Rosemount™ 2051 Pressure Transmitter
and Rosemount 2051CF Series Flow
Meter
with 4–20 mA HART® and 1–5 Vdc Low
Power HART Protocol (Revision 5 and 7)
Page 2
Quick Start GuideMay 2021
Safety messages
This guide provides basic guidelines for this product. It does not provide instructions for configuration,
diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe
(I.S.) installations.
CAUTION
The products described in this document are NOT designed for nuclear-qualified applications. Using
non-nuclear qualified products in applications that require nuclear-qualified hardware or products may
cause inaccurate readings. For information on Rosemount nuclear-qualified products, contact your
local Emerson Sales Representative.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate
local, national, and international standards, codes, and practices. Review the approvals section of this
manual for any restrictions associated with a safe
• Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments in
the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
• In an explosion-proof/flameproof installation, do not remove the transmitter covers when power
is applied to the unit.
Process leaks may cause harm or result in death.
• Install and tighten process connectors before applying pressure.
• Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
• Before connecting a handheld communicator in an explosive atmosphere, ensure the instruments
in the loop are installed in accordance with intrinsically safe or non-incendive field wiring
practices.
• In an Explosion-Proof/Flameproof installation, do not remove the transmitter covers when power
is applied to the unit.
Physical access
• Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of
end users’ equipment. This could be intentional or unintentional and needs to be protected
against.
• Physical security is an important part of any security program and fundamental to protecting your
system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is
true for all systems used within the facility.
Replacement equipment or spare parts not approved by Emerson for use as spare parts could
reduce the pressure retaining capabilities of the transmitter and may render the instrument
dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
2Emerson.com/Rosemount
Page 3
May 2021Quick Start Guide
WARNING
Improper assembly of manifolds to traditional flange can damage sensor module.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e., bolt
hole) but must not contact sensor module housing.
Contents
System readiness......................................................................................................................... 5
Mount the transmitter..................................................................................................................7
• If using HART based control or asset management systems, confirm the
HART capability of those systems prior to transmitter installation. Not all
systems are capable of communicating with HART Revision 7 protocol.
This transmitter can be configured for either HART Revision 5 or 7.
• For instructions on how to change the HART Revision of your transmitter,
see Switch HART Revision mode.
1.2Confirm correct device driver
• Verify the correct device driver (DD/DTM™) is loaded on your systems to
ensure proper communications.
• Download the correct device driver at your host vendor download site,
Emerson.com or FieldComm Group.
1.2.1Device revisions and drivers
Table 1-1 provides the information necessary to ensure you have the correct
device driver and documentation for your device.
Table 1-1: Rosemount 2051 FOUNDATION Fieldbus Device Revisions and
Files
Device
revision
(1)
2AllDD4: DD
Quick Start Guide5
HostDevice
AllDD5: DD
Emerson AMS Device
Emerson AMS Device
Emerson 375/475:
driver
(2)
(DD)
Rev 1
Rev 1
Manager V
10.5 or
higher: DD
Rev 2
Manager V
8 to 10.5:
DD Rev 1
DD Rev 2
Obtain atDevice driver
FieldComm
Group
FieldComm
Group
Emerson.com
Emerson.com
FieldCommun
icator.com
(DTM)
Emerson.com 00809-0200-
Reference
document
4101,
Rev BA or
newer
Page 6
Quick Start GuideMay 2021
Table 1-1: Rosemount 2051 FOUNDATION Fieldbus Device Revisions and
Files (continued)
Device
revision
(1)
1AllDD4: DD
HostDevice
driver
(DD)
(2)
Obtain atDevice driver
FieldComm
Rev 4
Group
AllDD5: NAN/A
Emerson AMS Device
Emerson.com
(DTM)
document
Emerson.com 00809-0200-
4101,
Rev BA
Reference
Manager V
8 or higher:
DD Rev 2
Emerson 375/475:
DD Rev 2
FieldCommun
icator.com
(1) FOUNDATION Fieldbus® device revision can be read using a FOUNDATION Fieldbus
capable configuration tool.
(2) Device driver file names use device and DD revision. To access functionality, the
correct device driver must be installed on your control and asset management
hosts, and on your configuration tools.
Figure 1-1: Installation Flowchart
6Emerson.com/Rosemount
Page 7
May 2021Quick Start Guide
2Mount the transmitter
2.1Liquid applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so the drain/vent valves are oriented upward.
