Rosemount 2088, 2090P, and 2090F Pressure Transmitters with 4–20 mA HART and 1–5 Vdc HART Low Power Protocol Quick Start Guide

Page 1
Quick Start Guide
00825-0100-4690, Rev GD
February 2019
Rosemount™ 2088, 2090P, and 2090F Pressure Transmitters
with 4–20 mA HART® and 1–5 Vdc HART Low Power Protocol
Page 2
Quick Start Guide February 2019
Contents
Mount the transmitter................................... 3
Set the jumpers..............................................7
Connect the wiring and power....................... 9
Verify configuration..................................... 12
Trim the transmitter.................................... 14
Safety instrumented systems.......................16
Product Certifications.................................. 19
Rosemount 2088 and 2090 Declaration of
Conformity.................................................. 40
2 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
Page 3
February 2019 Quick Start Guide

1 Mount the transmitter

1.1 Rosemount™ 2088

Mount directly to the impulse line without using an additional mounting bracket or mount directly to a wall, panel, or two-inch pipe using an optional mounting bracket.

1.2 Rosemount™ 2090P

Mount directly to the process pipe using an existing weld spud, or have a skilled welder install a new weld spud using a TIG welder. Refer to Reference
Manual for complete welding instructions. Improper installation may result in
weld spud distortion. Recommended mounting in upright or horizontal position to allow proper draining of vent.

1.3 Rosemount™ 2090F

Mount directly to the process pipe using a standard sanitary fitting (either a
1.5- or 2-in. Tri Clamp connection). Recommended mounting in upright or horizontal position to allow proper draining of vent.
Figure 1-1: Transmitter Direct Mounting
Do not apply torque directly to the electronics housing. To avoid damage, apply torque only to the hex-shaped process connection.
Rosemount 2088
A. ½–14 NPT female process connection B. Vessel wall C. Weld spud
D. O-ring
E. 1½- or 2-in. Tri Clamp connection
Quick Start Guide 3
Rosemount 2090P Rosemount
2090F
Page 4
Quick Start Guide February 2019
Figure 1-2: Panel and Pipe Mounting
Panel mount Pipe mount

1.4 Liquid flow applications

Transmitter mounting procedure for liquid flow applications.
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
Example

1.5 Gas flow applications

Transmitter mounting procedure for gas flow applications.
Procedure
1. Place taps in the top or side of the line.
2. Mount level or above the taps.
4 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
Page 5
February 2019 Quick Start Guide
Example

1.6 Steam flow applications

Transmitter mounting procedure for steam flow applications.
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
Example
1.7
Quick Start Guide 5

Environmental seal for housing

Thread sealing (PTFE) tape or paste on male threads of conduit is required to provide a water/dust tight conduit seal and meets requirements of NEMA Type 4X, IP66, and IP68. Consult factory if other Ingress Protection ratings are required. For M20 threads, install conduit plugs to full thread engagement or until mechanical resistance is met.
®
Page 6
A
Quick Start Guide February 2019

1.8 Gage transmitter orientation

The low side pressure port (atmospheric reference) on the gage transmitters with aluminum housings are located in the neck of the transmitter, behind the housing. The vent path is 360° around the transmitter between the housing and sensor. (See Figure 1-3.)
Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so that the process can drain away.
Figure 1-3: Gage Low Side Pressure Port
A. Low side pressure port (atmospheric reference)
6 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
Page 7
February 2019 Quick Start Guide

2 Set the jumpers

If alarm and security jumpers are not installed, the transmitter will operate normally with the default alarm condition alarm high and the security off.
Procedure
1. If the transmitter is installed, secure the loop, and remove power.
2. Remove the housing cover opposite the field terminal side. Do not remove the instrument cover in explosive atmospheres when the circuit is live.
3. Ensure full contact with terminal block screw and washer. When using a direct wiring method, wrap wire clockwise to ensure it is in place when tightening the terminal block screw.
Note
The use of a pin or a ferrule wire terminal is not recommended as the connection may be more susceptible to loosening over time or under vibration.
4. Reposition the jumper. Avoid contact with the leads and the terminals. See Figure 2-1 for the location of the jumper and the ON and OFF positions.
5. Reattach the transmitter cover. The cover must be fully engaged to comply with explosion-proof requirements.
Example
Figure 2-1: Rosemount 2088 Transmitter Electronics Board
Without LCD display
Low power without LCD display Low power with LCD display
Quick Start Guide 7
With LCD display
Page 8
Quick Start Guide February 2019
A. Alarm B. Security
8 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
Page 9
February 2019 Quick Start Guide

3 Connect the wiring and power

Use the following steps to wire the transmitter:
Procedure
1. Remove the housing cover on the side marked field terminals.
2. Connect the positive lead to the “PWR/COMM+” terminal, and the negative lead to the “–” terminal.
3. Ensure proper grounding. It is important that the instrument cable shield:
Be trimmed close and insulated from touching the transmitter
housing
Be connected to the next shield if cable is routed through a
junction box
Be connected to a good earth ground at the power supply end
Note
Installation of the transient protection terminal block does not provide transient protection unless the Rosemount 2088 case is properly grounded.
Note
Do not connect the powered signal wiring to the test terminals. Power could damage the test diode in the test connection. Twisted pair cable yields best results. For high EMI/RFI environments, shielded twisted pair cable should be used. Use 24 AWG or larger wire and do not exceed 5,000 ft. (1,500 m).
4. Plug and seal unused conduit connections.
5. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.
6. Replace the housing cover.
Figure 3-1 and Figure 3-2 show wiring connections necessary to power
a Rosemount 2088 Transmitter and enable communications with a hand-held Field Communicator:
Quick Start Guide 9
Page 10
Quick Start Guide February 2019
Example
Figure 3-1: Bench Hook-up Wiring Diagrams (4–20 mA Transmitters)
A. RL ≥ 250Ω B. 24 Vdc supply C. Current meter
Figure 3-2: Field Wiring for Rosemount 2088 — Low Power Option Code N
A. Voltmeter B. Power supply
3.1
10 Rosemount 2088, 2090P, and 2090F Pressure Transmitters

