Rosemount™ 2051 Pressure Transmitter
and Rosemount 2051CF Series Flow
Meter
with PROFIBUS® PA Protocol
Page 2
Quick Start GuideMay 2021
Safety messages
This guide provides basic guidelines for the Rosemount 2051HT Transmitter. It does not provide
instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof,
Flameproof, or intrinsically safe (I.S.) installations.
CAUTION
The products described in this document are NOT designed for nuclear-qualified applications. Using
non-nuclear qualified products in applications that require nuclear-qualified hardware or products may
cause inaccurate readings. For information on Rosemount nuclear-qualified products, contact your
local Emerson Sales Representative.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate
local, national, and international standards, codes, and practices. Review the approvals section of this
manual for any restrictions associated with a safe
• Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments in
the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
• In an explosion-proof/flameproof installation, do not remove the transmitter covers when power
is applied to the unit.
Process leaks may cause harm or result in death.
• Install and tighten process connectors before applying pressure.
• Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
• Before connecting a handheld communicator in an explosive atmosphere, ensure the instruments
in the loop are installed in accordance with intrinsically safe or non-incendive field wiring
practices.
• In an Explosion-Proof/Flameproof installation, do not remove the transmitter covers when power
is applied to the unit.
Process leaks may cause harm or result in death.
• Install and tighten process connectors before applying pressure.
Physical access
• Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of
end users’ equipment. This could be intentional or unintentional and needs to be protected
against.
• Physical security is an important part of any security program and fundamental to protecting your
system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is
true for all systems used within the facility.
2 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
Page 3
May 2021Quick Start Guide
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare parts could
reduce the pressure retaining capabilities of the transmitter and may render the instrument
dangerous.
• Use only bolts supplied or sold by Emerson as spare parts.
Improper assembly of manifolds to traditional flange can damage sensor module.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e., bolt
hole) but must not contact sensor module housing.
Physical access
• Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of
end users’ equipment. This could be intentional or unintentional and needs to be protected
against.
• Physical security is an important part of any security program and fundamental to protecting your
system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is
true for all systems used within the facility.
Contents
Mount the transmitter..................................................................................................................5
4 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
Page 5
May 2021Quick Start Guide
1Mount the transmitter
1.1Liquid applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so the drain/vent valves are oriented upward.
1.2Gas applications
Procedure
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
Quick Start Guide5
Page 6
Quick Start GuideMay 2021
1.3Steam applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
6 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
Page 7
May 2021Quick Start Guide
Figure 1-1: Panel and Pipe Mounting
Panel mount
Coplanar flange
Traditional flange
(1)
Pipe mount
Rosemount 2051T
(1) × 1 panel bolts are customer supplied.
Quick Start Guide7
Page 8
A
4 × 1.75-in.
(44 mm)
D
4 × 1.75-in.
(44 mm)
4 × 2.25-in.
(57 mm)
C
4 × 1.75-in.
(44 mm)
4
× 1.50-in.
(38 mm)
B
4 × 2.88-in.
(73 mm)
Quick Start GuideMay 2021
1.4Bolting considerations
If the transmitter installation requires assembly of the process flanges,
manifolds, or flange adapters, follow the assembly guidelines to ensure a
tight seal for optimal performance characteristics of the transmitters. Use
only bolts supplied with the transmitter or sold by Emerson as spare parts.
Figure 1-2 illustrates common transmitter assemblies with the bolt length
required for proper transmitter assembly.
Figure 1-2: Common Transmitter Assemblies
A. Transmitter with coplanar flange
B. Transmitter with coplanar flange and optional flange adapters
C. Transmitter with traditional flange and optional flange adapters
D. Transmitter with coplanar flange and optional manifold and flange
adapters
Bolts are typically carbon steel (CS) or stainless steel (SST). Confirm the
material by viewing the markings on the head of the bolt and referencing
Table 1-1. If bolt material is not shown in Table 1-1, contact a local Emerson
representative for more information.
Carbon steel bolts do not require lubrication and the stainless steel bolts are
coated with a lubricant to ease installation. However, no additional lubricant
should be applied when installing either type of bolt.
Use the following bolt installation procedure:
Procedure
1. Tighten the bolts by hand.
2. Torque the bolts to the initial torque value using a crossing pattern.
8 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
See Table 1-1 for initial torque value.