2.2Gas applications
Procedure
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
Quick Start Guide7
Page 8
Quick Start GuideMay 2021
2.3Steam applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
8Emerson.com/Rosemount
Page 9
May 2021Quick Start Guide
Figure 2-1: Panel and Pipe Mounting
Panel mount
Coplanar flange
Traditional flange
(1)
Pipe mount
Rosemount 2051T
(1) × 1 panel bolts are customer supplied.
Quick Start Guide9
Page 10
A
4 × 1.75-in.
(44 mm)
D
4 × 1.75-in.
(44 mm)
4 × 2.25-in.
(57 mm)
C
4 × 1.75-in.
(44 mm)
4
× 1.50-in.
(38 mm)
B
4 × 2.88-in.
(73 mm)
Quick Start GuideMay 2021
2.4Bolting considerations
If the transmitter installation requires assembly of the process flanges,
manifolds, or flange adapters, follow the assembly guidelines to ensure a
tight seal for optimal performance characteristics of the transmitters. Use
only bolts supplied with the transmitter or sold by Emerson as spare parts.
Figure 2-2 illustrates common transmitter assemblies with the bolt length
required for proper transmitter assembly.
Figure 2-2: Common Transmitter Assemblies
A. Transmitter with coplanar flange
B. Transmitter with coplanar flange and optional flange adapters
C. Transmitter with traditional flange and optional flange adapters
D. Transmitter with coplanar flange and optional manifold and flange
adapters
Bolts are typically carbon steel (CS) or stainless steel (SST). Confirm the
material by viewing the markings on the head of the bolt and referencing
Table 2-1. If bolt material is not shown in Table 2-1, contact a local Emerson
representative for more information.
Carbon steel bolts do not require lubrication and the stainless steel bolts are
coated with a lubricant to ease installation. However, no additional lubricant
should be applied when installing either type of bolt.
Use the following bolt installation procedure:
Procedure
1. Tighten the bolts by hand.
2. Torque the bolts to the initial torque value using a crossing pattern.
10Emerson.com/Rosemount
See Table 2-1 for initial torque value.
Page 11
B7M
316
316
316
SW
316
STM
316
R
B8M
May 2021Quick Start Guide
3. Torque the bolts to the final torque value using the same crossing
pattern. See Table 2-1 for final torque value.
4. Verify the flange bolts are protruding through the sensor module
bolt holes before applying pressure.
Table 2-1: Torque Values for the Flange and Flange Adapter Bolts
Bolt material Head markingsInitial torque Final torque
CS
SST
300 in-lb650 in-lb
150 in-lb300 in-lb
2.5O-rings
The two styles of Rosemount flange adapters (Rosemount
3051/2051/2024/3095) each require a unique O-ring (see Figure 2-3). Use
only the O-ring designed for the corresponding flange adapter.
WARNING
Failure to install proper flange adapter O-rings may cause process leaks,
which can result in death or serious injury. The two flange adapters are
distinguished by unique O-ring grooves. Only use the O-ring that is designed
for its specific flange adapter, as shown below. When compressed, PTFE Orings tend to cold flow, which aids in their sealing capabilities.
Quick Start Guide11
Page 12
Quick Start GuideMay 2021
Figure 2-3: O-rings
A. Flange adapter
B. O-ring
C. PFTE based
D. Elastomer
Note
You should replace PTFE O-rings if you remove the flange adapter.
2.6Environmental seal for housing
Thread sealing (PTFE) tape or paste on male threads of conduit is required to
provide a water/dust tight conduit seal and meets requirements of NEMA
Type 4X, IP66, and IP68. Consult factory if other Ingress Protection ratings
are required.
For M20 threads, install conduit plugs to full thread engagement or until
mechanical resistance is met.
®
2.7
12Emerson.com/Rosemount
In-line gage transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage
transmitter is located in the neck of the transmitter, behind the housing. The
vent path is 360° around the transmitter between the housing and sensor.
(See Figure 2-4.)
Keep the vent path free of any obstruction, including but not limited to
paint, dust, and lubrication by mounting the transmitter so fluids can drain
away.
