Read this manual before working with the product. For personal and system safety, and for optimum product
performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
See listed technical assistance contacts.
Customer Central
Technical support, quoting, and order-related questions.
United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)
Asia Pacific- 65 777 211
Europe/ Middle East/Africa - 49 (8153) 9390
North American Response Center
Equipment service needs.
1-800-654-7768 (24 hours—includes Canada)
Outside of these areas, contact your local Emerson representative.
CAUTION
The products described in this document are NOT designed for nuclear-qualified applications.
Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate
readings.
For information on Rosemount nuclear-qualified products, contact your local Emerson Sales Representative.
WARNING
Explosions can result in death or serious injury.
Do not remove the transmitter covers in explosive environments when the circuit is live.
Fully engage both transmitter covers to meet explosion-proof requirements.
Before connecting a communicator in an explosive atmosphere, make sure the instruments in the loop are installed in accordance
with intrinsically safe or non-incendive field wiring practices.
Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals.
Process leaks could result in death or serious injury.
Install and tighten all four flange bolts before applying pressure.
Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Replacement equipment or spare parts not approved by Emerson or use as spare parts could reduce the pressure retaining
capabilities of the transmitter and may render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
Improper assembly of manifolds to traditional flange can damage SuperModule™ Platform.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e., bolt hole) but must not contact
sensor module housing.
2
WARNING
SuperModule and electronics housing must have equivalent approval labeling in order to maintain hazardous location
approvals.
When upgrading, verify SuperModule and electronics housing certifications are equivalent. Differences in temperature class
ratings may exist, in which case the complete assembly takes the lowest of the individual component temperature classes (for
example, a T4/T5 rated electronics housing assembled to a T4 rated SuperModule is a T4 rated transmitter.)
Severe changes in the electrical loop may inhibit HART® Communication or the ability to reach alarm values. Therefore, Emerson
cannot absolutely warrant or guarantee that the correct failure alarm level (HIGH or LOW) can be read by the host system at the
time of annunciation.
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could
be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access
by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
C.1 LOI menu tree..........................................................................................................................121
C.2 LOI menu tree - extended menu.............................................................................................. 122
C.3 Number entry..........................................................................................................................123
C.4 Text entry................................................................................................................................124
6Rosemount 2051 Pressure Transmitter
Reference Manual
00809-0100-4107September 2020
Introduction
1Introduction
1.1Using this manual
The sections in this manual provides information on configuring, troubleshooting,
operating, and maintaining the Rosemount 2051 Pressure Transmitter specifically with
HART® Revision 5 and 7 Selectable Protocol.
The sections in this manual are organized as follows:
• Configuration provides instruction on configuration of the tranmitter, information on
software functions, configuration parameters, and other variables are also included.
• Hardware Installation contains mechanical installation instructions, and field upgrade
options.
• Electrical Installation contains electrical installation instructions, and field upgrade
options.
• Operation and Maintenance provides detailed information on calibrating and changing
HART® Revisions.
• Troubleshooting provides troubleshooting techniques for the most common operating
problems.
• Safety Instrumented Systems Requirements provides identification, installation,
configuration, operation and maintenance, and inspection information for Safety
Instrumented Systems.
• Reference data supplies links to updated specifications, ordering information, intrinsic
safety approval information, European ATEX directive information, and approval
drawings.
• Field Communicator Menu Trees and Fast Keys provides full menu trees and
abbreviated Fast Key sequences for commisioning tasks.
• Local Operator Interface (LOI) Menu provides detailed LOI menu trees.
1.2Models covered
The following 2051 Transmitters are covered by this manual:
• Rosemount 2051C Coplanar™ Pressure Transmitter
— Measures differential and gauge pressure up to 2000 psi (137.9 bar).
• Rosemount 2051T In-Line Pressure Transmitter
— Measures gauge/absolute pressure up to 10000 psi (689.5 bar).
• Rosemount 2051L Level Transmitter
— Measures level and specific gravity up to 300 psi (20.7 bar).
• Rosemount 2051CF Series Flowmeter
— Measures flow in line sizes from -in. (15mm) to 96-in. (2400 mm).
Reference Manual7
IntroductionReference Manual
September 202000809-0100-4107
Note
For Rosemount 2051 with FOUNDATION Fieldbus, see Reference Manual. For Rosemount
2051 with PROFIBUS PA Protocol, see Reference Manual.
1.3HART installation flowchart
Figure 1-1: HART Installation Flowchart
8Rosemount 2051 Pressure Transmitter
Reference ManualIntroduction
00809-0100-4107September 2020
1.4Transmitter overview
The Rosemount 2051C Coplanar™ design is offered for Differential Pressure (DP) and
Gauge Pressure (GP) measurements. The Rosemount 2051C utilizes capacitance sensor
technology for DP and GP measurements. The Rosemount 2051T utilizes piezoresistive
sensor technology for AP and GP measurements.
The major components of the transmitter are the sensor module and the electronics
housing. The sensor module contains the oil filled sensor system (isolating diaphragm, oil
fill system, and sensor) and the sensor electronics. The sensor electronics are installed
within the sensor module and include a temperature sensor, a memory module, and the
analog-to-digital signal converter (A/D converter). The electrical signals from the sensor
module are transmitted to the output electronics in the electronics housing. The
electronics housing contains the output electronics board, the optional external
configuration buttons, and the terminal block. The basic block diagram of the transmitter
is illustrated in Figure 1-3.
When pressure is applied to the isolating diaphragm, the oil deflects the sensor which then
changes its capacitance or voltage signal. This signal is then changed to a digital signal by
the Signal Processing. The microprocessor then takes the signals from the Signal
Processing and calculates the correct output of the transmitter. This signal is then sent to
the D/A converter, which converts the signal back to the analog signal, then superimposes
the HART® signal on the 4–20 mA output.
An optional LCD display can be ordered that connects directly to the interface board which
maintains direct access to the signal terminals. The display indicates output and
abbreviated diagnostic messages. A glass display cover is provided. For 4-20 mA HART
output, the LCD display features a two-line display. The first line displays the actual
measured value, the second line of six characters displays the engineering units. The LCD
display can also display diagnostic messages.
Note
LCD display utilizes a 5 × 6 character display and can display output and diagnostic
messages. The LOI display uses an 8 × 6 character display and can display output,
diagnostic messages, and LOI menu screens. The LOI display comes with two buttons
mounted on the front of the display board. See Figure 1-2.
Figure 1-2: LCD/LOI display
LCD display
LOI display
Reference Manual9
IntroductionReference Manual
September 202000809-0100-4107
Figure 1-3: Block Diagram Of Operation
A. Sensor Module
B. Electronics Board
C. 4-20 mA Signal to Control System
D. Field Communicator
1.5Product recycling/disposal
Recycling of equipment and packaging should be taken into consideration and disposed of
in accordance with local and national legislation/regulations.
10Rosemount 2051 Pressure Transmitter
Reference ManualConfiguration
00809-0100-4107September 2020
2Configuration
2.1Overview
This section contains information on commissioning and tasks that should be performed
on the bench prior to installation, as well as tasks performed after installation as described
in Performing transmitter tests.
Field Communicator, AMS Device Manager, and Local Operator Interface (LOI) instructions
are given to perform configuration functions. For convenience, Field Communicator Fast
Key sequences are labeled “Fast Keys,” and abbreviated LOI menus are provided for each
function below.
Full Field Communicator menu trees and Fast Key sequences are available in Field
Communicator Menu Trees and Fast Keys. LOI menu trees are available in Local Operator
Interface (LOI) Menu.
2.2Safety messages
Procedures and instructions in this section may require special precautions to ensure the
safety of the personnel performing the operation. Refer to the following safety messages
before performing an operation preceded by this symbol.
WARNING
Explosions
Explosions could result in death or serious injury.
Review the approvals section of this manual for any restrictions associated with a safe
installation.
Before connecting a communicator in an explosive atmosphere, ensure the instruments in
the segment are installed in accordance with intrinsically safe or non-incendive field wiring
practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when
power is applied to the unit.
Process leaks
Process leaks may cause harm or result in death.
Install and tighten process connectors before applying pressure.
Electrical shocks
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals.High voltage that my be present on leads can
cause electrical shock.
Reference Manual11
ConfigurationReference Manual
September 202000809-0100-4107
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare
parts could reduce the pressure retaining capabilities of the transmitter and may
render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
Improper assembly of manifolds
Improper assembly of manifolds to traditional flange can damage the SuperModule
Platform.
For safe assembly of manifold to traditional flange, bolts must break black plane of flange
web (i.e., bolt hole) but must not contact module housing.
Physical access
Unauthorized personnel may potentially cause significant damage to and/or
misconfiguration of end users’ equipment. This could be intentional or unintentional and
needs to be protected against.
™
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access by unauthorized personnel to protect end
users’ assets. This is true for all systems used within the facility.
2.3System readiness
• If using HART®-based control or asset management systems, confirm the HART
capability of such systems prior to commissioning and installation. Not all systems are
capable of communicating with HART revision 7 devices.
• For instructions on how to change the HART revision of your transmitter, see Switching
HART revision.
2.3.1
Confirm correct Device Driver
Procedure
1. Verify the latest Device Driver (DD/DTM™) is loaded on your systems to ensure
proper communications.
2. Reference Emerson.com or FieldCommGroup.org for the latest DD.
3. In the browse by member dropdown menu, select Rosemount business unit of
Emerson.
4. Select desired Product.
a) Within Table 2-1, use the HART Universal Revision and Device Revision
numbers to find the correct Device Driver
12Rosemount 2051 Pressure Transmitter
Reference ManualConfiguration
00809-0100-4107September 2020
Example
Table 2-1: Rosemount 2051 Device Revisions and Files
Software
release
date
NAMUR
software
revision
August
2012
January
1998
(1) NAMUR Software Revision is located on the hardware tag of the device
(2) HART Software Revision can be read using a HART capable configuration tool.
(3) Device Driver file names use Device and DD Revision, e.g. 10_01. HART Protocol is designed to
enable legacy device driver revisions to continue to communicate with new HART devices. To
access new functionality, the new Device Driver must be downloaded. It is recommended to
download new Device Driver files to ensure full functionality.
Set all transmitter hardware adjustments during commissioning to avoid exposing the
transmitter electronics to the plant environment after installation.
The transmitter can be configured either before or after installation. Configuring the
transmitter on the bench using either a Field Communicator, AMS Device Manager, or LOI
ensures all transmitter components are in working order prior to installation. Verify that
the security switch is set in the unlock ( ) position in order to proceed with configuration.
See Figure 4-2 for switch location.
2.4.1
Configuring on the bench
To configure on the bench, required equipment includes a power supply, and a Field
Communicator, AMS Device Manager, or an LOI (option M4). Wire equipment as shown in
Figure 2-1. To ensure successful HART® communication, a resistance of at least 250 Ωs
must be present between the transmitter and the power supply, see Power supply for
details. Connect the Field Communicator leads to the terminals labeled “COMM” on the
terminal block or 1–5 V configuration, wire as shown in Figure 2-1. The Field
Communicator is connected to the terminals labeled VOUT/COMM.
Reference Manual13
ConfigurationReference Manual
September 202000809-0100-4107
Figure 2-1: Wiring the Transmitter (4–20 mA HART)
A. Vdc supply
B. R L ≥ 250 (necessary for HART communication only)
2.4.2
Configuration tools
Figure 2-2: Wiring the Transmitter (1–5 Vdc Low Power)
A. DC power supply
B. Voltmeter
Configuring with a Field Communicator
There are two interfaces available with the Field Communicator: Traditional and
Dashboard interfaces. All steps using a Field Communicator will be described using
Dashboard interfaces. HART® shows the Device Dashboard interface. As stated in System
readiness, it is critical that the latest DD’s are loaded into the Field Communicator. Visit
Emerson.com or FieldCommGroup.org to download latest DD library.
Field Communicator menu trees and Fast Keys are available in Field Communicator Menu
Trees and Fast Keys.
14Rosemount 2051 Pressure Transmitter
SAVE
1. Overview
2. Configure
3. Service Tools
2088 FT 45B
Online
Reference ManualConfiguration
00809-0100-4107September 2020
Figure 2-3: Device Dashboard
Configuring with AMS Device Manager
Full configuration capability with AMS Device Manager requires loading the most current
Device Descriptor (DD) for this device. Download the latest DD at Emerson.com or
FieldCommGroup.org.
Note
All steps using AMS Device Manager will be described using version 11.5.
Configuring with a LOI
The LOI requires option code M4 to be ordered. To activate the LOI push either
configuration button. Configuration buttons are located on the LCD display (must remove
housing cover to access), or underneath the top tag of the transmitter. See Table 2-2 for
configuration button functionality and Figure 2-4 for configuration button location. When
using the LOI for configuration, several features require multiple screens for a successful
configuration. Data entered will be saved on a screen-by-screen basis; the LOI will indicate
this by flashing “SAVED” on the LCD display each time.
LOI menu trees are available in Local Operator Interface (LOI) Menu.
Reference Manual15
ConfigurationReference Manual
September 202000809-0100-4107
Figure 2-4: LOI Configuration Buttons
A. Internal configuration buttons B. External configuration buttons
Table 2-2: LOI Button Operation
Button
LeftNoSCROLL
RightYesENTER
2.4.3Setting the loop to manual
Whenever sending or requesting data that would disrupt the loop or change the output of
the transmitter, set the process application loop to manual control. The Field
Communicator, AMS Device Manager, or the LOI will prompt you to set the loop to manual
when necessary. The prompt is only a reminder; acknowledging this prompt does not set
the loop to manual. It is necessary to set the loop to manual control as a separate
operation.