Power supply

The dc power supply (Option S: 10.5–42.4 V and Option N: 6–14 V) should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, and related pieces. The resistance of intrinsic safety barriers, if used, must be included.
Page 11
February 2019 Quick Start Guide
Figure 3-3: Maximum Loop Resistance = 43.5 × (Power Supply Voltage –
10.5)
The Field Communicator requires a minimum loop resistance of 250Ω for communication.
Quick Start Guide 11
Page 12
Quick Start Guide February 2019

4 Verify configuration

A check () indicates the basic configuration parameters. At minimum, these parameters should be verified as part of the configuration and startup procedure.
Function HART Fast Key sequence
Analog Output Alarm 1, 4, 3, 2, 4
Burst Mode Control 1, 4, 3, 3, 3
Burst Option 1, 4, 3, 3, 4
Calibration 1, 2, 3
Damping 1, 3, 5
Date 1, 3, 4, 1
Descriptor 1, 3, 4, 2
Digital To Analog Trim (4–20 mA Output) 1, 2, 3, 2, 1
Disable Local Span/Zero Adjustment 1, 4, 4, 1, 7
Field Device Info 1, 4, 4, 1
Keypad Input 1, 2, 3, 1, 1
Loop Test 1, 2, 2
Lower Range Value 4, 1
Lower Sensor Trim 1, 2, 3, 3, 2
Message 1, 3, 4, 3
Meter Type 1, 3, 6, 1
Number of Requested Preambles 1, 4, 3, 3, 2
Output Trim 1, 2, 3, 2
Percent Range 1, 1, 2
Poll Address 1, 4, 3, 3, 1
Range Values 1, 3, 3
Rerange 1, 2, 3, 1
Scaled D/A Trim (4–20 mA Output) 1, 2, 3, 2, 2
Self Test (Transmitter) 1, 2, 1, 1
Sensor Info 1, 4, 4, 2
Sensor Trim (Full Trim) 1, 2, 3, 3
12 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
Page 13
February 2019 Quick Start Guide
Function HART Fast Key sequence
Sensor Trim Points 1, 2, 3, 3, 5
Status 1, 2, 1, 2
Tag 1, 3, 1
Transmitter Security (Write Protect) 1, 3, 4, 4
Units (Process Variable) 1, 3, 2
Upper Range Value 5, 2
Upper Sensor Trim 1, 2, 3, 3, 3
Zero Trim 1, 2, 3, 3, 1
Quick Start Guide 13
Page 14
Quick Start Guide February 2019

5 Trim the transmitter

Note
Transmitters are shipped fully calibrated per request or by the factory default of full scale (span = upper range limit).

5.1 Zero trim

A zero trim is a single-point adjustment used for compensating mounting position effects. If zero offset is less than 3 percent of true zero, follow the
Using the Field Communicator instructions below. If zero offset is greater than
3 percent of true zero, follow the Using the transmitter zero adjustment
button instructions below to rerange.

5.1.1 Using the Field Communicator

Fast Keys 1, 2, 3, 3, 1
Procedure
1. Vent the transmitter and connect Field Communicator.
2. At the menu, input the HART Fast Key sequence.
3. Follow the commands to perform a zero trim.

5.1.2 Using the transmitter zero adjustment button

Procedure
1. Loosen the certifications label screw and rotate the label to expose the zero adjustment button.
2. Apply the desired pressure for the 4 mA output.
3. Set the 4 mA point by pressing the zero button for two seconds. Verify that the output is 4 mA. The optional LCD display will show “ZERO PASS”.
14 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
Page 15
February 2019 Quick Start Guide
Example
A. Zero adjustment button
Quick Start Guide 15
Page 16
Quick Start Guide February 2019

6 Safety instrumented systems

The following section applies to Rosemount 2088 Transmitters used in SIS applications.
Note
Transmitter output is not safety-rated during the following: configuration changes, multidrop, loop test. Alternative means should be used to ensure process safety during transmitter configuration and maintenance activities.

6.1 Installation

No special installation is required in addition to the standard installation practices outlined in this document. Always ensure a proper seal by installing the electronics housing cover(s) so that metal contacts metal.
The loop must be designed so the terminal voltage does not drop below 10.5 Vdc when the transmitter output is 22.5 mA.
Position the security switch to the “ON” position to prevent accidental or deliberate change of configuration data during normal operation.

6.2 Configuration

Use any HART-compliant master to communicate with and verify configuration of the Rosemount 2088.
User-selected damping will affect the transmitters ability to respond to changes in the applied process. The damping value + response time must not exceed the loop requirements.
Note
DCS or safety logic solver must be configured to match transmitter configuration. Figure 6-1 identifies the two alarm levels available and their operation values. Position the alarm switch to the required HI or LO alarm position.
Figure 6-1: Alarm Levels
Rosemount alarm level
16 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
Page 17
February 2019 Quick Start Guide
Namur alarm level
A. Transmitter Failure, hardware alarm in LO position. B. Transmitter Failure, hardware alarm in HI position.
Note
Some detected faults are indicated on the analog output at a level above high alarm regardless of the alarm switch selection.