Page 13
A
May 2021Quick Start Guide
Figure 2-4: In-line Gage Low Side Pressure Port
A. Pressure port location
Quick Start Guide13
Page 14
A
Quick Start GuideMay 2021
3Housing rotation
To improve field access to wiring or to better view the optional LCD display
follow the procedure steps.
Figure 3-1: Housing Rotation
A. Housing rotation set screw (5/64-in.)
Procedure
1. Loosen the housing rotation set screw using a 5/64 -in. hex wrench.
2. Rotate the housing clockwise to the desired location.
3. If the desired location cannot be achieved due to thread limit, rotate
the housing counterclockwise to the desired location (up to 360°
from thread limit).
4. Retighten the housing rotation set screw to no more than 7 in-lbs
when desired location is reached.
14Emerson.com/Rosemount
Page 15
B
A
May 2021Quick Start Guide
4Set the switches
Set alarm and security switch configuration before installation as shown in
Figure 4-1.
• The alarm switch sets the analog output alarm to high or low.
• Default alarm is high.
• The security switch allows (
) or prevents ( ) any configuration of the
transmitter.
• Default security is off ( ).
Use the following procedure to change the switch configuration:
Procedure
1. If the transmitter is installed, secure the loop, and remove power.
2. Remove the housing cover opposite the field terminal side. Do not
remove the instrument cover in explosive atmospheres when the
circuit is live.
3. Slide the security and alarm switches into the preferred position
using a small screwdriver.
4. Reattach the transmitter cover. The cover must be fully engaged to
comply with explosion-proof requirements.
Example
Figure 4-1: Transmitter Electronics Board
Without LCD display meter
With LOI/LCD display
A. Alarm
B. Security
Quick Start Guide15
Page 16
Quick Start GuideMay 2021
5Connect the wiring and power up
Figure 5-1: Transmitter Wiring Diagrams (4–20 mA)
Aluminum
Polished 316 SST
A. 24 Vdc supply
B. RL ≥ 250
C. Current meter (optional)
Shielded twisted pair cable should be used for best results. Use 24 AWG or
larger wire that does not exceed 5,000 ft. (1500 m) in length. If applicable,
install wiring with a drip loop. Arrange the drip loop so the bottom is lower
than the conduit connections and the transmitter housing.
16Emerson.com/Rosemount
Page 17
May 2021Quick Start Guide
CAUTION
• Installation of the transient protection terminal block does not provide
transient protection unless the Rosemount 2051HT case is properly
grounded.
• Do not run signal wiring in conduit or open trays with power wiring, or
near heavy electrical equipment.
• Do not connect the powered signal wiring to the test terminals. Power
could damage the test diode in the terminal block.
Use the following steps to wire the transmitter:
Procedure
1. Remove the housing cover on the FIELD TERMINALS side.
2. Connect the positive lead to the “+” terminal (PWR/COMM) and the
negative lead to the “–” terminal.
3. Ensure full contact with Terminal Block screw and washer. When
using a direct wiring method, wrap wire clockwise to ensure it is in
place when tightening the terminal block screw.
Note
The use of a pin or a ferrule wire terminal is not recommended as the
connection may be more susceptible to loosening over time or under
vibration
4. Ground housing to fulfill local grounding regulations.
5. Ensure proper grounding. It is important the instrument cable shield
be:
• Trimmed close and insulated from touching the transmitter
housing
• Connected to the next shield if cable is routed through a junction
box
• Connected to a good earth ground at the power supply end
6. If transient protection is needed, refer to section “Grounding for
transient terminal block” for grounding instructions.
7. Plug and seal unused conduit connections.
8. Reattach the transmitter covers. It is recommended that the cover be
tightened until there is no gap between the cover and the housing.
The covers must only be capable of being released or removed with
the aid of a tool to comply with applicable ordinary locations
requirements.
Quick Start Guide17
Page 18
DP
A
B
D
E
C
DP
A
B
D
E
C
Quick Start GuideMay 2021
Figure 5-2: Wiring
AluminumPolished 316 SST
A. Minimize distance
B. Trim shield and insulate
C. Protective grounding terminal
D. Insulate shield
E. Connect shield back to the power supply ground
5.1Grounding for transient terminal block
Ground termination is provided on the outside of the electronics housing
and inside the terminal compartment. These grounds are used when the
transient protection terminal blocks are installed. It is recommended that 18
AWG or larger wire is used to connect housing ground to earth ground
(internal or external).
