Rosemount™ 2088, 2090F, and 2090P
Pressure Transmitter
with 4–20 mA HART® and 1–5 Vdc Low Power
HART Protocol (Revision 5 and 7)
January 2018
Page 2
Quick Start Guide
January 2018
NOTICE
This guide provides basic guidelines for Rosemount 2088, 2090F, and 2090P Transmitters. It does not provide
instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof,
Flameproof, or intrinsically safe (I.S.) installations. See the Rosemount 2088 Reference Ma nual
information. This manual is also available elec tronically on Emerson.com/Rosemount
Explosions could result in death or serious injury.
Installation of these transmitters in an explosive environment must be in accordance with the appropriate local,
national, and international standards, codes, and practices. Review the approvals section of the Rosemount
2088 Reference Manual
Before connecting a HART-based communicator in an explosive atmosphere, make sure the instruments in
the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In an Explosion-proof/Flameproof installation, do not remove the transmitter covers when power is applied
to the unit.
Process leaks may cause harm or result in death.
To avoid process leaks, only use the O-ring designed to seal with the corresponding flange adapter.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and the terminals. High voltage that may be present on leads can cause electrical
shock.
Conduit/cable entries
Unless marked, the conduit/cable entries in the transmitter housing use a
marked “M20” are M20 x 1.5 thread form. On devices with multiple conduit entries, all entries will have the same
thread form. Only use plugs, adapters, glands or conduit with compatible thread form when closing these
entries .
for any restrictions associated with a safe installation.
If using HART-based control or asset management systems, confirm the
HART capability of those systems prior to transmitter installation. Not all
systems are capable of communicating with HART Revision 7 Protocol. This
transmitter can be configured for either HART Revision 5 or 7.
For instructions on how to change the HART revision of the transmitter, see
page 14.
Quick Start Guide
1.2Confirm correct device driver
Device
revision
™
) is loaded on your systems to
Review
functionality
Change
description
Review instructions
Reference manual
(3)
Rosemount 2088
Reference Manual
Rosemount 2090
Reference Manual
(4)(5)
(5)
(4)
Verify the latest device driver (DD/DTM
ensure proper communication.
Note
The Rosemount 2088, 2090F, and 2090P Transmitters all use Rosemount 2088 Device
Revisions and Drivers.
1. Download the latest DD at Emerson.com or FieldCommGroup.org.
2. In the Browse by Member dropdown menu, select Emerson.
3. Select desired product.
a. Reference Tab l e 1 and Table 2, Find Device Driver Files column to find the
correct device driver.
Table 1. Rosemount 2088 and 2090 with 4–20 mA HART Protocol Device Revisions
and Files
(2)
universal
Device driver
identification
HART
revision
710
59
710
59
Device identification
Release
Aug-161.1.xx1.0.xx3
NAMUR
date
hardware
revision
Jan-13N/A1.0.xx1
Jan-98N/AN/A17853N/A
(1)
NAMUR
software
revision
software
1
revision
HART
1. NAMUR revision is located on the hardware tag of the device. Differences in level 3 changes, signified above by
xx, represent minor product changes as defined per NE53. Compatibility and functionality are preserved and
product can be used interchangeably.
2. HART software revision can be read using a HART capable configuration tool. Value shown is minimum revision
that cou ld correspo nd to NAMUR revis ions.
3. Device driver file names use device and DD revision, e.g. 10_01. HART Protocol is designed to enable legacy
device driver revisions to continue to communicate with new HART devices. To access new functionality, the
new device driver must be downloaded. It is recommended to download new device driver files to ensure full
functionality.
4. HART Revision 5 and 7 selectable, Local Operator Interface (LOI), scaled variable, configurable alarms,
expanded engineering units.
5. Updated electronics hardware design. Intrinsic Safety temperature classification change.
3
Page 4
Quick Start Guide
January 2018
Table 2. Rosemount 2088 with 1–5 Vdc Low Power HART Protocol Device Revisions
and Files
(2)
Device driver
identification
HART
universal
revision
710
59
Device
revision
Review instructions
Reference manual
(3)
Rosemount 2088
Reference Manual
Rosemount 2090
Reference Manual
Device identification
Release
Jan-13N/A1.0.23
Jan-98N/AN/A17853N/A
1. NAMUR Revision is located on the hardware tag of the device. Differences in level 3 changes, signified above by
2. HART soft ware revision can be read using a HART capable configuration tool. Value shown is minimum revision
3. Device driver file names use device and DD revision, e.g. 10_01. HART Protocol is designed to enable legacy
xx, represent minor product changes as defined per NE53. Compatibility and functionality are preser ved and
product can be used interchangeably.
that could correspond to NAM UR revisions.
device driver revisions to continue to communicate with new HART devices. To access new functionality, the new
device driver must be downloaded. It is recommended to download new device driver files to ensure full
functionality.
(1)
NAMUR
software
revision
software
1
revision
HART
Review
functionality
Change
description
(4)
2.0Mount the transmitter
2.1Rosemount 2088
Mount directly to the impulse line without using an additional mounting bracket
or mount directly to a wall, panel, or 2-in. pipe using an optional mounting
bracket.
(4)
2.2Rosemount 2090P
Mount directly to the process pipe using an existing weld spud, or have a skilled
welder install a new weld spud using a TIG welder. See Rosemount 2088
Reference Manual
for complete welding instructions. Improper installation may
result in weld spud distortion. Upright or horizontal position mounting is
recommended to allow proper draining of vent.
2.3Rosemount 2090F
Mount directly to the process pipe using a standard sanitary fitting (either a 1.5or 2-in.Tri-Clamp
recommended to allow proper draining of vent.
4
®
connection). Upright or horizontal position mounting is
Page 5
January 2018
1.5 in.