2.5Verify configuration
It is recommended that various configuration parameters are verified prior to installation
into the process. The various parameters are detailed out for each configuration tool.
Depending on what configuration tool(s) are available follow the steps listed relevant to
each tool.
16Rosemount 2051 Pressure Transmitter
Reference ManualConfiguration
00809-0100-4107September 2020
2.5.1Verifying configuration with Field Communicator
Configuration parameters listed in Table 2-3 are to be reviewed prior to transmitter
installation. A Full list of configuration parameters that can be reviewed and configured
using a Field Communicator are located in Field Communicator Menu Trees and Fast Keys.
Fast key sequences for the latest DD are shown in Table 2-3. For Fast Key sequences for
legacy DD's contact your local Emerson Representative.
Table 2-3: Device Dashboard Fast Key sequence
From the HOME screen, enter the Fast Key sequences listed
FunctionFast Key sequence
HART 7HART 5
Alarm and Saturation Levels2, 2, 2, 52, 2, 2, 5
Damping2, 2, 1, 1, 52, 2, 1, 1, 5
Primary Variable2, 1, 1, 4, 12, 1, 1, 4, 1
Range Values2, 1, 1, 42, 1, 1, 4
Tag2, 2, 7, 1, 12, 2, 7, 1, 1
Transfer Function2, 2, 1, 1, 62, 2, 1, 1, 6
Units2, 2, 1, 1, 42, 2, 1, 1, 4
2.5.2Verifying configuration with AMS Device Manager
Right select on the device and select Configuration Properties from the menu. Navigate
the tabs to review the transmitter configuration data.
2.5.3
Verifying configuration with LOI
Press any configuration button to activate the LOI. Select VIEW CONFIG to review the
below parameters. Use the configuration buttons to navigate through the menu. The
parameters to be reviewed prior to installation include:
• Tag
• Units
• Transfer function
• Alarm and saturation levels
• Primary variable
• Range values
• Damping
Reference Manual17
ConfigurationReference Manual
September 202000809-0100-4107
2.5.4Verifying process variables configuration
This section describes how to verify that the correct process variables are selected.
Verifying process variables with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys3, 2, 1
Verifying process variables with AMS Device Manager
Procedure
1. Right click the device and select Overview from the menu.
2. Select the All Variables button to display the primary, secondary, tertiary and
quaternary variables.
2.6Basic setup of the transmitter
This section goes through the necessary steps for basic setup of a pressure transmitter.
When installing in DP level or DP flow applications, refer to Configuring scaled variable for
setup instructions.
2.6.1
Setting pressure units
The pressure unit command sets the unit of measure for the reported pressure.
Setting pressure units with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Setting pressure units with AMS Device Manager
Procedure
1. Right select the device and select Configure.
2. Select Manual Setup and select desired units from Pressure Units dropdown menu.
3. Select Send when complete.
2, 2, 1, 1, 4
Setting pressure units with a LOI
Follow Figure 2-5 to select desired pressure and temperature units. Use the SCROLL and
ENTER buttons to select desired unit. Save by selecting SAVE as indicated on the LCD
display screen.
The transmitter has two output settings: Linear and square root. As shown in Figure 2-7,
activating the square root options makes analog output proportional to flow, and includes
a fixed low flow cutoff at five percent.
However, for DP Flow and DP Level applications it is recommended to use scaled variable.
Refer to Configuring scaled variable for setup instructions.
Setting transmitter output with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 1, 1, 6
Setting transmitter output with AMS Device Manager
Procedure
1. Right click on the device and select Configure.
2. Select Manual Setup and choose output type from analog output transfer function
and select Send.
3. Carefully read the warning and select Yes if it is safe to apply the changes.
Setting transmitter output with a LOI
Reference Figure 2-6 to select either linear or square root transfer function using the LOI.
Reference Manual19
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT
VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
TRANSFER FUNCT
LINEAR TRANSFER
FUNCTION
SQR ROOT TRANSFER
FUNCTION
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
ConfigurationReference Manual
September 202000809-0100-4107
Figure 2-6: Set Output with LOI
Figure 2-7: 4–20 mA HART Square Root Output Transition Point
A. Square root curve
B. Five percent transition point
C. Four percent transition point
2.6.3
Rerange the transmitter
The range values command sets each of the lower and upper range analog values (4 and
20 mA/1–5 Vdc points) to a pressure. The lower range point represents 0 percent of range
and the upper range point represents 100 percent of range. In practice, the transmitter
range values may be changed as often as necessary to reflect changing process
requirements.
Select from one of the methods below to rerange the transmitter. Each method is unique;
20Rosemount 2051 Pressure Transmitter
examine all options closely before deciding which method works best for your process.
• Rerange by manually setting range points with a Field Communicator, AMS Device
Manager, or LOI.
RERANGE
ENTER VALUES
APPLY VALUES
BACK TO MENU
EXIT MENU
ENTER VALUES
LRV
URV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
Reference ManualConfiguration
00809-0100-4107September 2020
• Rerange with a pressure input source and a Field Communicator, AMS Device Manager,
LOI, or local zero and span buttons.
Manually rerange the transmitter by entering range points
Entering range points with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys2, 2, 2, 1
Entering range points with AMS Device Manager
Procedure
1. Right select the device and select Configure.
2. Select Manual Setup and select Analog Output.
3. Enter upper and lower range values in the Range Limits box and click Send.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
Entering range points with a LOI
Reference Figure 2-8 to rerange the transmitter using the LOI. Enter values using SCROLL
and ENTER buttons.
Figure 2-8: Rerange with LOI
Rerange the transmitter with applied pressure source
Reranging using an applied pressure source is a way of reranging the transmitter without
entering specific 4 and 20 mA (1–5 Vdc) points.
Rerange with an applied pressure source using a Field Communicator
From the HOME screen, enter the Fast Key sequence
Device Dashboard Fast Keys
Rerange with an applied pressure source using AMS Device Manager
2, 2, 2, 2
Reference Manual21
Procedure
1. Right select the device, select Configure.
2. Select the Analog Output tab.
3. Select Range by Applying Pressure button and follow the screen prompts range the
transmitter.
RERANGE
ENTER VALUES
APPLY VALUES
BACK TO MENU
EXIT MENU
APPLY VALUES
LRV
URV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
ConfigurationReference Manual
September 202000809-0100-4107
Rerange with an applied pressure source using a Field Communicator
Use Figure 2-9 to manually rerange the device using an applied pressure source with
an LOI.
Figure 2-9: Rerange with Applied Pressure Using LOI
Rerange with an applied pressure source using local zero and span
buttons
If ordered, local zero and span buttons (option code D4) can be used to rerange the
transmitter with an applied pressure. Refer to Figure 2-10 for analog zero and span button
location.
To rerange the transmitter using the span and zero buttons, perform the following
procedure:
Procedure
1. Loosen the screw holding the top tag of the transmitter housing. Rotate the label to
expose the zero and span buttons.
2. Confirm device has local zero and span buttons by verifying blue retainer under the
tag.
3. Apply transmitter pressure.
4. Rerange the transmitter.
a) To change the zero (4 mA/1 V point) while maintaining the span: press and
hold zero button for at least two seconds then release.
b) To change the span (20 mA/5 V point) while maintaining the zero point:
press and hold the span button for at least two seconds and then release.
Example
Note
4 mA and 20 mA points must maintain the minimum span.
22Rosemount 2051 Pressure Transmitter
Reference ManualConfiguration
00809-0100-4107September 2020
Figure 2-10: Analog Zero and Span Buttons
A. Zero and span buttons
Note
• If the transmitter security is on, adjustments to the zero and span will not be able to be
made. Refer to Configure security and simulation for security information.
2.6.4
• The span is maintained when the 4 mA/1 V point is set. The span changes when the 20
mA 5 V point is set. If the lower range point is set to a value that causes the upper range
point to exceed the sensor limit, the upper range point is automatically set to the
sensor limit, and the span is adjusted accordingly.
• Regardless of the range points, the transmitter measure and report all readings within
the digital limits of the sensor. For example, if the 4 and 20 mA(1–5 Vdc) points are set
to 0 and 10 inH2O, and the transmitter detects a pressure of 25 inH2O, it digitally
outputs the 25 inH2O reading and a 250 percent of range reading.
Damping
The damping command changes the response time of the transmitter; higher values can
smooth variations in output readings caused by rapid input changes. Determine the
appropriate damping setting based on the necessary response time, signal stability, and
other requirements of the loop dynamics within your system. The damping command
utilizes floating point configuration allowing the user to input any damping value within
0.0–60.0 seconds.
Damping with a Field Communicator
Procedure
1. From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2. Enter desired Damping Value and select APPLY.
Reference Manual23
2, 2, 1, 1, 5
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
ConfigurationReference Manual
September 202000809-0100-4107
Damping with AMS Device Manager
Procedure
1. Right select the device and select Configure.
2. Select Manual Setup.
3. Within the Pressure Setup box, enter desired damping value and click Send.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
Damping with a LOI
Reference Figure 2-11 to enter damping values using an LOI.
Figure 2-11: Damping with LOI
2.7Configuring the LCD display
2.7.1
24Rosemount 2051 Pressure Transmitter
The LCD display configuration command allows customization of the LCD display to suit
application requirements. The LCD display will alternate between the selected items.
• Pressure Units
• % of Range
• Scaled Variable
• Sensor Temperature
• mA/Vdc Output
In the following instructions, the LCD display can also be configured to display
configuration information during the device startup. Select Review Parameters at Startup
to enable or disable this functionality.
Reference Configuring the LCD display with LOI for image of LCD display screen.
Configuring LCD display with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 4
DISPLAY
PRESS (on/off)
SCALED (on/off)
TEMP (on/off)
%RANGE (on/off)
ANALOG (on/off)
STRTUP (on/off)
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
Reference ManualConfiguration
00809-0100-4107September 2020
2.7.2Configuring LCD display with AMS Device Manager
Procedure
1. Right select on the device and select Configure.
2. Select Manual Setup, select the Display tab.
3. Select desired display options and click Send.
2.7.3Configuring LCD display with a LOI
Refer to Figure 2-12 for LCD display configuration using a LOI.
Figure 2-12: Display with LOI
2.8Detailed transmitter setup
2.8.1Configuring alarm and saturation levels
Reference Manual25
In normal operation, the transmitter will drive the output in response to pressure from the
lower to upper saturation points. If the pressure goes outside the sensor limits, or if the
output would be beyond the saturation points, the output will be limited to the associated
saturation point.
The transmitter automatically and continuously performs self-diagnostic routines. If the
self-diagnostic routines detect a failure, the transmitter drives the output to configured
alarm and value based on the position of the alarm switch. See Setting transmitter alarm.
Table 2-4: Rosemount Alarm and Saturation Values
Level4–20 mA (1–5 Vdc) saturation4–20 mA (1–5 Vdc alarm
Low3.90 mA (0.97 V)≤ 3.75 mA (0.95 V)
High20.80 mA (5.20 V)≥ 21.75 mA (5.40 V)
Table 2-5: NAMUR-Compliant Alarm and Saturation Values
Level4–20 mA (1–5 Vdc) saturation4–20 mA (1–5 Vdc) alarm
Low3.80 mA (0.95 V)≤ 3.60 mA (0.90 V) (.90 –.95 V)
High20.50 mA (5.13 V)≥22.50 mA (5.63 V) (5.05 –5.75 V)
ConfigurationReference Manual
September 202000809-0100-4107
Table 2-6: Custom Alarm and Saturation Values
Level4–20 mA (1–5 Vdc) saturation4–20 mA (1–5 Vdc) alarm
Low3.70 mA– 3.90 mA (.90 –.95 V)3.60–3.80 mA (.90 –.95 V)
High20.10 mA –22.90 mA (5.025 –5.725 V)20.20 mA – 23.00 mA (5.05 –5.75 V)
Failure mode alarm and saturation levels can be configured using a Field Communicator,
AMS Device Manager, and the LOI. The following limitations exist for custom levels:
• Low alarm level must be less than the low saturation level
• High alarm level must be higher than the high saturation level
• Alarm and saturation levels must be separated by at least 0.1 mA (0.025 Vdc)
The configuration tool will provide an error message if the configuration rule is violated.
Note
Transmitters set to HART® multidrop mode send all saturation and alarm information
digitally; saturation and alarm conditions will not affect the analog output. See also
Establishing multidrop communication.
Configuring alarm and saturation levels using a Field
Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 2, 5
Configuring alarm and saturation levels with AMS Device
Manager
Procedure
1. Right select on the device, and select Configure.
2. Select Configure Alarm and Saturation Levels button.
3. Follow screen prompts to configure Alarm and Saturation Levels.
Configuring alarm and saturation levels using LOI
Refer to Figure 2-13 for instructions to configure alarm and saturation levels.
26Rosemount 2051 Pressure Transmitter
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
ALARM SAT VALUES
ROSEMOUNT VALUES
NAMUR VALUES
OTHER VALUES
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
Reference ManualConfiguration
00809-0100-4107September 2020
Figure 2-13: Configuring Alarm and Saturation with LOI
2.8.2Configuring scaled variable
The Scaled Variable configuration allows the user to create a relationship/conversion
between the pressure units and user-defined/custom units. There are two use cases for
Scaled Variable. The first use case is to allow custom units to be displayed on the
transmitter's LCD/LOI display. The second use case is to allow custom units to drive the
transmitter's 4–20 mA (1–5 Vdc) output.
If the user desires custom units to drive the 4–20 mA (1–5 Vdc) output, Scaled Variable
must be re-mapped as the primary variable. Refer to Re-mapping device variables.
