Rosemount 2051G Pressure Transmitter with 4-20 mA HART Protocol (Revision 5 and 7) Quick Start Guide

Quick Start Guide
00825-0700-4101, Rev AD
May 2019
Rosemount™ 2051G Pressure Transmitter
with 4-20 mA HART® Protocol (Revision 5 and 7)
Quick Start Guide May 2019
Contents
About this guide...........................................................................................................................3
System readiness......................................................................................................................... 5
Mount the transmitter..................................................................................................................6
Set the switches........................................................................................................................... 9
Connect the wiring and power up...............................................................................................10
Verify transmitter configuration.................................................................................................13
Trim the transmitter...................................................................................................................19
Safety instrumented systems..................................................................................................... 22
Product certifications................................................................................................................. 23
2 Emerson.com/Rosemount
May 2019 Quick Start Guide

1 About this guide

This guide provides basic guidelines for Rosemount™ 2051G Transmitters. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations. See the Rosemount 2051G Reference Manual for more information.
WARNING
Explosions could result in death or serious injury.
Installation of these transmitters in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the approvals section of the Rosemount 2051 Reference Manual for any restrictions associated with a safe installation.
Before connecting a HART-based communicator in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is applied to the unit.
Process leaks could result in death or serious injury.
To avoid process leaks, only use the O-ring designed to seal with the corresponding flange adapter.
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
Conduit/cable entries
Unless marked, the conduit/cable entries in the transmitter housing use a ½–14 NPT thread form. Entries marked “M20” are M20 × 1.5 thread form. On devices with multiple conduit entries, all entries will have the same thread form. Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries.
Quick Start Guide 3
Quick Start Guide May 2019
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
4 Emerson.com/Rosemount
May 2019 Quick Start Guide

2 System readiness

2.1 Confirm HART Revision capability

If using HART® based control or asset management systems, confirm the
HART capability of those systems prior to transmitter installation. Not all systems are capable of communicating with HART Revision 7. This transmitter can be configured for either HART Revision 5 or 7.
For instructions on how to change the HART revision of the transmitter,
see Switch HART revision mode.

2.2 Confirm correct device driver

Procedure
1. Verify the latest Device Driver (DD/DTM™) is loaded on your systems to ensure proper communications.
2. Reference Emerson.com or FieldCommGroup.org for the latest DD.
3. Select desired product and download the DD.
a) Reference Table 2-1 for the correct DD.
Table 2-1: Device Revisions and Files
Identify device Find device driver
Softwar e release date
June 2016
(1) NAMUR revision is located on the hardware tag of the device. Differences in level 3 changes,
(2) HART software revision can be read using a HART capable configuration tool. Value shown
(3) Device driver file names use device and DD revision (e.g. 10_01). HART Protocol is designed
(4) HART Revision 5 and 7 selectable, Local Operator Interface (LOI), scaled variable,
Quick Start Guide 5
NAMUR hardwar e revision
1)
1.1.xx 1.0.xx 03 7 10 Reference
signified above by xx, represent minor product changes as defined per NE53. Compatibility and functionality are preserved and product can be used interchangeably.
is minimum revision that could correspond to NAMUR revisions.
to enable legacy device driver revisions to continue to communicate with new HART devices. To access new functionality, the new device driver must be downloaded. It is recommended to download new device driver files to ensure full functionality.
configurable alarms, expanded engineering units. Updated electronics hardware design. Intrinsically Safe temperature classification change.
NAMUR software revision
(
1)
HART software
(
revision
2)
files
HART universa
(
l revision
5 9
Device revision
3)
Review instructio ns
00809-04
(
00-4101
Manual
Review functionali ty
Changes to software
(4)
(4)
Quick Start Guide May 2019

3 Mount the transmitter

Mount directly to the impulse line without using an additional mounting bracket or mount directly to a wall, panel, or two-inch pipe using an optional mounting bracket.
Figure 3-1: Transmitter Direct Mounting
A. Process connection
Note
Do not apply torque directly to the electronics housing. To avoid damage, apply torque only to the hex-shaped process connection.
Figure 3-2: Panel and Pipe Mounting
Panel mount
Pipe mount

3.1 Liquid flow applications

Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so the drain/vent valves are oriented upward.
6 Emerson.com/Rosemount
May 2019 Quick Start Guide

3.2 Gas flow applications

Procedure
1. Place taps in the top or side of the line.
2. Mount level or above the taps.