B
C
A
Figure 1. Transmitter Direct Mounting
Do not apply torque directly to the electronics housing.
To avoid damage, apply torque only to the hex-shaped
process connection.
Rosemount 2088Rosemount 2090P Rosemount 2090F
A. 1/2–14 NPT female process connection
B. Vessel wall
C. Weld spud
Figure 2. Panel and Pipe Mounting
1.0 in.
B
D
E
D. O-ring
1
E. 1
/2- or 2-in. Tri-Clamp connection
Panel mountPipe mount
Quick Start Guide
2.4Environmental seal for housing
Thread sealing (PTFE) tape or paste on male threads of conduit is required to
provide a water/dust tight conduit seal and meets requirements of NEMA
4X, IP66, and IP68. Consult factory if other Ingress Protection ratings are
required.
For M20 threads, install conduit plugs to full thread engagement or until
mechanical resistance is met.
®
Type
2.5Liquid flow applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so the drain/vent
valves are oriented upward.
5
Page 6
Quick Start Guide
A
2.6Gas flow applications
1. Place taps in the top or side of the line.
2. Mount level or above the taps.
2.7Steam flow applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
2.8Gage transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage
transmitter is located in the neck of the transmitter, behind the housing. The
vent path is 360° around the transmitter between the housing and sensor (see
Figure 3).
January 2018
Keep the vent path free of any obstruc tion, including but not limited to paint, dust, and lubrication
by mounting the transmitter so the contaminants can drain away.
Figure 3. Gage Low Side Pressure Port
A. Low side pressure port (atmospheric reference)
6
Page 7
January 2018
3.0Set the switches
Set alarm and security switch configuration before installation as shown in
Figure 4.
The alarm switch sets the analog output alarm to high or low. Default alarm
is high.
The security switch allows () or prevents () any configuration of the
transmitter. Default security is off ().
Use the following procedure to change the switch configuration:
1. If the transmitter is installed, secure the loop, and remove power.
2. Remove the housing cover opposite the field terminal side. Do not remove
the instrument cover in explosive atmospheres when the circuit is live.
3. Slide the security and alarm switches into the preferred position using a small
screwdriver.
4. Reattach the transmitter cover. The cover must be fully engaged to comply
with explosion-proof requirements.
Figure 4. Transmitter Electronics Board
Without LCD displayWith LOI/LCD display
Quick Start Guide
A
A. Alarm
B. Security
3.1Electronics board
The Rosemount 2088 and 2090 electronics board should not be tampered with
or removed from the housing as it could cause permanent damage to the
transmitter.
3.2LOI/LCD display
The LOI/LCD display can be removed and rotated as needed by following the
“Rotating LCD display/LOI display” instructions in the Rosemount 2088
Reference Manual.
B
7
Page 8
Quick Start Guide
A
B
4.0Connect the wiring and power up
Shielded twisted pair cable should be used for best results. Use 24 AWG or larger
wire that does not exceed 5000 ft. (1500 m) in length. If applicable, install wiring
with a drip loop. Arrange the drip loop so the bottom is lower than the conduit
connections and the transmitter housing.
Figure 5. Wiring the Transmitter (4–20 mA HART)
A. Vdc supply
B. R
≥ 250 (necessary for HART Communication only)
L
Figure 6. Wiring the Transmitter (1–5 Vdc Low Power)
January 2018
B
C
A
A. Power supply
B. Voltmeter
C. Field terminals
Installation of the transient protection terminal block does not provide transient protection
unless the transmitter case is properly grounded.
Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical
equipment.
Do not connect the powered signal wiring to the test terminals. Power could damage the test
diode in the terminal block.
8
Page 9
January 2018
DP
A
B
C
D
E
Use the following steps to wire the transmitter:
1. Remove the housing cover on the FIELD TERMINALS side.
2. Connect the leads as shown in Figure 5 or Figure 6.
3. Tighten the terminal screws to ensure full contact with the terminal block
Note
The use of a pin or ferrule wire terminal is not recommended as the connection may be
more susceptible to loosening over time or under vibration.
4. Ground housing to fulfill local grounding regulations.
5. Ensure proper grounding. It is important that the instrument cable shield:
6. If transient protection is needed, refer to Grounding for transient terminal
7. Plug and seal unused conduit connections.
8. Replace the housing cover.
Figure 7. Grounding
Quick Start Guide
screw and washer. When using a direct wiring method, wrap wire clockwise
to ensure it is in place when tightening the terminal block screw.
Be trimmed close and insulated from touching the transmitter housing
Be connected to the next shield if cable is routed through a junction box
Be connected to a good earth ground at the power supply end
block for grounding instructions.
A.Trim shield and insulate
B. Insulate shield
C. Terminate cable shield drain wire to earth ground
4.1Grounding for transient terminal block
Ground termination is provided on the outside of the electronics housing and
D. Internal ground location
E. External ground location
inside the terminal compartment. These grounds are used when the transient
protection terminal blocks are installed. It is recommended that 18 AWG or
larger wire is used to connect housing ground to earth ground (internal or
external).
9
Page 10
Quick Start Guide
If the transmitter is currently not wired for power up and communication (follow
steps in “Connect the wiring and power up” on page 8. When the transmitter is
properly wired, refer to Figure 7 for internal and external transient grounding
locations.
5.0Verify transmitter configuration
Verify the configuration using any HART capable configuration tool or LOI option code M4. Configuration instructions for a Field Communicator and LOI
are included in this step. See Rosemount 2088 Reference Manual
configuration instructions using AMS Device Manager.
5.1Verifying configuration with a Field Communicator
A Rosemount 2088 DD must be installed on the Field Communicator to verify
configuration. Fast Key sequences vary depending on device and DD revisions.
Use the Determine Fast Key sequence table process below to identify the
appropriate Fast Key sequences.