Page 9
B7M
316
316
316
SW
316
STM
316
R
B8M
May 2021Quick Start Guide
3. Torque the bolts to the final torque value using the same crossing
pattern. See Table 1-1 for final torque value.
4. Verify the flange bolts are protruding through the sensor module
bolt holes before applying pressure.
Table 1-1: Torque Values for the Flange and Flange Adapter Bolts
Bolt material Head markingsInitial torque Final torque
CS
SST
300 in-lb650 in-lb
150 in-lb300 in-lb
1.5O-rings
The two styles of Rosemount flange adapters (Rosemount
3051/2051/2024/3095) each require a unique O-ring (see Figure 1-3). Use
only the O-ring designed for the corresponding flange adapter.
WARNING
Failure to install proper flange adapter O-rings may cause process leaks,
which can result in death or serious injury. The two flange adapters are
distinguished by unique O-ring grooves. Only use the O-ring that is designed
for its specific flange adapter, as shown below. When compressed, PTFE Orings tend to cold flow, which aids in their sealing capabilities.
Quick Start Guide9
Page 10
Quick Start GuideMay 2021
Figure 1-3: O-rings
A. Flange adapter
B. O-ring
C. PFTE based
D. Elastomer
Note
You should replace PTFE O-rings if you remove the flange adapter.
1.6Environmental seal for housing
Thread sealing (PTFE) tape or paste on male threads of conduit is required to
provide a water/dust tight conduit seal and meets requirements of NEMA
Type 4X, IP66, and IP68. Consult factory if other Ingress Protection ratings
are required.
For M20 threads, install conduit plugs to full thread engagement or until
mechanical resistance is met.
®
1.7
10 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
In-line gage transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage
transmitter is located in the neck of the transmitter, behind the housing. The
vent path is 360° around the transmitter between the housing and sensor.
(See Figure 1-4.)
Keep the vent path free of any obstruction, including but not limited to
paint, dust, and lubrication by mounting the transmitter so fluids can drain
away.
Page 11
A
May 2021Quick Start Guide
Figure 1-4: In-line Gage Low Side Pressure Port
A. Pressure port location
Quick Start Guide11
Page 12
A
Quick Start GuideMay 2021
2Housing rotation
To improve field access to wiring or to better view the optional LCD display
follow the procedure steps.
Figure 2-1: Housing Rotation
A. Housing rotation set screw (5/64-in.)
Procedure
1. Loosen the housing rotation set screw using a 5/64 -in. hex wrench.
2. Rotate the housing clockwise to the desired location.
3. If the desired location cannot be achieved due to thread limit, rotate
the housing counterclockwise to the desired location (up to 360°
from thread limit).
4. Retighten the housing rotation set screw to no more than 7 in-lbs
when desired location is reached.
12 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
Page 13
May 2021Quick Start Guide
3Set jumpers and switches
3.1Security
After the transmitter is configured, you may want to protect the
configuration data from unwarranted changes. Each transmitter is equipped
with a security jumper that can be positioned ON to prevent the accidental
or deliberate change of configuration data. The jumper is labeled “Security”.
The security jumper also prevents changes made using the Local Operator
Interface.
3.2Simulate
The simulate jumper is used in conjunction with the analog input (AI) block.
This jumper is used to simulate the pressure measurement and is used as a
lock-out feature for the AI block. To enable the simulate feature, the jumper
must be moved to the ON position after power is applied. This feature
prevents the transmitter from being accidentally left in simulate mode.
Figure 3-1: Transmitter Jumper Locations
Quick Start Guide13
Page 14
Quick Start GuideMay 2021
4Connect wiring and power up
Use the following steps to wire the transmitter:
Procedure
1. Remove the housing cover on the field terminals side.
2. Connect the power leads to the terminals indicated on the terminal
block label.
3. Power terminals are polarity insensitive - connect positive or negative
to either terminal.
4. Ensure full contact with Terminal Block screw and washer. When
using a direct wiring method, wrap wire clockwise to ensure it is in
place when tightening the terminal block screw.
Note
The use of a pin or a ferrule wire terminal is not recommended as the
connection may be more susceptible to loosening over time or under
vibration.