3.3 Steam flow applications

Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
3.4
Quick Start Guide 7

Environmental seal for housing

Thread sealing (PTFE) tape or paste on male threads of conduit is required to provide a water/dust tight conduit seal and meets requirements of NEMA Type 4X, IP66, and IP68. Consult factory if other ingress protection ratings are required.
®
Quick Start Guide May 2019
For M20 threads, install conduit plugs to full thread engagement or until mechanical resistance is met.

3.5 Gage transmitter orientation

The low side pressure port (atmospheric reference) on the inline gage transmitter is located in the neck of the transmitter, behind the housing. The vent path is 360° around the transmitter between the housing and sensor. (See Figure 3-3).
CAUTION
Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so the contaminants can drain away.
Figure 3-3: Gage Low Side Pressure Port
A
Low side pressure port (atmospheric reference)
8 Emerson.com/Rosemount
May 2019 Quick Start Guide

4 Set the switches

Set alarm and security switch configuration before installation as shown in
Figure 4-1.
The alarm switch sets the analog output alarm to high or low. Default
alarm is high.
The security switch allows (
transmitter. Default security is off (
Use the following procedure to change the switch configuration:
Procedure
1. If the transmitter is installed, secure the loop, and remove power.
2. Remove the housing cover opposite the field terminal side. Do not remove the instrument cover in explosive atmospheres when the circuit is live.
3. Slide the security and alarm switches into the preferred position using a small screwdriver.
4. Reattach the transmitter cover. The cover must be fully engaged to comply with explosion-proof requirements.
Figure 4-1: Transmitter Electronics Board
Without LCD display With LOI/LCD display
) or prevents ( ) any configuration of the
).
A. Alarm B. Security
Quick Start Guide 9
Quick Start Guide May 2019

5 Connect the wiring and power up

CAUTION
Do not tamper with or remove the electronics board in the Rosemount 2051G. This will cause permanent damage to the transmitter.
Shielded twisted pair cable should be used for best results. Use 24 AWG or larger wire that does not exceed 5000 ft. (1500 m) in length. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.
Figure 5-1: Wiring the Transmitter (4–20 mA HART)
A
Vdc supply
B
RL ≥ 250 (necessary for HART® communication only)
CAUTION
Installation of the transient protection terminal block does not provide transient protection unless the transmitter case is properly grounded.
Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment.
Do not connect the powered signal wiring to the test terminals. Power could damage the test diode in the terminal block.
Use the following steps to wire the transmitter:
Procedure
1. Remove the housing cover on the FIELD TERMINALS side.
10 Emerson.com/Rosemount
May 2019 Quick Start Guide
2. Connect the leads as shown in Figure 5-1.
3. Tighten the terminal screws to ensure full contact with the terminal block screw and washer. When using a direct wiring method, wrap wire clockwise to ensure it is in place when tightening the terminal block screw.
Note
The use of a pin or ferrule wire terminal is not recommended as the connection may be more susceptible to loosening over time or under vibration.
4. Ground housing to fulfill local grounding regulations.
5. Ensure proper grounding. It is important that the instrument cable shield:
Be trimmed close and insulated from touching the transmitter
housing
Be connected to the next shield if cable is routed through a
junction box
Be connected to a good earth ground at the power supply end
6. If transient protection is needed, refer to Grounding for transient
terminal block section for grounding instructions.
7. Plug and seal unused conduit connections.
8. Replace the housing cover.
Quick Start Guide 11
DP
A
B
C
D
E
Quick Start Guide May 2019
Figure 5-2: Grounding
A. Trim shield and insulate B. Insulate shield C. Terminate cable shield drain wire to earth ground
D. Internal ground location
E. External ground location

5.1 Grounding for transient terminal block

Ground termination is provided on the outside of the electronics housing and inside the terminal compartment. These grounds are used when the transient protection terminal blocks are installed. It is recommended that 18 AWG or larger wire is used to connect housing ground to earth ground (internal or external).
If the transmitter is currently not wired for power up and communication, follow Connect the wiring and power up. When the transmitter is properly wired, refer to Figure 5-2 for internal and external transient grounding locations.
12 Emerson.com/Rosemount
May 2019 Quick Start Guide

6 Verify transmitter configuration

Verify the configuration using any HART® capable configuration tool or LOI ­option code M4. Configuration instructions for a Field Communicator and LOI are included in this step. See Rosemount™ 2051 Reference Manual for configuration instructions using AMS Device Manager.