6.3 Operation and maintenance

6.3.1 Proof test and inspection

The following proof tests are recommended. Proof test results and corrective actions taken must be documented at Emerson.com/Rosemount/Safety in the event that an error is found in the safety functionality.
Use Table 7-1 to perform a Loop Test, Analog Output Trim, or Sensor Trim. See the Rosemount 2088 Reference Manual for additional information.

6.3.2 Proof test

This proof test will detect 92 percent of DU failures not detected by the Rosemount 2088 automatic diagnostics.
Procedure
1. Bypass the safety PLC and take appropriate action to avoid a false trip.
2. Send a HART command to the transmitter to go to the high alarm current output and verify that the analog current reaches that value.
3. Send a HART command to the transmitter to go to the low alarm current output and verify that the analog current reaches that value.
4. Perform a minimum two-point sensor calibration check using the 4-20 mA range points as the calibration points and verify that the mA output corresponds to the pressure input value.
(3)
5. Restore loop to full operation.
(1) This tests for compliance voltage problems such as a low loop power supply voltage
or increased wiring resistance. This also tests for other possible failures.
(2) This tests for possible quiescent current related failures. (3) If the two-point calibration is performed with electrical instrumentation, this proof
test will not detect any failures of the sensor.
Quick Start Guide 17
(1)
(2)
Page 18
Quick Start Guide February 2019
6. Remove the bypass and otherwise restore normal operation.

6.3.3 Product repair

All failures detected by the transmitter diagnostics or by the proof-test must be reported. Feedback can be submitted electronically at Emerson.com/
Rosemount/Safety.
The Rosemount 2088 is repairable by major component replacement. Follow the instructions in the Rosemount 2088 Reference Manual for additional information.

6.4 Reference

6.4.1 Specifications

The Rosemount 2088 must be operated in accordance to the functional and performance specifications provided in the Rosemount 2088 Reference
Manual.

6.4.2 Failure rate data

The FMEDA report includes failure rates. This report is available at
Emerson.com/Rosemount.

6.4.3 2088 safety failure values

Safety accuracy: 2.0% Safety response time: 1.5 sec
Note
A 2% variation of the transmitter mA output is allowed before a safety trip. Trip values in the DCS or safety logic solver should be derated by 2%.
Safety response time: 1.5 sec

6.4.4 Product life

50 years – based on worst case component wear-out mechanisms – not based on wear-out process wetted materials.
18 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
Page 19
February 2019 Quick Start Guide

7 Product Certifications

7.1 Rosemount™ 2088

Mount directly to the impulse line without using an additional mounting bracket or mount directly to a wall, panel, or two-inch pipe using an optional mounting bracket.

7.1.1 European Directive Information

A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount.

7.1.2 Ordinary Location Certification

As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).

7.1.3 North America

E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate:
Standards:
Markings:
I5 USA Safety (IS) and Nonincendive (NI)
Certificate:
Standards:
Markings:
Special Condition for Safe Use (X):
1. The Rosemount 2088 Transmitter with the transient terminal block
Quick Start Guide 19
1V2A8.AE
FM Class 3600 – 2011, FM, Class 3615 – 2006, FM Class 3616 – 2011, FM Class 3810 – 2005, ANSI/NEMA 250 – 1991
XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T5(– 40 °C ≤ Ta ≤ +85 °C); Factory Sealed; Type 4X
0V9A7.AX
FM Class 3600 – 1998, FM Class 3610 – 2010, FM Class 3611 – 2004, FM Class 3810 – 1989
IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV 1 when connected per Rosemount drawing 02088-1018; NI CL 1, DIV 2, GP A, B, C, D; T4(–40 °C ≤ Ta ≤ +70 °C); Type 4x
(Option code T1) will not pass the 500 Vrms dielectric strength test and this must be taken into account during installation.
Page 20
Quick Start Guide February 2019
C6 Canada Explosionproof, Intrinsic Safety and Division 2, Dust­Ignitionproof
Certificate:
Standards:
Markings:

7.1.4 Europe

ED ATEX Flameproof
Certificate:
Standards:
Markings:
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance
1015441
CAN/CSA C22.2 No. 0-M91 (R2001), CSA Std C22.2 No. 25-1966, CSA Std C22.2 No. 30-M1986, CAN/CSA-C22.2 No. 94-M91, CSA Std C22.2 No. 142-M1987, CAN/CSA-C22.2 No. 157-92, CSA Std C22.2 No. 213-M1987, ANSI­ISA-12.27.01-2003
Explosionproof for Class I, Division 1, Groups B,C and D; Dust­Ignitionproof Class II, Division 1, Groups E, F, G; Class III Division 1; Intrinsically Safe Class I, Division 1 Groups A, B, C, D when connected in accordance with Rosemount drawing 02088-1024, Temperature Code T3C; Class I Division 2 Groups A, B, C and D; Type 4X; Factory Sealed; Single Seal
KEMA97ATEX2378X
EN60079-0:2012 + A11:2013, EN60079-1:2014, EN60079-26:2015
II 1/2 G Ex db IIC T6....T4, Ga/Gb, T6(–60 °C ≤ Ta ≤ +70 °C),
T4/T5(–60 °C ≤ Ta ≤ +80 °C)
and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
I1 ATEX Intrinsic Safety
Certificate:
Standards:
20 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
BAS00ATEX1166X
EN60079-0:2012 + A11:2013, EN60079-11:2012
Page 21
February 2019 Quick Start Guide
Markings:
II 1 G Ex ia IIC T4 Ga (–55 °C ≤ Ta ≤ +70 °C)
Table 7-1: Input Parameters
Parameter HART
Voltage U
Current I
Power P
Capacitance C
i
i
i
i
30 V
200 mA
0.9 W
0.012 μF
Special Condition for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test required by EN60079-11. This must be taken into account when installing the apparatus.
N1 ATEX Type n
Certificate:
Standards:
Markings:
BAS00ATEX3167X
EN60079-0:2012 + A11:2013, EN60079-15:2010
II 3 G Ex nA IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C)
Special Condition for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test required by EN60079-15. This must be taken into account when installing the apparatus.
ND ATEX Dust
Certificate:
Standards:
Markings:
BAS01ATEX1427X
EN60079-0:2012 + A11:2013, EN60079-31:2009
II 1 D Ex t IIIC T50 °C T
60 °C Da
500
Special Conditions for Safe Use (X):
1. The user must ensure the maximum rated voltage and current (36 volts, 24 milliamps, d.c.) are not exceeded. All connection to other apparatus or associated apparatus shall have control over this voltage and current to a category 'ib' circuit.
2. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
3. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.
Quick Start Guide 21
Page 22
Quick Start Guide February 2019
4. Cable entries and blanking plugs must be suitable for the ambient range of the apparatus and capable of withstanding a 7 J impact test.
5. The Rosemount 2088/2090 sensor module must be securely screwed in place to maintain the ingress protection of the enclosure.