5. Ensure proper grounding. It is important that the instrument cable
shield:
• Be trimmed close and insulated from touching the transmitter
housing.
• Be connected to the next shield if cable is routed through a
junction box.
• Be connected to a good earth ground at the power supply end.
6. Plug and seal unused conduit connections.
7. If applicable, install wiring with a drip loop. Arrange the drip loop
so the bottom is lower than the conduit connections and the
transmitter housing.
8. Replace the housing cover.
14 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
Page 15
A
B
May 2021Quick Start Guide
Example
Figure 4-1: Terminals
A. Power terminals
B. Ground terminal
Quick Start Guide15
Page 16
B
A
C
DE
G
F
I
I
J
H
Quick Start GuideMay 2021
Figure 4-2: Wiring
A. 6234 ft. (1900 m) maximum (depending on cable characteristics)
B. Integrated power conditioner and filter
C. Terminators
D. Power supply
E. DP/PA coupler/link
F. Trunk
4.1
16 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
G. DP network
H. Signal wiring
I. Spur
J. PROFIBUS PA device
Signal wiring grounding
Do not run signal wiring in conduit or open trays with power wiring, or near
heavy electrical equipment. Grounding terminations are provided on the
outside of the electronics housing and inside the terminal compartment.
These grounds are used when transient protect terminal blocks are installed
or to fulfill local regulations. See step 2 below for more information on how
the cable shield should be grounded.
Page 17
DP
A
B
C
May 2021Quick Start Guide
Procedure
1. Remove the field terminals housing cover.
2. Connect the wiring pair and ground as indicated in Figure 4-3. The
cable shield should:
• Be trimmed close and insulated from touching the transmitter housing.
• Continuously connect to the termination point.
• Be connected to a good earth ground at the power supply end.
Figure 4-3: Wiring
A. Trim shield and insulate
B. Insulate shield
C. Connect shield back to the power supply ground
3. Replace the housing cover. It is recommended that the cover be
tightened until there is no gap between the cover and the housing.
4. Plug and seal unused conduit connections.
4.1.1Power supply
The dc power supply should provide power with less than two percent ripple.
The transmitter requires between 9 and 32 Vdc at the terminals to operate
and provide complete functionality.
4.1.2Power conditioner
The DP/PA coupler/link often includes an integrated power conditioner.
4.1.3Grounding
Transmitters are electrically isolated to 500 Vac rms. Signal wiring cannot be
grounded.
4.1.4Shield wire ground
Shield wire usually requires a single grounding point to avoid creating a
ground loop. The ground point is typically at the power supply.
Quick Start Guide17
Page 18
Quick Start GuideMay 2021
5Basic configuration
5.1Configuration tasks
The transmitter can be configured via either the local operator interface
(LOI) – option code M4, or via a Class 2 master (DD or DTM™ based). The two
basic configuration tasks for the PROFIBUS PA Pressure transmitter are:
Procedure
1. Assign address.
2. Configure engineering units (scaling).
Note
Rosemount 2051 PROFIBUS PA Profile 3.02 devices are set to
identification number adaptation mode when shipped from the
factory. This mode allows the transmitter to communicate with any
PROFIBUS PA control host with either the generic Profile GSD (9700)
or Rosemount 2051 specific GSD (3333) loaded on the host;
therefore, it is not required to change the transmitter identification
number at start-up.
5.1.1Assign address
The Rosemount 2051 Pressure Transmitter is shipped with a temporary
address of 126. This must be changed to a unique value between 0 and 125
in order to establish communication with the host. Usually, addresses 0–2
are reserved for masters or couplers, therefore transmitter addresses
between 3 and 125 are recommended.
Address can be set via either:
• LOI – see Table 5-1 and Figure 5-1
• Class 2 master – see Class 2 Master Manual for setting address
5.1.2Configure engineering units
Unless otherwise requested, the Rosemount 2051 Pressure Transmitter
ships with the following settings:
• Measurement mode: Pressure
• Engineering units: inches H2O
• Scaling: None
Engineering units should be confirmed or configured before installation.
Units can be configured for Pressure, Flow, or Level measurement.