6.1 Verifying configuration with a Field Communicator

A Rosemount™ 2051 DD must be installed on the Field Communicator to verify configuration. Fast Key sequences vary depending on device and DD revisions. Use the Determine Fast Key sequence table process below to identify the appropriate Fast Key sequences.

6.2 Field Communicator user interface

6.2.1 Determine Fast Key sequence table

Procedure
1. Connect Field Communicator to Rosemount™ 2051G.
2. If Home screen matches Figure 6-1, refer to Table 6-1 for Fast Key sequences.
3. If Home screen matches Figure 6-2:
a) Perform Fast Key sequence 1, 7, 2 to identify Field Revision
and HART® Revision.
b) Refer to Table 6-2 and the appropriate column based on your
Field Revision and HART Revision for Fast Key sequences.
Note
Emerson recommends installing the latest DD to access the complete functionality. Visit Emerson.com or FieldCommGroup.org.
Figure 6-1: Traditional Interface
Quick Start Guide 13
Quick Start Guide May 2019
Figure 6-2: Device Dashboard
Note
A check () indicates the basic configuration parameters. At minimum, these parameters should be verified as part of the configuration and startup procedure.
Table 6-1: Traditional Interface Fast Keys
Function Fast Key sequence
Analog Output Alarm 1,4,3,2,4
Burst Mode Control 1,4,3,3,3
Burst Option 1,4,3,3,4
Calibration 1,2,3
Damping 1,3,5
Date 1,3,4,1
Descriptor 1,3,4,2
Digital To Analog Trim (4–
20 mA Output)
Disable Local Span/Zero
Adjustment
Field Device Info 1,4,4,1
Keypad Input 1,2,3,1,1
Loop Test 1,2,2
Lower Range Value 4,1
Lower Sensor Trim 1,2,3,3,2
Message 1,3,4,3
Meter Type 1,3,6,1
Number of Requested 1,4,3,3,2
1,2,3,2,1
1,4,4,1,7
14 Emerson.com/Rosemount
May 2019 Quick Start Guide
Table 6-1: Traditional Interface Fast Keys (continued)
Function Fast Key sequence
Output Trim 1,2,3,2
Percent Range 1,1,2
Poll Address 1,4,3,3,1
Range Values 1,3,3
Rerange 1,2,3,1
Scaled D/A Trim (4–20 mA 1,2,3,2,2
Self Test (Transmitter) 1,2,1,1
Sensor Info 1,4,4,2
Sensor Trim (Full Trim) 1,2,3,3
Sensor Trim Points 1,2,3,3,5
Status 1,2,1,2
Tag 1,3,1
Transmitter Security (Write
Protect)
Units (Process Variable) 1,3,2
Upper Range Value 5,2
Upper Sensor Trim 1,2,3,3,3
Zero Trim 1,2,3,3,1
1,3,4,4
Note
A check () indicates the basic configuration parameters. At minimum, these parameters should be verified as part of the configuration and startup procedure.
Table 6-2: Device Dashboard Fast Keys
Function Fast Key sequence
Field Revision Rev 3 Rev 5 Rev 7
HART Revision HART 5 HART 5 HART 7
Alarm and Saturation
Levels
Damping 2,2,1,2 2,2,1,1,5 2,2,1,1,5
Range Values 2,2,2 2,2,2 2,2,2
Tag 2,2,6,1,1 2,2,7,1,1 2,2,7,1,1
Quick Start Guide 15
N/A 2,2,2,5,7 2,2,2,5,7
Quick Start Guide May 2019
Table 6-2: Device Dashboard Fast Keys (continued)
Function Fast Key sequence
Field Revision Rev 3 Rev 5 Rev 7
HART Revision HART 5 HART 5 HART 7
Transfer Function 2,2,1,3 2,2,1,1,6 2,2,1,1,6
Units 2,2,1,1 2,2,1,1,4 2,2,1,1,4
Burst Mode 2,2,4,1 2,2,5,3 2,2,5,3
Custom Display
Configuration
Date 2,2,6,1,4 2,2,7,1,3 2,2,7,1,4
Descriptor 2,2,6,1,5 2,2,7,1,4 2,2,7,1,5
Digital to Analog Trim
(4-20 mA Output)
Disable Configuration
Buttons
Rerange with Keypad 2,2,2 2,2,2,1 2,2,2,1
Loop Test 3,5,1 3,5,1 3,5,1
Upper Sensor Trim 3,4,1,1 3,4,1,1 3,4,1,1
Lower Sensor Trim 3,4,1,2 3,4,1,2 3,4,1,2
Message 2,2,6,1,5 2,2,7,1,5 2,2,7,1,6
Sensor Temperature/Trend 3,3,2 3,3,3 3,3,3
Digital Zero Trim 3,4,1,3 3,4,1,3 3,4,1,3
Password N/A 2,2,6,4 2,2,6,5
Scaled Variable N/A 3,2,2 3,2,2
HART Revision 5 to HART
Revision 7 switch
Long Tag N/A N/A 2,2,7,1,2
Find Device N/A N/A 3,4,5
Simulate Digital Signal N/A N/A 3,4,5
2,2,3 2,2,4 2,2,4
3,4,2 3,4,2 3,4,2
2,2,5,2 2,2,6,3 2,2,6,3
N/A 2,2,5,2,3 2,2,5,2,3

