Rosemount 2051HT Hygienic Pressure Transmitter with FOUNDATION Fieldbus Quick Start Guide

Quick Start Guide
00825-0200-4591, Rev BA
November 2019
Rosemount™ 2051HT Hygienic Pressure Transmitter
with FOUNDATION™ Fieldbus Protocol
Quick Start Guide November 2019
Contents
About this guide...........................................................................................................................3
System readiness......................................................................................................................... 6
Transmitter installation................................................................................................................ 7
Product certifications................................................................................................................. 23
2 Rosemount 2051HT
November 2019 Quick Start Guide

1 About this guide

1.1 Safety messages

This guide provides basic guidelines for the Rosemount 2051HT Transmitter. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations.
CAUTION
The products described in this document are NOT designed for nuclear­qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings. For information on Rosemount nuclear-qualified products, contact your local Emerson Sales Representative.
Quick Start Guide 3
Quick Start Guide November 2019
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the approvals section of this manual for any restrictions associated with a safe
Before connecting a Field Communicator in an explosive atmosphere,
ensure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the
transmitter covers when power is applied to the unit.
Process leaks may cause harm or result in death.
Install and tighten process connectors before applying pressure.
Do not attempt to loosen or remove flange bolts while the transmitter is
in service.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be
present on leads can cause electrical shock.
Before connecting a handheld communicator in an explosive
atmosphere, ensure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In an Explosion-Proof/Flameproof installation, do not remove the
transmitter covers when power is applied to the unit.
Process leaks may cause harm or result in death.
Install and tighten process connectors before applying pressure.
Physical access
Unauthorized personnel may potentially cause significant damage to
and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and
fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
4 Rosemount 2051HT
November 2019 Quick Start Guide
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
Improper assembly of manifolds to traditional flange can damage sensor module.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e., bolt hole) but must not contact sensor module housing.
Physical access
Unauthorized personnel may potentially cause significant damage to
and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and
fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
Quick Start Guide 5
Quick Start Guide November 2019

2 System readiness

2.1 Confirm correct device driver

Verify the latest device driver (DD/DTM™) is loaded on your systems to
ensure proper communications.
Download the latest device driver at Emerson.com or
FieldCommGroup.org.

2.1.1 Device revisions and drivers

Table 2-1 provides the information necessary to ensure you have the correct
device driver and documentation for your device.
Table 2-1: FOUNDATION Fieldbus Device Revisions and Files
Device Revision
(1)
2 All DD4: DD Rev 1 FieldCommGrou
(1) FOUNDATION Fieldbus device revision can be read using a FOUNDATION Fieldbus capable
(2) Device driver file names use device and DD revision. To access functionality, the correct
Host Device driver
All DD5: DD Rev 1 FieldCommGrou
Emerson AMS Device
Emerson AMS Device
Emerson Field
configuration tool.
device driver must be installed on your control and asset management hosts, and on your configuration tools.
(2)
(DD)
Manager V 10.5 or higher: DD Rev 2
Manager V 8 to
10.5: DD Rev 1
Communicator: DD Rev 2
Obtain at Device driver
(DTM)
Emerson.com Rosemount
p.org
p.org
Emerson.com
Emerson.com
Easy upgrade utility
Manual Document Number
2051 Pressure Transmitter
Reference Manual or
newer
6 Rosemount 2051HT
Start
Mount the
transmitter
Commissioning
tag
Done
Zero trim the
transmitter
Configuration
Grounding, wiring,
and power up
Set switches and
software write lock
Locate device
November 2019 Quick Start Guide

3 Transmitter installation

Figure 3-1: Installation Flowchart

3.1 Mount the transmitter

Adjust the transmitter to desired orientation before mounting. Transmitter must not be securely mounted or clamped in place when changing transmitter orientation.

3.1.1 Conduit entry orientation

When installing a Rosemount 2051HT, it is recommended installing so a conduit entry faces downward toward the ground to maximize drainability when cleaning.