If the transmitter is currently not wired for power up and communication,
follow Connect the wiring and power up step Step 1 through Step 8. When
the transmitter is properly wired, refer to Figure 5-2 for internal and external
transient grounding locations.
Note
The Rosemount 2051HT polished 316 SST housing only provides ground
termination inside the terminal compartment.
18Emerson.com/Rosemount
Page 19
May 2021Quick Start Guide
6Verify configuration
Verify the configuration using any HART-capable configuration tool or Local
Operator Interface (LOI) - option code M4. Configuration instructions for a
Field Communicator and LOI are included in this step.
6.1Verifying configuration with a Field Communicator
A Rosemount 2051 DD must be installed on the Field Communicator to
verify configuration. Fast Key sequences for the latest DD are shown in Table
6-1. For Fast Key sequences using legacy DD's, contact your local Emerson
representative.
Note
Emerson recommends installing the latest DD to access the complete
functionality. Visit Emerson.com/Field-Communicator for information on
updating the DD Library.
Procedure
1. Verify device configuration using the Fast Key sequences in Table
6-1.
2. A check (✓) indicates the basic configuration parameters. At
minimum, these parameters should be verified as part of
configuration and startup.
Table 6-1: Device Revision 9 and 10 (HART 7), DD Revision 1 Fast
Key Sequence
Table 6-1: Device Revision 9 and 10 (HART 7), DD Revision 1 Fast
Key Sequence (continued)
FunctionHART 7HART 5
Disable Configuration Buttons2, 2, 6, 32, 2, 6, 3
Rerange with Keypad2, 2, 2, 12, 2, 2, 1
Loop Test3, 5, 13, 5, 1
Lower Sensor Trim3, 4, 1, 23, 4, 1, 2
Message2, 2, 7, 1, 62, 2, 7, 1, 5
Scaled D/A Trim (4–20 mA
output)
Sensor Temperature/Trend3, 3, 23, 3, 2
Upper Sensor Trim3, 4, 1, 13, 4, 1, 1
Digital Zero Trim3, 4, 1, 33, 4, 1, 3
Password2, 2, 6, 52, 2, 6, 4
Scaled Variable3, 2, 23, 2, 2
HART Revision 5 to HART
Revision 7 switch
Long Tag
Find Device
Simulate Digital Signal
(1)
(1)
(1)
3, 4, 23, 4, 2
2, 2, 5, 2, 32, 2, 5, 2, 3
2, 2, 7, 1, 2N/A
3, 4, 5N/A
3, 4, 5N/A
(1) Only available in HART Revision 7 mode.
6.2
Verifying configuration with LOI
The optional LOI can be used for commissioning the device. The LOI is a twobutton design with internal and external/rear buttons. On a polished
stainless steel housing, buttons are located internally both on the display
and terminal side of the transmitter. On an aluminum housing, buttons are
located on the display and externally underneath the top metal tag. To
activate the LOI, push any button. LOI button functionality is shown on the
bottom corners of the display. See Table 6-2 and Figure 6-1 for button
operation and menu information.
20Emerson.com/Rosemount
Page 21
Assign PV
HART Revision
May 2021Quick Start Guide
Table 6-2: LOI Button Operation
Button
LeftNoSCROLL
RightYesENTER
Figure 6-1: LOI Menu
6.3Switch HART Revision mode
If the HART configuration tool is not capable of communicating with HART
Revision 7, the Rosemount 2051 will load a generic menu with limited
capability. The following procedures will switch the HART Revision mode
from the generic menu:
Procedure
Navigate to Manual Setup → Device Information → Identification →
Message
a) To change to HART Revision 5, Enter: HART5 in the Message field.
b) To change to HART Revision 7, Enter: HART7 in the Message field.
Quick Start Guide21
Page 22
Quick Start GuideMay 2021
Note
See Table 6-1 to change HART Revision when the correct device driver is
loaded.
22Emerson.com/Rosemount
Page 23
May 2021Quick Start Guide
7Trim the transmitter
Devices are calibrated by the factory. Once installed, it is recommended to
perform a zero trim on gage transmitters to eliminate error due to mounting
position or static pressure effects. A zero trim can be performed using either
a Field Communicator or configuration buttons.