5.2Field Communicator User Interface
Determine Fast Key sequence table
1. Connect Field Communicator to Rosemount 2088, 2090F, or 2090P.
2. If Home screen matches Figure 8, refer to Ta ble 3 for Fast Key sequences.
3. If Home screen matches Figure 9:
a. Perform Fast Key sequence 1,7,2 to identify Field Revision and HART
Revision.
b. Refer to Table 4 and the appropriate column based on your Field Revision
and HART Revision for Fast Key sequences.
for
January 2018
10
Note
Emerson recommends installing the latest DD to access the complete functionality. Visit
Emerson.com or FieldCommGroup.org.
Figure 8. Traditional Interface
Page 11
January 2018
Figure 9. Device Dashboard
Note
A check () indicates the basic configuration parameters. At minimum, these parameters
should be verified as part of the configuration and startup procedure.
Table 3. Traditional Interface Fast Key
Quick Start Guide
Func tionFast Key sequence
Analog Output Alarm1, 4, 3, 2, 4
Burst Mode Control1, 4, 3, 3, 3
Burst Option 1, 4, 3, 3, 4
Calibration1, 2, 3
Damping1, 3, 5
Date1, 3, 4,1
Descriptor1, 3, 4, 2
Digital To Analog Trim (4–20 mA Output)1, 2, 3,2,1
Disable Local Span/Zero Adjustment1, 4, 4, 1, 7
Field Device Info1,4, 4, 1
Keypad Input1, 2, 3, 1, 1
Loop Test1,2, 2
Lower Range Val ue4, 1
Lower Sensor Trim1, 2, 3, 3, 2
Message1, 3, 4, 3
Meter Type1, 3, 6, 1
Number of Requested 1, 4, 3, 3, 2
Output Trim1, 2, 3, 2
Percent Range1, 1, 2
Poll Address1, 4, 3, 3, 1
Range Values1, 3, 3
Rerange1, 2, 3, 1
11
Page 12
Quick Start Guide
Table 3. Traditional Interface Fast Key
FunctionFast Key sequence
Scaled D/A Trim (4–20 mA)1, 2, 3, 2, 2
Self Test (Transmitter)1, 2, 1, 1
Sensor Info1, 4, 4, 2
Sensor Trim (Full Trim)1, 2, 3, 3
Sensor Trim Points1, 2, 3, 3, 5
Status1, 2, 1, 2
Tag1, 3, 1
Transmitter Security (Write Protect)1, 3, 4, 4
Units (Process Variable)1, 3, 2
Upper Range Value5, 2
Upper Sensor Trim1, 2, 3, 3, 3
Zero Trim1, 2, 3, 3, 1
Note
A check () indicates the basic configuration parameters. At minimum, these parameters
should be verified as part of the configuration and startup procedure.
The optional LOI can be used for commissioning the device. The LOI is a
two-button design with internal and external buttons. The internal buttons are
located on the display of the transmitter, while the external buttons are located
underneath the top metal tag. To activate the LOI push any button. LOI button
functionality is shown on the bottom corners of the display. See Table 5 and
Figure 11 for button operation and menu information.
Figure 10. Internal and External LOI Buttons
Quick Start Guide
A
A. Internal buttons
B. External buttons
Note
See Figure 12 on page 15 to confirm external button functionality.
Table 5. LOI Button Operation
Button
LeftNoSCROLL
RightYesENTER
13
Page 14
Quick Start Guide
Assign PV
HART Revision
Figure 11. LOI Menu
5.4Switch HART revision mode
If the HART configuration tool is not capable of communicating with HART
Revision 7, the Rosemount 2088, 2090F, or 2090P will load a generic menu with
limited capability. The following procedures will switch the HART revision mode
from the generic menu:
1. Go to Manual Setup > Device Information > Identification > Message.
a. To change to HART Revision 5, Enter: “HART5” in the Message field.
b. To change to HART Revision 7, Enter: “HART7” in the Message field.
January 2018
6.0Trim the transmitter
Devices are calibrated by the factory. Once installed, it is recommended to
perform a zero trim on gage and absolute pressure transmitters to eliminate
error due to mounting position or static pressure effects. A zero trim can be
performed using either a Field Communicator or configuration buttons.
For instructions using AMS Device Manager, see the Rosemount 2088 Reference
Manual.
It is not recommended to zero an absolute transmitter.
1. Select trim procedure.
a. Analog zero trim – sets the analog output to 4 mA.
Also referred to as a “rerange,” it sets the Lower Range Value (LRV)
equal to the measured pressure.
The display and digital HART output remains unchanged.
14
Page 15
January 2018
B
C
D
A
b. Digital zero trim – recalibrates the sensor zero.
The LRV is unaffected. The pressure value will be zero (on display and
HART output). 4 mA point may not be at zero.
This requires that the factory calibrated zero pressure is within a range
of 3% of the URV [0 ± 3% x URV].
Example
URV = 250 inH2O
Applied Zero Pressure = +0.03 x 250 inH
O = +7.5 inH2O (compared to factory
2
settings) values outside this range will be rejected by the transmitter
6.1Trimming with a Field Communicator
1. Connect the Field Communicator, see “Connect the wiring and power up” on
page 8 for instructions.
2. Follow the HART menu to perform the desired zero trim.
Table 6. Zero Trim Fast Keys
Analog zero (Set 4 mA)Digital zero
Fast Key sequence3, 4, 23, 4, 1, 3
6.2Trimming with configuration buttons
A zero trim is to be performed using one of the three possible sets of external
configuration buttons located under the top tag.
To access the configuration buttons, loosen the screw and slide the tag on the
top of the transmitter. Confirm the functionality using Figure 10.
