Rosemount 2090P Quick Start Guide

Page 1
Quick Start Guide
00825-0100-4108, Rev CA
Rosemount™ 2088, 2090F, and 2090P Pressure Transmitter
with 4–20 mA HART® and 1–5 Vdc Low Power HART Protocol (Revision 5 and 7)
January 2018
Page 2
Quick Start Guide
January 2018
NOTICE
This guide provides basic guidelines for Rosemount 2088, 2090F, and 2090P Transmitters. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations. See the Rosemount 2088 Reference Ma nual information. This manual is also available elec tronically on Emerson.com/Rosemount
Explosions could result in death or serious injury.
Installation of these transmitters in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the approvals section of the Rosemount 2088 Reference Manual
Before connecting a HART-based communicator in an explosive atmosphere, make sure the instruments in
the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In an Explosion-proof/Flameproof installation, do not remove the transmitter covers when power is applied
to the unit.
Process leaks may cause harm or result in death.
To avoid process leaks, only use the O-ring designed to seal with the corresponding flange adapter.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and the terminals. High voltage that may be present on leads can cause electrical shock.
Conduit/cable entries
Unless marked, the conduit/cable entries in the transmitter housing use a marked “M20” are M20 x 1.5 thread form. On devices with multiple conduit entries, all entries will have the same thread form. Only use plugs, adapters, glands or conduit with compatible thread form when closing these entries .
for any restrictions associated with a safe installation.
1
/2–14 NPT thread form. Entries
for more
.
Contents
System readiness . . . . . . . . . . . . . . . . . . . . . . . . 3
Mount the transmitter . . . . . . . . . . . . . . . . . . . 4
Set the switches . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Connect the wiring and power up . . . . . . . . . . . 8
2
Verify transmitter configuration . . . . . . . . . . . . . . 10
Trim the transmitter . . . . . . . . . . . . . . . . . . . . . . . .14
Safety instrumented systems installation . . . . . .16
Product certifications . . . . . . . . . . . . . . . . . . . . . . 17
Page 3
January 2018

1.0 System readiness

1.1 Confirm HART revision capability

If using HART-based control or asset management systems, confirm the
HART capability of those systems prior to transmitter installation. Not all systems are capable of communicating with HART Revision 7 Protocol. This transmitter can be configured for either HART Revision 5 or 7.
For instructions on how to change the HART revision of the transmitter, see
page 14.
Quick Start Guide

1.2 Confirm correct device driver

Device
revision
) is loaded on your systems to
Review
functionality
Change
description
Review instructions
Reference manual
(3)
Rosemount 2088
Reference Manual
Rosemount 2090
Reference Manual
(4)(5)
(5)
(4)
Verify the latest device driver (DD/DTM
ensure proper communication.
Note
The Rosemount 2088, 2090F, and 2090P Transmitters all use Rosemount 2088 Device Revisions and Drivers.
1. Download the latest DD at Emerson.com or FieldCommGroup.org.
2. In the Browse by Member dropdown menu, select Emerson.
3. Select desired product. a. Reference Tab l e 1 and Table 2, Find Device Driver Files column to find the
correct device driver.
Table 1. Rosemount 2088 and 2090 with 4–20 mA HART Protocol Device Revisions
and Files
(2)
universal
Device driver identification
HART
revision
7 10
5 9
7 10
5 9
Device identification
Release
Aug-16 1.1.xx 1.0.xx 3
NAMUR
date
hardware revision
Jan-13 N/A 1.0.xx 1
Jan-98 N/A N/A 178 5 3 N/A
(1)
NAMUR software revision
software
1
revision
HART
1. NAMUR revision is located on the hardware tag of the device. Differences in level 3 changes, signified above by xx, represent minor product changes as defined per NE53. Compatibility and functionality are preserved and product can be used interchangeably.
2. HART software revision can be read using a HART capable configuration tool. Value shown is minimum revision that cou ld correspo nd to NAMUR revis ions.
3. Device driver file names use device and DD revision, e.g. 10_01. HART Protocol is designed to enable legacy device driver revisions to continue to communicate with new HART devices. To access new functionality, the new device driver must be downloaded. It is recommended to download new device driver files to ensure full functionality.
4. HART Revision 5 and 7 selectable, Local Operator Interface (LOI), scaled variable, configurable alarms, expanded engineering units.
5. Updated electronics hardware design. Intrinsic Safety temperature classification change.
3
Page 4
Quick Start Guide
January 2018
Table 2. Rosemount 2088 with 1–5 Vdc Low Power HART Protocol Device Revisions
and Files
(2)
Device driver identification
HART
universal
revision
7 10
5 9
Device
revision
Review instructions
Reference manual
(3)
Rosemount 2088
Reference Manual
Rosemount 2090
Reference Manual
Device identification
Release
Jan-13 N/A 1.0.2 3
Jan-98 N/A N/A 178 5 3 N/A
1. NAMUR Revision is located on the hardware tag of the device. Differences in level 3 changes, signified above by
2. HART soft ware revision can be read using a HART capable configuration tool. Value shown is minimum revision
3. Device driver file names use device and DD revision, e.g. 10_01. HART Protocol is designed to enable legacy
4. HART Revision 5 and 7 selectable, LOI, scaled variable, configurable alarms, expanded engineering units.
NAMUR
date
hardware
revision
xx, represent minor product changes as defined per NE53. Compatibility and functionality are preser ved and product can be used interchangeably.
that could correspond to NAM UR revisions.
device driver revisions to continue to communicate with new HART devices. To access new functionality, the new device driver must be downloaded. It is recommended to download new device driver files to ensure full functionality.
(1)
NAMUR software revision
software
1
revision
HART
Review
functionality
Change
description
(4)

2.0 Mount the transmitter

2.1 Rosemount 2088

Mount directly to the impulse line without using an additional mounting bracket or mount directly to a wall, panel, or 2-in. pipe using an optional mounting bracket.
(4)

2.2 Rosemount 2090P

Mount directly to the process pipe using an existing weld spud, or have a skilled welder install a new weld spud using a TIG welder. See Rosemount 2088
Reference Manual
for complete welding instructions. Improper installation may result in weld spud distortion. Upright or horizontal position mounting is recommended to allow proper draining of vent.

