Rosemount 2051HT Hygienic Pressure Transmitter with 4-20mA HART Quick Start Guide

Page 1
Quick Start Guide
00825-0100-4591, Rev BA
March 2018
Rosemount™ 2051HT Hygienic Pressure Transmitter
with 4–20 mA HART® Revision 5 and 7 Protocol
Note
Before installing the transmitter, confirm the correct device driver is loaded on the host systems. See page 3 for system readiness.
Page 2
Quick Start Guide
March 2018
NOTICE
This guide provides basic guidelines for the Rosemount 2051HT Transmitter. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations.
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices.
Before connecting a HART the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Process leaks may cause harm or result in death.
To avoid process leaks, only use the gasket designed to seal with the corresponding flange adapter.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and the terminals. High voltage that may be present on leads can cause electrical shock.
Conduit/cable entries
Aluminum housings: Unless marked, the conduit/cable entries in the transmitter housing use a 1/2–14 NPT
thread form.
Stainless steel (SST) housings: conduit/cable entries can be determined by crossing referencing the model
string printed on the transmitter with the ordering table listed in the Pro duct Data Sheet. Conduit type is not cast into the transmitter housing to minimize surface irregularities.
Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries.
®
-based communicator in an explosive atmosphere, make sure the instruments in
4
Contents
System readiness . . . . . . . . . . . . . . . . . . . . . . . . . 3
Transmitter installation . . . . . . . . . . . . . . . . . . . 3
Mount the transmitter . . . . . . . . . . . . . . . . . . . . 3
Set the switches . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2
Connect the wiring and power up . . . . . . . . . . 6
Verify configuration . . . . . . . . . . . . . . . . . . . . . . 8
Trim the transmitter . . . . . . . . . . . . . . . . . . . . . 11
Product certifications . . . . . . . . . . . . . . . . . . . . 14
Page 3
March 2018

1.0 System readiness

1.1 Confirm HART Revision capability
If using HART based control or asset management systems, confirm the
HART capability of those systems prior to transmitter installation. Not all systems are capable of communicating with HART Revision 7 protocol. This transmitter can be configured for either HART Revision 5 or 7.
For instructions on how to change the HART Revision of your transmitter, see
page 11.
Quick Start Guide
1.2 Confirm correct device driver
Verify the latest device driver (DD/DTM
ensure proper communications.
Download the latest device driver at Emerson.com or FieldCommGroup.org.
Rosemount 2051 device revisions and drivers
Table 1 provides the information necessary to ensure you have the correct
device driver and documentation for your device.
Table 1. Rosemount 2051 Device Revisions and Files
Identify device Find device driver
Software
release
date
Dec-11 1.0.0 01
1. NAMUR software revision is located on the hardware tag of the device. In accordance with NE53, revisions of the least significant level X (of 1.0.X) do not change functionalit y or operation of the device and will bot be reflected in this device revision histor y.
2. HART software revision can be read using a HART capable configuration tool.
NAMUR
software
revision
(1)
HART
software
revision
HART
universal
(2)
revision
7 10 Rosemou nt
5 9

2.0 Transmitter installation

) is loaded on your systems to
Device
revision
Review instruction
Referen ce
manual
2051
Pressure
Tra ns mi tte r
Reference
Manual
Review
functionality
Changes to
software
N/A
2.1 Mount the transmitter
Orient the transmitter to desired orientation before mounting. Transmitter must not be securely mounted or clamped in place when changing transmitter orientation.
Conduit entry orientation
When installing a Rosemount 2051HT, it is recommended installing so the conduit entry faces downward towards the ground to maximize drain ability when cleaning.
3
Page 4
Quick Start Guide
A
Environmental seal for housing
Thread sealing (PTFE) tape or paste on male threads of conduit is required to provide a water/dust tight conduit seal and meets requirements of NEMA 4X, IP66, IP68, and IP69K. Consult factory if other Ingress Protection ratings are required.
For M20 threads, install conduit plugs to full thread engagement or until mechanical resistance is met.
Note
IP69K rating only available on units with a SST housing and option code V9 in the model string.