Quick Start Guide
Figure 12. External Configuration Buttons
A. Configuration buttons
B. LOI
C. Analog zero and span
D. Digital zero
Use the following procedures to perform a zero trim:
Perform trim with LOI (option M4)
1. Set the transmitter pressure.
2. See Figure 10 on page 13 for the operating menu.
a. Select Rerange to perform an analog zero trim.
b. Select Zero Trim to perform a digital zero trim.
15
Page 16
Quick Start Guide
Perform trim with analog zero and span (option D4 or standard on
Rosemount 2090F and 2090P)
1. Set the transmitter pressure.
2. Press and hold the Zero button for two seconds to perform an analog zero
trim.
Perform trim with digital zero (option DZ)
1. Set the transmitter pressure.
2. Press and hold the Zero button for two seconds to perform a digital zero
trim.
7.0Safety instrumented systems installation
For safety certified installations, refer to Rosemount 2090 Manual Supplement
for installation procedure and system requirements.
January 2018
16
Page 17
January 2018
8.0Product certifications
8.1Rosemount 2090
Rev 2.1
European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the Quick
Start Guide. The most recent revision of the EU Declaration of Conformity can
be found at Emerson.com/Rosemount
Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that
the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited by
the Federal Occupational Safety and Health Administration (OSHA).
North America
E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate: 1015441
Standards: FM Class 3600 - 2011, FM, Class 3615 - 2006, FM class 3616 - 2011,
FM Class 3810 - 2005, ANSI/NEMA 250 - 1991
Markings: XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III, DIV 1;
I5 USA Intrinsic Safety (IS) and Nonincendive (NI)
Certificate: 1015441
Standards: FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 - 2004,
Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III
C6 Canada Explosionproof, Intrinsic Safety and Division 2, Dust-Ignitionproof
and G; Class III; Intrinsically Safe Class I, Division 1 when connected in
accordance with Rosemount drawing 02088-1024, Temperature Code T3C;
Ex ia; Class I Division 2 Groups A, B, C and D; Type 4X; Factory Sealed
≤ Ta ≤ +85 °C); Conduit Seal Not Required; Type 4X
≤ Ta ≤ +70 °C); when connected per Rosemount drawing
.
Quick Start Guide
Europe
ED ATEX Flameproof
Certificate: KEMA97ATEX2378X
Standards: EN60079-0:2012 + A11:2013, EN60079-1:2014, EN60079-26:2015
Markings: II 1/2 G Ex db IIC T6…T4 Ga/Gb, T6(–60 °C
T4/T5(–60 °C
≤ Ta ≤ +80 °C);
≤ Ta ≤ +70 °C),
17
Page 18
Quick Start Guide
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance and use shall
take into account the environmental conditions to which the diaphragm will be
subjected. The manufacturer's instructions for installation and maintenance shall be
followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid
installations that could cause electrostatic build-up on painted surfaces, and only
clean the painted surfaces with a damp cloth. If paint is ordered through a special
option code, contact the manufacturer for more information.
I1 AT EX I ntr insic Safe ty
Certificate: BAS00ATEX1166X
Standards: EN60079-0:2012+A11:2013, EN60079-11:2012
Markings: II 1 G Ex ia IIC T4 Ga (–55 °C
Table 7. Input Parameters
ParametersHART
Volt age U
Current I
Power P
Capacitance C
Special Condition for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test required by
EN60079-11. This must be taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane
paint finish; however, care should be taken to protect it from impact or abrasion if
located in a Zone 0 environment.
N1 AT EX Typ e n
Certificate: BAS00ATEX3167X
Standards: EN60079-0:2012+A11:2013, EN60079-15:2010
Markings: II 3 G Ex nA IIC T5 Gc (–55 °C
Special Condition for Safe Use (X):
1. When fitted with a transient suppression terminal block, the equipment is not capable
of withstanding the 500 V insulation test that is required by EN60079-15. This must be
taken into account when installing the apparatus.
ND ATE X Du st
Certificate: BAS01ATEX1427X
Standards: EN60079-0:2012+A11:2013, EN60079-31:2009
Markings: II 1 D Ex t IIIC T50 °C T
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to
at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the
ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient range of the
apparatus and capable of withstanding a 7J impact test.
January 2018
≤ Ta ≤ +70 °C)
i
i
i
i
30 V
200 mA
0.9 W
0.012 μF
500
≤ Ta ≤ +70 °C)
60 °C Da
18
Page 19
January 2018
International
K7 IECEx Flameproof
Certificate: IECEx KEM 06.0021X
Standards: IEC60079-0:2011, IEC60079-1:2014, IEC60079-26:2014
Markings: Ex db IIC T6…T4 Ga/Gb, T6(–60 °C
Special Condition for Safe Use (X):
1. The device contains a thin wall diaphragm less than 1 mm thickness that forms a
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid
IECEx Dust: see Approval Option NK
IECEx Intrinsic Safety
Certificate: IECEx BAS 12.0071X
Standards: IEC60079-0:2011, IEC60079-11:2011
Markings: Ex ia IIC T4 Ga (–55 °C
Tabl e 8. I nput Par amet ers
Quick Start Guide
≤ Ta ≤ +70 °C), T4/T5(–60 °C ≤ Ta ≤ +80 °C)
boundary between EPL Ga (process connection) and EPL Gb (all other parts of the
equipment). The model code and datasheet are to be consulted for details of the
diaphragm material. Installation, maintenance and use shall take into account the
environmental conditions to which the diaphragm shall be subjected. The
manufacturer's instructions for installation and maintenance shall be followed in detail
to assure safety during its expected lifetime.
installations that could cause electrostatic build-up on painted surfaces, and only clean
the painted surfaces with a damp cloth. If paint is ordered through a special option
code, contact the manufacturer for more information.