2.3 Rosemount 2090F

Mount directly to the process pipe using a standard sanitary fitting (either a 1.5­or 2-in.Tri-Clamp recommended to allow proper draining of vent.
4
®
connection). Upright or horizontal position mounting is
Page 5
January 2018
1.5 in.
B
C
A
Figure 1. Transmitter Direct Mounting
Do not apply torque directly to the electronics housing. To avoid damage, apply torque only to the hex-shaped process connection.
Rosemount 2088 Rosemount 2090P Rosemount 2090F
A. 1/2–14 NPT female process connection B. Vessel wall C. Weld spud
Figure 2. Panel and Pipe Mounting
1.0 in.
B
D
E
D. O-ring
1
E. 1
/2- or 2-in. Tri-Clamp connection
Panel mount Pipe mount
Quick Start Guide

2.4 Environmental seal for housing

Thread sealing (PTFE) tape or paste on male threads of conduit is required to provide a water/dust tight conduit seal and meets requirements of NEMA 4X, IP66, and IP68. Consult factory if other Ingress Protection ratings are required.
For M20 threads, install conduit plugs to full thread engagement or until mechanical resistance is met.
®
Type

2.5 Liquid flow applications

1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so the drain/vent
valves are oriented upward.
5
Page 6
Quick Start Guide
A

2.6 Gas flow applications

1. Place taps in the top or side of the line.
2. Mount level or above the taps.

2.7 Steam flow applications

1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.

2.8 Gage transmitter orientation

The low side pressure port (atmospheric reference) on the in-line gage transmitter is located in the neck of the transmitter, behind the housing. The vent path is 360° around the transmitter between the housing and sensor (see
Figure 3).
January 2018
Keep the vent path free of any obstruc tion, including but not limited to paint, dust, and lubrication by mounting the transmitter so the contaminants can drain away.
Figure 3. Gage Low Side Pressure Port
A. Low side pressure port (atmospheric reference)
6
Page 7
January 2018

3.0 Set the switches

Set alarm and security switch configuration before installation as shown in
Figure 4.
The alarm switch sets the analog output alarm to high or low. Default alarm
is high.
The security switch allows ( ) or prevents ( ) any configuration of the
transmitter. Default security is off ( ).
Use the following procedure to change the switch configuration:
1. If the transmitter is installed, secure the loop, and remove power.
2. Remove the housing cover opposite the field terminal side. Do not remove
the instrument cover in explosive atmospheres when the circuit is live.
3. Slide the security and alarm switches into the preferred position using a small
screwdriver.
4. Reattach the transmitter cover. The cover must be fully engaged to comply
with explosion-proof requirements.
Figure 4. Transmitter Electronics Board
Without LCD display With LOI/LCD display
Quick Start Guide
A
A. Alarm B. Security

3.1 Electronics board

The Rosemount 2088 and 2090 electronics board should not be tampered with or removed from the housing as it could cause permanent damage to the transmitter.

3.2 LOI/LCD display

The LOI/LCD display can be removed and rotated as needed by following the “Rotating LCD display/LOI display” instructions in the Rosemount 2088
Reference Manual.
B
7
Page 8
Quick Start Guide
A
B

4.0 Connect the wiring and power up

Shielded twisted pair cable should be used for best results. Use 24 AWG or larger wire that does not exceed 5000 ft. (1500 m) in length. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.
Figure 5. Wiring the Transmitter (4–20 mA HART)
A. Vdc supply B. R
250 (necessary for HART Communication only)
L
Figure 6. Wiring the Transmitter (1–5 Vdc Low Power)
January 2018
B
C
A
A. Power supply B. Voltmeter C. Field terminals
Installation of the transient protection terminal block does not provide transient protection
unless the transmitter case is properly grounded.
Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical
equipment.
Do not connect the powered signal wiring to the test terminals. Power could damage the test
diode in the terminal block.
8
Page 9
January 2018
DP
A
B
C
D
E
Use the following steps to wire the transmitter:
1. Remove the housing cover on the FIELD TERMINALS side.
2. Connect the leads as shown in Figure 5 or Figure 6.
3. Tighten the terminal screws to ensure full contact with the terminal block
Note
The use of a pin or ferrule wire terminal is not recommended as the connection may be more susceptible to loosening over time or under vibration.
4. Ground housing to fulfill local grounding regulations.
5. Ensure proper grounding. It is important that the instrument cable shield:
6. If transient protection is needed, refer to Grounding for transient terminal
7. Plug and seal unused conduit connections.
8. Replace the housing cover.
Figure 7. Grounding
Quick Start Guide
screw and washer. When using a direct wiring method, wrap wire clockwise to ensure it is in place when tightening the terminal block screw.
Be trimmed close and insulated from touching the transmitter housingBe connected to the next shield if cable is routed through a junction boxBe connected to a good earth ground at the power supply end
block for grounding instructions.
A.Trim shield and insulate B. Insulate shield C. Terminate cable shield drain wire to earth ground

4.1 Grounding for transient terminal block

Ground termination is provided on the outside of the electronics housing and
D. Internal ground location E. External ground location
inside the terminal compartment. These grounds are used when the transient protection terminal blocks are installed. It is recommended that 18 AWG or larger wire is used to connect housing ground to earth ground (internal or external).
9
Page 10
Quick Start Guide
If the transmitter is currently not wired for power up and communication (follow steps in “Connect the wiring and power up” on page 8. When the transmitter is properly wired, refer to Figure 7 for internal and external transient grounding locations.

5.0 Verify transmitter configuration

Verify the configuration using any HART capable configuration tool or LOI ­option code M4. Configuration instructions for a Field Communicator and LOI are included in this step. See Rosemount 2088 Reference Manual configuration instructions using AMS Device Manager.

5.1 Verifying configuration with a Field Communicator

A Rosemount 2088 DD must be installed on the Field Communicator to verify configuration. Fast Key sequences vary depending on device and DD revisions. Use the Determine Fast Key sequence table process below to identify the appropriate Fast Key sequences.

