Lloyd (excludes Alarm and Fault relays) SRS Russian Maritime Registered Shipping (RMRS)

Drinking water approval

Ordinary location certification for CSA

G6 Certificate Number: 06 CSA 1805769
The switch has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by CSA, a nationally recognized testing laboratory as accredited by the Standards Council of Canada (SCC). Single process seal.

Safety Integrity Level (SIL) certification

The Rosemount 2130 is SIL2-certified, it has been independently certified to IEC 61508 as required by IEC 61511. Certification was conducted by Exida. If required, add “QT” to the end of the model code. For example, 2130 L A 2 E S 9 NN B A 0000 1 NA Q8 QT.

Canadian Registration Number

CRN 0F04227.2C
Note
The requirements of CRN are met when a Rosemount 2130 CSA-approved (G6, E6, or I6 codes) vibrating fork level switch is configured with 316/316L stainless steel (1.4401/1.4404) wetted parts and either NPT threaded or 2-in. to 8-in. ASME B16.5 flanged process connections.
Rosemount Measurement Ltd., Slough, UK confirms that the wetted parts of the Rosemount type 2130 vibrating level switches are suitable and approved for use in potable water. The wetted parts of the vibrating level switches executed in: Stainless steel (option code S) and Alloy C / Alloy C-276 (option code H) with Flanged (option code R), NPT thread (option code N), BSPT(R) thread (option code B) or Tri Clamp (option code C)
process connections, are in accordance with the requirements of
DVGW*- Worksheet W270.The materials used are classified as toxicologically and microbiologically safe.

Ordinary location certification for FM

G5 Project ID: 3021776
The switch has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by FM, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).

Hazardous locations certifications

North American approvals
Factory Mutual (FM) explosion-proof approval E5 Project ID: 3012658
Explosion-proof for Class I, Div. 1, Groups A, B, C, and D Temperature Class: T6 (T Enclosure: Type 4X
Factory Mutual (FM) intrinsically safe approval and non-incendive approvals
I5 Project ID: 3011456
Intrinsically Safe for Class I, Div. 1, Groups A, B, C, and D Class I, Zone 0, AEx ia IIC Non-incendive for Class I, Div. 2, Groups A, B, C, and D Class I, Zone 2, IIC Temperature Code: T5 (Tamb –40 to 80 °C, Tproc < 80 °C) Control Drawing: 71097/1154 (with NAMUR electronics) Control Drawing: 71097/1314 (with 8/16 mA electronics)
Note
A certified isolating amplifier or barrier must be used for intrinsic safety.
–50 to +75 °C)
amb
12
Emerson.com/Rosemount
Page 13
March 2017
Rosemount 2130
Canadian approvals
Canadian Standards Association (CSA) explosion-proof E6 Project ID: 1786345
Explosion-proof for Class I, Div. 1, Groups A, B, C, and D Temperature Class: T6 (T Enclosure: Type 4X Single Seal
Canadian Standards Association (CSA) intrinsically safe and non-incendive approvals
I6 Certificate Number: 06 CSA 1786345