6.3 Verifying configuration with LOI

The optional LOI can be used for commissioning the device. The LOI is a two­button design with internal and external buttons. The internal buttons are located on the display of the transmitter, while the external buttons are
16 Emerson.com/Rosemount
May 2019 Quick Start Guide
located underneath the top metal tag. To activate the LOI, push any button. LOI button functionality is shown on the bottom corners of the display. See
Table 6-3 and Figure 6-4 for button operation and menu information.
Figure 6-3: Internal and External LOI Buttons
A. Internal buttons B. External buttons
Note
See Figure 7-1 to confirm external button functionality.
Table 6-3: LOI Button Operation
Butto n
Left No SCROLL
Right Yes ENTER
Quick Start Guide 17
Assign PV
HART Revision
Quick Start Guide May 2019
Figure 6-4: LOI Menu

6.3.1 Switch HART revision mode

If the HART configuration tool is not capable of communicating with HART Revision 7, the Rosemount™ 2051G will load a Generic Menu with limited capability. The following procedures will switch the HART revision mode from the Generic Menu:
®
Procedure
Manual Setup Device Information Identification Message
a) To change to HART Revision 5, Enter: “HART5” in the Message field.
b) To change to HART Revision 7, Enter: “HART7” in the Message field.
18 Emerson.com/Rosemount
May 2019 Quick Start Guide

7 Trim the transmitter

Devices are calibrated by the factory. Once installed, it is recommended to perform a zero trim on gage and absolute transmitters to eliminate error due to mounting position or static pressure effects. A zero trim can be performed using either a Field Communicator or configuration buttons.
For instructions using AMS Device Manager, see the Rosemount™ 2051
Reference Manual.
Note
When performing a zero trim, ensure the equalization valve is open and all wet legs are filled to the correct level.
CAUTION
It is not recommended to zero an absolute transmitter
Procedure
Select trim procedure.
a) Analog Zero Trim – Sets the analog output to 4 mA.
Also referred to as a “rerange,” it sets the Lower Range Value
(LRV) equal to the measured pressure.
The display and digital HART output remains unchanged.
b) Digital Zero Trim – Recalibrates the sensor zero.
The LRV is unaffected. The pressure value will be zero (on display
and HART output). 4 mA point may not be at zero.
This requires that the factory calibrated zero pressure is within a
range of three percent of the URV [0 ± 3% x URV].
7.1
7.2
Quick Start Guide 19