5.2 Field Communicator User Interface

Determine Fast Key sequence table
1. Connect Field Communicator to Rosemount 2088, 2090F, or 2090P.
2. If Home screen matches Figure 8, refer to Ta ble 3 for Fast Key sequences.
3. If Home screen matches Figure 9: a. Perform Fast Key sequence 1,7,2 to identify Field Revision and HART
Revision.
b. Refer to Table 4 and the appropriate column based on your Field Revision
and HART Revision for Fast Key sequences.
for
January 2018
10
Note
Emerson recommends installing the latest DD to access the complete functionality. Visit
Emerson.com or FieldCommGroup.org.
Figure 8. Traditional Interface
Page 11
January 2018
Figure 9. Device Dashboard
Note
A check () indicates the basic configuration parameters. At minimum, these parameters should be verified as part of the configuration and startup procedure.
Table 3. Traditional Interface Fast Key
Quick Start Guide
Func tion Fast Key sequence
Analog Output Alarm 1, 4, 3, 2, 4
Burst Mode Control 1, 4, 3, 3, 3
Burst Option 1, 4, 3, 3, 4
Calibration 1, 2, 3
Damping 1, 3, 5
Date 1, 3, 4,1
Descriptor 1, 3, 4, 2
Digital To Analog Trim (4–20 mA Output) 1, 2, 3,2,1
Disable Local Span/Zero Adjustment 1, 4, 4, 1, 7
Field Device Info 1,4, 4, 1
Keypad Input 1, 2, 3, 1, 1
Loop Test 1,2, 2
Lower Range Val ue 4, 1
Lower Sensor Trim 1, 2, 3, 3, 2
Message 1, 3, 4, 3
Meter Type 1, 3, 6, 1
Number of Requested 1, 4, 3, 3, 2
Output Trim 1, 2, 3, 2
Percent Range 1, 1, 2
Poll Address 1, 4, 3, 3, 1
Range Values 1, 3, 3
Rerange 1, 2, 3, 1
11
Page 12
Quick Start Guide
Table 3. Traditional Interface Fast Key
Function Fast Key sequence
Scaled D/A Trim (4–20 mA) 1, 2, 3, 2, 2
Self Test (Transmitter) 1, 2, 1, 1
Sensor Info 1, 4, 4, 2
Sensor Trim (Full Trim) 1, 2, 3, 3
Sensor Trim Points 1, 2, 3, 3, 5
Status 1, 2, 1, 2
Tag 1, 3, 1
Transmitter Security (Write Protect) 1, 3, 4, 4
Units (Process Variable) 1, 3, 2
Upper Range Value 5, 2
Upper Sensor Trim 1, 2, 3, 3, 3
Zero Trim 1, 2, 3, 3, 1
Note
A check () indicates the basic configuration parameters. At minimum, these parameters should be verified as part of the configuration and startup procedure.
Table 4. Device Dashboard Fast Keys
Function Fast Key Se quence
Field Revision Rev 3 Rev 5 Rev 7
HART Revision HART 5 HART 5 HART 7
Alarm and Saturation Levels N/A 2, 2, 2, 5, 7 2, 2, 2, 5, 7
Damping 2, 2, 1, 2 2, 2,1, 1, 5 2, 2, 1, 1, 5
Range Values 2, 2, 2 2, 2, 2 2, 2, 2
Tag 2, 2, 6, 1, 1 2, 2, 7, 1, 1 2, 2, 7, 1, 1
Transfer Function 2,2, 1, 3 2, 2, 1, 1, 6 2, 2, 1, 1, 6
Units 2, 2, 1, 1 2, 2, 1, 1, 4 2, 2, 1, 1, 4
Burst Mode 2, 2, 4, 1 2, 2, 5, 3 2, 2, 5, 3
Custom Display Configuration 2, 2, 3 2, 2, 4 2, 2, 4
Date 2, 2, 6,1, 4 2, 2, 7, 1, 3 2, 2, 7, 1, 4
Descriptor 2, 2, 6, 1, 5 2, 2, 7, 1, 4 2, 2, 7, 1, 5
Digital to Analog Trim (4–20 mA Output) 3, 4,2 3, 4, 2 3, 4, 2
Disable Configuration Buttons 2, 2, 5, 2 2, 2, 6, 3 2, 2, 6, 3
Rerange with Keypad 2, 2, 2 2, 2, 2, 1 2, 2, 2, 1
Loop Test 3, 5, 1 3, 5, 1 3, 5, 1
Upper Sensor Trim 3, 4, 1, 1 3, 4, 1,1 3, 4, 1, 1
Lower Sensor Trim 3,4,1,2 3, 4, 1, 2 3, 4, 1, 2
Message 2, 2, 6, 1, 5 2, 2, 7, 1, 5 2, 2, 7, 1, 6
Sensor Temperature/Trend 3, 3, 2 3, 3, 3 3, 3, 3
Digital Zero Trim 3, 4, 1, 3 3, 4, 1, 3 3, 4, 1, 3
Password N/A 2, 2, 6, 4 2, 2, 6, 5
January 2018
12
Page 13
January 2018
B
Table 4. Device Dashboard Fast Keys
Function Fast Key Se quen ce
Field Revision Rev 3 Rev 5 Rev 7
HART Revision HART 5 HART 5 HART 7
Scaled Variable N/A 3, 2, 2 3, 2, 2
HART Revision 5 to HART Revision 7 switch N/A 2, 2, 5, 2, 3 2, 2, 5, 2, 3
Long Tag N/A N/A 2, 2, 7, 1, 2
Find Device N/A N/A 3, 4, 5
Simulate Digital Signal N/A N/A 3, 4, 5

5.3 Verifying configuration with LOI

The optional LOI can be used for commissioning the device. The LOI is a two-button design with internal and external buttons. The internal buttons are located on the display of the transmitter, while the external buttons are located underneath the top metal tag. To activate the LOI push any button. LOI button functionality is shown on the bottom corners of the display. See Table 5 and
Figure 11 for button operation and menu information.
Figure 10. Internal and External LOI Buttons
Quick Start Guide
A
A. Internal buttons B. External buttons
Note
See Figure 12 on page 15 to confirm external button functionality.
Table 5. LOI Button Operation
Button
Left No SCROLL
Right Yes ENTER
13
Page 14
Quick Start Guide
Assign PV
HART Revision
Figure 11. LOI Menu

5.4 Switch HART revision mode

If the HART configuration tool is not capable of communicating with HART Revision 7, the Rosemount 2088, 2090F, or 2090P will load a generic menu with limited capability. The following procedures will switch the HART revision mode from the generic menu:
1. Go to Manual Setup > Device Information > Identification > Message. a. To change to HART Revision 5, Enter: “HART5” in the Message field.
b. To change to HART Revision 7, Enter: “HART7” in the Message field.
January 2018