Intrinsically Safe for Class I, Div. 1, Groups A, B, C, and D Class 1, Zone 0, Ex ia IIC Non-incendive for Class I, Div. 2, Groups A, B, C, and D Temperature Code: T5 (T Control Drawing: 71097/1179 (with NAMUR electronics) Control Drawing: 71097/1315 (with 8/16 mA electronics) Single Seal
Note
A certified isolating amplifier or barrier must be used for intrinsic safety.
–50 to +75 °C)
amb
–50 to +80 °C, Tproc < 80 °C)
amb
European approvals
ATEX flameproof and dust proof approval E1 Certificate: Sira 05ATEX1129X
Flameproof and dust proof: ATEX Marking II 1/2 G D Ex db IIC T6...T2 Ga/Gb Ex tb IIIC T85 °C...T265 °C Db
ATEX intrinsically safe approval I1 Certificate: Sira 05ATEX2130X
Intrinsic Safety for gas and dust atmospheres: ATEX Marking II 1 GD Ex ia IIC T5...T2 Ga Ex ia IIIC T85 °C...T265 °C Da
Note
A certified isolating amplifier or barrier must be used for intrinsic safety.
International approvals
INMETRO flameproof and dust proof approval E2 Certificate Number: TÜV 12.1285 X
Flameproof and dust proof: Ex d IIC T6 to T1 Ga/Gb, Ex tb IIIC T85 °C to T265 °C Db
INMETRO intrinsically safe approval I2 Certificate Number: TÜV 12.1391 X
Intrinsically Safe for gas and dust atmospheres: Ex ia IIC T* Ga, Ex ia IIIC T* Da (* See table in the certificate) Ta* (* See table in the certificate)
Note
A certified isolating amplifier or barrier must be used for intrinsic safety.
National Supervision and Inspection Centre for Explosion Protection and Safety Instrumentation (NEPSI) flameproof and dust proof approval
E3 Certificate Number: GYJ101373
Flameproof and dust proof: Ex d IIC T6 to T2 DIP A21 T
National Supervision and Inspection Centre for Explosion Protection and Safety Instrumentation (NEPSI) intrinsically safe approval
I3 Certificate Number: GYJ101372X (NAMUR electronics)
Intrinsic Safety: Ex ia IIC T5 to T2
Note
A certified isolating amplifier or barrier must be used for intrinsic safety.
International Electrotechnical Commission (IEC) flameproof and dust proof approval
E7 Certificate: IECEx SIR 06.0051X
Flameproof and dust proof: Ex db IIC T6...T2 Ga/Gb Ex tb IIIC T85 °C...T265 °C Db
International Electrotechnical Commission (IEC) intrinsically safe approval
I7 Certificate: IECEx SIR 06.0070X
Intrinsically Safe for gas and dust atmospheres: Ex ia IIC T5...T2 Ga Ex ia IIIC T85 °C...T265 °C Da
Note
A certified isolating amplifier or barrier must be used for intrinsic safety.
Note
A certified isolating amplifier or barrier must be used for intrinsic safety.
Technical Regulation Customs Union (EAC) approvals EM Certificate: RU C-GB.AB72.B.01385
Flameproof:= 1Exd IIC T6...T2 X Ta (see table in the certificate)
IM Certificate: RU C-GB.AB72.B.01385
Intrinsic Safety: 0Exia IIC T5...T2 X Ta (see table in the certificate)
(T85°C to 265°C) IP6X
A
Emerson.com/Rosemount
13
Page 14
Rosemount 2130
A
0.5 (13)
Switchpoint (when
mounted horizontally)
0.5 (13) Switchpoint (when mounted vertically)
13.7
(348)
4.7 (120)
1.7 (44)
B
2.8
(70)
Allow 1.2 (30) to
remove cover
2130***E
2130***M
Allow 1.2 (30) to
remove cover
4.7 (120)
7.1
(182)
2.7
(69)
1.7 (44)
0.5 (13) Switchpoint (when mounted vertically)
0.5 (13)
Switchpoint (when
mounted horizontally)
A
B
C D
C D