3.1.2 Environmental seal for housing

Thread sealing (PTFE) tape or paste on male threads of conduit is required to provide a water/dust tight conduit seal and meets requirements of NEMA Type 4X, IP66, IP68, and IP69K. Consult factory if other Ingress Protection ratings are required.
For M20 threads, install conduit plugs to full thread engagement or until mechanical resistance is met.
Note
IP69K rating only available on units with a SST housing and option code V9 in the model string.
Note
For aluminum housings ordered with M20 conduit entries, transmitters shipped will have NPT threads machined into the housing and a NPT to M20
Quick Start Guide 7
thread adapter will be provided. Considerations for environmental sealing listed above should be taken into account when installing the thread adapter.
®
A
Quick Start Guide November 2019

3.1.3 In-line gage transmitter orientation

The low side pressure port (atmospheric reference) on the in-line gage transmitter is located on the neck of the transmitter via a protected gage vent (See Figure 3-2).
Keep the vent path free from obstructions including but not limited to paint, dust, and viscous fluids by mounting the transmitter so the process can drain away. Recommended installations have a conduit entry facing the ground so the gage vent port is pointing parallel to the ground.
Figure 3-2: In-line Protected Gage Vent Low Side Pressure Port
Aluminum Polished 316 SST
A. Low side pressure port (atmospheric reference)

3.1.4 Clamping

When installing clamp, follow recommended torque values provided by gasket manufacturer.
Note
To maintain performance, torquing a 1.5. Tri-Clamp® beyond 50 in-lb is not recommended on pressure ranges below 20 psi.
3.2
8 Rosemount 2051HT

Commissioning (paper) tag

To identify which device is at a particular location use the removable tag provided with the transmitter. Ensure the physical device tag (PD tag field) is properly entered in both places on the removable commissioning tag and tear off the bottom portion for each transmitter.
November 2019 Quick Start Guide
Note
The device description loaded in the host system must be at the same revision as this device.
Figure 3-3: Commissioning Tag
A. Device revision
Note
The device description loaded in the host system must be at the same revision as this device. The device description can be downloaded from the host system website or Emerson.com/Rosemount by selecting Download Device Drivers under Product Quick Links. You can also visit Fieldbus.org and select End User Resources.
3.3
Quick Start Guide 9

Setting security switch

Prerequisites
Set Simulate and Security switch configuration before installation as shown in Figure 3-4.
The simulate switch enables or disables simulated alerts and simulated
AI Block status and values. The default simulate switch position is enabled.
The Security switch allows (unlocked symbol) or prevents (locked
symbol) any configuration of the transmitter.
Default security is off (unlocked symbol).
The security switch can be enabled or disabled in software.
Use the following procedures to change the switch configuration:
A
B
Quick Start Guide November 2019
Procedure
1. If the transmitter is installed, secure the loop, and remove power.
2. Remove the housing cover opposite the field terminal side. Do not remove the instrument cover in explosive atmospheres when the circuit is live.
3. Slide the security and simulate switches into the preferred position.
4. Reattach transmitter housing cover; it is recommended the cover be tightened until there is no gap between the cover and housing to comply with explosion proof requirements.

3.4 Setting simulate switch

The simulate switch is located on the electronics. It is used in conjunction with the transmitter simulate software to simulate process variables and/or alerts and alarms. To simulate variables and/or alerts and alarms, the simulate switch must be moved to the enable position and the software enabled through the host. To disable simulation, the switch must be in the disable position or the software simulate parameter must be disabled through the host.
Figure 3-4: Transmitter Electronics Board
Aluminum Polished 316 SST
A. Simulate switch B. Security switch
10 Rosemount 2051HT
November 2019 Quick Start Guide