6.0 Trim the transmitter

Devices are calibrated by the factory. Once installed, it is recommended to perform a zero trim on gage and absolute pressure transmitters to eliminate error due to mounting position or static pressure effects. A zero trim can be performed using either a Field Communicator or configuration buttons.
For instructions using AMS Device Manager, see the Rosemount 2088 Reference
Manual.
It is not recommended to zero an absolute transmitter.
1. Select trim procedure. a. Analog zero trim – sets the analog output to 4 mA.
Also referred to as a “rerange,” it sets the Lower Range Value (LRV)
equal to the measured pressure.
The display and digital HART output remains unchanged.
14
Page 15
January 2018
B
C
D
A
b. Digital zero trim – recalibrates the sensor zero.
The LRV is unaffected. The pressure value will be zero (on display and
HART output). 4 mA point may not be at zero.
This requires that the factory calibrated zero pressure is within a range
of 3% of the URV [0 ± 3% x URV].
Example
URV = 250 inH2O
Applied Zero Pressure = +0.03 x 250 inH
O = +7.5 inH2O (compared to factory
2
settings) values outside this range will be rejected by the transmitter

6.1 Trimming with a Field Communicator

1. Connect the Field Communicator, see “Connect the wiring and power up” on
page 8 for instructions.
2. Follow the HART menu to perform the desired zero trim.
Table 6. Zero Trim Fast Keys
Analog zero (Set 4 mA) Digital zero
Fast Key sequence 3, 4, 2 3, 4, 1, 3

6.2 Trimming with configuration buttons

A zero trim is to be performed using one of the three possible sets of external configuration buttons located under the top tag.
To access the configuration buttons, loosen the screw and slide the tag on the top of the transmitter. Confirm the functionality using Figure 10.
Quick Start Guide
Figure 12. External Configuration Buttons
A. Configuration buttons B. LOI C. Analog zero and span D. Digital zero
Use the following procedures to perform a zero trim:
Perform trim with LOI (option M4)
1. Set the transmitter pressure.
2. See Figure 10 on page 13 for the operating menu. a. Select Rerange to perform an analog zero trim. b. Select Zero Trim to perform a digital zero trim.
15
Page 16
Quick Start Guide
Perform trim with analog zero and span (option D4 or standard on Rosemount 2090F and 2090P)
1. Set the transmitter pressure.
2. Press and hold the Zero button for two seconds to perform an analog zero trim.
Perform trim with digital zero (option DZ)
1. Set the transmitter pressure.
2. Press and hold the Zero button for two seconds to perform a digital zero trim.

7.0 Safety instrumented systems installation

For safety certified installations, refer to Rosemount 2090 Manual Supplement for installation procedure and system requirements.
January 2018
16
Page 17
January 2018