7.1.5 International

E7 IECEx Flameproof
Certificate:
Standards:
Markings:
IECEx KEM 06.0021X
IEC 60079-0:2011, IEC60079-1:2014, IEC60079-26:2014
Ex d IIC T6...T4 Ga/Gb, T6(–60 °C ≤ Ta ≤ +70 °C), T4/T5 (–60 °C ≤ Ta ≤ +80 °C)
Special Conditions for Safe Use (x):
1. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
I7 IECEx Intrinsic Safety
Certificate:
Standards:
Markings:
IECEx BAS 12.0071X
IEC60079-0:2011, IEC60079-11:2011
Ex ia IIC T4 Ga (–55 °C ≤ Ta ≤ +70 °C)
Table 7-2: Entity Parameters
Parameter HART
Voltage U
Current I
Power P
Capacitance C
22 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
i
i
i
30 V
200 mA
0.9 W
0.012 μF
i
Page 23
February 2019 Quick Start Guide
Special Conditions for Safe Use (X):
1. When fitted with a transient suppression terminal block, the Rosemount 2088 is incapable of passing the 500 V isolation test. This must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 environment.
N7 IECEx Type n
Certificate:
Standards:
Markings:
IECEx BAS 12.0072X
IEC60079-0:2011, IEC60079-15:2010
Ex nA IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C)
Special Condition for Safe Use (X):
1. When fitted with a transient suppression terminal block, the Rosemount 2088 is incapable of passing the 500 V isolation test. This must be taking into account during installation.
NK IECEx Dust
Certificate:
Standards:
Markings:
IECEx BAS12.0073X
IEC60079-0:2011, IEC60079-31:2008
Ex t IIIC T50 °C T
60 °C Da
500
Table 7-3: Input Parameters
Parameter HART
Voltage U
Current I
i
i
36 V
24 mA
Special Conditions For Safe Use (x):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient range of the apparatus and capable of withstanding a 7 J impact.
Quick Start Guide 23
Page 24
Quick Start Guide February 2019

7.1.6 Brazil

E2 INMETRO Flameproof
Certificate:
Standards:
UL-BR 15.0728X
ABNT NBR IEC60079-0:2008 + Errata 1:2011, ABNT NBR IEC 60079-1:2009 + Errata 1:2011
Markings:
Ex d IIC T* Gb, *T4(–20 °C ≤ Ta ≤ +80 °C), *T6(–20 °C ≤ Ta ≤ +40 °C)
Special Conditions For Safe Use (x):
1. This device contains a thin wall diaphragm less than 1mm thickness that forms a boundary between zone 0 (process connection) and zone 1 (all other parts of the equipment). The model code and data sheet are to be consulted for details of the diaphragm material. Installations, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint Is ordered through a special option code, contact the manufacturer for more information.
I2 INMETRO Intrinsic Safety
Certificate:
Standards:
UL-BR 13.0246X
ABNT NBR IEC60079-0:2008 + Errata 1:2011, ABNT NBR IEC60079-11:2009
Markings:
Ex ia IIC T4 Ga (–55 °C ≤ Ta ≤ +70 °C)
Table 7-4: Input Parameters
Parameter HART
Voltage U
Current I
Power P
Capacitance C
24 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
i
i
i
30 V
200 mA
0.9 W
0.012 μF
i
Page 25
February 2019 Quick Start Guide
Special Conditions for Safe Use (X):
1. When fitted with a transient suppression terminal block, the Rosemount 2088 is incapable of passing the 500 V isolation test. This must be taken into account when installing the equipment.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in Zone 0.