The Scaled Variable configuration defines the following items:
• Scaled Variable units - custom units to be displayed.
• Scaled data options - defines the transfer function for the application (linear and square
root)
• Pressure value position 1 - lower known value point with consideration of linear offset.
• Scaled Variable value position 1 - custom unit equivalent to the lower known value
point.
• Pressure value position 2 - upper known value point
• Scaled Variable value position 2 - custom unit equivalent to the upper known value
point
• Linear offset - the value required to zero out pressures effecting the desired pressure
reading.
• Low flow cutoff - point at which output is driven to zero to prevent problems caused by
process noise. It is highly recommended to use the low flow cutoff function in order to
have a stable output and avoid problems due to process noise at a low flow or no flow
condition. A low flow cutoff value that is practical for the flow element in the
application should be entered.
Reference Manual27
Configuring scaled variable using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 1, 4, 7
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
SCALED VARIAB
VIEW SCALED
CONFIG SCALED
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
ConfigurationReference Manual
September 202000809-0100-4107
Procedure
Follow the screen prompts to configure Scaled Variable.
a) When configuring for level, select Linear under Select Scaled data options.
b) When configuring for flow, select Square Root under Select Scaled data options.
Configuring scaled variable using AMS Device Manager
Procedure
1. Right select on the device and, select Configure.
2. Select the Scaled Variable tab and select the Scaled Variable button.
3. Follow screen prompts to configure Scaled Variable
a) When configuring for level applications, select Linear under Select Scaled
data options.
b) When configuring for flow applications, select Square Root under Select
Scaled data options.
Configuring scaled variable using a LOI
Refer to Figure 2-14 for instructions to configure Scaled Variable using a LOI.
Figure 2-14: Configuring Scaled Variable Using a LOI
28Rosemount 2051 Pressure Transmitter
H
L
230-in.
200-in.
12-in.
0.94 sg
Reference ManualConfiguration
00809-0100-4107September 2020
DP level example
Figure 2-15: Example Tank
A differential transmitter is used in a level application. Once installed on an empty tank
and taps vented, the process variable reading is –209.4 inH2O. The process variable
reading is the head pressure created by fill fluid in the capillary. Based on Table 2-7, the
scaled variable configuration would be as follows:
Table 2-7: Scaled Variable Configuration for Tank Application
Scaled variable units:inch
Scaled data 13:linear
Pressure value position 1:0 inH2O
Scaled Variable position 1:12-in.
Pressure value position 2:188 inH2O
Scaled Variable position 2:212-in.
Linear offset:–209.4 inH2O
DP flow example
A differential pressure transmitter is used in conjunction with an orifice plate in a flow
application where the differential pressure at full scale flow is 125 inH2O. In this particular
application, the flow rate at full scale flow is 20,000 gallons of water per hour. It is highly
recommended to use the low flow cutoff function in order to have a stable output and
avoid problems due to process noise at a low flow or no flow condition. A low flow cutoff
value that is practical for the flow element in the application should be entered. In this
Reference Manual29
ConfigurationReference Manual
September 202000809-0100-4107
particular example, the low flow cutoff value is 1000 gallons of water per hour. Based on
this information, the Scaled Variable configuration would be as follows:
Table 2-8: Scaled Variable Configuration for Flow Application
Scaled Variable units:gal/h
Scaled data options:square root
Pressure value position 2:125 inH2O
Scaled Variable position 2:20,000 gal/h
Low Flow Cutoff:1000 gal/h
Note
Pressure value position 1 and Scaled Variable position 1 are always set to zero for a flow
application. No configuration of these values is required.
2.8.3
Re-mapping device variables
The re-mapping function allows the transmitter primary, secondary, tertiary, and
quaternary variables (PV, 2V, 3V, and 4V) to be configured as desired. The PV can be
remapped with a Field Communicator, AMS Device Manager, or a LOI. Variables (2V, 3V,
and 4V) can only be re-mapped via Field Communicator or AMS Device Manager.
Note
The variable assigned to the primary variable drives the 4–20 mA (1–5 Vdc) output. This
value can be selected as Pressure or Scaled Variable. The 2, 3, and 4 variables only apply if
HART® burst mode is being used.
Re-mapping using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Fast Keys
Re-mapping using AMS Device Manager
Procedure
1. Right select the device and select Configure.
2. Select Manual Setup and click on the HART tab.
3. Assign Primary, secondary, tertiary, and quaternary variables under Variable
Mapping.
4. Select Send.
5. Carefully read the warning and select Yes if it is safe to apply the changes.
2, 1, 1, 3
Re-mapping using LOI
Refer to Figure 2-16 for instructions to remap the primary variable using a LOI.
30Rosemount 2051 Pressure Transmitter
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
EXTENDED MEN U
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO
MENU
EXIT MENU
Reference ManualConfiguration
00809-0100-4107September 2020
Figure 2-16: Re-mapping with LOI
2.9Performing transmitter tests
2.9.1Verifying alarm level
2.9.2
If the transmitter is repaired or replaced, verify the transmitter alarm level before
returning the transmitter to service. This is useful in testing the reaction of the control
system to a transmitter in an alarm state. Thus ensuring the control system recognizes the
alarm when activated. To verify the transmitter alarm values, perform a loop test and set
the transmitter output to the alarm value see Configuring alarm and saturation levels.
Note
Before returning transmitter to service, verify security switch is set to the correct position.
Refer to Verify configuration.
Performing an analog loop test
The analog loop test command verifies the output of the transmitter, the integrity of the
loop, and the operations of any recorders or similar devices installed in the loop. It is
recommended that the 4–20 mA (1–5 Vdc) points in addition to alarm levels when
installing, repairing, or replacing a transmitter.
The host system may provide a current measurement for the 4–20 mA (1–5 Vdc) HART
output. If not, connect a reference meter to the transmitter by either connecting the
meter to the test terminals on the terminal block, or shunting transmitter power through
the meter at some point in the loop. For 1–5 V output, voltage measurement is directly
measured from Vout to (–) terminals.
Performing an analog loop test using a Field Communicator
®
Reference Manual31
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
3, 5, 1
ConfigurationReference Manual
September 202000809-0100-4107
Performing an analog loop test using AMS Device Manager
Procedure
1. Right select on the device and, within the Methods drop down menu, move cursor
over Diagnostics and Test. In the Diagnostics and Test drop down menu select LoopTest.
2. Select Next after setting the control loop to manual.
3. Follow Screen prompts to perform a Loop Test.
4. Select Finish to acknowledge the method is complete.
Performing analog loop test using a LOI
To perform an analog loop test using the LOI, the 4 mA (1 V), 20 mA (5 V), and custom mA
point may be set manually. Reference Figure 2-17 for instructions on how to perform a
transmitter loop test using an LOI.
Figure 2-17: Performing an Analog Loop Test Using an LOI
2.9.3
Simulate device variables
It is possible to temporarily set the Pressure, Sensor Temperature, or Scaled Variable to a
user-defined fixed value for testing purposes. Once the simulated variable method is left,
the process variable will be automatically returned to a live measurement. Simulate device
variables is only available in HART® Revision 7 mode.
Simulate digital signal with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
3, 5
Simulate digital signal with AMS Device Manager
Procedure
1. Right select on the device and select Service Tools.
2. Select Simulate.
3. Under Device Variables select a digital value to simulate.
a) Pressure
32Rosemount 2051 Pressure Transmitter
Reference ManualConfiguration
00809-0100-4107September 2020
b) Sensor Temperature
c) Scaled Variable
4. Follow the screen prompts to simulate selected digital value.
2.10Configuring burst mode
Burst mode is compatible with the analog signal. Because the HART® protocol features
simultaneous digital and analog data transmission, the analog value can drive other
equipment in the loop while the control system is receiving the digital information. Burst
mode applies only to the transmission of dynamic data (pressure and temperature in
engineering units, pressure in percent of range, Scaled Variable, and/or analog output),
and does not affect the way other transmitter data is accessed. However, when activated,
bust mode can slow down communication of non-dynamic data to the host by 50 percent.
Access to information other than dynamic transmitter data is obtained through the
normal poll/response method of HART communication. A Field Communicator, AMS
Device Manager, or the control system may request any of the information that is
normally available while the transmitter is in burst mode. Between each message sent by
the transmitter, a short pause allows the Field Communicator, AMS Device Manager, or a
control system to initiate a request.
2.10.1
2.10.2
Choosing burst mode options in HART® 5
Message content options:
• PV only
• Percent of Range
• PV, 2V, 3V, 4V
• Process Variables
• Device Status
Choosing burst mode options in HART® 7
Message content options:
• PV only
• Percent of Range
• PV, 2V, 3V, 4V
• Process Variables and Status
• Process Variables
• Device Status
2.10.3
Reference Manual33
Choosing a HART® 7 trigger mode
When in HART 7 mode, the following trigger modes can be selected.
ConfigurationReference Manual
September 202000809-0100-4107
• Continuous (same as HART5 burst mode)
• Rising
• Falling
• Windowed
• On Change
Note
Consult your host system manufacturer for burst mode requirements.
2.10.4Configuring burst mode using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 5, 3
2.10.5Configuring burst mode using AMS Device Manager
Procedure
1. Right select on the device and select Configure.
2. Select the HART tab.
3. Enter the configuration in Burst Mode Configuration fields.
2.11Establishing multidrop communication
Multidropping transmitters refers to the connection of several transmitters to a single
communications transmission line. Communication between the host and the
transmitters takes place digitally with the analog output of the transmitters deactivated.
Multidrop installation requires consideration of the update rate necessary from each
transmitter, the combination of transmitter models, and the length of the transmission
line. Communication with transmitters can be accomplished with HART® modems and a
host implementing HART protocol. Each transmitter is identified by a unique address and
responds to the commands defined in the HART protocol. Field Communicators and AMS
Device Manager can test, configure, and format a multidropped transmitter the same way
as a transmitter in a standard point-to-point installation.
Figure 2-18 shows a typical multidrop network. This figure is not intended as an
installation diagram.
34Rosemount 2051 Pressure Transmitter
Reference ManualConfiguration
00809-0100-4107September 2020
Figure 2-18: Typical Multidrop Network (4–20 mA only)
A. HART modem
B. Power supply
The product is set to address zero (0) at the factory, which allows operation in the
standard point-to-point manner with a 4–20 mA (1–5 Vdc) output signal. To activate
multidrop communication, the transmitter address must be changed to a number from 1
to 15 for HART Revision 5, or 1–63 for HART Revision 7. This change deactivates the 4–
20 mA (1–5 Vdc) analog output, sending it to 4 mA (1 Vdc). It also disables the failure
mode alarm signal, which is controlled by the upscale/downscale switch position. Failure
signals in multidropped transmitters are communicated through HART messages.
2.11.1
Changing a transmitter address
To activate multidrop communication, the transmitter poll address must be assigned a
number from 1 to 15 for HART® Revision 5, and 1–63 for HART Revision 7. Each
transmitter in a multidropped loop must have a unique poll address.
Changing transmitter address using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Changing transmitter address using AMS Device Manager
Procedure
1. Right select on the device and select Configure.
2. In HART Revision 5 mode:
a) Select Manual Setup, select the HART tab.
b) In the Communication Settings box enter polling address in the Polling
Address box, select Send.
3. In HART Revision 7 mode:
HART Revision 7
Reference Manual35
ConfigurationReference Manual
September 202000809-0100-4107
a) Select Manual Setup, select the HART tab and select the Change Polling
Address button.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
2.11.2Communicating with a multidropped transmitter
To communicate with a multidrop transmitter, the Field Communicator or AMS Device
Manager has to be set up for Polling.
Communicating with a multidropped transmitter using a
Field Communicator
Procedure
1. Select Utility and Configure HART Application.
2. Select Polling Addresses.
3. Enter 0–63.
Communicating with a multidropped transmitter using AMS
Device Manager
Procedure
Select on the HART® modem icon and select Scan All Devices.
36Rosemount 2051 Pressure Transmitter
Reference ManualHardware Installation
00809-0100-4107September 2020
3Hardware Installation
3.1Overview
The information in this section covers installation considerations for the Rosemount 2051
with HART® protocols. A Quick Installation Guide is shipped with every transmitter to
describe recommended pipe-fitting and wiring procedures for initial installation.
Dimensional drawings for each transmitter variation and mounting configuration are
included on Bolt installation.
Note
For transmitter disassembly and reassembly refer to Disassembly procedures, and
Reassembly procedures.
3.2Safety messages
Procedures and instructions in this section may require special precautions to ensure the
safety of the personnel performing the operation. Refer to the following safety messages
before performing an operation preceded by this symbol.
WARNING
Explosions
Explosions could result in death or serious injury.
Review the approvals section of this manual for any restrictions associated with a safe
installation.
Before connecting a communicator in an explosive atmosphere, ensure the instruments in
the segment are installed in accordance with intrinsically safe or non-incendive field wiring
practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when
power is applied to the unit.
Process leaks
Process leaks may cause harm or result in death.
Install and tighten process connectors before applying pressure.
Electrical shocks
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals.High voltage that my be present on leads can
cause electrical shock.
Reference Manual37
Hardware InstallationReference Manual
September 202000809-0100-4107
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare
parts could reduce the pressure retaining capabilities of the transmitter and may
render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
Improper assembly of manifolds
Improper assembly of manifolds to traditional flange can damage the SuperModule
Platform.
For safe assembly of manifold to traditional flange, bolts must break black plane of flange
web (i.e., bolt hole) but must not contact module housing.