8.0 Product certifications

8.1 Rosemount 2090

Rev 2.1
European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount
Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
North America
E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate: 1015441 Standards: FM Class 3600 - 2011, FM, Class 3615 - 2006, FM class 3616 - 2011,
FM Class 3810 - 2005, ANSI/NEMA 250 - 1991
Markings: XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III, DIV 1;
I5 USA Intrinsic Safety (IS) and Nonincendive (NI)
Certificate: 1015441 Standards: FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 - 2004,
Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III
C6 Canada Explosionproof, Intrinsic Safety and Division 2, Dust-Ignitionproof
Certificate: 1015441 Standards: CAN/CSA C22.2 No. 0-M91 (R2001), CSA Std C22.2 No. 25-1966,
Markings: Explosionproof for Class I, Division 1, Groups B, C and D; Class II, Groups E, F,
T5(–40 °C
FM Class 3810 - 2005
T4(–50 °C 02088-1024; NI CL 1, DIV 2, GP A, B, C, D; Type 4x
CSA Std C22.2 No. 30-M1986, CAN/CSA-C22.2 No. 94-M91, CSA Std C22.2 No. 142-M1987, CAN/CSA-C22.2 No. 157-92, CSA Std C22.2 No. 213-M1987, ANSI-ISA-12.27.01-2003
and G; Class III; Intrinsically Safe Class I, Division 1 when connected in accordance with Rosemount drawing 02088-1024, Temperature Code T3C; Ex ia; Class I Division 2 Groups A, B, C and D; Type 4X; Factory Sealed
Ta ≤ +85 °C); Conduit Seal Not Required; Type 4X
Ta ≤ +70 °C); when connected per Rosemount drawing
.
Quick Start Guide
Europe
ED ATEX Flameproof
Certificate: KEMA97ATEX2378X Standards: EN60079-0:2012 + A11:2013, EN60079-1:2014, EN60079-26:2015 Markings: II 1/2 G Ex db IIC T6…T4 Ga/Gb, T6(–60 °C
T4/T5(–60 °C
Ta ≤ +80 °C);
Ta ≤ +70 °C),
17
Page 18
Quick Start Guide
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid
installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
I1 AT EX I ntr insic Safe ty
Certificate: BAS00ATEX1166X Standards: EN60079-0:2012+A11:2013, EN60079-11:2012 Markings: II 1 G Ex ia IIC T4 Ga (–55 °C
Table 7. Input Parameters
Parameters HART
Volt age U
Current I
Power P
Capacitance C
Special Condition for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test required by EN60079-11. This must be taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane
paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 environment.
N1 AT EX Typ e n
Certificate: BAS00ATEX3167X Standards: EN60079-0:2012+A11:2013, EN60079-15:2010 Markings: II 3 G Ex nA IIC T5 Gc (–55 °C
Special Condition for Safe Use (X):
1. When fitted with a transient suppression terminal block, the equipment is not capable of withstanding the 500 V insulation test that is required by EN60079-15. This must be taken into account when installing the apparatus.
ND ATE X Du st
Certificate: BAS01ATEX1427X Standards: EN60079-0:2012+A11:2013, EN60079-31:2009 Markings: II 1 D Ex t IIIC T50 °C T
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the
ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient range of the
apparatus and capable of withstanding a 7J impact test.
January 2018
Ta +70 °C)
i
i
i
i
30 V
200 mA
0.9 W
0.012 μF
500
Ta +70 °C)
60 °C Da
18
Page 19
January 2018
International
K7 IECEx Flameproof
Certificate: IECEx KEM 06.0021X Standards: IEC60079-0:2011, IEC60079-1:2014, IEC60079-26:2014 Markings: Ex db IIC T6…T4 Ga/Gb, T6(–60 °C
Special Condition for Safe Use (X):
1. The device contains a thin wall diaphragm less than 1 mm thickness that forms a
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid
IECEx Dust: see Approval Option NK
IECEx Intrinsic Safety Certificate: IECEx BAS 12.0071X Standards: IEC60079-0:2011, IEC60079-11:2011 Markings: Ex ia IIC T4 Ga (–55 °C
Tabl e 8. I nput Par amet ers
Quick Start Guide
Ta +70 °C), T4/T5(–60 °C Ta +80 °C)
boundary between EPL Ga (process connection) and EPL Gb (all other parts of the equipment). The model code and datasheet are to be consulted for details of the diaphragm material. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm shall be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
Ta +70 °C)
Parameter HART
Voltag e U
i
Current I
i
Power P
i
Capacitance C
i
30 V
200 mA
0.9 W
0.012 μF
Special Conditions for Safe Use (X):
1. When fitted with a transient suppression terminal block, the Rosemount 2088 is incapable of passing the 500 V isolation test. This must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane
paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 environment.
IECEx Type n
Certificate: IECEx BAS 12.0072X Standards: IEC60079-0:2011, IEC60079-15:2010 Markings: Ex nA IIC T5 Gc (–40 °C
Ta +70 °C)
Special Condition for Safe Use (X):
1. When fitted with a transient suppression terminal block, the Rosemount 2088 is incapable of passing the 500 V isolation test. This must be taken into account during installation.
19
Page 20
Quick Start Guide
NK IECEx Dust
Certificate: IECEx BAS12.0073X Standards: IEC60079-0:2011, IEC60079-31:2008 Markings: Ex t IIIC T50 °C T
Table 9. Input Parameters
Parameter HART
Volt age U
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the
ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient temperature range
of the apparatus and capable of withstanding a 7 J impact test.
China
E3 China Flameproof
Certificate: GYJ15.1506X Standards: GB3836.1-2010, GB3836.2-2010 Markings: Ex d IIC T6/T4 Gb, T6(–20 °C
Special Conditions of Use (X):
1. The ambient temperature is as follows:
January 2018
60 °C Da
500
i
36 Vdc
Ta +40 °C), T4(–20 °C Ta +80 °C)
2. The earth connection facility on the enclosure should be connected reliably.
3. During installation in hazardous location, cable glands, conduits, and blanking plugs,
certified by state-appointed inspection bodies with Ex d IIC type of protection, should be used.
4. During installation, use and maintenance in explosive gas atmospheres, observe the
warning “Do not open when energized”.
5. During installation, there should be no mixture harm to flameproof housing.
6. End user is not permitted to change any components insides, but to settle the problem
in conjunction with manufacturer to avoid damage to the product.
7. Maintenance should be done in non-hazardous location.
8. During installation, use and maintenance of this product, observe the following
standards: GB3836.13-2013, GB3836.15-2000, GB3836.16-2006, GB50257-2014
I3 China Intrinsic Safety
Certificate: GYJ15.1508X Standards: GB3836.1-2010, GB3836.4-2010, GB3836.20-2010 Markings: Ex ia IIC T4 Ga
Special Conditions for Safe Use (X):
1. The enclosure may contain light metal, attention should be taken to avoid ignition hazard due to impact or friction when used in Zone 0.
2. When transient protection board is chosen (option code T1), this apparatus is not
capable of withstanding the 500 V r.m.s insulation test required by Clause 6.3.12 of
20
–20 °C ≤ T
–20 °C ≤ T
T
a
80 °C T4
a
40 °C T6
a
Tem per atu re c las s
Page 21
January 2018
GB3836.4-2010.
Technical Regulations Customs Union (EAC)
EM EAC Flameproof
Certificate: RU C-US.GB05.B.01197 Markings: Ga/Gb Ex d IIC T4/T6 X, T4(–40 °C
Ta +80 °C), T6(–40 °C Ta +40 °C)
Special Condition for Safe Use (X):
1. See certificate for special conditions.
IM EAC Intrinsically Safe
Certificate: RU C-US.GB05.B.01197 Markings: 0Ex ia IIC T4 Ga X, T4(–55 °C
Ta +70 °C)
Special Condition for Safe Use (X):
1. See certificate for special conditions.
Combinations
K1 Combination of ED, I1, ND, and N1 K5 Combination of E5 and I5 K6 Combination of C6, ED, and I1 KB Combination of K5 and C6
KM Combination of EM and IM
KH Combination of ED, I1, K5
Conduit Plugs and Adapters
IECEx Flameproof and Increased Safety Certificate: IECEx FMG 13.0032X Standards: IEC60079-0:2011, IEC60079-1:2007-04, IEC60079-7:2006-07 Markings: Ex de IIC Gb
ATEX Flameproof and Increased Safety Certificate: FM13ATEX0076X Standards: EN60079-0:2012, EN60079-1:2007, EN60079-7:2007 Markings: Ex II 2 G Ex de IIC Gb
Table 10. Conduit Plug Thread Sizes
Quick Start Guide
Thread Identification mark
M20 x 1.5–6g M20
1
/2–14 NPT
G1/2A G1/2
1
/2 NPT
Table 11. Thread Adapter Thread Sizes
Male thread Identification mark
M20 x 1.5–6 H M20
1
/2–14 NPT
3
/4 –14 NPT
Femal e thread Identification mark
M20 x 1.5–6 H M20
1
/2–14 NPT
3
/4–14 NPT
21
Page 22
Quick Start Guide
Table 11. Thread Adapter Thread Sizes
1
Special Condition for Safe Use (X):
1. When the thread adapter or blanking plug is used with an enclosure in type of protection increased safety “e” the entry thread shall be suitably sealed in order to maintain the ingress protection rating (IP) of the enclosure.
2. The blanking plug shall not be used with an adapter.
3. Blanking Plug and Threaded Adapter shall be either NPT or Metric thread forms. G
and PG 13.5 thread forms are only acceptable for existing (legacy) equipment installations.
/2–14 NPT
PG 13.5 PG 13.5
1
/2–14 NPT
January 2018
1
/2
22
Page 23
January 2018