7.1.7 China

E3 China Flameproof
Certificate:
Standards:
Markings:
GYJ15.1505
GB3836.1-2010, GB3836.2-2010
Ex d IIC T4/T6 Gb, T6(–20 °C ≤ Ta ≤ +40 °C), T4(–20 °C ≤ Ta ≤ +80 °C)
Special Conditions For Safe Use (X):
1. The ambient temperature is as follows:
T
a
–20 °C ≤ Ta ≤ 80 °C T4
–20 °C ≤ Ta ≤ 40 °C T6
Temperature class
2. The earth connection facility in the enclosure should be connected reliably.
3. During installation in hazardous location, cable glands, conduits, and blanking plugs, certified by state-appointed inspection bodies with Ex d IIC type of protection, should be used.
4. During installation, use and maintenance in explosive gas atmospheres, observe the warning “Do not open when energized”.
5. During installation, there should be no mixture harm to flameproof housing.
6. End user is not permitted to change any components insides, but to settle the problem in conjunction with manufacturer to avoid damage to the product.
7. Maintenance should be done in non-hazardous location.
8. During installation, use and maintenance of this product, observe the following standards: GB3836.13-2013, GB3836.15-2000, GB3836.16-2006, GB50257-2014.
Quick Start Guide 25
Page 26
Quick Start Guide February 2019
I3 China Intrinsic Safety
Certificate:
Standards:
Markings:
GYJ15.1507
GB3836.1-2010, GB3836.4-2010, GB3836.20-2010
Ex ia IIC T4/T5 Ga
Special Conditions for Safe Use (X):
1. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 environment.
2. This apparatus is not capable of withstanding the 500 V r.m.s. insulation test required by Clause 6.3.12 of GB3836.4-2010.
3. The ambient temperature is:
T
a
–55 °C ≤ Ta ≤ 70 °C T4
Temperature class
4. Intrinsically safe parameters:
Parameter HART
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
30 V
200 mA
0.9 W
0.012 μF
0 mH
5. The product should be used with Ex-certified linear associated apparatus to establish explosion protection system that can be used in explosive gas atmospheres. Wiring and terminals should comply with the instruction manual of the product and associated apparatus.
6. The cables between this product and associated apparatus should be shielded cables (the cables must have insulated shields). The shield has to be grounded reliably in a non-hazardous area.
7. End users are not permitted to change any internal components, but to settle the problem in conjunction with the manufacturer to avoid damage to the product.
8. During installation, use and maintenance of this product, observe the following standards: GB3836.13-2013, GB3836.15-2000, GB3836.16-2006, GB3836.18-2010, GB50257-2014.
26 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
Page 27
February 2019 Quick Start Guide
N3 China Type n
Certificate:
Standards:
Markings:
Special Conditions For Safe Use (X):

7.1.8 Japan

GYJ15.1108X
GB3836.1-2000, GB3836. 8-2003
Ex nA nL IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C)
1. The apparatus is not capable of withstanding the 500 V r.m.s. insulation test required by GB3836.8-2003.
2. The ambient temperature range is –40 °C ≤ Ta ≤ +70 °C.
3. Maximum input voltage: 50 V.
4. Cable glands, conduit or blanking plugs, certified by NEPSI with Ex e or Ex n protection types should be used on external connections and redundant cable entries.
5. Maintenance should be done in non-hazardous location.
6. End users are not permitted to change any internal components, but to settle the problem in conjunction with manufacturer to avoid damage to the product.
7. During installation, use and maintenance of this product, observe the following standards: GB3836.13-2013, GB3836.15-2000, GB3836.16-2006, GB50257-1996.
E4 Japan Flameproof
Certificate:
Markings:
TC20869, TC20870
Ex d IIC T5

7.1.9 Technical Regulations Customs Union (EAC)

EM EAC Flameproof
Certificate:
Markings:
Special Condition for Safe Use (X):
1. See certificate for special conditions.
Quick Start Guide 27
RU C-US.GB05.B.01197
Ga/Gb Ex d IIC T4/T6 X, T4(–40 °C ≤ Ta ≤ +80 °C), T6(–40 °C ≤ T ≤ +40 °C)
a
Page 28
Quick Start Guide February 2019
IM EAC Intrinsically Safe
Certificate:
Markings:
RU C-US.GB05.B.01197
0Ex ia IIC T4 Ga X (–55 °C ≤ Ta ≤ +70 °C)

7.1.10 Combinations

K1 Combination of ED, I1, ND and N1
K2 Combination of E2 and I2
K5 Combination of E5 and I5
K6 Combination of C6, ED and I1
K7 Combination of E7, I7, NK and N7
KB Combination of K5 and C6
KM Combination of EM and IM
KH Combination of ED, I1, K5

7.1.11 Conduit Plugs and Adapters

IECEx Flameproof and Increased Safety
Certificate:
Standards:
Markings:
IECEx FMG 13.0032X
IEC60079-0:2011, IEC60079-1:2007-04, IEC60079-7:2006-07
Ex de IIC Gb
ATEX Flameproof and Increased Safety
Certificate:
Standards:
Markings:
FM13ATEX0076X
EN60079-0:2012, EN60079-1:2007, IEC60079-7:2007
II 2 G Ex de IIC Gb
Table 7-5: Conduit Plug Thread Sizes
Thread Identification mark
M20 × 1.5 – 6g M20
1/2–14 NPT 1/2 NPT
G1/2A G1/2
Table 7-6: Thread Adapter Thread Sizes
Male thread Identification mark
28 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
Page 29
February 2019 Quick Start Guide
Table 7-6: Thread Adapter Thread Sizes
(continued)
M20 × 1.5 – 6H M20
1/2–14 NPT 1/2–14 NPT
3/4–14 NPT 3/4–14 NPT
Female thread Identification mark
M20 × 1.5 – 6H M20
1/2–14 NPT 1/2–14 NPT
G1/2 G1/2
Special Conditions For Safe Use (X):
1. When the thread adapter or blanking plug is used with an enclosure in type of protection increased safety “e” the entry thread shall be suitably sealed in order to maintain the ingress protection rating (IP) of the enclosure.
2. The blanking plug shall not be used with an adapter.
3. Blanking Plug and Threaded Adapter shall be either NPT or Metric thread forms. G1/2 thread forms are only acceptable for existing (legacy) equipment installations.