3.5 Connect the wiring and power up

Use copper wire of sufficient size to ensure the voltage across the transmitter power terminals does not drop below 9 Vdc. Power supply voltage can be variable, especially under abnormal conditions such as when operating on battery backup. A minimum of 12 Vdc under normal operating conditions is recommended. Shielded twisted pair type A cable is recommended.
Use the following steps to wire the transmitter:
Procedure
1. To power the transmitter, connect the power leads to the terminals indicated on the terminal block label.
Note
The Rosemount 2051 power terminals are polarity insensitive, which means the electrical polarity of the power leads does not matter when connecting to the power terminals. If polarity sensitive devices are connected to the segment, terminal polarity should be followed. When wiring to the screw terminals, the use of crimped legs is recommended.
2. Ensure full contact with terminal block screw and washer. When using a direct wiring method, wrap wire clockwise to ensure it is in place when tightening the terminal block screw. No additional power is needed.
Note
The use of a pin or a ferrule wire terminal is not recommended as the connection may be more susceptible to loosening over time or under vibration.
3. Ensure proper grounding. It is important the instrument cable shield be:
4. Trimmed close and insulated from touching the transmitter housing.
5. Connected to the next shield if cable is routed through a junction box.
6. Connected to a good earth ground at the power supply end.
7. If transient protection is needed, refer to section “Signal ground
wiring” for grounding instructions.
8. Plug and seal unused conduit connections.
9. Reattach the transmitter covers. It is recommended that the cover be tightened until there is no gap between the cover and the housing.
Quick Start Guide 11
DP
A
B
D
E
C
DP
A
B
D
E
C
Quick Start Guide November 2019
10. The covers must only be capable of being released or removed with the aid of a tool to comply with applicable ordinary locations requirements.
Example
Figure 3-5: Wiring
Aluminum Polished 316 SST
A. Minimize distance B. Trim shield and insulate C. Protective grounding terminal (do not ground cable shield at the
transmitter)
D. Insulate shield
E. Connect shield back to the power supply ground

3.5.1 Signal ground wiring

Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. Grounding terminations are provided on the outside of the electronics housing and inside the terminal compartment. These grounds are used when transient protect terminal blocks are installed or to fulfill local regulations.
Procedure
1. Remove the field terminals housing cover.
2. Connect the wiring pair and ground as indicated in Figure 3-5. a) Trim the cable shield as short as practical and insulate from
touching the transmitter housing.
12 Rosemount 2051HT
November 2019 Quick Start Guide
Note
Do NOT ground the cable shield at the transmitter; if the cable shield touches the transmitter housing, it can create ground loops and interfere with communications.
3. Continuously connect the cable shields to the power supply ground. a) Connect the cable shields for the entire segment to a single
good earth ground at the power supply.
Note
Improper grounding is the most frequent cause of poor segment communications.
4. Replace the housing cover. It is recommended that the cover be
tightened until there is no gap between the cover and the housing.
a) The covers must only be capable of being released or
removed with the aid of a tool to comply with applicable ordinary locations requirements.
5. Plug and seal unused conduit connections.
Note
The Rosemount 2051HT polished 316 SST housing only provides ground termination inside the terminal compartment.

3.5.2 Power supply

The transmitter requires between 9 and 32 Vdc (9 and 30 Vdc for intrinsic safety) to operate and provide complete functionality.

3.5.3 Power conditioner

A Fieldbus segment requires a power conditioner to isolate the power supply, filter, and decouple the segment from other segments attached to the same power supply.

3.5.4 Grounding

Signal wiring of the Fieldbus segment cannot be grounded. Grounding out one of the signal wires will shut down the entire Fieldbus segment.

3.5.5 Shield wire ground

To protect the Fieldbus segment from noise, grounding techniques for shield wire require a single grounding point for shield wire to avoid creating a ground loop. Connect the cable shields for the entire segment to a single good earth ground at the power supply.
Quick Start Guide 13
Quick Start Guide November 2019

3.5.6 Signal termination

For every Fieldbus segment a terminator should be installed at the beginning and at the end of each segment.

3.5.7 Locating devices

Devices are frequently installed, configured, and commissioned over time by different personnel. A “Locate Device” capability uses the LCD display (when installed) to assist personnel in finding the desired device.
From the device Overview screen, select the Locate Device button. This will launch a method allowing the user to display a “Find me” message or enter a custom message to display on the device LCD display. When the user exits the “Locate Device” method, the device LCD display automatically returns to normal operation.
Note
Some hosts do not support “Locate Device” in the DD.