8.2 Rosemount 2088

Rev 1.13
European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount
Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
North America
E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate: 1V2A8.AE Standards: FM Class 3600 - 2011, FM, Class 3615 - 2006, FM class 3616 - 2011,
Markings: XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III;
I5 USA Intrinsic Safety (IS) and Nonincendive (NI)
Certificate: 1015441 Standards: FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 - 2004,
Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV 1 when
C6 Canada Explosionproof, Intrinsic Safety and Division 2, Dust-Ignitionproof
Certificate: 1015441 Standards: CAN/CSA C22.2 No. 0-M91 (R2001), CSA Std C22.2 No. 25-1966,
Markings: Explosionproof for Class I, Division 1, Groups B, C and D; Class II,
FM Class 3810 - 2005, ANSI/NEMA 250 - 1991
T5(–40 °C
FM Class 3810 - 2005
connected per Rosemount drawing 02088-1024; NI CL 1, DIV 2, GP A, B, C, D; T4(–50 °C
CSA Std C22.2 No. 30-M1986, CAN/CSA-C22.2 No. 94-M91, CSA Std C22.2 No. 142-M1987, CAN/CSA-C22.2 No. 157-92, CSA Std C22.2 No. 213-M1987, ANSI-ISA-12.27.01-2003
Groups E, F, and G; Class III; Intrinsically Safe Class I, Division 1 when connected in accordance with Rosemount drawing 02088-1024, Temperature Code T3C; Ex ia; Class I Division 2 Groups A, B, C and D; Type 4X; Factory Sealed; Single Seal
Ta ≤ +85 °C); Factory Sealed; Type 4X
Ta ≤ +70 °C); Type 4x
.
Quick Start Guide
Europe
ED ATEX Flameproof
Certificate: KEMA97ATEX2378X Standards: EN60079-0:2012 + A11:2013, EN60079-1:2014, EN60079-26:2015 Markings: II 1/2 G Ex db IIC T6…T4 Ga/Gb, T6(–60 °C
T4/T5(–60 °C
Ta ≤ +80 °C);
Ta ≤ +70 °C),
23
Page 24
Quick Start Guide
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid
installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
I1 ATEX I ntrinsi c Sa fety
Certificate: BAS00ATEX1166X Standards: EN60079-0:2012 + A11:2013, EN60079-11:2012 Markings: Ex II 1 G Ex ia IIC T4 Ga (–55 °C
Table 12. Input Parameters
Parameters HART
Volt age U
Current I
Power P
Capacitance C
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test required by EN60079-11. This must be taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane
paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 environment.
N1 AT EX Typ e n
Certificate: BAS00ATEX3167X Standards: EN60079-0:2012 + A11:2013, EN60079-15:2010 Markings: Ex II 3 G Ex nA IIC T5 Gc (–40 °C
Special Condition for Safe Use (X):
1. This apparatus is not capable of withstanding the 500 V insulation test required by EN60079-15. This must be taken into account when installing the apparatus.
ND ATEX Dus t
Certificate: BAS01ATEX1427X Standards: EN60079-0:2012 + A11:2013, EN60079-31:2009 Markings: Ex II 1 D Ex t IIIC T50 °C T
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the
ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient range of the
apparatus and capable of withstanding a 7 J impact test.
January 2018
Ta +70 °C)
i
i
i
i
30 V
200 mA
0.9 W
0.012 μF
500
Ta +70 °C)
60 °C Da
24
Page 25
January 2018
International
E7 IECEx Flameproof
Certificate: IECEx KEM 06.0021X Standards: IEC 60079-0:2011, IEC60079-1:2014, IEC60079-26:2014 Markings: Ex db IIC T6…T4 Ga/Gb, T6(–60 °C
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid
installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
I7 IECEx Intrinsic Safety
Certificate: IECEx BAS 12.0071X Standards: IEC60079-0:2011, IEC60079-11:2011 Markings: Ex ia IIC T4 Ga (–55 °C
Table 13. Input Parameters
Parameter HART
Voltag e U
Current I
Power P
Capacitance C
Special Conditions for Safe Use (X):
1. When fitted with a transient suppression terminal block, the Rosemount 2088 is incapable of passing the 500 V isolation test. This must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane
paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 environment.
N7 IECEx Type n
Certificate: IECEx BAS 12.0072X Standards: IEC60079-0:2011, IEC60079-15:2010 Markings: Ex nA IIC T5 Gc (–40 °C
Special Condition for Safe Use (X):
1. When fitted with a transient suppression terminal block, the Rosemount 2088 is incapable of passing the 500 V isolation test. This must be taken into account during installation.
NK IECEx Dust
Certificate: IECEx BAS12.0073X Standards: IEC60079-0:2011, IEC60079-31:2008 Markings: Ex t IIIC T50 °C T
Quick Start Guide
Ta ≤ +70 °C), T4/T5(–60 °C ≤ Ta ≤ +80 °C)
Ta ≤ +70 °C)
i
i
i
i
30 V
200 mA
0.9 W
0.012 μF
500
Ta +70 °C)
60 °C Da
25
Page 26
Quick Start Guide
Table 14. Input Parameters
Parameter HART
Volt age U
i
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the
ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient temperature range
of the apparatus and capable of withstanding a 7 J impact test.
Brazil
E2 INMETRO Flameproof
Certificate: UL-BR 15.0728X Standards: ABNT NBR IEC60079-0:2008 + Errata 1:2011,
Markings: Ex db IIC T6…T4 Ga/Gb, T4/T5(–60 °C
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm less than 1mm thickness that forms a boundary between zone 0 (process connection) and zone 1 (all other parts of the equipment). The model code and datasheet are to be consulted for details of the diaphragm material. Installations, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid
installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint Is ordered through a special option code, contact the manufacturer for more information.
I2 INMETRO Intrinsic Safety