7.1.12 Additional Certifications

SBS American Bureau of Shipping (ABS) Type Approval
Certificate:
Intended Use:
ABS Rules:
SBV Bureau Veritas (BV) Type Approval
Certificate:
Requirements:
Application:
Quick Start Guide 29
09-HS446883D-3-PDA
Measure gauge or absolute pressure of liquid, gas or vapor applications on ABS classed vessels, marine, and offshore installations.
2014 Steel Vessels Rules 1-1-4/7.7, 1-1-Appendix 3, 4-8-3/1.7, 4-8-3/13.1, 4-8-3/13.3.1 & 13.3.2, 4-8-4/27.5.1
23156/B0 BV
Bureau Veritas Rules for the Classification of Steel Ships
Class notations: AUT-UMS, AUT-CCS, AUT-PORT and AUT­IMS; Pressure transmitter type 2088 cannot be installed on diesel engines
Page 30
Quick Start Guide February 2019
SDN Det Norske Veritas (DNV) Type Approval
Certificate:
Intended Use:
Application:
TAA000004F
DNV GL Rules for Classification - Ships and offshore units
Location classes
Temperature D
Humidity B
Vibration A
EMC B
Enclosure D
SLL Lloyds Register (LR) Type Approval
Certificate:
Application:
11/60002
Environmental categories ENV1, ENV2, ENV3 and ENV5

7.2 Rosemount 2090 Product Certification

Rev 1.6

7.2.1 European Directive Information

A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at EmersonProcess.com/Rosemount.

7.2.2 Ordinary Location Certification

As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).

7.2.3 North America

E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate:
Standards:
Markings:
30 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
1V2A8.AE
FM Class 3600 – 2011, FM Class 3615 – 2006, FM class 3616 – 2011, FM Class 3810 – 2005, ANSI/NEMA 250 – 1991
XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III, DIV 1; T5(–40 °C ≤ Ta ≤ +85 °C); Factory Sealed; Type 4X
Page 31
February 2019 Quick Start Guide
I5 USA Intrinsic Safety (IS) and Nonincendive (NI)
Certificate:
Standards:
0V9A7.AX
FM Class 3600 – 1998, FM Class 3610 – 2010, FM Class 3611 – 2004, FM Class 3810 – 1989
Markings:
IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV 1 when connected per Rosemount drawing 02088-1018; NI CL 1, DIV 2, GP A, B, C, D; T4(–40 °C ≤ Ta ≤ +70 °C); Type 4x
Special Condition for Safe Use (X):
1. The Rosemount 2090 Transmitter with the transient terminal block (option code T1) will not pass the 500 V r.m.s.dielectric strength test and this must be taken into account during installation.
C6 Canada Explosionproof, Intrinsically Safe, and Division 2, Dust­Ignitionproof
Certificate:
Standards:
1015441
CAN/CSA C22.2 No. 0-M91 (R2001), CSA Std C22.2 No. 25-1966, CSA Std C22.2 No. 30-M1986, CAN/CSA-C22.2 No. 94-M91, CSA Std C22.2 No. 142-M1987, CAN/CSA-C22.2 No. 157-92, CSA Std C22.2 No. 213-M1987, ANSI­ISA-12.27.01-2003
Markings:
Explosionproof for Class I, Division 1, Groups B, C and D; Class II, Groups E, F, and G; Class III; Intrinsically Safe Class I, Division 1 when connected in accordance with Rosemount drawing 02088-1024, Temperature Code T3C; Ex ia; Class I Division 2 Groups A, B, C and D; Type 4X; Factory Sealed

7.2.4 Europe

ED ATEX Flameproof
Certificate:
Standards:
Markings:
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance
Quick Start Guide 31
KEMA97ATEX2378X
EN60079-0:2012 + A11:2013, EN60079-1:2014, EN60079-26:2015
II 1/2 G Ex db IIC T6… T4, T6(–60 °C ≤ Ta ≤ +70 °C), T4/T5(–
60 °C ≤ Ta ≤ +80 °C)
and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for
Page 32
Quick Start Guide February 2019
installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
I1 ATEX Intrinsic Safety
Certificate:
Standards:
Markings:
BAS00ATEX1166X
EN60079-0:2012, EN60079-11:2012
II 1 G Ex ia IIC T5/T4 Ga, T5(–55 °C ≤ Ta ≤ +40 °C), T4(–55 °C ≤
Ta ≤ +70 °C)
Table 7-7: Input Parameters
Parameter HART
Voltage U
Current I
Power P
Capacitance C
i
i
i
i
30 V
200 mA
0.9 W
0.012 μF
Special Condition for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test required by EN60079-11. This must be taken into account when installing the apparatus.
N1 ATEX Type n
Certificate:
Standards:
Markings:
BAS00ATEX3167X
EN60079-0:2012, EN60079-15:2010
II 3 G Ex nA IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C)
Special Condition for Safe Use (X):
1. This apparatus is not capable of withstanding the 500 V insulation test that is required by EN60079-15. This must be taken into account when installing the apparatus.
32 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
Page 33
February 2019 Quick Start Guide
ND ATEX Dust
Certificate:
Standards:
Markings:
Special Conditions for Safe Use (X):
1. The user must ensure that the maximum rated voltage and current (36 volts, 24 milliamps, d.c.) are not exceeded. All connection to other apparatus or associated apparatus shall have control over this voltage and current to a category ‘ib’ circuit.
2. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
3. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.
4. Cable entries and blanking plugs must be suitable for the ambient range of the apparatus and capable of withstanding a 7 J impact test.
5. The Rosemount 2090 sensor module must be securely screwed in place to maintain the ingress protection of the enclosure.