Measurement type, Units, Scaling, and Low Flow Cutoff (when applicable)
can be set via either:
18 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
Page 19
1. ADDRESS
6. IDENTIFICATION #
7. EXIT
4. DAMPING
5. DISPLAY
3. UNITS
2. CALIBRATION
PRESSURE
FLOW
LEVEL
TEMPERATURE
0-126
ZERO
LOWER SENSOR
UPPER SENSOR
RESET FACTORY
May 2021Quick Start Guide
• LOI – see Table 5-1 and Figure 5-1
• Class 2 master – see Table 5-2 for parameter configuration
5.2Configuration tools
5.2.1Local operator interface (LOI)
When ordered, the LOI can be used for commissioning the device. To
activate the LOI, push either configuration button located under the top tag
of the transmitter. See Table 5-1 and Figure 5-1 for operation and menu
information. The security jumper prevents changes made using the LOI.
Note
Buttons must be fully engaged ≈ 0.5-in. (10 mm) of travel.
Table 5-1: LOI Button Operation
Button Action NavigationCharacter EntrySave?
ScrollMoves down menu
categories
EnterSelects menu
category
Changes character
(1)
value
Enters character and
advances
Changes between
Save and Cancel
Saves
(1) Characters blink when they can be changed.
Figure 5-1: LOI Menu
5.3
Class 2 Master
The Rosemount 2051 PROFIBUS DD and DTM files are available at
Emerson.com/Rosemount or by contacting your local salesperson. See Table
5-2 for steps to configure the transmitter for Pressure measurement. See
Rosemount 2051 Reference Manual for Flow or Level configuration
instructions.
Quick Start Guide19
Page 20
Quick Start GuideMay 2021
Table 5-2: Pressure Configuration via Class 2 Master
StepsActions
Set blocks to Out of ServicePut Transducer Block into Out of Service mode
Put Analog Input Block into Out of Service mode
Select Measurement TypeSet Primary Value type to Pressure
Select UnitsSet Engineering Units
• Primary and secondary units must match
Enter ScalingSet Scale In in Transducer Block to 0–100
Set Scale Out in Transducer Block to 0–100
Set PV Scale in Analog Input Block to 0–100
Set Out Scale in Analog Input Block to 0–100
Set Linearization in Analog Input Block to No
Set blocks to AutoPut Transducer Block into Auto mode
Put Analog Input Block into Auto mode
Linearization
5.4Host integration
5.4.1Control host (Class 1)
The Rosemount 2051 device utilizes condensed status as recommended by
the Profile 3.02 specification and NE 107. See Rosemount 2051 Reference
Manual for condensed status bit assignment information.
The appropriate GSD file must be loaded on the control host - Rosemount
2051 specific (rmt3333.gsd) or Profile 3.02 Generic (pa139700.gsd). These
files can be found on Emerson.com/Rosemount or Profibus.com.
5.4.2Configuration host (Class 2)
The appropriate DD or DTM file must be installed in the configuration host.
These files can be found at Emerson.com/Rosemount.
20 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
Page 21
May 2021Quick Start Guide
6Trim the transmitter
Devices are calibrated by the factory. Once installed, it is recommended to
perform a zero trim on the sensor to eliminate error due to mounting
position or static pressure effects.
This can be done by performing a zero trim via:
• LOI – see Table 5-1 and Figure 5-1
• Class 2 master – see Zero trim via Class 2 Master for parameter settings
6.1Zero trim via Class 2 Master
Procedure
1. Place the transducer block into Out of Service (OOS) mode.
2. Apply zero pressure to device and allow to stabilize.
3. Go to Basic Setup > Calibration and set the lower calibration point to
0.0.
4. Place the transducer block to AUTO mode.
Quick Start Guide21
Page 22
Quick Start GuideMay 2021
7Product certifications
7.1Overview
This Appendix contains information on approved manufacturing locations,
European directive information, Ordinary Location certification, Hazardous
Locations Certifications and approval drawings.
7.2European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EU Declaration of
Conformity can be found at Emerson.com/Rosemount.
7.3Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine
that the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health Administration (OSHA).
7.4Hazardous Locations Certifications
Note
Device ambient temperature ratings and electrical parameters may be
limited to the levels dictated by the hazardous location certificate
parameters.