≤ Ta ≤ +70 °C)
ParameterHART
Voltag e U
i
Current I
i
Power P
i
Capacitance C
i
30 V
200 mA
0.9 W
0.012 μF
Special Conditions for Safe Use (X):
1. When fitted with a transient suppression terminal block, the Rosemount 2088 is
incapable of passing the 500 V isolation test. This must be taken into account during
installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane
paint finish; however, care should be taken to protect it from impact or abrasion if
located in a Zone 0 environment.
IECEx Type n
Certificate: IECEx BAS 12.0072X
Standards: IEC60079-0:2011, IEC60079-15:2010
Markings: Ex nA IIC T5 Gc (–40 °C
≤ Ta ≤ +70 °C)
Special Condition for Safe Use (X):
1. When fitted with a transient suppression terminal block, the Rosemount 2088 is
incapable of passing the 500 V isolation test. This must be taken into account during
installation.
19
Page 20
Quick Start Guide
NK IECEx Dust
Certificate: IECEx BAS12.0073X
Standards: IEC60079-0:2011, IEC60079-31:2008
Markings: Ex t IIIC T50 °C T
Table 9. Input Parameters
ParameterHART
Volt age U
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to
at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the
ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient temperature range
of the apparatus and capable of withstanding a 7 J impact test.
China
E3 China Flameproof
Certificate: GYJ15.1506X
Standards: GB3836.1-2010, GB3836.2-2010
Markings: Ex d IIC T6/T4 Gb, T6(–20 °C
Special Conditions of Use (X):
1. The ambient temperature is as follows:
January 2018
60 °C Da
500
i
36 Vdc
≤ Ta ≤ +40 °C), T4(–20 °C ≤ Ta ≤ +80 °C)
2. The earth connection facility on the enclosure should be connected reliably.
3. During installation in hazardous location, cable glands, conduits, and blanking plugs,
certified by state-appointed inspection bodies with Ex d IIC type of protection, should
be used.
4. During installation, use and maintenance in explosive gas atmospheres, observe the
warning “Do not open when energized”.
5. During installation, there should be no mixture harm to flameproof housing.
6. End user is not permitted to change any components insides, but to settle the problem
in conjunction with manufacturer to avoid damage to the product.
7. Maintenance should be done in non-hazardous location.
8. During installation, use and maintenance of this product, observe the following
Certificate: GYJ15.1508X
Standards: GB3836.1-2010, GB3836.4-2010, GB3836.20-2010
Markings: Ex ia IIC T4 Ga
Special Conditions for Safe Use (X):
1. The enclosure may contain light metal, attention should be taken to avoid ignition
hazard due to impact or friction when used in Zone 0.
2. When transient protection board is chosen (option code T1), this apparatus is not
capable of withstanding the 500 V r.m.s insulation test required by Clause 6.3.12 of
20
–20 °C ≤ T
–20 °C ≤ T
T
a
≤ 80 °CT4
a
≤ 40 °CT6
a
Tem per atu re c las s
Page 21
January 2018
GB3836.4-2010.
Technical Regulations Customs Union (EAC)
EM EAC Flameproof
Certificate: RU C-US.GB05.B.01197
Markings: Ga/Gb Ex d IIC T4/T6 X, T4(–40 °C
≤ Ta ≤ +80 °C), T6(–40 °C ≤ Ta ≤ +40 °C)
Special Condition for Safe Use (X):
1. See certificate for special conditions.
IM EAC Intrinsically Safe
Certificate: RU C-US.GB05.B.01197
Markings: 0Ex ia IIC T4 Ga X, T4(–55 °C
≤ Ta ≤ +70 °C)
Special Condition for Safe Use (X):
1. See certificate for special conditions.
Combinations
K1 Combination of ED, I1, ND, and N1
K5 Combination of E5 and I5
K6 Combination of C6, ED, and I1
KB Combination of K5 and C6
KM Combination of EM and IM
KH Combination of ED, I1, K5
Conduit Plugs and Adapters
IECEx Flameproof and Increased Safety
Certificate: IECEx FMG 13.0032X
Standards: IEC60079-0:2011, IEC60079-1:2007-04, IEC60079-7:2006-07
Markings: Ex de IIC Gb
ATEX Flameproof and Increased Safety
Certificate: FM13ATEX0076X
Standards: EN60079-0:2012, EN60079-1:2007, EN60079-7:2007
Markings: Ex II 2 G Ex de IIC Gb
Table 10. Conduit Plug Thread Sizes
Quick Start Guide
ThreadIdentification mark
M20 x 1.5–6gM20
1
/2–14 NPT
G1/2AG1/2
1
/2 NPT
Table 11. Thread Adapter Thread Sizes
Male threadIdentification mark
M20 x 1.5–6 HM20
1
/2–14 NPT
3
/4 –14 NPT
Femal e threadIdentification mark
M20 x 1.5–6 HM20
1
/2–14 NPT
3
/4–14 NPT
21
Page 22
Quick Start Guide
Table 11. Thread Adapter Thread Sizes
1
Special Condition for Safe Use (X):
1. When the thread adapter or blanking plug is used with an enclosure in type of
protection increased safety “e” the entry thread shall be suitably sealed in order to
maintain the ingress protection rating (IP) of the enclosure.
2. The blanking plug shall not be used with an adapter.
3. Blanking Plug and Threaded Adapter shall be either NPT or Metric thread forms. G
and PG 13.5 thread forms are only acceptable for existing (legacy) equipment
installations.
/2–14 NPT
PG 13.5PG 13.5
1
/2–14 NPT
January 2018
1
/2
22
Page 23
January 2018
8.2Rosemount 2088
Rev 1.13
European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the Quick
Start Guide. The most recent revision of the EU Declaration of Conformity can
be found at Emerson.com/Rosemount
Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that
the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited by
the Federal Occupational Safety and Health Administration (OSHA).