Example

URV = 150 psi
Applied Zero Pressure = + 0.03 x 150 psi = + 4.5 psi (compared to factory settings) values outside this range will be rejected by the transmitter

Trimming with a Field Communicator

Procedure
1. Connect the Field Communicator, see Connect the wiring and power
up for instructions.
Quick Start Guide May 2019
2. Follow the HART menu to perform the desired zero trim.
Table 7-1: Zero Trim Fast Keys
Analog zero (set 4 mA) Digital zero
Fast Key Sequence 3, 4, 2 3, 4, 1, 3

7.3 Trimming with configuration buttons

A zero trim is to be performed using one of the three possible sets of external configuration buttons located under the top tag.
To access the configuration buttons, loosen the screw and slide the tag on the top of the transmitter. Confirm the functionality using Figure 6-3.
Figure 7-1: External Configuration Buttons
A. Configuration buttons B. LOI C. Analog zero and span
D. Digital zero
Use the following procedures to perform a Zero Trim:

7.3.1 Perform trim with LOI (option M4)

Procedure
1. Set the transmitter pressure.
2. See Figure 6-3 for the operating menu. a) Select Rerange to perform an analog zero trim.
b) Select Zero Trim to perform a digital zero trim.

7.3.2 Perform trim with analog zero and span (option D4)

Procedure
1. Set the transmitter pressure.
20 Emerson.com/Rosemount
May 2019 Quick Start Guide
2. Press and hold the zero button for two seconds to perform an analog zero trim.

7.3.3 Perform trim with digital zero (option DZ)

Procedure
1. Set the transmitter pressure.
2. Press and hold the zero button for two seconds to perform a digital zero trim.
Quick Start Guide 21
Quick Start Guide May 2019

8 Safety instrumented systems

For safety certified installations, refer to the Rosemount™ 2051G Reference
Manual for installation procedure and system requirements.
22 Emerson.com/Rosemount
May 2019 Quick Start Guide

9 Product certifications

Rev. 1.5

9.1 European Directive Information

A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount.

9.2 North America

E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate
Standards
Markings
I5 USA Intrinsic Safety (IS) and Nonincendive (NI)
Certificate
Standards
Markings
E6 Canada Explosionproof, Division 2, Dust-Ignitionproof
Certificate
Standards
Markings
1015441
FM Class 3600 - 2011, FM, Class 3615 - 2006, FM class 3616 ­2011, FM Class 3810 - 2005
XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T5(– 50 °C ≤ Ta ≤ +85 °C); Factory Sealed; Type 4X
1015441
FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 ­2004, FM Class 3810 - 2005
IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV 1 when connected per Rosemount™ drawing 02088-1024; NI CL 1, DIV 2, GP A, B, C, D; T4(–50 °C ≤ Ta ≤ +70 °C); Type 4x
1015441
CAN/CSA C22.2 No. 0-M91 (R2001), CSA Std C22.2 No. 25-1966, CSA Std C22.2 No. 30-M1986, CAN/CSA-C22.2 No. 94-M91, CSA Std C22.2 No. 142-M1987, CAN/CSA-C22.2 No. 157-92, CSA Std C22.2 No. 213-M1987, ANSI­ISA-12.27.01-2003
Class I, Division 1, Groups B, C and D; Class II, Groups E, F, and G; Class III; Class I Division 2 Groups A, B, C and D; Type 4X; Factory Sealed; Single Seal
I6 Canada Intrinsic Safety
Certificate
Quick Start Guide 23
1015441
Quick Start Guide May 2019
Standards
Markings