Physical access
Unauthorized personnel may potentially cause significant damage to and/or
misconfiguration of end users’ equipment. This could be intentional or unintentional and
needs to be protected against.
™
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access by unauthorized personnel to protect end
users’ assets. This is true for all systems used within the facility.
3.3Considerations
3.3.1Installation considerations
Measurement accuracy depends upon proper installation of the transmitter and impulse
piping. Mount the transmitter close to the process and use a minimum of piping to
achieve best accuracy. Keep in mind the need for easy access, personnel safety, practical
field calibration, and a suitable transmitter environment. Install the transmitter to
minimize vibration, shock, and temperature fluctuation.
Important
Install the enclosed pipe plug (found in the box) in unused conduit opening. Engage a
minimum of five threads to comply with explosion-proof requirements. For tapered
threads, install the plug wrench tight. For material compatibility considerations, see
Material Selection Technical Note on Emerson.com/Rosemount.
3.3.2
Environmental considerations
Best practice is to mount the transmitter in an environment that has minimal ambient
temperature change. The transmitter electronics temperature operating limits are –40 to
185 °F (–40 to 85 °C). Mount the transmitter so that it is not susceptible to vibration and
mechanical shock and does not have external contact with corrosive materials.
38Rosemount 2051 Pressure Transmitter
A
Reference ManualHardware Installation
00809-0100-4107September 2020
3.3.3Mechanical considerations
Steam service
For steam service or for applications with process temperatures greater than the limits of
the transmitter, do not blow down impulse piping through the transmitter. Flush lines
with the blocking valves closed and refill lines with water before resuming measurement.
Side mounted
When the transmitter is mounted on its side, position the coplanar flange to ensure proper
venting or draining. Mount the flange as shown in Mounting requirements, keeping drain/
vent connections on the bottom for gas service and on the top for liquid service.
3.4Installation procedures
3.4.1Mount the transmitter
Process flange orientation
Mount the process flanges with sufficient clearance for process connections. For safety
reasons, place the drain/vent valves so the process fluid is directed away from possible
human contact when the vents are used. In addition, consider the need for a testing or
calibration input.
Note
Most transmitters are calibrated in the horizontal position. Mounting the transmitter in
any other position will shift the zero point to the equivalent amount of liquid head
pressure caused by the varied mounting position. To reset zero point, refer to Trim the
pressure signal.
Housing rotation
To improve field access to wiring or to better view the optional LCD display follow the
procedure steps.
Figure 3-1: Housing Rotation
A. Housing rotation set screw (5/64 in.)
Procedure
1. Loosen the housing rotation set screw using a 5/64 -in. hex wrench.
Reference Manual39
Hardware InstallationReference Manual
September 202000809-0100-4107
2. Rotate the housing clockwise to the desired location.
3. If the desired location cannot be achieved due to thread limit, rotate the housing
counterclockwise to the desired location (up to 360° from thread limit).
4. Retighten the housing rotation set screw to no more than 7 in-lbs when desired
location is reached.
Electronics housing clearance
Mount the transmitter so the terminal side is accessible. Clearance of 0.75 in. (19 mm) is
required for cover removal. Use a conduit plug in the unused conduit opening. Three
inches of clearance is required for cover removal if a meter is installed.
Environmental seal for housing
For NEMA 4X, IP66, and IP68 requirements, use thread seal (PTFE) tape or paste on male
threads of conduit to provide a watertight seal.
Always ensure a proper seal by installing the electronics housing cover(s) so that metal
contacts metal. Use Rosemount O-rings.
Flange bolts
The Rosemount 2051 can be shipped with a coplanar flange or a traditional flange
installed with four 1.75-inch flange bolts. Mounting bolts and bolting configurations for
the coplanar and traditional flanges can be found on Bolt installation. Stainless steel bolts
supplied by Emerson are coated with a lubricant to ease installation. Carbon steel bolts do
not require lubrication. No additional lubricant should be applied when installing either
type of bolt. Bolts supplied by Emerson are identified by their head markings.
Bolt installation
Only use bolts supplied with the transmitter or sold by Emerson as spare parts. The use of
non approved bolts could reduce pressure. Use the following bolt installation procedure:
Table 3-1: Bolt installation torque values
Bolt materialInitial torque valueFinal torque value
ASTM A 193 Class 2, Grade B8M optionL8300 in.-lb (34 N-m)650 in.-lb (73 N-m)
40Rosemount 2051 Pressure Transmitter
Reference ManualHardware Installation
00809-0100-4107September 2020
Figure 3-2: Traditional Flange Bolt Configurations
A. Differential transmitter
B. Gauge/Absolute transmitter
C. Drain/vent
D. Plug
E. 1.75 (44) × 4
F. 1.50 (38) × 4
(1)
Note: Dimensions are in inches (millimeters)
Figure 3-3: Mounting Bolts and Bolt Configurations for Coplanar Flange
A. Transmitter with flange bolts
B. Transmitter with flange adapters and flange/adapter bolts
C. 1.75 (44) × 4
D. 2.88 (73) × 4
Dimensions are in inches (millimeters).
For Gauge and Absolute Transmitters: 150 (38) x 2
(1)
Reference Manual41
Hardware InstallationReference Manual
September 202000809-0100-4107
Table 3-2: Bolt configurations values
DescriptionQuantitySize in. (mm)
Differential pressure
Flange bolts41.75 (44)
Flange/adapter bolts42.88 (73)
Gauge/Absolute pressure
Flange bolts41.75 (44)
Flange/adapter bolts22.88 (73)
(1) Rosemount 2051T Transmitters are direct mount and do not require bolts for process
connection.
(1)
Figure 3-4: Mounting Bracket Option Codes B1, B7, and BA
A. 3.75 (95)
B. 1.63 (41)
C. 4.09 (104)
D. 2.73 (69)
E. 4.97 (126)
F. 2.81 (71)
42Rosemount 2051 Pressure Transmitter
Reference ManualHardware Installation
00809-0100-4107September 2020
Figure 3-5: Panel Mounting Bracket Option Codes B2 and B8
A. 3.75 (95)
B. 1.63 (41)
C. 4.09 (104)
D. 2.81 (71)
E. 4.5 (114)
A. 1.40 (36)
B. Mounting holes 0.375 diameter (10)
C. 1.405 (35,7)
D. 1.405 (35,7)
Figure 3-6: Flat Mounting Bracket Option Codes B3 and BC
A. 1.625 (41)
B. 2.125 (54)
C. 2.81 (71)
D. 8.00 (203)
Note: Dimensions are in inches (millimeters).
Procedure
1. Finger-tighten the bolts.
2. Torque the bolts to the initial torque value using a crossing pattern (see Table 3.4.2
for torque values).
3. Torque the bolts to the final torque value using the same crossing pattern.
Reference Manual43
Hardware InstallationReference Manual
September 202000809-0100-4107
Mounting brackets
Rosemount 2051 transmitters may be panel-mounted or pipe-mounted via an optional
mounting bracket. Refer to Table 3-2 for the complete offering and see Figure 3-7 through
Figure 3-6 on pages Figure 3-7 and 39 for dimensional and mounting configuration
information.
Table 3-3: Mounting brackets
Option
code
B4XXXXXXX
B1XXXX
B2XXXX
B3XXXX
B7XXXX
B8XXXX
B9XXXX
BAXXXX
BCXXXX
Process connectionsMountingMaterials
CoplanarIn-lineTraditionalPipe
mount
Panel
mount
Flat
panel
mount
CS
bracket
SST
bracket
CS bolts SST
bolts
44Rosemount 2051 Pressure Transmitter
Reference ManualHardware Installation
00809-0100-4107September 2020
Figure 3-7: Mounting Bracket Option Code B4
A. 5/16 x 1
½ Bolts for panel mounting(not supplied)
B. 3.4 (85)
C. 3/8-16 x 1¼ Bolts for mounting to transmitter
D. 2.8 (71)
E. 3.85 (98)
F. 5.16 (131)
G. 1.99 (51)
H. 4.72 (120)
I. 6.90 (175)
Note: Dimensions are in inches (millimeters).
Reference Manual45
Hardware InstallationReference Manual
September 202000809-0100-4107
1. Carbon steel (CS) head markings
2. Stainless steel (SST) head markings
3. Alloy K-500 head marking
3.4.2
Note
The last digit in the F593_head marking may be any letter between A and M.
Impulse piping
Mounting requirements
Impulse piping configurations depend on specific measurement conditions. Refer to
Figure 3-8 for examples of the following mounting configurations:
Liquid flow measurement
• Place taps to the side of the line to prevent sediment deposits on the process isolators.
• Mount the transmitter beside or below the taps so gases vent into the process line.
• Mount drain/vent valve upward to allow gases to vent.
Gas flow measurement
• Place taps in the top or side of the line.
• Mount the transmitter beside or above the taps so to drain liquid into the process line.
Steam flow measurement
• Place taps to the side of the line.
• Mount the transmitter below the taps to ensure that impulse piping will remain filled
with condensate.
• In steam service above 250 °F (121 °C), fill impulse lines with water to prevent steam
from contacting the transmitter directly and to ensure accurate measurement startup.
46Rosemount 2051 Pressure Transmitter
Reference ManualHardware Installation
00809-0100-4107September 2020
Note
For steam or other elevated temperature services, it is important that temperatures at the
process connection do not exceed the transmitter’s process temperature limits. See
Temperature limits for details.
Figure 3-8: Installation Examples
Best practices
The piping between the process and the transmitter must accurately transfer the pressure
to obtain accurate measurements. There are five possible sources of error: pressure
transfer, leaks, friction loss (particularly if purging is used), trapped gas in a liquid line,
liquid in a gas line, and density variations between the legs.
The best location for the transmitter in relation to the process pipe is dependent on the
process. Use the following guidelines to determine transmitter location and placement of
impulse piping:
• Keep impulse piping as short as possible.
• For liquid service, slope the impulse piping at least 1 in./ft (8 cm/m) upward from the
transmitter toward the process connection.
• For gas service, slope the impulse piping at least 1 in./ft (8 cm/m) downward from the
transmitter toward the process connection.
• Avoid high points in liquid lines and low points in gas lines.
• Use impulse piping large enough to avoid friction effects and blockage.
• Vent all gas from liquid piping legs.
• When purging, make the purge connection close to the process taps and purge
through equal lengths of the same size pipe. Avoid purging through the transmitter.
• Keep corrosive or hot [above 250 °F (121 °C)] process material out of direct contact
with the sensor module and flanges.
• Prevent sediment deposits in the impulse piping.
• Avoid conditions that might allow process fluid to freeze within the process flange.
Reference Manual47
Hardware InstallationReference Manual
September 202000809-0100-4107
3.4.3Process connections
Coplanar or traditional process connection
Install and tighten all four flange bolts before applying pressure, or process leakage will
result. When properly installed, the flange bolts will protrude through the top of the
sensor module housing. Do not attempt to loosen or remove the flange bolts while the
transmitter is in service.
Flange adapters
Rosemount 2051DP and GP process connections on the transmitter flanges are ¼–18
NPT. Flange adapters are available with standard ½–14 NPT Class 2 connections. The
flange adapters allow users to disconnect from the process by removing the flange
adapter bolts. Use plant-approved lubricant or sealant when making the process
connections. Refer to dimensional drawings on page 113 for the distance between
pressure connections. This distance may be varied ±¼in. (6.4 mm) by rotating one or both
of the flange adapters.
To install adapters to a Coplanar flange, perform the following procedure:
3.4.4
Procedure
1. Remove the flange bolts.
2. Leaving the flange in place, move the adapters into position with the o-ring
installed.
3. Clamp the adapters and the cCoplanar flange to the transmitter sensor module
using the larger of the bolts supplied.
4. Tighten the bolts. Refer to “Flange bolts” on page 36 for torque specifications.
Example
When removing flanges or adapters, visually inspect the PTFE o-rings. Replace with o-ring
designed for Rosemount transmitter if there are any signs of damage, such as nicks or
cuts. Undamaged o-rings may be reused. If you replace the O-rings, retorque the flange
bolts after installation to compensate for cold flow. Refer to the process sensor body
reassembly procedure in Section 5: Troubleshooting.
Note
PTFE O-rings should be replaced if the flange adapter is removed.
Inline process connection
Inline gauge transmitter orientation
CAUTION
Interfering or blocking the atmospheric reference port will cause the transmitter to output
erroneous pressure values.
48Rosemount 2051 Pressure Transmitter
Reference ManualHardware Installation
00809-0100-4107September 2020
The low side pressure port on the inline gauge transmitter is located in the neck of the
transmitter, behind the housing. The vent path is 360 degrees around the transmitter
between the housing and sensor (See Figure 3-9).
Keep the vent path free of any obstruction, such as paint, dust, and lubrication by
mounting the transmitter so that the process can drain away.
Figure 3-9: Inline gauge low side pressure port
A. Low side pressure port (atmospheric reference)
WARNING
3.5Rosemount 305, 306, and 304 Manifolds
The Rosemount 305 Integral Manifold is available in two designs: Traditional and Coplanar.
You can mount the traditional Rosemount 305 Integral Manifold to most primary
elements with mounting adapters in the market today. The 306 Integral Manifold is used
with the Rosemount 2051T In-Line Transmitters to provide block-and-bleed valve
capabilities of up to 10000 psi (690 bar).
Reference Manual49
Hardware InstallationReference Manual
September 202000809-0100-4107
Figure 3-10: Manifolds
3.5.1
A. 2051C and 304 Conventional
B. 2051C and 305 Integral Coplanar
C. 2051C and 305 Integral Traditional
D. 2051T and 306 In-Line
Install Rosemount 305 Integral Manifold
Procedure
1. Inspect the PTFE sensor module O-rings.
You may reuse undamaged O-rings. If the O-rings are damaged (if they have nicks
or cuts, for example), replace with O-rings designed for Rosemount transmitters.