3.6 Configure

Each Foundation Fieldbus host or configuration tool has a different way of displaying and performing configurations. Some use device descriptions (DD) or DD methods for configuration and to display data consistently across platforms. There is no requirement that a host or configuration tool support these features. Use the following block examples to do basic configuration to the transmitter. For more advanced configurations, see the Rosemount 2051 Reference Manual.
Note
DeltaV™ users should use DeltaV Explorer for the Resource and Transducer blocks and Control Studio for the Function Blocks.

3.6.1 Configure the AI block

If your configuration tool supports Dashboard DD's or DTM's you may use either guided setup or manual setup. If your configuration tools don't support Dashboard DD's or DTM's, use manual setup. Navigation instructions for each step are provided below. In addition the screens used for each step are shown in Device revisions and drivers.
14 Rosemount 2051HT
November 2019 Quick Start Guide
Figure 3-6: Configuration Flowchart
Quick Start Guide 15
Quick Start Guide November 2019
Figure 3-7: Basic Configuration Menu Tree
Standard text:
Text in parentheses:
Bold text:
Underlined text:
Available navigation options
Name of option used in parent menu
Automated methods
Configuration task numbers from configuration flow chart

3.6.2 Before you begin

See Figure 3-6 to graphically view the step-by-step process for basic device configuration. Before beginning configuration you may need to verify the Device Tag or deactivate hardware or software write protection on the transmitter. To do this perform this task. Otherwise, continue at navigating to AI block configuration.
16 Rosemount 2051HT
November 2019 Quick Start Guide
Procedure
1. To verify the device tag: a) Navigation: from the Overview screen, select Device
Information to verify the device tag.
2. To check the switches (see Figure 3-4): a) Verify the write lock switch is in the unlocked position if the
switch has been enabled in software.
3. To disable the software write lock: a) Navigation: from the Overview screen, select Device
Information and then select the Security and Simulation tab.
b) Perform “Write Lock Setup” to disable software write lock.
c) Place the control loop in “Manual” mode before beginning AI
block configuration.
Note
Place the control loop in “Manual” mode before beginning analog input block configuration.