Note
When performing a zero trim, ensure the equalization valve is open and all
wet legs are filled to the correct level.
CAUTION
It is not recommended to zero an absolute transmitter, Rosemount
2051HTA model.
Procedure
Choose your trim procedure.
a) Analog zero trim – Sets the analog output to 4 mA.
b) Also referred to as a “rerange,” it sets the lower range value (LRV)
equal to the measured pressure.
c) The display and digital HART output remains unchanged.
d) Digital zero trim – Recalibrates the sensor zero.
e) The LRV is unaffected. The pressure value will be zero (on display and
HART output). 4 mA point may not be at zero.
f) This requires the factory calibrated zero pressure is within a range of
3% of the URV [0 ± 3% x URV].
Example
URV = 250 inH2O Applied Zero Pressure = ± 0.03 x 250 inH2O = ± 7.5 inH2O
(compared to factory settings) values outside this range will be rejected by
the transmitter
7.1
Quick Start Guide23
Trimming with a Field Communicator
Procedure
1. Connect the Field Communicator, see Connect the wiring and power
up for instructions.
2. Follow the HART menu to perform the desired zero trim.
Page 24
Quick Start GuideMay 2021
Analog zero (set 4 mA) Digital zero
Fast Key sequence3, 4, 23, 4, 1, 3
7.2Trimming with configuration buttons
A zero trim is to be performed using one of the three possible sets of
configuration buttons located above the terminal block or under the top
tag.
To access the configuration buttons on a polished stainless steel housing,
remove the terminal side housing cover.
To access the configuration buttons on an aluminum housing, loosen the
screw on the top tag and slide the tag on the top of the transmitter.
Figure 7-1: External or Rear/Terminal-Side Configuration Buttons
(1)
LOI
Analog zero and
span
Digital zeroAluminum
Polished 316 SST
24Emerson.com/Rosemount
Page 25
May 2021Quick Start Guide
A. Configuration buttons
(1) LOI buttons (option M4) only offer front facing buttons on SST housing (option
1). Options D4 and DZ can still be purchased for rear/terminal-side facing
buttons.
Use one of the following procedures to perform a zero trim:
7.2.1Perform trim with LOI (option M4)
Procedure
1. Set the transmitter pressure.
2. See Figure 6-1 for the operating menu.
a) Perform an analog zero trim by selecting Rerange.
b) Perform a digital zero trim by selecting Zero Trim.
7.2.2Perform trim with analog zero and span (option D4)
Procedure
1. Set the transmitter pressure.
2. Press and hold the Zero button for two seconds to perform an analog
zero trim.
7.2.3Perform trim with digital zero (option DZ)
Procedure
1. Set the transmitter pressure.
2. Press and hold the Zero button for two seconds to perform a digital
zero trim.
Quick Start Guide25
Page 26
Quick Start GuideMay 2021
8Safety instrumented systems
For safety certified installations, refer to the Rosemount 2051 Reference
Manual for installation procedure and system requirements.
26Emerson.com/Rosemount
Page 27
May 2021Quick Start Guide
9Product certifications
9.1European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EU Declaration of
Conformity can be found at EmersonProcess.com/Rosemount.
9.2Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine
that the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health Administration (OSHA).
9.3Hazardous Locations Certifications
Note
Device ambient temperature ratings and electrical parameters may be
limited to the levels dictated by the hazardous location certificate
parameters.
9.4North America
E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate:
Standards:
Markings:
I5 USA Intrinsic Safety (IS) and Nonincendive (NI)
Certificate:
Standards:
Markings:
Quick Start Guide27
FM16US0232
FM Class 3600 - 2011, FM Class 3615 - 2006, FM Class 3616 2011, FM Class 3810 - 2005, ANSI/NEMA 250 - 2008. ANSI/IEC
60529 2004
XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III;
T5(-50 °C ≤ Ta ≤ +85 °C); Factory Sealed; Type 4X
FM16US0231X (HART®)
FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 2004, FM Class 3810 - 2005, ANSI/NEMA 250 - 2008
IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV
1 when connected per Rosemount drawing 02051-1009;
Class I, Zone 0; AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D;
T4(-50 °C ≤ Ta ≤ +70 °C); Type 4x
Page 28
Quick Start GuideMay 2021
Specific Conditions of Use:
The Model 2051 transmitter housing contains aluminum and is considered a
potential risk of ignition by impact or friction. Care must be taken into
account during installation and use to prevent impact and friction.