Important
If replacing the O-rings, take care not to scratch or deface the O-ring grooves or the
surface of the isolating diaphragm while you remove the damaged O-rings.
2. Install the Integral Manifold on the sensor module. Use the four 2.25-in. (57.2 mm).
manifold bolts for alignment. Finger tighten the bolts; then tighten the bolts
incrementally in a cross pattern to final torque value.
50Rosemount 2051 Pressure Transmitter
HL
Drain/Vent
valve
Drain/Vent
valve
Isolate
(open)
Isolate
(open)
Process
Equalize
(closed)
Reference ManualHardware Installation
00809-0100-4107September 2020
See Flange bolts for complete bolt installation information and torque values. When
fully tightened, the bolts should extend through the top of the sensor
module housing.
3. If you have replaced the PTFE sensor module O-rings, re-tighten the flange bolts
after installation to compensate for cold flow of the O-rings.
Note
Always perform a zero trim on the transmitter/manifold assembly after installation
to eliminate mounting effects.
3.5.2Install Rosemount 306 integral manifold
The Rosemount 306 Manifold is for use only with in-line pressure transmitters such as the
Rosemount 3051T and 2051T.
Assemble the Rosemount 306 manifold to the Rosemount 3051T or 2051T In-Line
Transmitters with a thread sealant.
3.5.3
3.5.4
Install Rosemount 304 Conventional Manifold
Procedure
1. Align the conventional manifold with the transmitter flange. Use the four manifold
bolts for alignment.
2. Finger tighten the bolts; then tighten the bolts incrementally in a cross pattern to
final torque value.
See Flange bolts for complete bolt installation information and torque values.When
fully tightened, the bolts should extend through the top of the sensor module
housing.
3. Leak-check assembly to maximum pressure range of transmitter.
Integral manifold operation
Three-valve configuration shown.
In normal operation the two isolate valves between the process and instrument ports will
be open and the equalizing valve(s) will be closed.
Reference Manual51
To zero the 2051, close the isolate valve to the low pressure (downstream side) of the
transmitter first.
HL
Drain/Vent
valve
Isolate
(open)
Drain/Vent
valve
Isolate
(closed)
Process
Equalize
(closed)
HL
Drain/Vent
valve
Isolate
(open)
Drain/Vent
valve
Isolate
(closed)
Process
Equalize
(open)
HL
Drain/Vent
valve
Isolate
(open)
Drain/Vent
valve
Isolate
(closed)
Process
Equalize
(closed)
HL
Drain/Vent
valve
Drain/Vent
valve
Isolate
(open)
Isolate
(open)
Process
Equalize
(closed)
Hardware InstallationReference Manual
September 202000809-0100-4107
Next, open the center (equalize) valve(s) to equalize the pressure on both sides of the
transmitter.
The manifold valves are now in the proper configuration for zeroing the transmitter. To
return the transmitter to service, close the equalizing valve(s) first.
Next, open the isolate valve on the low pressure side of the transmitter.
Five-valve Natural Gas configurations shown:
In normal operation, the two block valves between the process and instrument ports will
be open, and the equalizing valves will be closed.
52Rosemount 2051 Pressure Transmitter
H
L
(Plugged)
Isolate
(open)
Isolate
(open)
(Plugged)
Equalize
(closed)
Equalize
(closed)
ProcessProcessDrain vent
(closed)
H
L
(Plugged)
Isolate
(open)
Isolate
(closed)
(Plugged)
ProcessProcessDrain vent
(closed)
Equalize
(closed)
Equalize
(closed)
(Plugged)
Isolate
(open)
Equalize
(open)
Equalize
(closed)
ProcessProcessDrain vent
(closed)
Isolate
(closed)
(Plugged)
HL
Reference ManualHardware Installation
00809-0100-4107September 2020
To zero the Rosemount 2051, first close the block valve on the low pressure (downstream)
side of the transmitter.
Note
Do not open the low side equalize valve before the high side equalize valve. Doing so will
overpressure the transmitter.
Open the equalize valve on the high pressure (upstream) side of the transmitter.
Reference Manual53
(Plugged)
Isolate
(open)
Equalize
(open)
Equalize
(open)
ProcessProcessDrain vent
(closed)
Isolate
(closed)
(Plugged)
HL
Hardware InstallationReference Manual
September 202000809-0100-4107
Open the equalize valve on the low pressure (downstream) side of the transmitter. The
manifold is now in the proper configuration for zeroing the transmitter.
Operate three and five-valve manifolds
Performing zero trim at static line pressure
In normal operation, the two isolate (block) valves between the process ports and the
transmitter will be open, and the equalize valve will be closed.
A. Drain/vent valve
B. Isolate (open)
C. Equalize (closed)
D. Process
E. Isolate (open)
F. Drain/vent valve
Procedure
1. To zero trim the transmitter, close the isolate valve on the low side (downstream)
side of the transmitter.
54Rosemount 2051 Pressure Transmitter
Reference ManualHardware Installation
00809-0100-4107September 2020
A. Drain/vent valve
B. Isolate (open)
C. Equalize (closed)
D. Process
E. Isolate (closed)
F. Drain/vent valve
2. Open the equalize valve to equalize the pressure on both sides of the transmitter.
The manifold is now in the proper configuration for performing a zero trim on the
transmitter.
A. Drain/vent valve
B. Isolate (open)
C. Equalize (open)
D. Process
E. Isolate (closed)
F. Drain/vent valve
3. After zeroing the transmitter, close the equalize valve.
A. Drain/vent valve
B. Isolate (open)
C. Equalize (closed)
D. Process
E. Isolate (closed)
F. Drain/vent valve
4. Finally, to return the transmitter to service, open the low side isolate valve.
Reference Manual55
Hardware InstallationReference Manual
September 202000809-0100-4107
A. Drain/vent valve
B. Isolate (open)
C. Equalize (closed)
D. Process
E. Isolate (open)
F. Drain/vent valve
Operate five-valve natural gas manifold
Performing zero trim at static line pressure
Five-valve natural gas configurations shown:
In normal operation, the two isolate (block) valves between the process ports and the
transmitter will be open, and the equalize valves will be closed. Vent valves may be open
or closed.
A. (Plugged)
B. Isolate (open)
C. Process
D. Equalize (closed)
E. Equalize (closed)
F. Drain vent (closed)
G. Process
H. Isolate (open)
I. (Plugged)
Procedure
1. To zero trim the transmitter, first close the isolate valve on the low pressure
(downstream) side of the transmitter and the vent valve.
56Rosemount 2051 Pressure Transmitter
Reference ManualHardware Installation
00809-0100-4107September 2020
A. (Plugged)
B. Isolate (open)
C. Process
D. Equalize (closed)
E. Equalize (closed)
F. Drain vent (closed)
G. Process
H. Isolate (closed)
I. (Plugged)
2. Open the equalize valve on the high pressure (upstream) side of the transmitter.
A. (Plugged)
B. Isolate (open)
C. Process
D. Equalize (open)
E. Equalize (closed)
F. Drain vent (closed)
G. Process
H. Isolate (closed)
I. (Plugged)
3. Open the equalize valve on the low pressure (downstream) side of the transmitter.
The manifold is now in the proper configuration for zeroing the transmitter.
Reference Manual57
Hardware InstallationReference Manual
September 202000809-0100-4107
A. (Plugged)
B. Isolate (open)
C. Process
D. Equalize (open)
E. Equalize (open)
F. Drain vent (closed)
G. Process
H. Isolate (closed)
I. (Plugged)
4. After zeroing the transmitter, close the equalize valve on the low pressure
(downstream) side of the transmitter.
A. (Plugged)
B. Isolate (open)
C. Process
D. Equalize (open)
E. Equalize (closed)
F. Drain vent (closed)
G. Process
H. Isolate (closed)
I. (Plugged)
5. Close the equalize valve on the high pressure (upstream) side.
58Rosemount 2051 Pressure Transmitter
Reference ManualHardware Installation
00809-0100-4107September 2020
A. (Plugged)
B. Isolate (open)
C. Process
D. Equalize (closed)
E. Equalize (closed)
F. Drain vent (closed)
G. Process
H. Isolate (closed)
I. (Plugged)
6. Finally, to return the transmitter to service, open the low side isolate valve and vent
valve.
The vent valve can remain open or closed during operation.
3.5.5
A. (Plugged)
B. Isolate (open)
C. Process
D. Equalize (closed)
E. Equalize (closed)
F. Drain vent (closed)
G. Process
H. Isolate (open)
I. (Plugged)
Adjusting valve packing
Over time, the packing material inside a Rosemount manifold may require adjustment in
order to continue to provide proper pressure retention. Not all Rosemount manifolds have
this adjustment capability. The Rosemount manifold model number will indicate what
type of stem seal or packing material has been used.
The following steps are provided as a procedure to adjust valve packing:
Above steps can be repeated, if necessary. If the above procedure does not result in proper
pressure retention, the complete manifold should be replaced.
Figure 3-11: Valve Components
A. Bonnet
B. Ball seat
C. Packing
D. Stem
E. Packing adjuster
F. Jam nut
G. Packing follower
3.6Liquid level measurement
Differential pressure transmitters used for liquid level applications measure hydrostatic
pressure head. Liquid level and specific gravity of a liquid are factors in determining
pressure head. This pressure is equal to the liquid height above the tap multiplied by the
specific gravity of the liquid. Pressure head is independent of volume or vessel shape.
3.6.1
Open vessels
A pressure transmitter mounted near a tank bottom measures the pressure of the liquid
above.
Make a connection to the high pressure side of the transmitter, and vent the low pressure
side to the atmosphere. Pressure head equals the liquid’s specific gravity multiplied by the
liquid height above the tap.
60Rosemount 2051 Pressure Transmitter
Reference ManualHardware Installation
00809-0100-4107September 2020
Zero range suppression is required if the transmitter lies below the zero point of the
desired level range. Figure 3-12 shows a liquid level measurement example.
3.6.2Closed vessels
Pressure above a liquid affects the pressure measured at the bottom of a closed vessel.
The liquid specific gravity multiplied by the liquid height plus the vessel pressure equals
the pressure at the bottom of the vessel.
To measure true level, the vessel pressure must be subtracted from the vessel bottom
pressure. To do this, make a pressure tap at the top of the vessel and connect this to the
low side of the transmitter. Vessel pressure is then equally applied to both the high and
low sides of the transmitter. The resulting differential pressure is proportional to liquid
height multiplied by the liquid specific gravity.
Dry leg condition
Low-side transmitter piping will remain empty if gas above the liquid does not condense.
This is a dry leg condition. Range determination calculations are the same as those
described for bottom-mounted transmitters in open vessels, as shown in Figure 3-12.
Figure 3-12: Liquid level measurement example
Reference Manual61
Hardware InstallationReference Manual
September 202000809-0100-4107
Wet leg condition
Condensation of the gas above the liquid slowly causes the low side of the transmitter
piping to fill with liquid. The pipe is purposely filled with a convenient reference fluid to
eliminate this potential error. This is a wet leg condition.
The reference fluid will exert a head pressure on the low side of the transmitter. Zero
elevation of the range must then be made. See Figure 3-13.
Figure 3-13: Wet leg example
62Rosemount 2051 Pressure Transmitter
Reference ManualHardware Installation
00809-0100-4107September 2020
Bubbler system in open vessel
A bubbler system that has a top-mounted pressure transmitter can be used in open
vessels. This system consists of an air supply, pressure regulator, constant flow meter,
pressure transmitter, and a tube that extends down into the vessel.
Bubble air through the tube at a constant flow rate. The pressure required to maintain flow
equals the liquid’s specific gravity multiplied by the vertical height of the liquid above the
tube opening. Figure 3-14 shows a bubbler liquid level measurement example.
Figure 3-14: Bubbler liquid level measurement example
Reference Manual63
Hardware InstallationReference Manual
September 202000809-0100-4107
64Rosemount 2051 Pressure Transmitter
Reference ManualElectrical Installation
00809-0100-4107September 2020
4Electrical Installation
4.1Overview
The information in this section covers installation considerations for the Rosemount 2051
Pressure Transmitter with HART® protocol. A Quick Start Guide is shipped with every
transmitter to describe pipe-fitting, wiring procedures and basic configuration for initial
installation.
4.2Safety messages
Procedures and instructions in this section may require special precautions to ensure the
safety of the personnel performing the operation. Refer to the following safety messages
before performing an operation preceded by this symbol.
WARNING
Explosions
Explosions could result in death or serious injury.
Review the approvals section of this manual for any restrictions associated with a safe
installation.
Before connecting a communicator in an explosive atmosphere, ensure the instruments in
the segment are installed in accordance with intrinsically safe or non-incendive field wiring
practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when
power is applied to the unit.
Process leaks
Process leaks may cause harm or result in death.
Install and tighten process connectors before applying pressure.
Electrical shocks
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals.High voltage that my be present on leads can
cause electrical shock.
Replacement equipment or spare parts not approved by Emerson for use as spare
parts could reduce the pressure retaining capabilities of the transmitter and may
render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
Reference Manual65
A
B
C
Electrical InstallationReference Manual
September 202000809-0100-4107
WARNING
Improper assembly of manifolds
Improper assembly of manifolds to traditional flange can damage the SuperModule
Platform.
For safe assembly of manifold to traditional flange, bolts must break black plane of flange
web (i.e., bolt hole) but must not contact module housing.