Certificate: UL-BR 13.0246X Standards: ABNT NBR IEC60079-0:2008 + Errata 1:2011, ABNT NBR IEC60079-11:2009 Markings: Ex ia IIC T4 Ga (–55 °C
Table 15. Input Parameters
January 2018
36 V
ABNT NBR IEC 60079-1:2009 + Errata 1:2011, ABNT NBR IEC 60079-26:2008 + Errata 1:2008
Ta ≤ +80 °C), T6(–60 °C ≤ Ta ≤ +70 °C)
Ta ≤ +70 °C)
26
Parameter HART
Volt age U
i
Current I
i
Power P
i
Capacitance C
i
30 V
200 mA
0.9 W
0.012 μF
Special Conditions for Safe Use (X):
1. When fitted with a transient suppression terminal block, the Rosemount 2088 is incapable of passing the 500 V isolation test. This must be taken into account when installing the equipment.
Page 27
January 2018
2. The enclosure may be made of aluminum alloy and given a protective polyurethane
China
E3 China Flameproof
Certificate: GYJ15.1505 Standards: GB3836.1-2010, GB3836.2-2010 Markings: Ex d IIC T6/T4 Gb, T6(–20 °C
Special Conditions of Use (X):
1. The ambient temperature is as follows:
Quick Start Guide
paint finish; however, care should be taken to protect it from impact or abrasion if located in Zone 0.
Ta +40 °C), T4(–20 °C Ta +80 °C)
–20 °C ≤ T
–20 °C ≤ T
T
a
80 °C T4
a
40 °C T6
a
Temperature class
2. The earth connection facility on the enclosure should be connected reliably.
3. During installation in hazardous location, cable glands, conduits, and blanking plugs, certified by state-appointed inspection bodies with Ex d IIC type of protection, should be used.
4. During installation, use and maintenance in explosive gas atmospheres, observe the warning “Do not open when energized.”
5. During installation, there should be no mixture harm to flameproof housing.
6. End user is not permitted to change any components insides, but to settle the problem in conjunction with manufacturer to avoid damage to the product.
7. Maintenance should be done in non-hazardous location.
8. During installation, use and maintenance of this product, observe the following standards: GB3836.13-2013, GB3836.15-2000, GB3836.16-2006, GB50257-2014
I3 China Intrinsic Safety
Certificate: GYJ15.1507 Standards: GB3836.1-2010, GB3836.4-2010, GB3836.20-2010 Markings: Ex ia IIC T4 Ga
Special Conditions for Safe Use (X):
1. The enclosure may contain light metal, attention should be taken to avoid ignition
hazard due to impact or friction when used in Zone 0.
2. When transient protection board is chosen (option code T1),this apparatus is not capable of withstanding the 500V r.m.s insulation test required by Clause 6.3.12 of GB3836.4-2010.
N3 China Type n
Certificate: GYJ15.1108X Standards: GB3836.1-2000, GB3836.8-2003 Markings: Ex nA IIC T5 Gc (–40 °C
Ta +70 °C)
Special Condition for Safe Use (X):
1. When transient protection board is chosen (option code T1), this apparatus is not
capable of withstanding the 500 V r.m.s insulation test required by Clause 6.3.12 of GB3836.4-2010.
27
Page 28
Quick Start Guide
Korea
EP Korea Flameproof
Certificate: 13-KB4BO-0020X Markings: Ex d IIC T6…T4, T4/T5(–60 °C
Special Condition for Safe Use (X):
1. See certificate for special conditions.
Japan
E4 Japan Flameproof
Certificate: TC20869, TC20870 Markings: Ex d IIC T5
Technical Regulations Customs Union (EAC)
EM EAC Flameproof
Certificate: RU C-US.GB05.B.01197 Markings: Ga/Gb Ex d IIC T4/T6 X, T4(–40 °C
Special Condition for Safe Use (X):
1. See certificate for special conditions.
IM EAC Intrinsically Safe
Certificate: RU C-US.GB05.B.01197 Markings: 0Ex ia IIC T4 Ga X, T4(–55 °C
Special Condition for Safe Use (X):
1. See certificate for special conditions.
January 2018
Ta ≤ +80 °C), T6(–60 °C ≤ Ta ≤ +70 °C)
Ta ≤ +80 °C), T6(–40 °C ≤ Ta ≤ +40 °C)
Ta ≤ +70 °C)
Combinations
K1 Combination of ED, I1, ND, and N1 K2 Combination of E2 and I2 K5 Combination of E5 and I5 K6 Combination of C6, ED, and I1 K7 Combination of E7, I7, NK, and N7 KB Combination of K5 and C6 KM Combination of EM and IM KH Combination of ED, I1, K5
Conduit Plugs and Adapters
IECEx Flameproof and Increased Safety Certificate: IECEx FMG 13.0032X Standards: IEC60079-0:2011, IEC60079-1:2007-04, IEC60079-7:2006-07 Markings: Ex de IIC Gb
ATEX Flameproof and Increased Safety Certificate: FM13ATEX0076X Standards: EN60079-0:2012, EN60079-1:2007, EN60079-7:2007 Markings: Ex II 2 G Ex de IIC Gb
28
Page 29
January 2018
Table 16. Conduit Plug Thread Sizes
Table 17. Thread Adapter Thread Sizes
Special Conditions for Safe Use (X):
1. When the thread adapter or blanking plug is used with an enclosure in type of
2. The blanking plug shall not be used with an adapter.
3. Blanking Plug and Threaded Adapter shall be either NPT or Metric thread forms. G
Quick Start Guide
Thread Identification mark
M20 x 1.5–6g M20
1
/2–14 NPT
G1/2A G1/2
Male thread Identification mark
M20 x 1.5–6H M20
1
/2–14 NPT
3
/4 –14 NPT
Femal e thread Identification mark
M20 x 1.5–6H M20
1
/2–14 NPT
G 1/2 G 1/2
1
/2 NPT
1
/2–14 NPT
3
/4–14 NPT
1
/2–14 NPT
protection increased safety “e” the entry thread shall be suitably sealed in order to maintain the ingress protection rating (IP) of the enclosure.
thread forms are only acceptable for existing (legacy) equipment installations.
1
/2
Additional Certifications
SBS American Bureau of Shipping (ABS) Type Approval
Certificate: 09-HS446883D-3-PDA Intended Use: Measurement of either gauge or absolute pressure for liquid, gas, and
vapor
ABS Rules: 2014 Steel Vessels Rules 1-1-4/7.7, 1-1-Appendix 3, 4-8-3/1.7,
4-8-3/13.1, 4-8-3/13.3.1 & 13.3.2, 4-8-4/27.5.1
SBV Bureau Veritas (BV) Type Approval