3.6.3 AI block configuration

Procedure
1. To use guided setup: a) Navigate to Configure > Guided Setup.
b) Select AI Block Unit Setup.
Note
Guided setup will automatically go through each step in the proper order.
2. To use manual setup: a) Navigate to Configure > Manual Setup > Process Variable.
b) Select AI Block Unit Setup.
c) Place the AI Block in “Out of Service” mode.
Note
When using manual setup, perform the steps in the order described in the Configure the AI block.
Quick Start Guide 17
Quick Start Guide November 2019
Note
For convenience, AI Block 1 is pre-linked to the transmitter primary variable and should be used for this purpose. AI Block 2 is pre-linked to the transmitter sensor temperature.
Channel 1 is the primary variable.
Channel 2 is the sensor temperature.
Note
Step 4 through step 7 are all performed in a single step-by-step method under guided setup, or on a single screen using manual setup.
Note
If the L_TYPE selected in step 3 is “Direct”, step 4, step 5, and step 6 are not needed. If the L_TYPE selected is “Indirect”, step 6 is not needed. If guided setup is used, any unneeded steps will automatically be skipped.
3. To select the signal conditioning “L_TYPE” from the dropdown menu:
a) Select L_TYPE: “Direct” for pressure measurements using the
device default units.
b) Select L_TYPE: “Indirect” for other pressure or level units.
c) Select L_TYPE: “Indirect Square Root” for flow units.
4. To set “XD_SCALE” to the 0% and 100% scale points (the transmitter range):
a) Select the XD_SCALE_UNITS from the drop down menu.
b) Enter the XD_SCALE 0% point. This may be elevated or
suppressed for level applications.
c) Enter the XD_SCALE 100% point. This may be elevated or
suppressed for level applications.
d) If L_TYPE is “Direct”, the AI Block may be placed in AUTO
mode to return the device to service. Guided Setup does this automatically.
5. If L_TYPE is “Indirect” or “Indirect Square Root”, set “OUT_SCALE” to change engineering units.
a) Select the OUT_SCALE UNITS from the dropdown menu.
b) Set the OUT_SCALE low value. This may be elevated or
suppressed for level applications.
18 Rosemount 2051HT
November 2019 Quick Start Guide
c) Set the OUT_SCALE high value. This may be elevated or
suppressed for level applications.
d) If L_TYPE is “Indirect”, the AI Block may be placed in AUTO
mode to return the device to service. Guided Setup does this automatically.
6. Change damping. a) To use guided setup:
Navigate to Configure > Guided Setup, and select Change
Damping.
Note
Guided Setup will automatically go through each step in the proper order.
Enter the desired damping value in seconds. The
permitted range of values is 0.4 to 60 seconds.
b) To use manual setup:
Navigate to Configure > Manual Setup > Process Variable
and select Change Damping.
Enter the desired damping value in seconds. The
permitted range of values is 0.4 to 60 seconds.
7. Configure LCD display (if installed). a) To use guided setup:
Navigate to Configure > Guided Setup, and select Local
Display Setup.
Note
Guided setup will automatically go through each step in the proper order.
Check the box next to each parameter to be displayed to a
maximum of four parameters. The LCD display will continuously scroll through the selected parameters.
b) To use manual setup:
Navigate to Configure > Manual Setup and select Local
Display Setup.
Check each parameter to be displayed. The LCD display
will continuously scroll through the selected parameters.
Quick Start Guide 19
Quick Start Guide November 2019
8. Review transmitter configuration and place in service a) To review the transmitter configuration, navigate using the
guided setup navigation sequences for “AI Block Unit Setup”, “Change Damping”, and “Set up LCD Display”.
b) Change any values as necessary.
c) Return to the Overview screen.
d) If Mode is “Not in Service”, select the Change button, and
then select Return All to Service.
Note
If hardware or software write protection is not needed, step 10 can be skipped.
9. Set switches and software write lock. a) Check switches (see Figure 3-4).
Note
The write lock switch can be left in the locked or unlocked position. The simulate enable/disable switch may be in either position for normal device operation.
Enable software write lock
Procedure
1. Navigate from the Overview screen.
a. Select Device Information.
b. Select the Security and Simulation tab.
2. Perform Write Lock Setup to enable software write lock.
20 Rosemount 2051HT
November 2019 Quick Start Guide
AI block configuration parameters
Use the pressure examples for guides.
Parameters Enter data
Channel 1 = Pressure, 2 = Sensor Temp
L-Type Direct, Indirect, or Square Root
XD_Scale Scale and Engineering Units
Note
Select only the units that are supported by the device.
Out_Scale Scale and Engineering Units
Pressure example
Parameters Enter data
Channel 1
L_Type Direct
XD_Scale See list of supported engineering units.
Pa bar torr at 0 °C ftH2O at 4 °C mH2O at 4 °C
kPa mbar kg/cm
mPa psf kg/m
hPa Atm inH2O at 4°C mH2O at 4 °C inHg at 0 °C
°C psi inH2O at 60 °F mmH2O at 68°CmHg at 0 °C
°F g/cm2inH2O at 68 °F cmH2O at 4 °C
2
2
ftH2O at 60 °F mmHg at 0 °C
ftH2O at 68 °F cmHg at 0 °C
Note
Select only the units that are supported by the device.
Out_Scale Set values outside operating range.