Note
For aluminum housings ordered with M20 conduit entries, transmitters shipped will have
1
/2 NPT threads machined into the housing and a 1/2 NPT to M20 thread adapter will be provided. Considerations for environmental sealing listed above should be taken into account when installing the thread adapter.
In-line gage transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage transmitter is located on the neck of the transmitter via a protected gage vent (See Figure 1).
Keep the vent path free from obstructions including but not limited to paint, dust, and viscous fluids by mounting the transmitter so the process can drain away.
Recommended installations have a conduit entry facing the ground so the gage vent is pointing parallel to the ground.
March 2018
®
Type
Figure 1. In-line Protected Gage Vent Low Side Pressure Port
Aluminum Polished 316 SST
A. Low side pressure port (atmospheric reference)
4
Page 5
March 2018
A
B
Clamping
When installing clamp, follow recommended torque values provided by gasket manufacturer.
(1)
2.2 Set the switches
Set alarm and security switch configuration before installation as shown in
Figure 2.
The alarm switch sets the analog output alarm to high or low.
- Default alarm is high.
The security switch allows (unlocked symbol) or prevents (locked symbol)
any configuration of the transmitter.
- Default security is off (unlocked symbol).
Use the following procedure to change the switch configuration:
1. If the transmitter is installed, secure the loop and remove power.
2. Remove the housing cover opposite the field terminal side. Do not remove
the instrument cover in explosive atmospheres when the circuit is live.
3. Slide the security and alarm switches into the preferred position using a small
screwdriver.
4. Reattach the transmitter cover. It is recommended that the cover be
tightened until there is no gap between the cover and the housing.
The covers must only be capable of being released or removed with the aid of a tool to comply with applicable ordinary locations requirements.
Quick Start Guide
Figure 2. Transmitter Electronics Board
Without LCD display With LOI or LCD display
A. Alarm B. Security
1. To maintain transmitter performance, torquing a 1.5-in. Tri-Clamp beyond 50 in-lb is not recommended on pressure ranges below 20 psi.
Aluminum
Polished 316 SST
A
B
5
Page 6
Quick Start Guide
2.3 Connect the wiring and power up
Figure 3. Transmitter Wiring Diagrams (4–20 mA)
Aluminum
March 2018
A
B
A
B
A. 24 Vdc supply B. R
250
L
C. Current meter (optional)
C
Polished 316 SST
C
Shielded twisted pair cable should be used for best results. Use 24 AWG or larger wire that does not exceed 5,000 ft. (1500 m) in length. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.
6
Page 7
March 2018
Installation of the transient protection terminal block does not provide transient protection unless the
Rosemount 2051HT case is properly grounded.
Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment.
Do not connect the powered signal wiring to the test terminals. Power could damage the test diode in the
terminal block.
Quick Start Guide
Use the following steps to wire the transmitter:
1. Remove the housing cover on the FIELD TERMINALS side.
2. Connect the positive lead to the “+” terminal (PWR/COMM) and the negative lead to the “–” terminal.
3. Ensure full contact with Terminal Block screw and washer. When using a direct wiring method, wrap wire clockwise to ensure it is in place when tightening the terminal block screw.
Note
The use of a pin or a ferrule wire terminal is not recommended as the connection may be more susceptible to loosening over time or under vibration
4. Ground housing to fulfill local grounding regulations.
5. Ensure proper grounding. It is important the instrument cable shield be:
Trimmed close and insulated from touching the transmitter housingConnected to the next shield if cable is routed through a junction boxConnected to a good earth ground at the power supply end
6. If transient protection is needed, refer to section “Grounding for transient
terminal block ” for grounding instructions.
7. Plug and seal unused conduit connections.
8. Reattach the transmitter covers. It is recommended that the cover be tightened until there is no gap between the cover and the housing.
The covers must only be capable of being released or removed with the aid of a tool to comply with applicable ordinary locations requirements.
7
Page 8
Quick Start Guide
DP
A
B
D
E
C
Figure 4. Wiring
March 2018
Aluminum Polished 316 SST
A. Minimize distance B. Trim shield and insulate C. Protective grounding terminal
Grounding for transient terminal block
Ground termination is provided on the outside of the electronics housing and inside the terminal compartment. These grounds are used when the transient protection terminal blocks are installed. It is recommended that 18 AWG or larger wire is used to connect housing ground to earth ground (internal or external).