7.5
22 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
North America
E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate
Standards
Markings
I5 USA Intrinsic Safety (IS) and Nonincendive (NI)
Certificate
Standards
FM16US0232
FM Class 3600 – 2011, FM Class 3615 – 2006, FM Class 3616 –
2011, FM Class 3810 – 2005, ANSI/NEMA 250 – 2008,
ANSI/IEC 60529 2004
XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T5
(-50 °C ≤ Ta ≤ +85 °C); Factory Sealed; Type 4X
FM16US0231X (HART®)
FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 –
2004, FM Class 3810 – 2005, ANSI/NEMA 250 – 2008
Page 23
May 2021Quick Start Guide
Markings
IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV
1 when connected per Rosemount drawing 02051-1009; Class
I, Zone 0; AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D; T4 (-50 °C
≤ Ta ≤ +70 °C); Type 4x
Specific Condition of Use:
The Model 2051 transmitter housing contains aluminum and is considered a
potential risk of ignition by impact or friction. Care must be taken into
account during installation and use to prevent impact and friction.
IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV
1 when connected per Rosemount drawing 02051-1009; Class
I, Zone 0; AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D; T4 (-50 °C
≤ Ta ≤ +70 °C); Type 4x
IE USA FISCO
Certificate
Standards
FM16US0231X (HART®)
FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 –
2004, FM Class 3810 – 2005
Markings
IS CL I, DIV 1, GP A, B, C, D when connected per Rosemount
drawing 02051-1009 (-50 °C ≤ Ta ≤ +60 °C); Type 4x
Specific Condition of Use:
The Model 2051 transmitter housing contains aluminum and is considered a
potential risk of ignition by impact or friction. Care must be taken into
account during installation and use to prevent impact and friction.
Explosion-Proof for Class I, Divisions 1, Groups B, C, and D.
Dust-Ignition Proof for Class II and Class III, Division 1, Groups
E, F, and G. Suitable for Class I, Division 2; Groups A, B, C, and
D for indoor and outdoor hazardous locations. Class I Zone 1
Ex d IIC T5. Enclosure type 4X, factory sealed. Single Seal.
Intrinsically safe for Class I, Division 1, Groups A, B, C, and D
when connected in accordance with Rosemount drawing
02051-1008. Ex ia IIC T3C. Single Seal. Enclosure Type 4X
Intrinsically safe for Class I, Division 1, Groups A, B, C, and D
when connected in accordance with Rosemount drawing
02051-1008. Ex ia IIC T3C. Single Seal. Enclosure Type 4X
KEMA 08ATEX0090X
EN 60079-0:2012 + A11:2013, EN 60079-1:2014, EN
60079-26:2015
II 1/2 G Ex db IIC Ga/Gb T6 (–60 °C ≤ Ta ≤ +70 °C), T4/T5 (–
60 °C ≤ Ta ≤ +80 °C)
24 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
Page 25
May 2021Quick Start Guide
Table 7-1: Process Connection Temperature
Temperature classProcess connection
temperature
T6-60 °C to +70 °C-60 °C to +70 °C
T5-60 °C to +80 °C-60 °C to +80 °C
T4-60 °C to +120 °C-60 °C to +80 °C
Ambient temperature
Special Conditions for Safe Use (X):
1. Appropriate cable, glands and plugs need to be suitable for a
temperature of 5 °C greater than maximum specified temperature
for location where installed.
2. Non- standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic build-up
on painted surfaces, and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
3. The device contains a thin wall diaphragm less than 1 mm thickness
that forms a boundary between zone 0 (process connection) and
zone 1 (all other parts of the equipment). The model code and
datasheet are to be consulted for details of the diaphragm material.
Installation, maintenance and use shall take into account the
environmental conditions to which the diaphragm shall be
subjected. The manufacturer's instructions for installation and
maintenance shall be followed in detail to assure safety during its
expected lifetime.