Physical access
Unauthorized personnel may potentially cause significant damage to and/or
misconfiguration of end users’ equipment. This could be intentional or unintentional and
needs to be protected against.
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access by unauthorized personnel to protect end
users’ assets. This is true for all systems used within the facility.
™
4.3LOI/LCD display
Transmitters ordered with the LCD display option (M5) or LOI option (M4) are shipped with
the display installed. Installing the display on an existing transmitter requires a small
instrument screwdriver. Carefully align the desired display connector with the electronics
board connector. If connectors don't align, the display and electronics board are not
compatible.
Figure 4-1: LCD Display
A. Jumpers (top and bottom)
B. LCD display
C. Extended cover
66Rosemount 2051 Pressure Transmitter
Reference ManualElectrical Installation
00809-0100-4107September 2020
4.3.1Rotating LOI/LCD display
Procedure
1. Secure the loop to manual control and remove power to transmitter.
2. Remove transmitter housing cover.
3. Remove screws from the LCD display and rotate to desired orientation.
a) Insert 10 pin connector into the display board for the correct orientation.
Carefully align pins for insertion into the output board.
4. Re-insert screws.
5. Reattach transmitter housing cover; it is recommended the cover be tightened until
there is no gap between the cover and housing to comply with explosion proof
requirements.
6. Re-attach power and return loop to automatic control.
4.4Configure security and simulation
There are four security methods with the Rosemount 2051 Transmitter.
• Security switch
• HART Lock
• Configuration buttons lock
• LOI password
Figure 4-2: 4–20 mA Electronics Board
without LCD meter
with LCD display
A. Alarm
B. Security
Reference Manual67
Electrical InstallationReference Manual
September 202000809-0100-4107
Note
1-5 Vdc alarm and security switches are located in the same location as 4-20 mA output
boards.
4.4.1Setting security switch
The security switch is used to prevent changes to the transmitter configuration data. If the
security switch is set to the locked (
sent via HART®, LOI, or local configuration buttons will be rejected by the transmitter and
the transmitter configuration data will not be modified. Reference Figure 4-2 for the
location of the security switch. Follow the steps below to enable the security switch.
Procedure
1. Set loop to manual and remove power.
2. Remove transmitter housing cover.
3. Use a small screwdriver to slide the switch to the locked ( ) position.
4. Replace transmitter housing cover; cover must be fully engaged to comply with
explosion proof requirements.
) location, any transmitter configuration requests
4.4.2
HART Lock
The HART® Lock prevents changes to the transmitter configuration from all sources; all
changes requested via HART, LOI, and local configuration buttons will be rejected. The
HART Lock can only be set via HART communication, and is only available in HART Revision
7 mode. The HART Lock can be enabled or disabled with a Field Communicator or AMS
Device Manager.
Configuring HART Lock using Field Communicator
From the HOME screen, enter the fast key sequence.
Device Dashboard Fast Keys
Procedure
1. Right click on the device and select Configure.
2. Under Manual Setup select the Security tab.
3. Select Lock/Unlock button under HART Lock (Software) and follow the screen
prompts.
Configuring HART Lock using AMS Device Manager
Procedure
1. Right click on the device and select Configure.
2. Under Manual Setup select the Security tab.
3. Select Lock/Unlock button under HART Lock (Software) and follow the screen
prompts.
2, 2, 6, 4
68Rosemount 2051 Pressure Transmitter
Reference ManualElectrical Installation
00809-0100-4107September 2020
4.4.3Configuration Button lock
The configuration button lock disables all local button functionality. Changes to the
transmitter configuration from the LOI and local buttons will be rejected. Local external
keys can be locked via HART® communication only.
Configuring configuration button lock using a Field
Communicator
From the HOME screen, enter the fast key sequence
Device Dashboard Fast Keys2, 2, 6, 3
Procedure
1. Right click on the device and select Configure.
2. Under Manual Setup select the Security tab.
3. Within the Configuration Buttons dropdown menu select Disabled to lock external
local keys.
4. Select Send.
5. Confirm service reason and select Yes.
4.4.4
Configuring configuration button lock using AMS Device
Manager
Procedure
1. Right select the device and select Configure.
2. Under Manual Setup select the Security tab.
3. Within the Configuration Buttons dropdown menu select Disabled to lock external
local keys.
4. Select Send.
5. Confirm service reason and click Yes.
LOI Password
A LOI Password can be entered and enabled to prevent review and modification of device
configuration via the LOI. This does not prevent configuration from HART® or external keys
(analog zero and span; Digital Zero Trim). The LOI password is a 4 digit code that is to be
set by the user. If the password is lost or forgotten the master password is “9307”.
The LOI password can be configured and enabled/disabled by HART Communication via a
Field Communicator, AMS Device Manager, or the LOI.
Configuring password with Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Reference Manual69
2, 2, 6, 5, 2
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN P
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
PASSWORD
PASSWORD ENABLE
CHANGE PASSWORD
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
Electrical InstallationReference Manual
September 202000809-0100-4107
Configuring password with AMS Device Manager
Procedure
1. Right select the device and select Configure.
2. Under Manual Setup select the Security tab.
3. Within the LOI select the Configure Password button and follow the screen
prompts.
Configuring LOI password using LOI
Figure 4-3: LOI Password
4.5Setting transmitter alarm
4.6Electrical considerations
70Rosemount 2051 Pressure Transmitter
On the electronics board is an alarm switch, reference Figure 1 for switch location. Follow
the steps below to change the alarm switch location:
Procedure
1. Set loop to manual and remove power.
2. Remove transmitter housing cover.
3. Use a small screwdriver to slide switch to desired position.
4. Replace transmitter cover; cover must be fully engaged to comply with explosion
proof requirements.
Note
Make sure all electrical installation is in accordance with national and local code
requirements.
Reference ManualElectrical Installation
00809-0100-4107September 2020
WARNING
Electrical shock
Electrical shock can result in death or serious injury.
Do not run signal wiring in conduit or open trays with power wiring or near heavy electrical
equipment.
4.6.1Conduit installation
CAUTION
If all connections are not sealed, excess moisture accumulation can damage the
transmitter. Make sure to mount the transmitter with the electrical housing positioned
downward for drainage. To avoid moisture accumulation in the housing, install wiring with
a drip loop, and ensure the bottom of the drip loop is mounted lower than the conduit
connections of the transmitter housing.
4.6.2
Recommended conduit connections are shown in Figure 4-4.
Figure 4-4: Conduit Installation Diagrams
A. Possible conduit line positions
B. Sealing compound
Power supply
4–20 mA HART® (option code A)
Transmitter operates on 10.5–42.4 Vdc at the terminal of the transmitter. The DC power
supply should provide power with less than two percent ripple. A minimum of 16.6 V is
required for loops with a 250 Ω resistance.
Note
A minimum loop resistance of 250 Ω is required to communicate with a Field
Communicator. If a single power supply is used to power more than one Rosemount 2051
Reference Manual71
Electrical InstallationReference Manual
September 202000809-0100-4107
Transmitter, the power supply used, and circuitry common to the transmitters, should not
have more that 20 Ω of impedance at 1200 Hz.
Figure 4-5: Load Limitation
• Maximum loop resistance = 43.5 × (power supply voltage – 10.5)
• The Field Communicator requires a minimum loop resistance of 250 Ω for
communication.
The total resistance load is the sum of the resistance of the signal leads and the load
resistance of the controller, indicator, I.S. Barriers, and related pieces. If intrinsic safety
barriers are used, the resistance and voltage drop must be included.
4.6.3
1–5 Vdc low power HART® (output code M)
Low power transmitters operate on 9–28 Vdc. The DC power supply should provide power
with less than 2 percent ripple. The V
load should be 100 kΩ or greater.
out
Wiring the transmitter
CAUTION
Do not connect the power signal wiring to the test terminals. Incorrect wiring can damage
test circuit.
Note
Use shielded twisted pairs to yield best results. To ensure proper communication, use 24
AWG or larger wire and do not exceed 5000 ft. (1500 m). For 1–5 V 500 ft. (150 m)
maximum are recommended. unpaired three conductor or two twisted pairs is
recommended.
72Rosemount 2051 Pressure Transmitter
A
B
A
B
Reference ManualElectrical Installation
00809-0100-4107September 2020
Figure 4-6: Wiring the Transmitter (4–20 mA HART)
A. DC power supply
B. RL≥ 250 (necessary for HART® Communication only)
Figure 4-7: Wiring the Transmitter (1–5 Vdc low power)
A. DC power supply
B. Voltmeter
Perform the following procedure to make wiring connections:
Procedure
1. Remove the housing cover on terminal compartment side. Do not remove the
cover in explosive atmospheres when the circuit is live. Signal wiring supplies all
power to the transmitter.
2. For 4–20 mA HART Output, connect the positive lead to the terminal marked (pwr/
comm+) and the negative lead to the terminal marked (pwr/comm–). Do not
connect the powered signal wiring to the test terminals. Power could damage the
test diode.
Reference Manual73
Electrical InstallationReference Manual
September 202000809-0100-4107
a) For 1–5 Vdc HART Output, connect the positive lead to (PWR +) and the
negative to the (PWR–). Do not connect the powered signal wiring to the test
terminals. Power could damage the test diode.
3. Plug and seal unused conduit connection on the transmitter housing to avoid
moisture accumulation in the terminal side.
4.6.4Grounding the transmitter
Signal cable shield grounding
Signal cable shield grounding is summarized in Figure 4-8. The signal cable shield and
unused shield drain wire must be trimmed and insulated, ensuring the signal cable shield
and drain wire do not come in contact with the transmitter case. See Transmitter case
groundingTransmitter case grounding for instructions on grounding the transmitter case.
Follow the steps below to correctly ground the signal cable shield.
Procedure
1. Remove the field terminals housing cover.
2. Connect the signal wire pair at the field terminals as indicated in Figure 4-6.
3. At the field terminals, the cable shield and shield drain wire should be trimmed
close and insulated from transmitter housing.
4. Reattach the field terminals housing cover; cover must be fully engaged to comply
with explosion proof requirements.
5. At terminations outside the transmitter housing, the cable shield drain wire should
be continuously connected.
a) Prior to the termination point, any exposed shield drain wire should be
insulated as shown in Figure 4-7 (B).
6. Properly terminate the signal cable shield drain wire to an earth ground at or near
the power supply.
74Rosemount 2051 Pressure Transmitter
DP
A
B
C
Reference ManualElectrical Installation
00809-0100-4107September 2020
Example
Figure 4-8: Wiring Pair and Ground
A. Insulate Shield and shield drain wire
B. Insulate exposed shield drain wire
C. Terminate cable shield drain wire to earth ground
Transmitter case grounding
Always ground the transmitter case in accordance with national and local electrical codes.
The most effective transmitter case grounding method is a direct connection to earth
ground with minimal impedance. Methods for grounding the transmitter case include:
• Internal ground connection: The internal ground connection screw is inside the FIELD
TERMINALS side of the electronics housing. This screw is identified by a ground symbol
). The ground connection screw is standard on all Rosemount 2051 Transmitters.
(
Refer to Figure 4-9.
• External ground connection: The external ground connection is located on the exterior
of the transmitter housing. Refer to Figure 4-10. This connection is only available with
option V5 and T1.
Reference Manual75
Electrical InstallationReference Manual
September 202000809-0100-4107
Figure 4-9: Internal Ground Connection
A. Internal ground location
Figure 4-10: External Ground Connection (Option V5 or T1)
A. External ground location
Note
Grounding the transmitter case via threaded conduit connection may not provide
sufficient ground continuity.
Transient protection terminal block grounding
The transmitter can withstand electrical transients of the energy level usually encountered
in static discharges or induced switching transients. However, high-energy transients,
such as those induced in wiring from nearby lightning strikes, can damage the transmitter.
76Rosemount 2051 Pressure Transmitter
Reference ManualElectrical Installation
00809-0100-4107September 2020
The transient protection terminal block can be ordered as an installed option (code T1) or
as a spare part to retrofit existing transmitters in the field. See Spare parts for part
numbers. The lightning bolt symbol shown in Figure 4-11 identifies the transient
protection terminal block.
Figure 4-11: Transient Protection Terminal Block
A. Lightning bolt location
Note
The transient protection terminal block does not provide transient protection unless the
transmitter case is properly grounded. Use the guidelines to ground the transmitter case.
Refer to Figure 4-11.
Reference Manual77
Electrical InstallationReference Manual
September 202000809-0100-4107
78Rosemount 2051 Pressure Transmitter
Reference ManualOperation and Maintenance
00809-0100-4107September 2020
5Operation and Maintenance
5.1Overview
This section contains information on operation and maintenance procedures.
Field Communicator and AMS Device Manager instructions are given to perform
configuration functions.
5.2Safety messages
Procedures and instructions in this section may require special precautions to ensure the
safety of the personnel performing the operation. Refer to the following safety messages
before performing an operation preceded by this symbol.
WARNING
Explosions
Explosions could result in death or serious injury.
Review the approvals section of this manual for any restrictions associated with a safe
installation.
Before connecting a communicator in an explosive atmosphere, ensure the instruments in
the segment are installed in accordance with intrinsically safe or non-incendive field wiring
practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when
power is applied to the unit.
Process leaks
Process leaks may cause harm or result in death.
Install and tighten process connectors before applying pressure.
Electrical shocks
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals.High voltage that my be present on leads can
cause electrical shock.
Replacement equipment or spare parts not approved by Emerson for use as spare
parts could reduce the pressure retaining capabilities of the transmitter and may
render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
Reference Manual79
Operation and MaintenanceReference Manual
September 202000809-0100-4107
WARNING
Improper assembly of manifolds
Improper assembly of manifolds to traditional flange can damage the SuperModule
Platform.