If the transmitter is currently not wired for power up and communication, follow
Connect the wiring and power up
properly wired, refer to Figure 4 for internal and external transient grounding locations.
A
B
DP
D
E
D. Insulate shield E. Connect shield back to the power supply ground
, step 1 through 8. When the transmitter is
C
Note
The Rosemount 2051HT polished 316 SST housing only provides ground termination inside the terminal compartment.
2.4 Verify configuration
Verify the configuration using any HART capable configuration tool or Local Operator Interface (LOI) - option code M4. Configuration instructions for a Field Communicator and LOI are included in this step.
Verifying configuration with a Field Communicator
A Rosemount 2051 DD must be installed on the Field Communicator to verify configuration. Fast Key sequences for the latest DD are shown in Table 2 on
page 9. For Fast Key sequences using legacy DD's, contact your local Emerson
representative.
8
Page 9
March 2018
Quick Start Guide
Note
Emerson recommends installing the latest DD to access the complete functionality. Visit
Emerson.com/Field-Communicator for information on updating the DD Library.
1. Verify device configuration using the Fast Key sequences in Tab le 2 .
A check () indicates the basic configuration parameters. At minimum,
these parameters should be verified as part of configuration and startup.
Table 2. Device Revision 9 and 10 (HART7), DD Revision 1 Fast Key Sequence
Function Fast Key se quen ce
HART 7 HART 5
Alarm and Saturation Levels 2, 2, 2, 5, 7 2, 2, 2, 5, 7
Damping 2, 2, 1, 1, 5 2, 2, 1, 1, 5
Range Values 2, 2, 2 2, 2, 2
Tag 2, 2, 7, 1, 1 2, 2, 7, 1, 1
Transfer Function 2, 2, 1, 1, 6 2, 2, 1, 1, 6
Units 2, 2, 1, 1, 4 2, 2, 1, 1, 4
Burst Mode 2, 2, 5, 3 2, 2, 5, 3
Custom Display Configu ration 2, 2, 4 2, 2, 4
Date 2, 2, 7, 1, 4 2, 2, 7, 1, 3
Descriptor 2, 2, 7, 1, 5 2, 2, 7, 1, 4
Digital to Analog Trim (4–20 mA output) 3, 4, 2 3, 4, 2
Disable Configuration Buttons 2, 2, 6, 3 2, 2, 6, 3
Rerange with Keypad 2, 2, 2, 1 2, 2, 2, 1
Loop Test 3, 5, 1 3, 5, 1
Lower Sensor Trim 3, 4, 1, 2 3, 4, 1, 2
Message 2, 2, 7, 1, 6 2, 2, 7, 1, 5
Scaled D/A Trim (4–20 mA output) 3, 4, 2 3, 4, 2
Se nso r Temp era tur e/Trend 3, 3, 2 3, 3, 2
Upper Sensor Trim 3, 4, 1, 1 3, 4, 1, 1
Digital Zero Trim 3, 4, 1, 3 3, 4, 1, 3
Password 2, 2, 6, 5 2, 2, 6, 4
Scaled Variable 3, 2, 2 3, 2, 2
HART Revision 5 to HART Revision 7 switch 2, 2, 5, 2, 3 2, 2, 5, 2, 3
(1)
Long Tag
Find Device
Simulate Digital Signal
1
1
2, 2, 7, 1, 2 N/A
3, 4, 5 N/A
3, 4, 5 N/A
1. Only available in HART Revision 7 mode.
9
Page 10
Quick Start Guide
Assign PV
HART Revision
Verifying configuration with LOI
The optional LOI can be used for commissioning the device. The LOI is a two-button design with internal and external/rear buttons. On a polished stainless steel housing, buttons are located internally both on the display and terminal side of the transmitter. On an aluminum housing, buttons are located on the display and externally underneath the top metal tag. To activate the LOI, push any button. LOI button functionality is shown on the bottom corners of the display. See Table 3 and Figure 5 for button operation and menu information.