North America
E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate: 1V2A8.AE
Standards: FM Class 3600 - 2011, FM, Class 3615 - 2006, FM class 3616 - 2011,
Markings: XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III;
I5 USA Intrinsic Safety (IS) and Nonincendive (NI)
Certificate: 1015441
Standards: FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 - 2004,
Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV 1 when
C6 Canada Explosionproof, Intrinsic Safety and Division 2, Dust-Ignitionproof
Groups E, F, and G; Class III; Intrinsically Safe Class I, Division 1 when connected
in accordance with Rosemount drawing 02088-1024, Temperature Code T3C;
Ex ia; Class I Division 2 Groups A, B, C and D; Type 4X; Factory Sealed; Single
Seal
≤ Ta ≤ +85 °C); Factory Sealed; Type 4X
≤ Ta ≤ +70 °C); Type 4x
.
Quick Start Guide
Europe
ED ATEX Flameproof
Certificate: KEMA97ATEX2378X
Standards: EN60079-0:2012 + A11:2013, EN60079-1:2014, EN60079-26:2015
Markings: II 1/2 G Ex db IIC T6…T4 Ga/Gb, T6(–60 °C
T4/T5(–60 °C
≤ Ta ≤ +80 °C);
≤ Ta ≤ +70 °C),
23
Page 24
Quick Start Guide
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance and use shall
take into account the environmental conditions to which the diaphragm will be
subjected. The manufacturer's instructions for installation and maintenance shall be
followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid
installations that could cause electrostatic build-up on painted surfaces, and only
clean the painted surfaces with a damp cloth. If paint is ordered through a special
option code, contact the manufacturer for more information.
I1 ATEX I ntrinsi c Sa fety
Certificate: BAS00ATEX1166X
Standards: EN60079-0:2012 + A11:2013, EN60079-11:2012
Markings: Ex II 1 G Ex ia IIC T4 Ga (–55 °C
Table 12. Input Parameters
ParametersHART
Volt age U
Current I
Power P
Capacitance C
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test required by
EN60079-11. This must be taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane
paint finish; however, care should be taken to protect it from impact or abrasion if
located in a Zone 0 environment.
N1 AT EX Typ e n
Certificate: BAS00ATEX3167X
Standards: EN60079-0:2012 + A11:2013, EN60079-15:2010
Markings: Ex II 3 G Ex nA IIC T5 Gc (–40 °C
Special Condition for Safe Use (X):
1. This apparatus is not capable of withstanding the 500 V insulation test required by
EN60079-15. This must be taken into account when installing the apparatus.
ND ATEX Dus t
Certificate: BAS01ATEX1427X
Standards: EN60079-0:2012 + A11:2013, EN60079-31:2009
Markings: Ex II 1 D Ex t IIIC T50 °C T
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to
at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the
ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient range of the
apparatus and capable of withstanding a 7 J impact test.
January 2018
≤ Ta ≤ +70 °C)
i
i
i
i
30 V
200 mA
0.9 W
0.012 μF
500
≤ Ta ≤ +70 °C)
60 °C Da
24
Page 25
January 2018
International
E7 IECEx Flameproof
Certificate: IECEx KEM 06.0021X
Standards: IEC 60079-0:2011, IEC60079-1:2014, IEC60079-26:2014
Markings: Ex db IIC T6…T4 Ga/Gb, T6(–60 °C
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance and use shall
take into account the environmental conditions to which the diaphragm will be
subjected. The manufacturer's instructions for installation and maintenance shall be
followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid
installations that could cause electrostatic build-up on painted surfaces, and only clean
the painted surfaces with a damp cloth. If paint is ordered through a special option
code, contact the manufacturer for more information.
I7 IECEx Intrinsic Safety
Certificate: IECEx BAS 12.0071X
Standards: IEC60079-0:2011, IEC60079-11:2011
Markings: Ex ia IIC T4 Ga (–55 °C
Table 13. Input Parameters
ParameterHART
Voltag e U
Current I
Power P
Capacitance C
Special Conditions for Safe Use (X):
1. When fitted with a transient suppression terminal block, the Rosemount 2088 is
incapable of passing the 500 V isolation test. This must be taken into account during
installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane
paint finish; however, care should be taken to protect it from impact or abrasion if
located in a Zone 0 environment.
N7 IECEx Type n
Certificate: IECEx BAS 12.0072X
Standards: IEC60079-0:2011, IEC60079-15:2010
Markings: Ex nA IIC T5 Gc (–40 °C
Special Condition for Safe Use (X):
1. When fitted with a transient suppression terminal block, the Rosemount 2088 is
incapable of passing the 500 V isolation test. This must be taken into account during
installation.
NK IECEx Dust
Certificate: IECEx BAS12.0073X
Standards: IEC60079-0:2011, IEC60079-31:2008
Markings: Ex t IIIC T50 °C T
Quick Start Guide
≤ Ta ≤ +70 °C), T4/T5(–60 °C ≤ Ta ≤ +80 °C)
≤ Ta ≤ +70 °C)
i
i
i
i
30 V
200 mA
0.9 W
0.012 μF
500
≤ Ta ≤ +70 °C)
60 °C Da
25
Page 26
Quick Start Guide
Table 14. Input Parameters
ParameterHART
Volt age U
i
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to
at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the
ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient temperature range
of the apparatus and capable of withstanding a 7 J impact test.
1. This device contains a thin wall diaphragm less than 1mm thickness that forms a
boundary between zone 0 (process connection) and zone 1 (all other parts of the
equipment). The model code and datasheet are to be consulted for details of the
diaphragm material. Installations, maintenance and use shall take into account the
environmental conditions to which the diaphragm will be subjected. The
manufacturer's instructions for installation and maintenance shall be followed in detail
to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid
installations that could cause electrostatic build-up on painted surfaces, and only
clean the painted surfaces with a damp cloth. If paint Is ordered through a special
option code, contact the manufacturer for more information.