For safe assembly of manifold to traditional flange, bolts must break black plane of flange
web (i.e., bolt hole) but must not contact module housing.
Physical access
Unauthorized personnel may potentially cause significant damage to and/or
misconfiguration of end users’ equipment. This could be intentional or unintentional and
needs to be protected against.
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access by unauthorized personnel to protect end
users’ assets. This is true for all systems used within the facility.
™
5.3Recommended calibration tasks
CAUTION
Absolute pressure transmitters are calibrated at the factory. Trimming adjusts the position
of the factory characterization curve. It is possible to degrade performance of the
transmitter if any trim is done improperly or with inaccurate equipment.
5.3.1
Field installation tasks
Procedure
1. Perform sensor zero/lower trim: Compensate for mounting pressure effects
a) Refer to Install Rosemount 306 integral manifold for manifold operation
instructions to properly drain/vent valves.
2. Set/check basic configuration parameters.
a) Output units
b) Range points
c) Output type
d) Damping value
5.3.2
80Rosemount 2051 Pressure Transmitter
Bench calibration tasks
Procedure
1. Perform optional 4–20 mA 1–5 Vdc output trim.
Reference ManualOperation and Maintenance
00809-0100-4107September 2020
2. Perform a sensor trim.
a) Zero/lower trim Troubleshooting tables using line pressure effect correction.
Refer to Install Rosemount 306 integral manifold for manifold drain/vent
valve operation instructions.
b) Optional full scale trim. Sets the span of the device and requires accurate
calibration equipment.
c) Set/check basic configuration parameters.
5.4Calibration overview
The pressure transmitter is an accurate instrument that is fully calibrated in the factory.
Field calibration is provided to the user to meet plant requirements or industry standards.
Complete calibration of the transmitter can be split into two tasks:
1. Sensor calibration
2. Analog output calibration
5.4.1
5.4.2
Sensor Calibration and Analog Output Calibration.
Sensor calibration allows the user to adjust the pressure (digital value) reported by the
transmitter to be equal to a pressure standard. The sensor calibration can adjust the
pressure offset to correct for mounting conditions or line pressure effects. This correction
is recommended. The calibration of the pressure range (pressure span or gain correction)
requires accurate pressure standards (sources) to provide a full calibration.
Like the Sensor calibration, the analog output can be calibrated to match the user
measurement system. The Analog Output Trim (4–20 mA/ 1–5 V output trim) will
calibrate the loop at the 4 mA (1 V) and 20 mA (5 V) points.
The Sensor calibration and the analog output calibration combine to match the
transmitter’s measurement system to the plant standard.
Calibrate the sensor
• Sensor trim: (Perform a sensor trim )
• Zero trim: (Performing a digital zero trim (option DZ))
Calibrate the 4–20 mA output
• 4–20 mA/1–5V Output trim (Performing digital-to-analog trim (4–20 mA/1–5 V
output trim))
• 4–20 mA/1–5V Output trim using other scale (Performing digital-to-analog trim (4–20
mA/1–5 V output trim) using other scale)
5.4.3
Reference Manual81
Determining necessary sensor trims
Bench calibrations allow for calibrating the instrument for its desired range of operation.
Straight forward connections to pressure source allow for a full calibration at the planned
Operation and MaintenanceReference Manual
September 202000809-0100-4107
operating points. Exercising the Transmitter over the desired pressure range allows for
verification of the analog output. Trim the pressure signal discusses how the trim
operations change the calibration. It is possible to degrade the performance of the
transmitter if a trim is done improperly or with inaccurate equipment. The transmitter can
be set back to factory settings using the Recall factory trim—sensor trim.
For transmitters that are field installed, the manifolds discussed in Rosemount 305, 306,
and 304 Manifolds allow the differential transmitter to be zeroed using the zero trim
function. Both 3-valve and 5-valve manifolds are discussed. This field calibration will
eliminate any pressure offsets caused by mounting effects (head effect of the oil fill) and
static pressure effects of the process.
Determine the necessary trims with the following steps.
Procedure
1. Apply pressure.
2. Check digital pressure, if the digital pressure does not match the applied pressure,
perform a digital trim. See Perform a sensor trim .
3. Check reported analog output against the live analog output. If they do not match,
perform an analog output trim. See Performing digital-to-analog trim (4–20 mA/1–
5 V output trim).
5.4.4
Trimming with configuration buttons
Local configuration buttons are external buttons located underneath the top tag of the
transmitter. There are two possible sets of local configuration buttons that can be ordered
with the transmitter and used to perform trim operations: Digital zero trim and LOI. To
access the buttons, loosen screw and rotate top tag until buttons are visible.
• LOI (M4): Can perform both digital Sensor Trim and the 4–20 mA Output Trim (analog
output trim). Follow the same procedures listed in trimming with Field Communicator
or AMS Device Manager listed below.
• Digital zero trim (DZ): Used for performing a sensor zero trim. See Determining
calibration frequency for trim instructions.
All configuration changes should be monitored by a display or by measuring the loop
output. Figure 5-1 shows the physical differences between the two sets of buttons.
Figure 5-1: Local Configuration Button Options
A. LOI - greeb retainer
B. Digital zero trim - blue retainer
82Rosemount 2051 Pressure Transmitter
Reference ManualOperation and Maintenance
00809-0100-4107September 2020
5.5Determining calibration frequency
Calibration frequency can vary greatly depending on the application, performance
requirements, and process conditions. Use the following procedure to determine
calibration frequency that meets the needs of your application.
Procedure
1. Determine the performance required for your application.
2. Determine the operating conditions.
3. Calculate the Total Probable Error (TPE).
4. Calculate the stability per month.
5. Calculate the calibration frequency.
5.5.1
Sample calculation for Rosemount 2051
Procedure
1. Determine the performance required for your application.
Required Performance0.30% of span
2. Determine the operating conditions.
Transmitter
Calibrated Span150 inH2O (374 mbar)
Ambient Temperature
Change
Line Pressure500 psig (34,5 bar)
3. Calculate total probable error (TPE).
TPE =
of span
Where:
Reference
Accuracy =
± 0.065% of span
Rosemount 2051CD, Range 2 [URL=250
inH2O(623 mbar)]
± 50 °F (28 °C)
= 0.189%
Ambient
Temperature
Effect =
Span Static
Pressure
Effect=
Reference Manual83
Operation and MaintenanceReference Manual
September 202000809-0100-4107
Note
Zero static pressure effect removed by zero trimming at line pressure.
4. Calculate the stability per month.
5. Calculate calibration frequency.
5.5.2Sample calculation for Rosemount 2051C with P8 option
(0.05% accuracy & 5-year stability)
Procedure
1. Determine the performance required for your application.
Required Performance0.30% of span
2. Determine the operating conditions.
Transmitter
Calibrated Span150 inH2O (374 mbar)
Ambient Temperature Change ± 50 °F (28 °C)
Line Pressure500 psig (34,5 bar)
3. Calculate total probable error (TPE).
TPE =
of span
Where:
Reference
Accuracy =
Ambient
Temperature
Effect =
± 0.05% of span
2051CD, Range 2 [URL=250 inH2O(623 mbar)]
= 0.117%
Span Static
Pressure
Effect=
84Rosemount 2051 Pressure Transmitter
Reference ManualOperation and Maintenance
00809-0100-4107September 2020
Note
Zero static pressure effect removed by zero trimming at line pressure.
4. Calculate the stability per month.
5. Calculate calibration frequency.
5.6Compensating for span line pressure effects
(range 4 and 5)
Rosemount 2051 Range 4 and 5 Pressure Transmitters require a special calibration
procedure when used in differential pressure applications. The purpose of this procedure is
to optimize transmitter performance by reducing the effect of static line pressure in these
applications. The Rosemount Differential Pressure Transmitters (ranges 1 through 3) do
not require this procedure because optimization occurs at the sensor.
5.6.1
The systematic span shift caused by the application of static line pressure is –0.95 percent
of reading per 1000 psi (69 bar) for Range 4 transmitters and –1 percent of reading per
1000 psi (69 bar) for Range 5 transmitters. Using the following procedure, you can correct
the span effect to ±0.2 percent of reading per 1000 psi (69 bar) for line pressures from 0 to
3626 psi (0 to 250 bar).
Use the following example to compute correct input values.
Example
To correct for systematic error caused by high static line pressure, first use the following
formulas to determine the corrected values for the high trim value.
High trim value
HT = (URV – [S/100 ×P/1000 × LRV])
Where:
In this example:
URV =
S =–0.95%
HT =Corrected high trim value
URV =Upper range value
S =Span shift per specification (as a percent of reading)
Complete the upper sensor trim procedure as described in #unique_191. However, enter
the calculated correct upper sensor trim value of 1517.1 inH2O with a Field
Communicator.
5.7Trim the pressure signal
5.7.1Sensor trim overview
A sensor trim corrects the pressure offset and pressure range to match a pressure
standard. The upper sensor trim corrects the pressure range and the lower sensor trim
(Zero Trim) corrects the pressure offset. An accurate pressure standard is required for full
calibration. A zero trim can be performed if the process is vented, or the high and low side
pressure are equal (for differential pressure transmitters).
Zero trim is a single-point offset adjustment. It is useful for compensating for mounting
position effects and is most effective when performed with the transmitter installed in its
final mounting position. Since this correction maintains the slope of the characterization
curve, it should not be used in place of a sensor trim over the full sensor range.
When performing a zero trim, ensure the equalizing valve is open and all wet legs are filled
to the correct levels. Line pressure should be applied to the transmitter during a zero trim
to eliminate line pressure errors. Refer to Integral manifold operation.
Note
FOUNDATION Fieldbus has no analog signal that needs ranging. Therefore, ranging a new
device prior to installation is usually not necessary or recommended.
Note
Do not perform a zero trim on Rosemount 2051T Absolute Pressure Transmitters. Zero
trim is zero based, and absolute pressure transmitters reference absolute zero. To correct
mounting position effects on an absolute pressure transmitter, perform a low trim within
the sensor trim function. The low trim function provides an offset correction similar to the
zero trim function, but it does not require zero-based input.
Upper and lower sensor trim is a two-point sensor calibration where two end-point
pressures are applied, all output is linearized between them, and requires an accurate
pressure source. Always adjust the low trim value first to establish the correct offset.
Adjustment of the high trim value provides a slope correction to the characterization curve
based on the low trim value. The trim values help optimize performance over a specific
measurement range.
86Rosemount 2051 Pressure Transmitter
Reference ManualOperation and Maintenance
00809-0100-4107September 2020
Figure 5-2: Sensor Trim Example
A. Before Trim
B. After Trim
5.7.2
Perform a sensor trim
When performing a Sensor Trim, both the upper and lower limits can be trimmed. If both
upper and lower trims are to be performed, the lower trim must be done prior to the upper
time.
Note
Use a pressure input source that is at least four times more accurate than the transmitter,
and allow the input pressure to stabilize for 10 seconds before entering any values.
Performing a sensor trim with a Field Communicator
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field
Communicator to complete the sensor trim.
Device Dashboard Fast Keys
To calibrate the sensor with a Field Communicator using the sensor trim function, perform
the following procedure:
Procedure
1. Select 2: Lower Sensor Trim.
Note
Select pressure points so that lower and upper values are equal to or outside the
expected process operation range. This can be done by going toRerange the
transmitter.
3, 4, 1
2. Follow the commands provided by the Field Communicator to complete the
adjustment of the lower value.
3. Select 3: Upper Sensor Trim.
4. Follow the commands provided by the Field Communicator to complete the
adjustment of the upper value.
Reference Manual87
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
CALIBRAT
ZERO TRIM
LOWER TRIM
UPPER TRIM
ANALOG TRIM
FACTORY RECALL
BACK TO MENU
EXIT MENU
Operation and MaintenanceReference Manual
September 202000809-0100-4107
Performing a sensor trim with AMS Device Manager
Right click the device and, under the Method drop down menu, move cursor over Calibrate
and, under Sensor Trim, select Lower Sensor Trim.
Procedure
1. Follow the screen prompts to perform a sensor trim using AMS Device Manager.
2. If desired, right select the device and under the Method drop down menu, move
cursor over Calibrate and under Sensor Trim and select Upper Sensor Trim.
Performing a sensor trim using LOI
Perform an upper and lower sensor trim by referencing Figure 5-3.
Figure 5-3: Sensor trim with LOI
Performing a digital zero trim (option DZ)
A digital zero trim (option DZ) provides the same function as a zero/lower sensor trim, but
can be completed in hazardous areas at any given time by simply pushing the zero trim
button when the transmitter is at zero pressure. If the transmitter is not close enough to
zero when the button is pushed, the command may fail due to excess correction. If
ordered, a Digital Zero Trim can be performed by utilizing external configuration buttons
located underneath the top tag of the transmitter, see Figure 5-1 for DZ button location.
Procedure
1. Loosen the top tag of the transmitter to expose buttons.
2. Press and hold the digital zero button for at least two seconds, then release to
perform a digital zero Trim.
5.7.3
88Rosemount 2051 Pressure Transmitter
Recall factory trim—sensor trim
The recall factory trim-sensor trim command allows the restoration of the as-shipped
factory settings of the Sensor Trim. This command can be useful for recovering from an
inadvertent zero trim of an absolute pressure unit or inaccurate pressure source.