7.2.5 International

K7 Combination
IECEx Flameproof
BAS01ATEX1427X
EN60079-0:2012, EN60079-31:2009
Ex t IIIC T 50 °C T
500
60 °C Da
Certificate:
Standards:
Markings:
IECEx KEM 06.0021X
IEC60079-0:2011, IEC60079-1:2014, IEC60079-26:2014
Ex db IIC T6…T4 Ga/Gb, T6(–60 °C ≤ Ta ≤ +70 °C), T4/T5(–60 °C ≤ Ta ≤ +80 °C)
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp
Quick Start Guide 33
Page 34
Quick Start Guide February 2019
cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
IECEx Dust
Certificate:
Standards:
Markings:
IECEx BAS12.0073X
IEC60079-0:2011, IEC60079-31:2008
Ex t IIIC T 50 °C T
500
60 °C Da
Table 7-8: Input Parameters
Parameter HART
Voltage U
Current I
i
i
36 Vdc
24 mA
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient temperature range of the apparatus and capable of withstanding a 7 J impact test.
IECEx Intrinsic Safety
Certificate:
Standards:
Markings:
IECEx BAS 12.0071X
IEC60079-0:2011, IEC60079-11:2011
Ex ia IIC T5/T4 Ga, T5(–55 °C ≤ Ta ≤ +40 °C), T4(–55 °C ≤ Ta ≤ +70 °C)
Table 7-9: Input Parameters
Parameter HART
Voltage U
Current I
Power P
Capacitance C
34 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
i
i
i
i
30 V
200 mA
0.9 W
0.012 μF
Page 35
February 2019 Quick Start Guide
Special Conditions for Safe Use (X):
1. When fitted with a transient suppression terminal block, the Rosemount 2090 is incapable of passing the 500 V isolation test. This must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 environment.
IECEx Type n
Certificate:
Standards:
Markings:
IECEx BAS 12.0072X
IEC60079-0:2011, IEC60079-15:2010
Ex nA IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C)
Special Conditions for Safe Use (X):
1. When fitted with a transient suppression terminal block, the Rosemount 2090 is incapable of passing the 500 V isolation test. This must be taken into account during installation.
NK IECEx Dust
Certificate:
Standards:
Markings:
IECEx BAS12.0073X
IEC60079-0:2011, IEC60079-31:2008
Ex t IIIC T 50 °C T
60 °C Da
500
Table 7-10: Input Parameters
Parameter HART
Voltage U
Current I
i
i
36 Vdc
24 mA
Special Conditions for Safe Use (X):
1. Cable entries must be used which mention the ingress protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient range of the apparatus and capable of withstanding a 7 J impact test.
Quick Start Guide 35
Page 36
Quick Start Guide February 2019

7.2.6 China

E3 China Flameproof
Certificate:
Standards:
Markings:
GYJ15.1506X
GB3836.1-2010, GB3836.2-2010
Ex d IIC T6/T4 Gb, T6(–20 °C ≤ Ta ≤ +40 °C), T4(–20 °C ≤ Ta ≤ +80 °C)
Special Conditions for Safe Use (X):
1. The ambient temperature is as follows:
T
a
–20 °C ≤ Ta ≤ 80 °C T4
–20 °C ≤ Ta ≤ 40 °C T6
Temperature class
2. The earth connection facility in the enclosure should be connected reliably.
3. During installation in hazardous location, cable glands, conduits, and blanking plugs, certified by state-appointed inspection bodies with Ex d IIC type of protection, should be used.
4. During installation, use and maintenance in explosive gas atmospheres, observe the warning “Do not open when energized.”
5. During installation, there should be no mixture harm to flameproof housing.
6. End user is not permitted to change any components insides, but to settle the problem in conjunction with manufacturer to avoid damage to the product.
7. Maintenance should be done in non-hazardous location.
8. During installation, use and maintenance of this product, observe the following standards: GB3836.13-2013, GB3836.15-2000, GB3836.16-2006, GB50257-2014.
I3 China Intrinsic Safety
Certificate:
Standards:
Markings:
36 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
GYJ15.1508X
GB3836.1-2010, GB3836.4-2010, GB3836.20-2010
Ex ia IIC T4/T5 Ga
Page 37
February 2019 Quick Start Guide
Special Conditions for Safe Use (X):
1. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 environment.
2. This apparatus is not capable of withstanding the 500 V r.m.s. insulation test required by Clause 6.3.12 of GB3836.4-2010.
3. The ambient temperature is:
T
a
–55 °C ≤ Ta ≤ 40 °C T5
–55 °C ≤ Ta ≤ 70 °C T4
Temperature class
4. Intrinsically safe parameters:
Parameter HART
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
30 V
200 mA
0.9 W
0.012 μF
0 mH
5. The product should be used with Ex-certified linear associated apparatus to establish explosion protection system that can be used in explosive gas atmospheres. Wiring and terminals should comply with the instruction manual of the product and associated apparatus.
6. The cables between this product and associated apparatus should be shielded cables (the cables must have insulated shields). The shield has to be grounded reliably in a non-hazardous area.
7. End users are not permitted to change any internal components, but to settle the problem in conjunction with the manufacturer to avoid damage to the product.
8. During installation, use and maintenance of this product, observe the following standards: GB3836.13-2013, GB3836.15-2000, GB3836.16-2006, G3836.18-2010, GB50257-2014.
Quick Start Guide 37
Page 38
Quick Start Guide February 2019

7.2.7 Technical Regulations Customs Union (EAC)

EM EAC Flameproof
Certificate:
Markings:
Special Conditions for Safe Use (X):
See certificate for special conditions.
IM EAC Intrinsically Safe
Certificate:
Markings:
Special Conditions for Safe Use (X):
See certificate for special conditions.