9.3 Europe

E1 ATEX Flameproof
Certificate
Standards
Markings
Table 9-1: Process Connection Temperature
Temperature class Process connection
T6 –60 to +70 °C –60 to +70 °C
T5 –60 to +80 °C –60 to +80 °C
T4 –60 to +120 °C –60 to +80 °C
CAN/CSA C22.2 No. 0-M91 (R2001), CSA Std C22.2 No. 25-1966, CSA Std C22.2 No. 30-M1986, CAN/CSA-C22.2 No. 94-M91, CSA Std C22.2 No. 142-M1987, CAN/CSA-C22.2 No. 157-92, CSA Std C22.2 No. 213-M1987, ANSI­ISA-12.27.01-2003
Intrinsically Safe Class I, Division 1 when connected in accordance with Rosemount drawing 02088-1024, Temperature Code T4; Ex ia; Type 4X; Factory Sealed; Single Seal
KEMA97ATEX2378X
EN 60079-0:2012 + A11:2013, EN60079-1:2014, EN60079-26:2015
II 1/2 G Ex db IIC T6..T4 Ga/Gb, T6(–60 °C ≤ Ta ≤ +70 °C),
T5/T4 (–60 °C ≤ Ta ≤ +80 °C)
Ambient temperature
temperature
Special Conditions for Safe Use(X)
1. This device contains a thin wall diaphragm less than 1 mm thickness that forms a boundary between zone 0 (process connection) and zone 1 (all other parts of the equipment). The model code and datasheet are to be consulted for details of the diaphragm material. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp
24 Emerson.com/Rosemount
May 2019 Quick Start Guide
cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
4. Appropriate cable, glands and plugs need to be suitable for a temperature of 5 °C greater than maximum specified temperature for location where installed.
I1 ATEX Intrinsic Safety
Certificate
Standards
Markings
BAS00ATEX1166X
EN60079-0:2012 + A11:2013, EN60079-11:2012
Ex II 1 G Ex ia IIC T4 Ga (–55 °C ≤ Ta ≤ +70 °C)
Table 9-2: Input Parameters
HART
Voltage U
Current I
Power P
Capacitance Ci0.012 μF
i
i
30 V
i
200 mA
0.9 W
Special Conditions for Safe Use(X)
1. The apparatus is not capable of withstanding the 500 V insulation test required by EN60079-11. This must be taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 environment.
N1 ATEX Type n
Certificate
Standards
Markings
BAS00ATEX3167X
EN60079-0:2012 + A11:2013, EN60079-15:2010
Ex II 3 G Ex nA IIC T5 Gc (–55 °C ≤ Ta ≤ +70 °C)
Special Conditions for Safe Use(X)
1. This apparatus is not capable of withstanding the 500V insulation test required by EN60079-15. This must be taken into account when installing the apparatus.
ND ATEX Dust
Certificate
Quick Start Guide 25
BAS01ATEX1427X
Quick Start Guide May 2019
Standards
Markings
Special Conditions for Safe Use(X)
1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient range of the apparatus and capable of withstanding a 7J impact test.

9.4 International

E7 IECEx Flameproof
Certificate
Standards
Markings
Table 9-3: Process Connection Temperature
Temperature class Process connection
T6 –60 to +70 °C –60 to +70 °C
T5 –60 to +80 °C –60 to +80 °C
T4 –60 to +120 °C –60 to +80 °C
IECEx KEM 06.0021X
IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-26:2014
Ex db IIC T6…T4 Ga/Gb T6(–60 °C ≤ Ta ≤ +70 °C), T5/T4(–60 °C ≤ Ta ≤ +80 °C)
EN60079-0:2012 + A11:2013, EN60079-31:2009
Ex II 1 D Ex t IIIC T50 °C T
temperature
60 °C Da
500
Ambient temperature
Special Conditions for Safe Use(X)
1. This device contains a thin wall diaphragm less than 1 mm thickness that forms a boundary between zone 0 (process connection) and zone 1 (all other parts of the equipment). The model code and datasheet are to be consulted for details of the diaphragm material. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
26 Emerson.com/Rosemount
May 2019 Quick Start Guide
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
4. Appropriate cable, glands, and plugs need to be suitable for a temperature of 5 °C greater than maximum specified temperature for location where installed.
I7 IECEx Intrinsic Safety
Certificate
Standards
Markings
IECEx BAS 12.0071X
IEC60079-0:2011, IEC60079-11:2011
Ex ia IIC T4 Ga (–55 °C ≤ Ta ≤ +70 °C)
Table 9-4: Input Parameters
Voltage U
Current I
Power P
Capacitance Ci0.012 μF
i
i
30 V
i
200 mA
0.9 W
Special Conditions for Safe Use(X)
1. When fitted with a transient suppression terminal block, the Rosemount™ 2088 is incapable of passing the 500 V isolation test. This must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 environment.
N7 IECEx Type n
Certificate
Standards
Markings
IECEx BAS 12.0072X
IEC60079-0:2011, IEC60079-15:2010
Ex nA IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C)
Special Conditions for Safe Use(X)
1. When fitted with a transient suppression terminal block, the Rosemount 2088 is incapable of passing the 500 V isolation test. This must be taken into account during installation.
NK IECEx Dust
Quick Start Guide 27
Quick Start Guide May 2019
Certificate
Standards
Markings
Table 9-5: Input Parameters
HART
Voltage U
Current I
Special Conditions for Safe Use(X)
1. Cable entries must be used which maintain the ingress protection of
2. Unused cable entries must be filled with suitable blanking plugs
3. Cable entries and blanking plugs must be suitable for the ambient