3.6.4 Display pressure on the LCD display

Select the Pressure check box on the Display Configuration screen.
3.7
Quick Start Guide 21

Zero trim the transmitter

Note
Transmitters are shipped fully calibrated per request or by the factory default of full scale (span = upper range limit).
A zero trim is a single-point adjustment used for compensating mounting position and line pressure effects. When performing a zero trim, ensure the equalizing valve is open and all wet legs are filled to the correct level.
Quick Start Guide November 2019
The transmitter will only allow three to five percent URL zero error to be trimmed. For greater zero errors, compensate for the offset by using the XD_Scaling, Out_Scaling and Indirect L_Type, which are part of the AI Block.
Procedure
1. To use guided setup: a) Navigate to Configure > Guided Setup and select Zero Trim.
b) The method will execute the zero trim.
2. To use manual setup: a) Navigate to Overview > Calibration > Sensor Trim and select
Zero Trim.
b) The method will execute the zero trim.
22 Rosemount 2051HT
November 2019 Quick Start Guide

4 Product certifications

Rev 1.2

4.1 European Directive Information

A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount.

4.2 Ordinary Location Certification

As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).

4.3 Installing Equipment in North America

The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.

4.4 Hazardous Locations Certifications

Note
Device ambient temperature ratings and electrical parameters may be limited to the levels dictated by the hazardous location certificate parameters.
4.5

4.5.1 I5 USA Intrinsic Safety (IS) and Nonincendive (NI)

Quick Start Guide 23

North America

Certificate:
Standards:
Markings:
Specific Condition of Use:
1. 1. The Model 2051 transmitter housing contains aluminum and is
FM16US0231X (HART)
FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 – 2004, FM Class 3810 – 2005, ANSI/NEMA 250 – 2008
IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV 1 when connected per Rosemount drawing 02051-1009; Class I, Zone 0; AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D; T4(-50 °C ≤ Ta ≤ +70 °C); Type 4x
considered a potential risk of ignition by impact or friction. Care must
Quick Start Guide November 2019
be taken into account during installation and use to prevent impact and friction.
Certificate:
Standards:
2041384 (HART/Fieldbus/PROFIBUS®)
ANSI/ISA 12.27.01-2003, CSA Std. C22.2 No.142-M1987, CSA Std. C22.2. No.157-92
Markings:
IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV 1 when connected per Rosemount drawing 02051-1009; Class I, Zone 0; AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D; T4(-50 °C ≤ Ta ≤ +70 °C); Type 4x

4.5.2 I6 Canada Intrinsic Safety

Certificate:
Standards:
Markings:
2041384
CSA Std. C22.2 No. 142 - M1987, CSA Std. C22.2 No. 213 ­M1987, CSA Std. C22.2 No. 157 - 92, CSA Std. C22.2 No. 213
- M1987, ANSI/ISA 12.27.01 – 2003, CAN/CSA-E60079-0:07, CAN/CSA-E60079-11:02
Intrinsically safe for Class I, Division 1, Groups A, B, C, and D when connected in accordance with Rosemount drawing 02051-1008. Ex ia IIC T3C. Single Seal. Enclosure Type 4X

4.6 Europe

4.6.1 I1 ATEX Intrinsic Safety

Certificate:
Standards:
Markings:
Baseefa08ATEX0129X
EN60079-0:2012+A11:2013, EN60079-11:2012
Ex II 1 G Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +70 °C)
Table 4-1: Input Parameters
Parameter HART Fieldbus/PROFIBUS
Voltage U
Current I
Power P
i
Capacitance Ci0.012 μF 0 μF
Inductance Li0 mH 0 mH
24 Rosemount 2051HT
30 V 30 V
i
200 mA 300 mA
i
1 W 1.3 W
November 2019 Quick Start Guide
Specific Conditions of Safe Use (X):
1. If the equipment is fitted with an optional 90 V transient suppressor, it is incapable of withstanding the 500 V isolation from earth test and this must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however care should be taken to protect it from impact and abrasion when located in Zone 0 from earth test and this must be taken into account during installation.