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
CALIBRAT
ZERO TRIM
LOWER TRIM
UPPER TRIM
ANALOG TRIM
FACTORY RECALL
BACK TO MENU
EXIT MENU
FACTORY RECALL
SENSOR RECALL
ANALOG RECALL
BACK TO MENU
EXIT MENU
Reference ManualOperation and Maintenance
00809-0100-4107September 2020
Recalling factory trim with a Field Communicator
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field
Communicator to complete the sensor trim.
Device Dashboard Fast Keys3, 4, 3
Recalling factory trim with AMS Device Manager
Procedure
1. Right select on the device and, under the Method drop down menu, move cursor
over Calibrate and select Restore Factory Calibration.
2. Set the control loop to manual.
3. Select Next.
4. Select Sensor Trim under Trim to recall and click Next.
5. Follow the screen prompts to recall Sensor Trim.
Recalling factory trim with LOI
Refer to Figure 5-4 to recall factory sensor trim.
Figure 5-4: Recall Factory Trim with LOI
5.8Trim the analog output
The Analog Output Trim commands allow you to adjust the transmitter’s current output
at the 4 and 20 mA (1 – 5 Vdc) points to match the plant standards. This trim is performed
after the digital to analog conversion so only the 4–20 mA analog (1– 5 Vdc) signal will be
affected. Figure 5-5 graphically shows the two ways the characterization curve is affected
when an analog output trim is performed.
Reference Manual89
Operation and MaintenanceReference Manual
September 202000809-0100-4107
Figure 5-5: Analog Output Trim Example
A. Before trim
B. After Trim
5.8.1
Performing digital-to-analog trim (4–20 mA/1–5 V
output trim)
Note
If a resistor is added to the loop, ensure that the power supply is sufficient to power the
transmitter to a 20 mA output with additional loop resistance. Refer to Power supply.
Performing a 4–20 mA/1–5 V output trim with a Field
Communicator
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field
Communicator to complete the 4–20 mA output trim.
Device Dashboard Fast Keys
Performing a 4–20 mA/1–5 V output trim with AMS Device
Manager
Right select the device and, under the Method drop down menu, move cursor over
Calibrate and select Analog Calibration.
Procedure
1. Select Digital to Analog Trim.
2. Follow the screen prompts to perform a 4–20 mA output trim.
3, 4, 2, 1
90Rosemount 2051 Pressure Transmitter
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
CALIBRAT
ZERO TRIM
LOWER TRIM
UPPER TRIM
ANALOG TRIM
FACTORY RECALL
BACK TO MENU
EXIT MENU
Reference ManualOperation and Maintenance
00809-0100-4107September 2020
Performing 4–20 mA/1–5 V output trim using LOI
Figure 5-6: 4–20 mA output trim using LOI
5.8.2Performing digital-to-analog trim (4–20 mA/1–5 V
output trim) using other scale
The scaled 4–20 mA output Trim command matches the 4 and 20 mA points to a user
selectable reference scale other than 4 and 20 mA [for example, 2 to 10 volts if measuring
across a 500 Ω load, or 0 to 100 percent if measuring from a Distributed Control System
(DCS)]. To perform a scaled 4–20 mA output trim, connect an accurate reference meter to
the transmitter and trim the output signal to scale, as outlined in the output trim
procedure.
Performing a 4–20/1–5 V mA output trim using other scale
with a Field Communicator
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field
Communicator to complete the 4–20 mA output trim using other scale.
Device Dashboard Fast Keys
3, 4, 2, 2
Performing a 4–20 mA/ 1–5 V output trim using other scale
with AMS Device Manager
Procedure
1. Right select the device and under the Method drop down menu, move cursor over
Calibrate and select Analog Calibration.
2. Select Scaled Digital to Analog Trim.
3. Follow screen prompts to perform a 4–20 mA/ 1–5 V Output Trim.
Reference Manual91
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
CALIBRAT
ZERO TRIM
LOWER TRIM
UPPER TRIM
ANALOG TRIM
FACTORY RECALL
BACK TO MENU
EXIT MENU
FACTORY RECALL
SENSOR RECALL
ANALOG RECALL
BACK TO MENU
EXIT MENU
Operation and MaintenanceReference Manual
September 202000809-0100-4107
5.8.3Recalling factory trim—analog output
The Recall Factory Trim—Analog Output command allows the restoration of the asshipped factory settings of the analog output trim. This command can be useful for
recovering from an inadvertent trim, incorrect Plant Standard or faulty meter.
Recalling factory trim - analog output with a Field
Communicator
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field
Communicator to complete the digital to analog trim using other scale.
Device Dashboard Fast Keys3, 4, 3
Recalling factory trim - analog output with AMS Device
Manager
Procedure
1. Right select the device and, under the Method drop down menu, move cursor over
Calibrate and select Restore Factory Calibration.
2. Select Next to set the control loop to manual.
3. Select Analog Output Trim under Select trim to recall and click Next.
4. Follow screen prompts to recall analog output trim.
Recalling factory trim - analog output with LOI
Reference Figure 5-7 for LOI instructions.
Figure 5-7: Recall factory Trim – Analog Output with LOI
5.9Switching HART revision
Some systems are not capable of communicating with HART® Revision 7 devices. The
following procedures list how to change HART revisions between HART Revision 7 and
HART Revision 5.
92Rosemount 2051 Pressure Transmitter
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
Reference ManualOperation and Maintenance
00809-0100-4107September 2020
5.9.1Switching HART revision with generic menu
If the HART® configuration tool is not capable of communicating with a HART Revision 7
device, it should load a generic menu with limited capability. The following procedures
allow for switching between HART Revision 7 and HART Revision 5 from a generic menu.
Procedure
1. Locate “Message” field.
2. To change to HART Revision 5, Enter: HART5 in the message field.
3. To change to HART Revision 7, Enter: HART7 in the message field.
5.9.2Switching HART revision with Field Communicator
From the HOME screen, enter the Fast Key sequence and follow steps within the Field
Communicator to complete the HART® revision change.
5.9.3Switching HART revision with AMS Device Manager
Procedure
1. Select Manual Setup and select HART.
2. Select Change HART Revision, then follow the on screen prompts.
Note
AMS Device Manager versions 10.5 or greater are compatible with HART Revision 7.
5.9.4
Switching HART revision with LOI
Navigate to HART® REV within the extended menu and select either HART REV 5 or HARTREV 7. Use Figure 5-8 below to change HART Revision:
Figure 5-8: Change HART Revision with LOI
Reference Manual93
Operation and MaintenanceReference Manual
September 202000809-0100-4107
94Rosemount 2051 Pressure Transmitter
Reference ManualTroubleshooting
00809-0100-4107September 2020
6Troubleshooting
6.1Overview
Table 6-1 and Table 6-2 provide summarized maintenance and troubleshooting
suggestions for the most common operating problems.
If you suspect malfunction despite the absence of any diagnostic messages on the Field
Communicator display, consider using Diagnostic messages to identify any potential
problem.
6.2Safety messages
Procedures and instructions in this section may require special precautions to ensure the
safety of the personnel performing the operation. Refer to the following safety messages
before performing an operation preceded by this symbol.
WARNING
Explosions
Explosions could result in death or serious injury.
Review the approvals section of this manual for any restrictions associated with a safe
installation.
Before connecting a communicator in an explosive atmosphere, ensure the instruments in
the segment are installed in accordance with intrinsically safe or non-incendive field wiring
practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when
power is applied to the unit.
Process leaks
Process leaks may cause harm or result in death.
Install and tighten process connectors before applying pressure.
Electrical shocks
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals.High voltage that my be present on leads can
cause electrical shock.
Replacement equipment or spare parts not approved by Emerson for use as spare
parts could reduce the pressure retaining capabilities of the transmitter and may
render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
Reference Manual95
TroubleshootingReference Manual
September 202000809-0100-4107
WARNING
Improper assembly of manifolds
Improper assembly of manifolds to traditional flange can damage the SuperModule
Platform.
For safe assembly of manifold to traditional flange, bolts must break black plane of flange
web (i.e., bolt hole) but must not contact module housing.
Physical access
Unauthorized personnel may potentially cause significant damage to and/or
misconfiguration of end users’ equipment. This could be intentional or unintentional and
needs to be protected against.
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access by unauthorized personnel to protect end
users’ assets. This is true for all systems used within the facility.
™
6.3Service support
Within the United States, call the Emerson Instrument and Valve Response Center using
the 1-800-654-RSMT (7768) toll-free number. This center, available 24 hours a day, will
assist you with any needed information or materials.
The center will ask for product model and serial numbers, and will provide a Return
Material Authorization (RMA) number. The center will also ask for the process material to
which the product was last exposed.
For inquiries outside of the United States, contact the nearest Emerson representative for
RMA instructions.
To expedite the return process outside of the United States, contact the nearest Emerson
representative.
CAUTION
Individuals who handle products exposed to a hazardous substance can avoid injury if they
are informed of and understand the hazard. The product being returned will require a copy
of the required Safety Data Sheet (SDS) for each substance must be included with the
returned goods.
Emerson Instrument and Valve Response Center representatives will explain the additional
information and procedures necessary to return goods exposed to hazardous substances.
96Rosemount 2051 Pressure Transmitter
Reference ManualTroubleshooting
00809-0100-4107September 2020
6.4Troubleshooting tables
Table 6-1: Rosemount troubleshooting table for 4–20 mA output
SymptomCorrective actions
Transmitter milliamp reading is zeroVerify terminal voltage is 10.5 to 42.4 Vdc at
signal terminals
Check power wires for reversed polarity
Check that power wires are connected to signal
terminals
Check for open diode across test terminal
Transmitter not communicating with
Field Communicator
Transmitter milliamps reading is low or highVerify applied pressure
Transmitter will not respond to changes in
applied pressure
Check that power wires are connected to signal
terminals and not test terminals
Verify clean DC Power to transmitter (Max AC
noise 0.2 volts peak to peak)
Verify the output is between 1–5 Vdc or
saturation levels
Have Field Communicator poll for all addresses
Verify 1–5 Vdc range points
Verify output is not in alarm condition
Perform analog trim
Check that power wires are connected to the
correct signal terminals (positive to positive,
negative to negative) and not the test terminal
Transmitter will not respond to changes in
applied pressure
98Rosemount 2051 Pressure Transmitter
Check impulse piping or manifold for blockage
Reference ManualTroubleshooting
00809-0100-4107September 2020
Table 6-2: Rosemount troubleshooting for 1–5 Vdc output (continued)
SymptomCorrective actions
Verify applied pressure is between the 1–5 Vdc
points
Verify the output is not in alarm condition
Verify transmitter is not in loop test mode
Verify transmitter is not in multidrop mode
Check test equipment
Digital pressure variable reading is low or highCheck impulse piping for blockage or low fill in
wet leg
Verify transmitter is calibrated properly
Check test equipment (verify accuracy)
Verify pressure calculations for application
Digital pressure variable reading is erraticCheck application for faulty equipment in
pressure line
Voltage reading is erraticVerify power source to transmitter has adequate
6.5Diagnostic messages
Listed in the below sections are detailed table of the possible messages that will appear on
either the LCD/LOI display, a Field Communicator, or an AMS Device Manager system. Use
the tables below to diagnose particular status messages.
• Good
• Failed – fix now
• Maintenance – fix soon
• Advisory
Verify transmitter is not reacting directly to
equipment turning on/off
Verify damping is set properly for application
voltage and current
Check for external electrical interference
Verify transmitter is properly grounded
Verify shield for twisted pair is only grounded at
one end
Reference Manual99
TroubleshootingReference Manual
September 202000809-0100-4107
Table 6-3: Status: Failed – Fix Now
Alert nameLCD display
screen
No Pressure
Updates
Electronics
Board Failure
Critical Sensor
Data Error
Critical
Electronics
Data Error
Sensor FailureFAIL SENSORFAIL
Incompatible
Electronics and
Sensor
NO P
UPDATE
FAIL
BOARD
MEMRY
ERROR
XMTR
MSMTCH
LOI screen ProblemRecommended action
NO PRESS
UPDATE
FAIL
BOARD
MEMORY
ERROR
SENSOR
XMTR
MSMTCH
There are no pressure updates
from the sensor to the
electronics
A failure has been detected in
the electronics circuit board
A user written parameter does
not match the expected value
A user written parameter does
not match the expected value
A failure has been detected in
the pressure sensor
The pressure sensor is
incompatible with the
attached electronics
• Ensure the sensor cable connection
to the electronics is tight.
• Replace the transmitter.
• Replace the pressure transmitter.
• Confirm and correct all parameters
listed in Device Information.
• Perform a Device Reset.
• Replace Pressure Transmitter.
• Confirm and correct all parameters
listed in Device Information.
• Perform a Device Reset.
• Replace pressure transmitter.
• Replace pressure transmitter.
• Replace the pressure transmitter.
Table 6-4: Status: Maintenance – Fix Soon
Alert nameLCD display
screen
No
Temperature
Updates
Pressure Out of
Limits
Sensor
Temperature
Beyond Limits
NO T
UPDATE
PRES
LIMITS
TEMP
LIMITS
LOI screenProblemRecommended action
NO TEMP
UPDATE
PRES OUT
LIMITS
TEMP OUT
LIMITS
There are no temperature
updates from the sensor to
the electronics
The pressure is either above or
below the sensor limits
The sensor temperature has
exceeded its safe operating
range
• Ensure the sensor cable connection
to the electronics is tight.
• Replace the pressure transmitter.
• Check the transmitter pressure
connection to ensure it is not
plugged or the isolating diaphragms
are not damaged.
• Replace the pressure transmitter.
• Check the process and ambient
conditions are within –85 to 194 °F
(–65 to 90 °C).
• Replace the pressure transmitter.
100Rosemount 2051 Pressure Transmitter
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.