Certificate:
Standards:
2041384 (HART/Fieldbus/Profibus®)
FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 2004, FM Class 3810 - 2005, ANSI/NEMA 250 - 2008
Markings:
IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV
1 when connected per Rosemount drawing 02051-1009;
Class I, Zone 0; AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D; T4
(-50 °C ≤ Ta ≤ +70 °C); Type 4x
IE USA FISCO
Certificate:
Standards:
FM16US0231X (HART®)
FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 2004, FM Class 3810 - 2005
Markings:
IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV
1 when connected per Rosemount drawing 02051-1009;
Class I, Zone 0; AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D; T4
(-50 °C ≤ Ta ≤ +60 °C); Type 4x
Specific Conditions of Use:
The Model 2051 transmitter housing contains aluminum and is considered a
potential risk of ignition by impact or friction. Care must be taken into
account during installation and use to prevent impact and friction.
Explosion-Proof for Class I, Divisions 1, Groups B, C, and D.
Dust-Ignition Proof for Class II and Class III, Division 1, Groups
E, F, and G. Suitable for Class I, Division 2; Groups A, B, C, and
D for indoor and outdoor hazardous locations. Class I Zone 1
Ex d IIC T5. Enclosure type 4X, factory sealed. Single Seal.
Intrinsically safe for Class I, Division 1, Groups A, B, C, and D
when connected in accordance with Rosemount drawing
02051-1008. Ex ia IIC T3C. Single Seal. Enclosure Type 4X
Intrinsically safe for Class I, Division 1, Groups A, B, C, and D
when connected in accordance with Rosemount drawing
02051-1008. Ex ia IIC T3C. Single Seal. Enclosure Type 4X
9.5Europe
E1 ATEX Flameproof
Certificate:
Standards:
Markings:
Table 9-1: Process Connection Temperature
Temperature classProcess connection
T6-60 °C to +70 °C-60 °C to +70 °C
T5-60 °C to +80 °C-60 °C to +80 °C
Quick Start Guide29
KEMA 08ATEX0090X
EN 60079-0:2012 + A11:2013, EN 60079-1:2014, EN
60079-26:2015
II 1/2 G Ex db IIC Ga/Gb T6 (-60 °C ≤ Ta ≤ +70 °C), T4/T5 (-60
°C ≤Ta≤ +80 °C)
Ambient temperature
temperature
Page 30
Quick Start GuideMay 2021
Table 9-1: Process Connection Temperature (continued)
Temperature classProcess connection
temperature
T4-60 °C to +120 °C-60 °C to +80 °C
Ambient temperature
Special Conditions for Safe Use (X):
1. Appropriate cable, glands and plugs need to be suitable for a
temperature of 5 °C greater than maximum specified temperature
for location where installed.
2. Non- standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic build-up
on painted surfaces, and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
3. The device contains a thin wall diaphragm less than 1 mm thickness
that forms a boundary between zone 0 (process connection) and
zone 1 (all other parts of the equipment). The model code and
datasheet are to be consulted for details of the diaphragm material.
Installation, maintenance and use shall take into account the
environmental conditions to which the diaphragm shall be
subjected. The manufacturer's instructions for installation and
maintenance shall be followed in detail to assure safety during its
expected lifetime.
4. Flameproof joints are not intended for repair.
I1 ATEX Intrinsic Safety
Certificate:
Standards:
Markings:
Baseefa08ATEX0129X
EN60079-0:2012+A11:2013, EN60079-11:2012
II 1 G Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +70 °C)
Table 9-2: Input Parameters
®
HART
Voltage U
Current I
Power P
i
Capacitance Ci0.012 μF0 μF
Inductance Li0 mH0 mH
30Emerson.com/Rosemount
30 V30 V
i
200 mA300 mA
i
1 W1.3 W
Fieldbus/
PROFIBUS
®
Page 31
May 2021Quick Start Guide
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90V transient suppressor,
it is incapable of withstanding the 500V isolation from earth test and
this must be taken into account during installation
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however care should be taken to protect it
from impact and abrasion when located in Zone 0.