I2 INMETRO Intrinsic Safety
Certificate: UL-BR 13.0246X
Standards: ABNT NBR IEC60079-0:2008 + Errata 1:2011, ABNT NBR IEC60079-11:2009
Markings: Ex ia IIC T4 Ga (–55 °C
1. When fitted with a transient suppression terminal block, the Rosemount 2088 is
incapable of passing the 500 V isolation test. This must be taken into account when
installing the equipment.
Page 27
January 2018
2. The enclosure may be made of aluminum alloy and given a protective polyurethane
China
E3 China Flameproof
Certificate: GYJ15.1505
Standards: GB3836.1-2010, GB3836.2-2010
Markings: Ex d IIC T6/T4 Gb, T6(–20 °C
Special Conditions of Use (X):
1. The ambient temperature is as follows:
Quick Start Guide
paint finish; however, care should be taken to protect it from impact or abrasion if
located in Zone 0.
≤ Ta ≤ +40 °C), T4(–20 °C ≤ Ta ≤ +80 °C)
–20 °C ≤ T
–20 °C ≤ T
T
a
≤ 80 °CT4
a
≤ 40 °CT6
a
Temperature class
2. The earth connection facility on the enclosure should be connected reliably.
3. During installation in hazardous location, cable glands, conduits, and blanking plugs,
certified by state-appointed inspection bodies with Ex d IIC type of protection, should
be used.
4. During installation, use and maintenance in explosive gas atmospheres, observe the
warning “Do not open when energized.”
5. During installation, there should be no mixture harm to flameproof housing.
6. End user is not permitted to change any components insides, but to settle the problem
in conjunction with manufacturer to avoid damage to the product.
7. Maintenance should be done in non-hazardous location.
8. During installation, use and maintenance of this product, observe the following
standards: GB3836.13-2013, GB3836.15-2000, GB3836.16-2006, GB50257-2014
I3 China Intrinsic Safety
Certificate: GYJ15.1507
Standards: GB3836.1-2010, GB3836.4-2010, GB3836.20-2010
Markings: Ex ia IIC T4 Ga
Special Conditions for Safe Use (X):
1. The enclosure may contain light metal, attention should be taken to avoid ignition
hazard due to impact or friction when used in Zone 0.
2. When transient protection board is chosen (option code T1),this apparatus is not
capable of withstanding the 500V r.m.s insulation test required by Clause 6.3.12 of
GB3836.4-2010.
N3 China Type n
Certificate: GYJ15.1108X
Standards: GB3836.1-2000, GB3836.8-2003
Markings: Ex nA IIC T5 Gc (–40 °C
≤ Ta ≤ +70 °C)
Special Condition for Safe Use (X):
1. When transient protection board is chosen (option code T1), this apparatus is not
capable of withstanding the 500 V r.m.s insulation test required by Clause 6.3.12 of
GB3836.4-2010.
27
Page 28
Quick Start Guide
Korea
EP Korea Flameproof
Certificate: 13-KB4BO-0020X
Markings: Ex d IIC T6…T4, T4/T5(–60 °C
Special Condition for Safe Use (X):
1. See certificate for special conditions.
Japan
E4 Japan Flameproof
Certificate: TC20869, TC20870
Markings: Ex d IIC T5
Technical Regulations Customs Union (EAC)
EM EAC Flameproof
Certificate: RU C-US.GB05.B.01197
Markings: Ga/Gb Ex d IIC T4/T6 X, T4(–40 °C
Special Condition for Safe Use (X):
1. See certificate for special conditions.
IM EAC Intrinsically Safe
Certificate: RU C-US.GB05.B.01197
Markings: 0Ex ia IIC T4 Ga X, T4(–55 °C
Special Condition for Safe Use (X):
1. See certificate for special conditions.
January 2018
≤ Ta ≤ +80 °C), T6(–60 °C ≤ Ta ≤ +70 °C)
≤ Ta ≤ +80 °C), T6(–40 °C ≤ Ta ≤ +40 °C)
≤ Ta ≤ +70 °C)
Combinations
K1 Combination of ED, I1, ND, and N1
K2 Combination of E2 and I2
K5 Combination of E5 and I5
K6 Combination of C6, ED, and I1
K7 Combination of E7, I7, NK, and N7
KB Combination of K5 and C6
KM Combination of EM and IM
KH Combination of ED, I1, K5
Conduit Plugs and Adapters
IECEx Flameproof and Increased Safety
Certificate: IECEx FMG 13.0032X
Standards: IEC60079-0:2011, IEC60079-1:2007-04, IEC60079-7:2006-07
Markings: Ex de IIC Gb
ATEX Flameproof and Increased Safety
Certificate: FM13ATEX0076X
Standards: EN60079-0:2012, EN60079-1:2007, EN60079-7:2007
Markings: Ex II 2 G Ex de IIC Gb
28
Page 29
January 2018
Table 16. Conduit Plug Thread Sizes
Table 17. Thread Adapter Thread Sizes
Special Conditions for Safe Use (X):
1. When the thread adapter or blanking plug is used with an enclosure in type of
2. The blanking plug shall not be used with an adapter.
3. Blanking Plug and Threaded Adapter shall be either NPT or Metric thread forms. G
Quick Start Guide
ThreadIdentification mark
M20 x 1.5–6gM20
1
/2–14 NPT
G1/2AG1/2
Male threadIdentification mark
M20 x 1.5–6HM20
1
/2–14 NPT
3
/4 –14 NPT
Femal e threadIdentification mark
M20 x 1.5–6HM20
1
/2–14 NPT
G 1/2G 1/2
1
/2 NPT
1
/2–14 NPT
3
/4–14 NPT
1
/2–14 NPT
protection increased safety “e” the entry thread shall be suitably sealed in order to
maintain the ingress protection rating (IP) of the enclosure.
thread forms are only acceptable for existing (legacy) equipment installations.