9.5 Brazil

E2 INMETRO Flameproof
IECEx BAS12.0073X
IEC60079-0:2011, IEC60079-31:2008
Ex t IIIC T50 °C T
36 V
i
i
24 mA
500
60 °C Da
the enclosure to at least IP66.
which maintain the ingress protection of the enclosure to at least IP66.
temperature range of the apparatus and capable of withstanding a 7J impact test.
Certificate
Standards
UL-BR 15.0728X
ABNT NBR IEC 60079-0:2013, ABNT NBR IEC 60079-1:2016, ABNT NBR IEC 60079-26:2016
Markings
Ex db IIC T6…T4 Ga/Gb T4/T5(–60 °C ≤ Ta ≤ +80 °C), T6(–60 °C ≤ Ta ≤ +70 °C)
Special Conditions for Safe Use(X)
1. This device contains a thin wall diaphragm less than 1 mm thickness that forms a boundary between zone 0 (process connection) and zone 1 (all other parts of the equipment). The model code and datasheet are to be consulted for details of the diaphragm material. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
28 Emerson.com/Rosemount
May 2019 Quick Start Guide
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
I2 INMETRO Intrinsic Safety
9.6
Certificate
Standards
UL-BR 13.0246X
ABNT NBR IEC60079-0:2008 + Errata 1:2011, ABNT NBR IEC60079-11:2009
Markings
Ex ia IIC T4 Ga (–55 °C ≤ Ta ≤ +70 °C)
Table 9-6: Input Parameters
Voltage U
Current I
Power P
Capacitance Ci0.012 μF
Inductance Li0 mH
i
i
30 V
i
200 mA
0.9 W
Special Conditions for Safe Use(X)
1. When fitted with a transient suppression terminal block, the Rosemount™ 2088 is incapable of passing the 500 V isolation test. This must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 environment (areas that require EPL Ga).

China

E3 China Flameproof
Certificate
Standards
Markings
GYJ17.1158X
GB3836.1-2010, GB3836.2-2010, GB3836.20-2010
Ex d IIC T6 ~T4 Ga/Gb, T5/T4(–60 °C ≤ Ta ≤ +80 °C), T6(–60 °C ≤ Ta ≤ +70 °C)
Special Conditions for Safe Use(X)
1. Contact the original manufacturer when repair work relates to the flamepath.
Quick Start Guide 29
Quick Start Guide May 2019
I3 China Intrinsic Safety
9.7
Certificate
Standards
Markings
Special Conditions for Safe Use(X)
1. The enclosure may contain light metal, attention should be taken to avoid ignition hazard due to impact or friction when used in Zone 0.
2. When transient protection board is chosen (option code T1), this apparatus is not capable of withstanding the 500 V r.m.s insulation test required by Clause 6.3.12 of GB3836.4-2010.
N3 China Type n
Certificate
Standards
Markings
Special Conditions for Safe Use(X)
1. When transient protection board is chosen (option code T1),this apparatus is not capable of withstanding the 500 V r.m.s insulation test required by Clause 6.3.12 of GB3836.4-2010.
GYJ17.1157X
GB3836.1-2010, GB3836.4-2010, GB3836.20-2010
Ex ia IIC T4 Ga (–55 °C ≤ Ta ≤ +70 °C)
GYJ17.1159X
GB3836.1-2010, GB3836.8-2014
Ex nA IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C)