4.7 International

4.7.1 I7 IECEx Intrinsic Safety

Certificate:
Standards:
Markings:
IECEx BAS 08.0045X
IEC 60079-0:2011, IEC 60079-11:2011
Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +70 °C)
Table 4-2: Input Parameters
Parameter HART Fieldbus/PROFIBUS
Voltage U
Current I
Power P
i
Capacitance Ci0.012 μF 0 μF
Inductance Li0 mH 0 mH
30 V 30 V
i
200 mA 300 mA
i
1 W 1.3 W
Specific Conditions of Safe Use (X):
1. If the equipment is fitted with an optional 90 V transient suppressor, it is incapable of withstanding the 500 V isolation from earth test and this must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however care should be taken to protect it from impact and abrasion when located in Zone 0.
3. The equipment contains thin wall diaphragms. The installation, maintenance and use shall take into account the environmental conditions to which the diaphragms will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
Quick Start Guide 25
Quick Start Guide November 2019

4.8 Additional Certifications

®
3-A
All Rosemount 2051HT transmitters with the following connections are 3-A approved and labeled:
T32: 1½-in. Tri-Clamp
T42: 2-in. Tri-Clamp
If process connection B11 is selected, please reference the ordering table of the Rosemount 1199 Diaphragm Seal Product Data Sheet for availability of 3-A certifications.
A 3-A certificate of compliance is available by selecting option code QA.
EHEDG
All Rosemount 2051HT transmitters with the following connections are EHEDG approved and labeled:
T32: 1½-in. Tri-Clamp
T42: 2-in. Tri-Clamp
If process connection B11 is selected, please reference the ordering table of the Rosemount 1199 Diaphragm Seal Product Data Sheet for availability of EHEDG certifications.
An EHEDG certificate of compliance is available by selecting option code QE.
Ensure gasket selected for installation is approved to meet both application and EHEDG certification requirements.
26 Rosemount 2051HT
November 2019 Quick Start Guide

4.9 Rosemount 2051HT Declaration of Conformity

Quick Start Guide 27
Quick Start Guide November 2019
28 Rosemount 2051HT
November 2019 Quick Start Guide
Quick Start Guide 29
ᴹ
China RoHS
㇑᧗⢙䍘䎵䗷ᴰབྷ⎃ᓖ䲀٬Ⲵ䜘Ԧරࡇ㺘
Rosemount 2051HT
List of Rosemount 2051HT Parts with China RoHS Concentration above MCVs
䜘Ԧ〠
Part Name
ᴹᇣ⢙䍘
/ Hazardous Substances
䫵
Lead
(Pb)
⊎
Mercury
(Hg)
䭹
Cadmium
(Cd)
ޝԧ䬜
Hexavalent
Chromium
(Cr +6)
ཊⓤ㚄㤟
Polybrominated
biphenyls
(PBB)
ཊⓤ㚄㤟䟊
Polybrominated diphenyl ethers
(PBDE)
⭥ᆀ㓴Ԧ
Electronics
Assembly
X O O O O O
༣փ㓴Ԧ
Housing
Assembly
O O O O O O
Րᝏಘ㓴Ԧ
Sensor
Assembly
X O O O O O
ᵜ㺘Ṭ㌫׍ᦞ
SJ/T11364
Ⲵ㿴ᇊ㘼ࡦ֌
This table is proposed in accordance with the provision of SJ/T11364.
O:
᜿Ѫ䈕䜘ԦⲴᡰᴹ൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿൷վҾ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572.
X:
᜿Ѫ൘䈕䜘Ԧᡰ֯⭘Ⲵᡰᴹ൷䍘ᶀᯉ䟼ˈ㠣ቁᴹа㊫൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿儈Ҿ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.
Quick Start Guide November 2019

4.10 China RoHS

30 Rosemount 2051HT
November 2019 Quick Start Guide
Quick Start Guide 31
*00825-0200-4591*
00825-0200-4591, Rev. BA
Quick Start Guide
November 2019
Global Headquarters
Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 204 8889 RFQ.RMD-RCC@Emerson.com
Latin America Regional Office
Emerson Automation Solutions 1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office
Emerson Automation Solutions 1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com
North America Regional Office
Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 204 8889 RMT-NA.RCCRFQ@Emerson.com
Europe Regional Office
Emerson Automation Solutions Europe GmbH Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465 RFQ.RMTMEA@Emerson.com
Linkedin.com/company/Emerson-
Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/
RosemountMeasurement
©
2019 Emerson. All rights reserved.
Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners.
Loading...