7.2.8 Combinations

K1 Combination of ED, I1, ND, and N1
K5 Combination of E5 and I5
K6 Combination of C6, ED, and I1
K7 Combination of E7, I7, NK, and N7
KB Combination of K5 and C6
RU C-US.GB05.B.01197
Ga/Gb Ex d IIC T4/T6 X, T4(-40 °C ≤ Ta ≤ +80 °C), T6(-40 °C ≤ T ≤ +40 °C)
RU C-US.GB05.B.01197
0Ex ia IIC T4 Ga X (-55 °C ≤ Ta ≤ +70 °C)
a
KM Combination of EM and IM
KH Combination of ED, I1, and K5

7.2.9 Conduit plugs and adapters

IECEx Flameproof and Increased Safety
Certificate:
Standards:
Markings:
ATEX Flameproof and Increased Safety
Certificate:
Standards:
38 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
IECEx FMG 13.0032X
IEC60079-0:2011, IEC60079-1:2007, IEC60079-7:2006-2007
Ex de IIC Gb
FM13ATEX0076X
EN60079-0:2012, EN60079-1:2007, EN60079-7:2007
Page 39
February 2019 Quick Start Guide
Markings:
II 2 G Ex de IIC Gb
Table 7-11: Conduit Plug Thread Sizes
Thread Identification mark
M20 × 1.5 M20
1/2–14 NPT 1/2 NPT
G1/2A G1/2
Table 7-12: Thread Adapter Thread Sizes
Male thread Identification mark
M20 × 1.5 – 6H M20
1/2–14 NPT 1/2–14 NPT
3/4–14 NPT 3/4–14 NPT
Female thread Identification mark
M20 × 1.5 – 6H M20
1/2–14 NPT 1/2–14 NPT
PG 13.5 PG 13.5
Special Conditions for Safe Use (X):
1. When the thread adapter or blanking plug is used with an enclosure in type of protection increased safety “e” the entry thread shall be suitably sealed in order to maintain the ingress protection rating (IP) of the enclosure.
2. The blanking plug shall not be used with an adapter.
3. Blanking Plug and Threaded Adapter shall be either NPT or Metric thread forms. G1/2 and PG 13.5 thread forms are only acceptable for existing (legacy) equipment installations.
Quick Start Guide 39
Page 40
EU Declaration of Conformity
No: RMD 1010 Rev. N
Page 1 of 3
We,
Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
declare under our sole responsibility that the product,
Rosemount Pressure Transmitters 3051P, 2051G, 2088, and 2090
manufactured by,
Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
to which this declaration relates, is in conformity with the provisions of the European Union Directives, including the latest amendments, as shown in the attached schedule.
Assumption of conformity is based on the application of the harmonized standards and, when applicable or required, a European Union notified body certification, as shown in the attached schedule.
(signature)
Vice President of Global Quality
(function)
Chris LaPoint
(name)
1-Feb-19; Shakopee, MN USA (date of issue)
Quick Start Guide February 2019
8 Rosemount 2088 and 2090 Declaration of
Conformity
40 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
Page 41
EU Declaration of Conformity
No: RMD 1010 Rev. N
Page 2 of 3
EMC Directive (2014/30/EU)
Harmonized Standards: EN 61326-1:2013, EN 61326-2-3:2013
RoHS Directive (2011/65/EU)
Model 2090F Pressure Transmitter
Harmonized Standard: EN 50581:2012
ATEX Directive (2014/34/EU)
BAS00ATEX1166X - Intrinsic Safety Certificate
Equipment Group II Category 1 G
Ex ia IIC T4 Ga
Harmonized Standards:
EN60079-0:2012 + A11:2013, EN60079-11:2012
BAS00ATEX3167X - Type n Certificate
Equipment Group II Category 3 G
Ex nA IIC T5 Gc
Harmonized Standards:
EN60079-0:2012 + A11:2013, EN60079-15:2010
BAS01ATEX1427X - Dust Certificate
Equipment Group II Category 1 D
Ex t IIIC T50°C T
500
60°C Da
Harmonized Standards:
EN60079-0:2012 + A11:2013
Other Standards:
EN60079-31:2009 (A review against EN60079-31:2014 which is harmonized, shows no significant changes relevant to this equipment so EN60079-31:2009 continues to represent “State of the Art”.)
KEMA97ATEX2378X - Flameproof Certificate
Equipment Group II Category 1/2 G
Ex db IIC T6...T4 Ga/Gb
Harmonized Standards:
EN 60079-0:2012 + A11:2013; EN60079-1:2014; EN60079-26:2015
February 2019 Quick Start Guide
Quick Start Guide 41
Page 42
EU Declaration of Conformity
No: RMD 1010 Rev. N
Page 3 of 3
ATEX Notified Bodies
DEKRA (KEMA) [Notified Body Number: 0344]
Utrechtseweg 310, 6812 AR Arnhem P.O. Box 5185, 6802 ED Arnhem The Netherlands Postbank 6794687
SGS FIMCO OY [Notified Body Number: 0598] P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland
ATEX Notified Body for Quality Assurance
SGS FIMCO OY [Notified Body Number: 0598]
P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland
Quick Start Guide February 2019
42 Rosemount 2088, 2090P, and 2090F Pressure Transmitters
Page 43
February 2019 Quick Start Guide
Quick Start Guide 43
Page 44
*00825-0100-4690*
00825-0100-4690, Rev. GD
Quick Start Guide
February 2019
Global Headquarters
Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com
Latin America Regional Office
Emerson Automation Solutions 1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office
Emerson Automation Solutions 1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com
North America Regional Office
Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRF@Emerson.com
Europe Regional Office
Emerson Automation Solutions Europe GmbH Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465 RFQ.RMTMEA@Emerson.com
Linkedin.com/company/Emerson-
Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/
RosemountMeasurement
Google.com/+RosemountMeasurement
©
2019 Emerson. All rights reserved.