Table 3. LOI Button Operation
Button
Left No SCROLL
Right Yes ENTER
Figure 5. LOI Menu
March 2018
10
Page 11
March 2018
Switch HART Revision mode
If the HART configuration tool is not capable of communicating with HART Revision 7, the Rosemount 2051 will load a generic menu with limited capability. The following procedures will switch the HART Revision mode from the generic menu:
1. Manual Setup > Device Information > Identification > Message a.To change to HART Revision 5, Enter: HART5 in the Message field.
b.To change to HART Revision 7, Enter: HART7 in the Message field.
Note
See Table 2 on page 9 to change HART Revision when the correct device driver is loaded.
2.5 Trim the transmitter
Devices are calibrated by the factory. Once installed, it is recommended to perform a zero trim on gage transmitters to eliminate error due to mounting position or static pressure effects. A zero trim can be performed using either a Field Communicator or configuration buttons.
Note
When performing a zero trim, ensure the equalization valve is open and all wet legs are filled to the correct level.
Quick Start Guide
It is not recommended to zero an absolute transmitter, Rosemount 2051HTA model.
1. Choose your trim procedure. a. Analog zero trim – Sets the analog output to 4 mA.
b. Also referred to as a “rerange,” it sets the lower range value (LRV) equal to
the measured pressure. c. The display and digital HART output remains unchanged. d. Digital zero trim – Recalibrates the sensor zero. e. The LRV is unaffected. The pressure value will be zero (on display and
HART output). 4 mA point may not be at zero. f. This requires the factory calibrated zero pressure is within a range of 3%
of the URV [0 ± 3% x URV].
Example
URV = 250 inH2O Applied Zero Pressure = ± 0.03x 250 inH2O = ± 7.5 inH2O (compared to factory settings) values outside this range will be rejected by the transmitter
Trimming with a Field Communicator
1. Connect the Field Communicator, see “Connect the wiring and power up” on
page 6 for instructions.
11
Page 12
Quick Start Guide
A
A
2. Follow the HART menu to perform the desired zero trim.
Fast Key se quenc e 3, 4, 2 3, 4, 1, 3
Trimming with configuration buttons
A zero trim is to be performed using one of the three possible sets of configuration buttons located above the terminal block or under the top tag.
To access the configuration buttons on a polished stainless steel housing, remove the terminal side housing cover.
To access the configuration buttons on an aluminum housing, loosen the screw on the top tag and slide the tag on the top of the transmitter.
Figure 6. External or Rear/Terminal-Side Configuration Buttons
LOI
Analog zero (set 4 mA) Digital zero
Analog zero and
span
Digital zero
March 2018
Aluminum
12
Polished 316 SST
(1)
N/A
A. Configuration buttons
1. LOI buttons (option M4) only offer front facing buttons on SST housing (option 1).
Options D4 and DZ can still be purchased for rear/terminal-s ide facing buttons.
Page 13
March 2018
Quick Start Guide
Use the following procedures to perform a zero trim:
Perform trim with LOI (option M4)
1. Set the transmitter pressure.
2. See Figure 5 on page 10 for the operating menu. a. Perform an analog zero trim by selecting Rerange.
b. Perform a digital zero trim by selecting Zero Trim.
Perform trim with analog zero and span (option D4)
1. Set the transmitter pressure.
2. Press and hold the Zero button for two seconds to perform an analog zero trim.
Perform trim with digital zero (option DZ)
1. Set the transmitter pressure.
2. Press and hold the Zero button for two seconds to perform a digital zero trim.
13
Page 14
Quick Start Guide

3.0 Product certifications

3.1 European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount
3.2 Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
3.3 Installing Equipment in North America
The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.
3.4 Additional Certifications
®
3-A
All Rosemount 2051HT transmitters with the following connections are 3-A approved and labeled
1
/2-in. Tri-Clamp
T32: 1 T42: 2-in. Tri-Clamp
If process connection B11 is selected, please reference the ordering table of the Rosemount 1199 Diaphragm Seal Product Data Sheet certifications.
A 3-A certificate of compliance is available by selecting option code QA.
.