4. Flameproof joints are not intended for repair.
I1 ATEX Intrinsic Safety
Certificate
Standards
Markings
Baseefa08ATEX0129X
EN60079-0:2012+A11:2013, EN60079-11:2012
II 1 G Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +70 °C)
Table 7-2: Input Parameters
HARTFieldbus/PROFIBUS
Voltage U
Current I
Power P
Capacitance C
Quick Start Guide25
i
i
i
i
30 V30 V
200 mA300 mA
1 W1.3 W
0.012 μF0 μF
Page 26
Quick Start GuideMay 2021
Table 7-2: Input Parameters (continued)
HARTFieldbus/PROFIBUS
Inductance L
i
0 mH0 mH
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90V transient suppressor,
it is incapable of withstanding the 500V isolation from earth test and
this must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however care should be taken to protect it
from impact and abrasion when located in Zone 0.
IA ATEX FISCO
Certificate
Standards
Markings
Baseefa08ATEX0129X
EN60079-0:2012+A11:2013, EN60079-11:2012
II 1 G Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +60 °C)
Table 7-3: Input Parameters
FISCO
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
17.5 V
380 mA
5.32 W
0 μF
0 mH
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90V transient suppressor,
it is incapable of withstanding the 500V isolation from earth test and
this must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however care should be taken to protect it
from impact and abrasion when located in Zone 0.
N1 ATEX Type n
Certificate
Standards
Markings
26 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
Baseefa08ATEX0130X
EN60079-0:2012+A11:2013, EN60079-15:2010
II 3 G Ex nA IIC T4 Gc (–40 °C ≤ Ta ≤ +70 °C)
Page 27
May 2021Quick Start Guide
Special Condition for Safe Use (X):
If the equipment is fitted with an optional 90V transient suppressor, it is
incapable of withstanding the 500V electrical strength test as defined in
clause 6.5.1 of by EN 60079-15:2010. This must be taken into account
during installation.
ND ATEX Dust
Certificate
Standards
Baseefa08ATEX0182X
EN60079-0:2012+A11:2013, EN60079-31:2009
Markings
Special Condition for Safe Use (X):
If the equipment is fitted with an optional 90V transient suppressor, it is
incapable of withstanding the 500V isolation from earth test and this must
be taken into account during installation.
Ex db IIC T6...T4 Ga/Gb T6 (-60 °C ≤ Ta ≤ +70 °C), T4/T5 (-60 °C
≤ Ta ≤ +80 °C)
II 1 D Ex ta IIIC T95 °C T
temperature
105 °C Da (–20 °C ≤ Ta ≤ +85 °C)
500
Ambient
temperature
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm less than 1 mm thickness
that forms a boundary between zone 0 (process connection) and
zone 1 (all other parts of the equipment). The model code and
datasheet are to be consulted for details of the diaphragm material.
Installation, maintenance and use shall take into account the
environmental conditions to which the diaphragm shall be
subjected. The manufacturer's instructions for installation and
Quick Start Guide27
Page 28
Quick Start GuideMay 2021
maintenance shall be followed in detail to assure safety during its
expected lifetime.
2. Appropriate cable, glands and plugs need to be suitable for a
temperature of 5 °C greater than maximum specified temperature
for location where installed.
3. Flameproof joints are not intended for repair.
4. Non-standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic build-up
on painted surfaces, and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
I7 IECEx Intrinsic Safety
Certificate
Standards
Markings
IECEx BAS 08.0045X
IEC 60079-0:2011, IEC 60079-11:2011
Ex ia IIC T4 Ga (-60 °C ≤ Ta ≤ +70 °C)
Table 7-5: Input Parameters
HARTFieldbus/PROFIBUS
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
30 V30 V
200 mA300 mA
1 W1.3 W
12 nF0 μF
0 mH0 mH
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90V transient suppressor,
it is incapable of withstanding the 500V isolation from earth test and
this must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however care should be taken to protect it
from impact and abrasion when located in Zone 0.
3. The equipment contains thin wall diaphragms. The installation,
maintenance and use shall take into account the environmental
conditions to which the diaphragms will be subjected. The
manufacturer’s instructions for installation and maintenance shall be
followed in detail to assure safety during its expected lifetime.
28 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
Page 29
May 2021Quick Start Guide
IG IECEx FISCO
Certificate
Standards
Markings
IECEx BAS 08.0045X
IEC60079-0:2011, IEC60079-11:2011
Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +60 °C)
Table 7-6: Input Parameters
FISCO
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
17.5 V
380 mA
5.32 W
0 nF
0 μH
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90V transient suppressor,
it is incapable of withstanding the 500V isolation from earth test and
this must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however care should be taken to protect it
from impact and abrasion when located in Zone 0.