IA ATEX FISCO
Certificate:
Standards:
Markings:
Baseefa08ATEX0129X
EN60079-0:2012+A11:2013, EN60079-11:2012
II 1 G Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +60 °C)
Table 9-3: Input Parameters
FISCO
Voltage U
Current I
Power P
i
Capacitance Ci0 μF
Inductance Li0 mH
17.5 V
i
380 mA
i
5.32 W
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90V transient suppressor,
it is incapable of withstanding the 500V isolation from earth test and
this must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however care should be taken to protect it
from impact and abrasion when located in Zone 0.
N1 ATEX Type n
Certificate:
Standards:
Markings:
Baseefa08ATEX0130X
EN60079-0:2012+A11:2013, EN60079-15:2010
II 3 G Ex nA IIC T4 Gc (–40 °C ≤ Ta ≤ +70 °C)
Special Condition for Safe Use (X):
If the equipment is fitted with an optional 90V transient suppressor, it is
incapable of withstanding the 500V electrical strength test as defined in
Quick Start Guide31
Page 32
Quick Start GuideMay 2021
clause 6.5.1 of by EN 60079-15:2010. This must be taken into account
during installation.
ND ATEX Dust
Certificate:
Standards:
Baseefa08ATEX0182X
EN60079-0:2012+A11:2013, EN60079-31:2009
Markings:
Special Condition for Safe Use (X):
If the equipment is fitted with an optional 90V transient suppressor, it is
incapable of withstanding the 500V isolation from earth test and this must
be taken into account during installation.
Ex db IIC T6…T4 Ga/Gb T6 (-60 °C ≤ Ta ≤ +70 °C), T5/T5 (-60 °C
≤ Ta ≤ +80 °C)
II 1 D Ex ta IIIC T95 °C T
temperature
105 °C Da (–20 °C ≤ Ta ≤ +85 °C)
500
Ambient
temperature
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm less than 1 mm thickness
that forms a boundary between zone 0 (process connection) and
zone 1 (all other parts of the equipment). The model code and
datasheet are to be consulted for details of the diaphragm material.
Installation, maintenance and use shall take into account the
environmental conditions to which the diaphragm shall be
subjected. The manufacturer's instructions for installation and
maintenance shall be followed in detail to assure safety during its
expected lifetime.
32Emerson.com/Rosemount
Page 33
May 2021Quick Start Guide
2. Appropriate cable, glands and plugs need to be suitable for a
temperature of 5 °C greater than maximum specified temperature
for location where installed.
3. Flameproof joints are not intended for repair.
4. Non-standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic build-up
on painted surfaces, and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
I7 IECEx Intrinsic Safety
Certificate:
Standards:
Markings:
IECEx BAS 08.0045X
IEC 60079-0:2011, IEC 60079-11:2011
Ex ia IIC T4 Ga (-60 °C ≤ Ta ≤ +70 °C)
Table 9-5: Input Parameters
HARTFieldbus/PROFIBUS
Voltage U
Current I
Power P
i
Capacitance Ci12 nF0 μF
Inductance Li0 mH0 mH
30 V30 V
i
200 mA300 mA
i
1 W1.3 W
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90V transient suppressor,
it is incapable of withstanding the 500V isolation from earth test and
this must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however care should be taken to protect it
from impact and abrasion when located in Zone 0.
3. The equipment contains thin wall diaphragms. The installation,
maintenance and use shall take into account the environmental
conditions to which the diaphragms will be subjected. The
manufacturer’s instructions for installation and maintenance shall be
followed in detail to assure safety during its expected lifetime.
IG IECEx FISCO
Certificate:
Quick Start Guide33
IECEx BAS 08.0045X
Page 34
Quick Start GuideMay 2021
Standards:
Markings:
IEC60079-0:2011, IEC60079-11:2011
Ex ia IIC T4 Ga (-60 °C ≤Ta ≤ +60 °C)
Table 9-6: Input Parameters
FISCO
Voltage U
Current I
Power P
i
Capacitance Ci0 nF
Inductance Li0 μH
17.5 V
i
380 mA
i
5.32 W
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90V transient suppressor,
it is incapable of withstanding the 500V isolation from earth test and
this must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however care should be taken to protect it
from impact and abrasion when located in Zone 0.
3. The equipment contains thin wall diaphragms. The installation,
maintenance and use shall take into account the environmental
conditions to which the diaphragms will be subjected. The
manufacturer’s instructions for installation and maintenance shall be
followed in detail to assure safety during its expected lifetime.