Certificate: 23156/B0 BV Requirements: Bureau Veritas Rules for the Classification of Steel Ships Application: Class notations: AUT-UMS, AUT-CCS, AUT-PORT, and AUT-IMS;
Pressure transmitter type 2088 cannot be installed on diesel engines.
SDN Det Norske Veritas (DNV) Type Approval
Certificate: TAA000004F Intended Use: DNV GL Rules for Classification - Ships and offshore units Application:
Location classes
Tem pe ra tu r e D
Humidity B
Vibration A
29
Page 30
Quick Start Guide
EMC B
Enclosure D
SLL Lloyds Register (LR) Type Approval
Certificate: 11/60002 Application: Environmental categories ENV1, ENV2, ENV3, and ENV5
January 2018
30
Page 31
January 2018
EU Declaration of Conformity
No: RMD 1010 Rev. L
Page 1 of 3
We,
Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
declare under our sole responsibility that the product,
Rosemount Pressure Transmitters 3051P, 2051G, 2088, and 2090
manufactured by,
Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
to which this declaration relates, is in conformity with the provisions of the European Union Directives, including the latest amendments, as shown in the attached schedule.
Assumption of conformity is based on the application of the harmonized standards and, when applicable or required, a European Union notified body certification, as shown in the attached schedule.
(signature)
Vice President of Global Quality
(function)
Chris LaPoint
(name)
03-Apr-2017
(date of issue)
Figure 13. Rosemount 2088 and 2090 Declaration of Conformity
Quick Start Guide
31
Page 32
Quick Start Guide
EU Declaration of Conformity
No: RMD 1010 Rev. L
Page 2 of 3
EMC Directive (2014/30/EU)
Harmonized Standards: EN 61326-1:2013, EN 61326-2-3:2013
ATEX Directive (2014/34/EU)
BAS00ATEX1166X - Intrinsic Safety Certificate
Equipment Group II Category 1 G
Ex ia IIC T4 Ga
Harmonized Standards:
EN60079-0:2012 + A11:2013, EN60079-11:2012
BAS00ATEX3167X - Type n Certificate
Equipment Group II Category 3 G
Ex nA IIC T5 Gc
Harmonized Standards:
EN60079-0:2012 + A11:2013, EN60079-15:2010
BAS01ATEX1427X - Dust Certificate
Equipment Group II Category 1 D
Ex t IIIC T50°C T
500
60°C Da
Harmonized Standards:
EN60079-0:2012 + A11:2013
Other Standards:
EN60079-31:2009 (A review against EN60079-31:2014 which is harmonized, shows no significant changes relevant to this equipment so EN60079-31:2009 continues to represent “State of the Art”.)
KEMA97ATEX2378X - Flameproof Certificate
Equipment Group II Category 1/2 G
Ex db IIC T6...T4 Ga/Gb
Harmonized Standards:
EN 60079-0:2012 + A11:2013; EN60079-1:2014; EN60079-26:2015
January 2018
32
Page 33
January 2018
EU Declaration of Conformity
No: RMD 1010 Rev. L
Page 3 of 3
ATEX Notified Bodies
DEKRA (KEMA) [Notified Body Number: 0344]
Utrechtseweg 310, 6812 AR Arnhem P.O. Box 5185, 6802 ED Arnhem The Netherlands Postbank 6794687
SGS Baseefa Limited [Notified Body Number: 1180] Rockhead Business Park Staden Lane Buxton, Derbyshire SK17 9RZ United Kingdom
ATEX Notified Body for Quality Assurance
SGS Baseefa Limited [Notified Body Number: 1180]
Rockhead Business Park Staden Lane SK17 9RZ Buxton United Kingdom
Quick Start Guide
33
Page 34
Quick Start Guide
㇑᧗⢙䍘䎵䗷ᴰབྷ⎃ᓖ䲀٬Ⲵ䜘Ԧරࡇ㺘
䜘Ԧ〠
ᴹᇣ⢙䍘䍘
䫵
⊎
䭹
ޝԧ䬜䬜
ཊⓤ㚄㚄㤟
ཊⓤ㚄㚄㤟䟊
China RoHS
List of Rosemount 2088, 2090F, and 2090 Parts with China RoHS Concentration above MCVs
/ Hazardous Substances
Rosemount 2088, 2090F, and 2090
January 2018
Part Name
⭥ᆀ㓴Ԧ
Electronics
Assembly
༣փ㓴Ԧ
Housing
Assembly
Րᝏಘ㓴Ԧ
Sensor
Assembly
ᵜ㺘Ṭ㌫׍ᦞ
This table is proposed in accordance with the provision of SJ/T11364.
᜿Ѫ䈕䜘ԦⲴᡰᴹ൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿൷վҾ
O: O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572.
᜿Ѫ൘䈕䜘Ԧᡰ֯⭘Ⲵᡰᴹ൷䍘ᶀᯉ䟼ˈ㠣ቁᴹа㊫൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿儈Ҿ
X: X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.
Lead
(Pb)
Mercury
(Hg)
Cadmium
XO O O O O
XO O X O O
XO O X O O
Ⲵ㿴ᇊ㘼ࡦ֌
SJ/T11364
(Cd)
Hexavalent
Chromium
(Cr +6)
GB/T 26572
Polybrominated
biphenyls
(PBB)
ᡰ㿴ᇊⲴ䲀䟿㾱≲
GB/T 26572
Polybrominated diphenyl ethers
(PBDE)
ᡰ㿴ᇊⲴ䲀䟿㾱≲
34
Page 35
January 2018
Quick Start Guide
35
Page 36
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com
North America Regional Office
Emerson Automation Solutions
8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com
Latin America Regional Office
Emerson Automation Solutions
1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
Europe Regional Office
Emerson Automation Solutions
Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office
Emerson Automation Solutions
1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions
Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emi rates
+971 4 8118100 +971 4 8865465
RFQ.RMTMEA@Emerson.com
*00825-0100-4108*
Quick Start Guide
00825-0100-4108, Rev CA
Linkedin.com/company/Emerson-Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/us er/RosemountMeasur ement
Google.com/+RosemountMeasurement
Emerson Terms and Conditions of Sale are available upon r equest The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and Rosemount logotype are trademarks of Emerson. DTM is a trademark of the FDT Group. HART is a registered trademark of the FieldComm Group. Tri-Clamp is a registered trademark of Alfa Laval Corp., Sweden. NEMA is a registered trademark and service mark of the National Electrical Manufacturers Association. All other marks are the property of their respective owners. © 2018 Emerson. All rights reser ved.
January 2018
Loading...