Dimensional Drawings

Figure 3. 3/4- and 1-in. Threaded Mounting (Standard Length)
March 2017
A. Aluminum or stainless steel housing B. Cable entry M20 x 1.5 or
Note
Dimensions are in inches (millimeters). For Hygienic Rosemount 2130 dimensions, see Type 1 drawing downloads on Emerson.com/Rosemount.
3
/4-in. ANPT
C. 1.575 (40) A/F hexagon D. 3/4-in. or 1-in. thread
14
Emerson.com/Rosemount
Page 15
March 2017
A
D
E(M)
1.7 (44
B
0.5 (13)
Switchpoint (when
mounted horizontally)
0.5 (13) Switchpoint (when mounted vertically)
14.5
(368)
4.7 (120)
Allow 1.2 (30) to
remove cover
Ø1.1 (28) for 1-in. thread Ø0.9 (23) for
3
/4-in. thread
2130***E
4.7 (120)
A
B
Allow 1.2 (30) to
remove cover
8.0
(202)
C
D
Ø1.1 (28) for 1-in. thread Ø0.9 (23) for
3
/4-in. thread
0.5 (13) Switchpoint (when mounted vertically)
0.5 (13)
Switchpoint (when
mounted horizontally)
1.7 (44)
2130***M
E(M)
C
Figure 4. 3/4- and 1-in. Thread Mounting (Extended Length)
Rosemount 2130
A. Aluminum or stainless steel housing B. Cable entry M20 x 1.5 or
Note
Dimensions are in inches (millimeters). For Hygienic Rosemount 2130 dimensions, see Type 1 drawing downloads on Emerson.com/Rosemount.
Table 7. Fork Length for Threaded Rosemount 2130
Process
connection
3
/4-in. ANPT
Standard length
Fork Length code A
C. 1.575 (40) A/F hexagon D. 3/4-in. or 1-in. thread
Minimum length
Fork Length code E (M)
Maximum length
Fork Length code E (M)
(1)
3
1. Maximum extended length of fork with hand-polished option is 39.4-in. (1000 mm).
Emerson.com/Rosemount
/4-in. thread
1-in. thread 1.7-in. (44 mm) 3.74-in. (94 mm) 157.5-in. (4000 mm)
1.7-in. (44 mm) 3.75-in. (95 mm) 157.5-in. (4000 mm)
15
Page 16
Rosemount 2130
A
12.9
(328)
B
1.7
(4
4.0
(102)
0.5 (13)
Switchpoint (when
mounted horizontally)
Ø1.1 (28) for 1
1
/2 -in. or larger flange; Ø0.9 (23) for up to 1 -in. flange; Ø0.95 (24) for 1 -in. coated flange
0.5 (13) Switchpoint (when mounted vertically)
4.7 (120)
Allow 1.2 (30) to
remove cover
2130***E
2130***M
4.7 (120)
A
B
Allow 1.2 (30) to
remove cover
7.3
(185)
4.0
(102)
1.7 (
0.5 (13)
Switchpoint (when
mounted horizontally)
0.5 (13) Switchpoint (when mounted vertically)
Ø1.1 (28) for 1
1
/2 -in. or larger flange; Ø0.9 (23) for up to 1-in. flange; Ø0.95 (24) for 1-in. coated flange
Figure 5. Flanged Mounting (Standard Length)
March 2017
A. Aluminum or stainless steel housing B. Cable entry M20 x 1.5 or
3
/4-in. ANPT
Note
Dimensions are in inches (millimeters).
C. 1.575 (40) A/F hexagon D. 3/4-in. or 1-in. thread
16
Emerson.com/Rosemount
Page 17
March 2017
A
B
1.7 (44)
12.9
(328)
E(M)
0.5 (13)
Switchpoint (when
mounted horizontally)
Ø1.1 (28) for 1
1
/2 -in. or larger flange Ø0.9 (23) for up to 1-in. flange Ø0.95 (24) for 1-in. coated flange
0.5 (13) Switchpoint (when mounted vertically)
4.7 (120)
Allow 1.2 (30) to
remove cover
4.7 (120)
A
B
Allow 1.2 (30) to
remove cover
0.5 (13)
Switchpoint (when
mounted horizontally)
0.5 (13) Switchpoint (when mounted vertically)
Ø1.1 (28) for 1
1
/2 -in. or larger flange; Ø0.9 (23) for up to 1 -in. flange; Ø0.95 (24) for 1 -in. coated flange
E(M)
7.3
(185)
2130***E
2130***M
1.7 (44)
Figure 6. Flanged Mounting (Extended Length)
Rosemount 2130
A. Aluminum or stainless steel housing B. Cable entry M20 x 1.5 or 3/4-in. ANPT
Note
Dimensions are in inches (millimeters).
Table 8. Fork Length for Flanged Rosemount 2130
1. Maximum extended length of fork with hand-polished option is 39.4 -in. (1000 mm).
Material
Stainless steel
ECTFE copolymer coated
Standard length
Fork Length code H
4.0-in. (102 mm) 3.5-in. (89 mm) 157.5-in. (4000 mm)
4.0-in. (102 mm) 3.5-in. (89 mm) 59.1-in. (1500 mm)
Minimum length
Fork Length code E(M)
Fork Length code E(M)
Maximum length
(1)
Emerson.com/Rosemount
17
Page 18
Rosemount 2130
00813-0100-4130, Rev EE
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com
North America Regional Office
Emerson Automation Solutions
8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com
Latin America Regional Office
Emerson Automation Solutions
1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
Product Data Sheet
March 2017
Europe Regional Office
Emerson Automation Solutions Europe GmbH
Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office
Emerson Automation Solutions Asia Pacific Pte Ltd
1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions
Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465 RFQ.RMTMEA@Emerson.com
Linkedin.com/company/Emerson-Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/RosemountMeasurement
Google.com/+RosemountMeasurement
Standard Terms and Conditions of Sale can be found on the Terms and
Conditions of Sale page.
The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and Rosemount logotype are trademarks of Emerson. NEMA is a registered trademark and service mark of the National Eletrical Manufactures Association. All other marks are the property of their respective owners.
© 2017 Emerson. All rights reserved.
Loading...