Technical Regulations Customs Union (EAC)

EM EAC Flameproof
Certificate
Markings
Special Conditions for Safe Use(X)
1. See certificate for special conditions.
IM EAC Intrinsic Safety
Certificate
Markings
Special Conditions for Safe Use(X)
1. See certificate for special conditions.
30 Emerson.com/Rosemount
TC RU C-US.AA87.B.00534
Ga/Gb Ex db IIC T5/T6 X, T5 (–60 °C ≤ Ta ≤ +80 °C), T6(–60 °C ≤ Ta ≤ +70 °C)
TC RU C-US.AA87.B.00534
0Ex ia IIC T4 Ga X, T4(–55 °C ≤ Ta ≤ +70 °C)
May 2019 Quick Start Guide

9.8 Combinations

K1
K2
K3
K5
K6
K7
KB
KD
KM
combination of E1, I1, and N1
combination of E2 and I2
combination of E3 and I3
combination of E5 and I5
combination of E6 and I6
combination of E7, I7, N7, and NK
combination of K5 and K6
combination of E1, I1, K5, and K6
combination of EM and IM

9.9 Conduit plugs and adapters

IECEx Flameproof and Increased Safety
Certificate
Standards
Markings
ATEX Flameproof and Increased Safety
Certificate
Standards
Markings
IECEx FMG 13.0032X
IEC60079-0:2011, IEC60079-1:2007, IEC60079-7:2006-2007
Ex d e IIC Gb
FM13ATEX0076X
EN60079-0:2012, EN60079-1:2007, IEC60079-7:2007
Ex II 2 G Ex d e IIC Gb
Table 9-7: Conduit Plug Thread Sizes
Thread Identification mark
M20 x 1.5 M20
½ –14 NPT ½ NPT
G ½ G ½
Table 9-8: Thread Adapter Thread Sizes
Male thread Identification mark
M20 x 1.5–6H M20
½–14 NPT ½–14 NPT
¾–14 NPT ¾–14 NPT
Quick Start Guide 31
Quick Start Guide May 2019
Table 9-8: Thread Adapter Thread Sizes (continued)
Female thread Identification mark
M20 x 1.5–6H M20
½–14 NPT ½–14 NPT
G ½ G ½
Special Conditions for Safe Use(X)
1. When the thread adapter or blanking plug is used with an enclosure in type of protection increased safety “e” the entry thread shall be suitably sealed in order to maintain the ingress protection rating (IP) of the enclosure.
2. The blanking plug shall not be used with an adapter.
3. Blanking Plug and Threaded Adapter shall be either NPT or Metric thread forms. G 1/2 thread forms are only acceptable for existing (legacy) equipment installations.
32 Emerson.com/Rosemount
May 2019 Quick Start Guide
Figure 9-1: Rosemount™ 2051G Declaration of Conformity
Quick Start Guide 33
Quick Start Guide May 2019
34 Emerson.com/Rosemount
May 2019 Quick Start Guide
Quick Start Guide 35
Quick Start Guide May 2019
36 Emerson.com/Rosemount
May 2019 Quick Start Guide
Quick Start Guide 37
Quick Start Guide May 2019
38 Emerson.com/Rosemount
May 2019 Quick Start Guide
Quick Start Guide 39
*00825-0700-4101*
00825-0700-4101, Rev. AD
Quick Start Guide
May 2019
Global Headquarters
Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com
Latin America Regional Office
Emerson Automation Solutions 1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office
Emerson Automation Solutions 1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com
North America Regional Office
Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRF@Emerson.com
Europe Regional Office
Emerson Automation Solutions Europe GmbH Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465 RFQ.RMTMEA@Emerson.com
Linkedin.com/company/Emerson-
Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/
RosemountMeasurement
©
2019 Emerson. All rights reserved.
Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is mark of one of the Emerson family of companies. All other marks are the property of their respective owners.
Loading...