N7 IECEx Type n
Certificate:
Standards:
Markings:
IECEx BAS 08.0046X
IEC60079-0:2011, IEC60079-15:2010
Ex nA IIC T4 Gc (-40 °C ≤Ta ≤ +70 °C)
Special Condition for Safe Use (X):
If fitted with a 90V transient suppressor, the equipment is not capable of
withstanding the 500V electrical strength test as defined in clause 6.5.1 of
IEC60079-15:2010. This must be taken into account during installation.
Ex db IIC T6…T4 Ga/Gb IP66, T6 (-60 °C ≤Ta ≤ +70 °C), T4/T5
(-60 °C ≤Ta ≤ +80 °C)
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm less than 1 mm thickness
that forms a boundary between zone 0 (process connection) and
zone 1 (all other parts of the equipment). The model code and
datasheet are to be consulted for details of the diaphragm material.
Installation, maintenance and use shall take into account the
environmental conditions to which the diaphragm will be subjected.
The manufacturer's instructions for maintenance shall be followed in
detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic build-up
on painted surfaces, and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
1. If the equipment is fitted with an optional 90 V transient suppressor,
it is incapable of withstanding the 500 V insulation from earth test
and this must be taken into account during installation.
Quick Start Guide35
Page 36
Quick Start GuideMay 2021
2. The enclosure may be made of aluminium alloy and given a
protective polyurethane paint finish; however care should be taken
to protect it from impact and abrasion when located in atmospheres
that require EPL Ga.
1. If the equipment is fitted with an optional 90 V transient suppressor,
it is incapable of withstanding the 500 V insulation from earth test
and this must be taken into account during installation.
2. The enclosure may be made of aluminium alloy and given a
protective polyurethane paint finish; however care should be taken
to protect it from impact and abrasion when located in atmospheres
that require EPL Ga.
9.8
China
E3 China Flameproof
Certificate:
Standards:
Markings
GYJ18.1432X; GYJ20.1485X [Flowmeters]
GB3836.1-2010, GB3836.2-2010, GB3836.20-2010-2010
Pressure Transmitter: Ex d IIC Gb, T6~T4 Ga/Gb
Flowmeter: Ex d IIC T5/T6 Ga/Gb
Ga/Gb Ex d IIC X, T5(-50 °C ≤ Ta ≤ +80 °C), T6(-50 °C ≤ Ta ≤ +65
°C)
IM EAC Intrinsically Safe
Certificate:
Markings:
Special Condition for Safe Use (X):
See certificate for special conditions.
9.12
38Emerson.com/Rosemount
Combinations
K1
Combination of E1, I1, N1, and ND
K2
Combination of E2 and I2
K5
Combination of E5 and I5
K6
Combination of E6 and I6
EAEC RU C-US.EX01.B.00175
0Ex ia IIC T4 Ga X (-60 °C ≤ Ta ≤ +70 °C)
Page 39
May 2021Quick Start Guide
K7
Combination of E7, I7, N7 and IECEx Dust
IECEx Dust
Certificate
Standards
Markings
Special Condition for Safe Use (X):
If the equipment is fitted with an optional 90V transient suppressor, it is
incapable of withstanding a 500V isolation from earth test and this must be
taken into account during installation.
KA
KB
KC
KD
KP
KM
IECEx BAS 08.0058X
IEC60079-0:2011, IEC60079-31:2008
Ex tA IIIC T95 °C T500 105 °C Da (–20 °C ≤ Ta ≤ +85 °C)
Combination of E1, I1, and K6
Combination of K5 and K6
Combination of E1, I1, and K5
Combination of K1, K5, and K6
Combination of EP and IP
Combination of EM and IM
9.13Additional Certifications
SBS American Bureau of Shipping (ABS) Type Approval
Certificate
Intended Use
ABS Rules
18-HS1753847-PDA
Marine & Offshore Applications – Measurement of either
Gauge or Absolute Pressure for Liquid, Gas, and Vapor.
Emerson Terms and Conditions of Sale are
available upon request. The Emerson logo
is a trademark and service mark of
Emerson Electric Co. Rosemount is a mark
of one of the Emerson family of
companies. All other marks are the
property of their respective owners.
www.emerson.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.