3. The equipment contains thin wall diaphragms. The installation,
maintenance and use shall take into account the environmental
conditions to which the diaphragms will be subjected. The
manufacturer’s instructions for installation and maintenance shall be
followed in detail to assure safety during its expected lifetime.
N7 IECEx Type n
Certificate
Standards
Markings
IECEx BAS 08.0046X
IEC60079-0:2011, IEC60079-15:2010
Ex nA IIC T4 Gc (-40 °C ≤ Ta ≤ +70 °C)
Special Condition for Safe Use (X):
If fitted with a 90V transient suppressor, the equipment is not capable of
withstanding the 500V electrical strength test as defined in clause 6.5.1 of
IEC60079-15:2010. This must be taken into account during installation.
Ex db IIC T6...T4 Ga/Gb IP66, T6 (-60 °C ≤ Ta ≤ +70 °C), T4/T5
(-60 °C ≤ Ta ≤ +80 °C)
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm less than 1 mm thickness
that forms a boundary between zone 0 (process connection) and
zone 1 (all other parts of the equipment). The model code and
datasheet are to be consulted for details of the diaphragm material.
Installation, maintenance and use shall take into account the
environmental conditions to which the diaphragm will be subjected.
The manufacturer's instructions for maintenance shall be followed in
detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic build-up
on painted surfaces, and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
30 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flow Meter Quick Start Guide
i
i
i
i
i
30 V30 V
200 mA300 mA
1 W1.3 W
12 nF0
00
Page 31
May 2021Quick Start Guide
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90 V transient suppressor,
it is incapable of withstanding the 500 V insulation from earth test
and this must be taken into account during installation.
2. The enclosure may be made of aluminium alloy and given a
protective polyurethane paint finish; however care should be taken
to protect it from impact and abrasion when located in atmospheres
that require EPL Ga.
1. If the equipment is fitted with an optional 90 V transient suppressor,
it is incapable of withstanding the 500 V insulation from earth test
and this must be taken into account during installation.
2. The enclosure may be made of aluminium alloy and given a
protective polyurethane paint finish; however care should be taken
to protect it from impact and abrasion when located in atmospheres
that require EPL Ga.
Ga/Gb Ex d IIC X, T5 (–50 °C ≤ Ta ≤ +80 °C), T6 (–50 °C ≤ Ta ≤
+65 °C)
EAEC RU C-US.EX01.B.00175
0Ex ia IIC T4 Ga X (–60 °C ≤ Ta ≤ +70 °C)
K1
Combination of E1, I1, N1, and ND
K2
Combination of E2 and I2
K5
Combination of E5 and I5
K6
Combination of E6 and I6
K7
Combination of E7, I7, N7 and IECEx Dust
IECEx Dust
Certificate
Standards
Markings
Quick Start Guide33
IECEx BAS 08.0058X
IEC60079-0:2011, IEC60079-31:2008
Ex tA IIIC T95 °C T500 105 °C Da (–20 °C ≤ Ta ≤ +85 °C)
Page 34
Quick Start GuideMay 2021
Special Condition for Safe Use (X):
If the equipment is fitted with an optional 90V transient suppressor, it is
incapable of withstanding a 500V isolation from earth test and this must be
taken into account during installation.
KA
KB
KC
KD
KP
KM
Combination of E1, I1, and K6
Combination of K5 and K6
Combination of E1, I1, and K5
Combination of K1, K5, and K6
Combination of EP and IP
Combination of EM and IM
7.14Additional Certifications
SBS American Bureau of Shipping (ABS) Type Approval
Certificate
Intended Use
ABS Rules
SBV Bureau Veritas (BV) Type Approval
Certificate
BV Rules
Application
18-HS1753847-PDA
Marine & Offshore Applications – Measurement of either
Gauge or Absolute Pressure for Liquid, Gas, and Vapor.
Emerson Terms and Conditions of Sale are
available upon request. The Emerson logo
is a trademark and service mark of
Emerson Electric Co. Rosemount is a mark
of one of the Emerson family of
companies. All other marks are the
property of their respective owners.
www.emerson.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.