March 2018
for availability of 3-A
14
EHEDG
All Rosemount 2051HT transmitters with the following connections are EHEDG approved and labeled:
1
/2-in. Tri-Clamp
T32: 1 T42: 2-in. Tri-Clamp
If process connection B11 is selected, please reference the ordering table of the Rosemount 1199 Diaphragm Seal Product Data Sheet certifications.
An EHEDG certificate of compliance is available by selecting option code QE.
Ensure gasket selected for installation is approved to meet both application and EHEDG certification requirements. Transmitters and all associated accessories must be installed following EHEDG guidelines to ensure the assembly meets EHEDG certification requirements.
for availability of EHEDG
Page 15
March 2018
EU Declaration of Conformity
No: RMD 1115 Rev. A
Page 1 of 2
We,
Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
declare under our sole responsibility that the product,
Rosemount™ 2051HT Pressure Transmitters
manufactured by,
Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
to which this declaration relates, is in conformity with the provisions of the European Union Directives, including the latest amendments, as shown in the attached schedule.
Assumption of conformity is based on the application of the harmonized standards and, when applicable or required, a European Union notified body certification, as shown in the attached schedule.
(signature)
Vice President of Global Quality
(function)
Chris LaPoint
(name)
6-Feb-18; Shakopee, MN USA
(date of issue & place)
Figure 7. Declaration of Conformity
Quick Start Guide
15
Page 16
Quick Start Guide
EU Declaration of Conformity
No: RMD 1115 Rev. A
Page 2 of 2
EMC Directive (2014/30/EU)
Rosemount 2051HT Pressure Transmitters
Harmonized Standards:
EN 61326-1:2013, EN 61326-2-3:2013
RoHS Directive (2011/65/EU)
Rosemount 2051HT Pressure Transmitters
Harmonized Standard: EN 50581:2012
March 2018
16
Page 17
March 2018
㇑᧗⢙䍘䎵䗷ᴰབྷ⎃ᓖ䲀٬Ⲵ䜘Ԧරࡇ㺘
䜘Ԧ〠
ᴹᇣ⢙䍘䍘
䫵
⊎
䭹
ޝԧ䬜䬜
ཊⓤ㚄㚄㤟
ཊⓤ㚄㚄㤟䟊
China RoHS
List of Rosemount 2051HT Parts with China RoHS Concentration above MCVs
Rosemount 2051HT
/ Hazardous Substances
Quick Start Guide
Part Name
⭥ᆀ㓴Ԧ
Electronics
Assembly
༣փ㓴Ԧ
Housing
Assembly
Րᝏಘ㓴Ԧ
Sensor
Assembly
ᵜ㺘Ṭ㌫׍ᦞ
This table is proposed in accordance with the provision of SJ/T11364.
᜿Ѫ䈕䜘ԦⲴᡰᴹ൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿൷վҾ
O: O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572.
᜿Ѫ൘䈕䜘Ԧᡰ֯⭘Ⲵᡰᴹ൷䍘ᶀᯉ䟼ˈ㠣ቁᴹа㊫൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿儈Ҿ
X: X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.
Lead
(Pb)
Mercury
(Hg)
Cadmium
XO O O O O
XO O X O O
XO O X O O
Ⲵ㿴ᇊ㘼ࡦ֌
SJ/T11364
(Cd)
Hexavalent
Chromium
(Cr +6)
GB/T 26572
Polybrominated
biphenyls
(PBB)
ᡰ㿴ᇊⲴ䲀䟿㾱≲
GB/T 26572
Polybrominated
diphenyl ethers
(PBDE)
ᡰ㿴ᇊⲴ䲀䟿㾱≲
17
Page 18
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com
North America Regional Office
Emerson Automation Solutions
8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com
Latin America Regional Office
Emerson Automation Solutions
1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
Europe Regional Office
Emerson Automation Solutions
Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office
Emerson Automation Solutions
1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions
Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emi rates
+971 4 8118100 +971 4 8865465
RFQ.RMTMEA@Emerson.com
*00825-0100-4591*
Quick Start Guide
00825-0100-4591, Rev BA
Linkedin.com/company/Emerson-Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/us er/RosemountMeasur ement
Google.com/+RosemountMeasurement
Emerson Terms and Conditions of Sale are available upon r equest The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners. © 2018 Emerson. All rights reserved.
March 2018
Loading...