1
/2
Additional Certifications
SBS American Bureau of Shipping (ABS) Type Approval
Certificate: 09-HS446883D-3-PDA
Intended Use: Measurement of either gauge or absolute pressure for liquid, gas, and
Certificate: 23156/B0 BV
Requirements: Bureau Veritas Rules for the Classification of Steel Ships
Application: Class notations: AUT-UMS, AUT-CCS, AUT-PORT, and AUT-IMS;
Pressure transmitter type 2088 cannot be installed on diesel engines.
SDN Det Norske Veritas (DNV) Type Approval
Certificate: TAA000004F
Intended Use: DNV GL Rules for Classification - Ships and offshore units
Application:
Location classes
Tem pe ra tu r eD
HumidityB
VibrationA
29
Page 30
Quick Start Guide
EMCB
EnclosureD
SLLLloyds Register (LR) Type Approval
Certificate: 11/60002
Application: Environmental categories ENV1, ENV2, ENV3, and ENV5
January 2018
30
Page 31
January 2018
EU Declaration of Conformity
No: RMD 1010 Rev. L
Page 1 of 3
We,
Rosemount, Inc.
8200 Market Boulevard
Chanhassen, MN 55317-9685
USA
declare under our sole responsibility that the product,
Rosemount Pressure Transmitters 3051P, 2051G, 2088, and 2090
manufactured by,
Rosemount, Inc.
8200 Market Boulevard
Chanhassen, MN 55317-9685
USA
to which this declaration relates, is in conformity with the provisions of the European Union
Directives, including the latest amendments, as shown in the attached schedule.
Assumption of conformity is based on the application of the harmonized standards and, when
applicable or required, a European Union notified body certification, as shown in the attached
schedule.
(signature)
Vice President of Global Quality
(function)
Chris LaPoint
(name)
03-Apr-2017
(date of issue)
Figure 13. Rosemount 2088 and 2090 Declaration of Conformity
Quick Start Guide
31
Page 32
Quick Start Guide
EU Declaration of Conformity
No: RMD 1010 Rev. L
Page 2 of 3
EMC Directive (2014/30/EU)
Harmonized Standards: EN 61326-1:2013, EN 61326-2-3:2013
ATEX Directive (2014/34/EU)
BAS00ATEX1166X - Intrinsic Safety Certificate
Equipment Group II Category 1 G
Ex ia IIC T4 Ga
Harmonized Standards:
EN60079-0:2012 + A11:2013, EN60079-11:2012
BAS00ATEX3167X - Type n Certificate
Equipment Group II Category 3 G
Ex nA IIC T5 Gc
Harmonized Standards:
EN60079-0:2012 + A11:2013, EN60079-15:2010
BAS01ATEX1427X - Dust Certificate
Equipment Group II Category 1 D
Ex t IIIC T50°C T
500
60°C Da
Harmonized Standards:
EN60079-0:2012 + A11:2013
Other Standards:
EN60079-31:2009
(A review against EN60079-31:2014 which is harmonized, shows no significant
changes relevant to this equipment so EN60079-31:2009 continues to represent
“State of the Art”.)
KEMA97ATEX2378X - Flameproof Certificate
Equipment Group II Category 1/2 G
Ex db IIC T6...T4 Ga/Gb
Harmonized Standards:
EN 60079-0:2012 + A11:2013; EN60079-1:2014; EN60079-26:2015
January 2018
32
Page 33
January 2018
EU Declaration of Conformity
No: RMD 1010 Rev. L
Page 3 of 3
ATEX Notified Bodies
DEKRA (KEMA) [Notified Body Number: 0344]
Utrechtseweg 310, 6812 AR Arnhem
P.O. Box 5185, 6802 ED Arnhem
The Netherlands
Postbank 6794687
SGS Baseefa Limited [Notified Body Number: 1180]
Rockhead Business Park
Staden Lane
Buxton, Derbyshire
SK17 9RZ United Kingdom
ATEX Notified Body for Quality Assurance
SGS Baseefa Limited [Notified Body Number: 1180]
Rockhead Business Park Staden Lane
SK17 9RZ Buxton
United Kingdom
Quick Start Guide
33
Page 34
Quick Start Guide
ᴹ
㇑᧗⢙䍘䎵䗷ᴰབྷ⎃ᓖ䲀٬Ⲵ䜘Ԧරࡇ㺘
䜘Ԧ〠
ᴹᇣ⢙䍘䍘
䫵
⊎
䭹
ޝԧ䬜䬜
ཊⓤ㚄㚄㤟
ཊⓤ㚄㚄㤟䟊
China RoHS
List of Rosemount 2088, 2090F, and 2090 Parts with China RoHS Concentration above MCVs
/ Hazardous Substances
Rosemount 2088, 2090F, and 2090
January 2018
Part Name
⭥ᆀ㓴Ԧ
Electronics
Assembly
༣փ㓴Ԧ
Housing
Assembly
Րᝏಘ㓴Ԧ
Sensor
Assembly
ᵜ㺘Ṭ㌫ᦞ
This table is proposed in accordance with the provision of SJ/T11364.
Ѫ䈕䜘ԦⲴᡰᴹ൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿൷վҾ
O:
O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of
GB/T 26572.
Ѫ൘䈕䜘Ԧᡰ֯⭘Ⲵᡰᴹ൷䍘ᶀᯉ䟼ˈ㠣ቁᴹа㊫൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿儈Ҿ
X:
X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above
the limit requirement of GB/T 26572.