Rosemount 1595 Quick Start Guide

Page 1
Quick Start Guide
00825-0100-4828, Rev DC
July 2014
Rosemount 1595 Conditioning Orifice Plate
Page 2
July 2014
NOTICE
This installation guide provides basic guidelines for Rosemount 1595 Conditioning Orifice Plate. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flame-Proof, or intrinsically safe (I.S.) installations. Refer to the 1595 reference manual (document number 00809-0100-4828) for more instruction. This manual is also available electronically on www.rosemount.com.
WARNING
Process leaks may cause harm or result in death.
To avoid process leaks, only use gaskets designed to seal with the corresponding flange and o-rings to seal process connections.
Contents
Primary element location . . . . . . . . . . . . . 3
Primary element orientation . . . . . . . . . . 4
2
Primary element installation . . . . . . . . . . .6
Product Certifications . . . . . . . . . . . . . . . 10
Page 3
July 2014
Quick Start Guide

Step 1: Primary element location

Install the 1595 in the correct location within the piping branch to prevent inaccurate measurement caused by flow disturbances.
1
(1)
Table 1. 1595 Straight Pipe Requirements
Beta 0.20 0.40 0.50 0.65
Single 90° bend or tee
Two or more 90° bends in the same plane
Two or more 90° bends in different plane
Up to 10° of swirl
side of primary
Upstream (inlet)
Reducer (1 line size)
Butterfly valve (75% to 100% open)
Downstream (outlet) side of primary
1. Consult an Emerson Process Management representative if disturbance is not listed.
2. Not applicable in line sizes greater than 24-in. (600 mm).
(2) 2
(2)
(2)
Pressure tap orientation
Orient the 1595 Conditioning Orifice Plate so the pressure taps are centered between any two (of four) orifice bore holes. In addition, the pressure taps should be located at 90° to the plane of the last elbow.
2222
2 2 2 2
2222
2 2 2 2
2222
2 2 5 5
2222
Centering requirements
The 1595 should be installed so that it is centered in the pipe as recommended by ISO-5167.
3
Page 4
30°
Recommended
Zone 120°
30°
F
l
o
w
F
l
o
w

Step 2: Primary element orientation

The following drawings show paddle style conditioning orifice plate, but orientation pertains to both paddle and universal plate styles.
Horizontal pipe installation
Figure 1. Gas in Horizontal Pipes
FLOW
Figure 2. Liquid or Steam in Horizontal Pipes
July 2014
4
Page 5
July 2014
Flow
FLOW
Flow
Vertical pipe installation
Figure 3. Gas in Vertical Pipes
FLOW
Figure 4. Liquid or Steam in Vertical Pipes
Quick Start Guide
5
Page 6
July 2014

Step 3: Primary element installation

Use the following steps to install the 1595 Conditioning Orifice Plate (paddle or universal plate style).
1. Determine location and orientation (see page 4).
2. Install the orifice plate. a. Depressurize the line using site-specific requirements. b. Loosen all studs and nuts. c. Remove the studs in one-half of the flange union. d. Spread flange union by turning jackscrews clockwise. e. For line sizes > 24-in (600 mm), refer to Figure 7 and instructions using
alignment tool.
f. Install the new plate or remove the existing plate for replacement or
inspection.
g. Install the new gaskets when installing the plate. It is recommended that
new gaskets be installed each time the orifice flange union is separated. h. Center the plate in the pipe I.D. i. Release the flange union by turning the jackscrews counter-clockwise. j. Replace the studs. k. Tighten studs in a star pattern.
Note
Standa rd 1/16-in. thick fiber gaskets are recommended for use with the 1595. Using other gaskets could potentially affect the measurement.
6
Page 7
July 2014
A
I
G
F
E
C
B
A
H
D
D
F
l
o
w
Quick Start Guide
Figure 5. Rosemount 1595P Installation
A. Nuts F. Pipe Section B. Plug G. Stud C. Jackscrew H. Gasket D. Jackscrew Nut I. Transmitter E. Rosemount 1595
1. The installation drawings applies when using the Rosemount 2051C, Rosemount 3051C, Rosemount 3051S and Rosemount 3051SMV. See the following documents for quick installation instruction of the transmitters. Rosemount 2051C: document number 00825-0100-4101 Rosemount 3051C: document number 00825-0100-4001 Rosemount 3051S: document number 00825-0100-4801 Rosemount 3051SMV: document number 00825-0100-4803
1
(1)
7
Page 8
A
G
F
E
A
C
B
D
H
Figure 6. Rosemount 1595U with Plate Holder (PH) Installation
A. Nuts E. Pipe Section B. Jackscrew F. Stu d C. Universal Plate Screw G. Transmitter D. Rosemount 1595
1
(1)
H. Jackscrew Nut
July 2014
1. The installation drawings applies when using the Rosemount 2051C, Rosemount 3051C, Rosemount 3051S and Rosemount 3051SMV. See the following documents for quick installation instruction of the transmitters. Rosemount 2051C: document number 00825-0100-4101 Rosemount 3051C: document number 00825-0100-4001 Rosemount 3051S: document number 00825-0100-4801 Rosemount 3051SMV: document number 00825-0100-4803
Note
For 1595U Universal Conditioning Orifice Plate style, refer to manufacturer’s orifice fitting installation manual for installation details.
For sizes > 24-in. (600 mm) and use with alignment tool
1. When an alignment tool is provided, install the alignment tool on the flange studs shown in Figure 7.
2. For horizontal installation, use the horizontal lift hole (stamped HLH on paddle) to lift the conditioning orifice plate from a horizontal position and guide into location between the flanges.
3. For vertical installation, first use the horizontal lift hole (HLH) to lift the conditioning orifice plate from a horizontal position to vertical, then use the vertical lift hole (stamped VLH on paddle) to lift the conditioning orifice plate vertically and guide into location between the flanges.
8
Page 9
July 2014
A
C
B
A
F
B
C
H
D
G
I
E
DETAIL “A”
D
E
H
DETAIL “A”
Figure 7. Rosemount 1595P (sizes > 24-in (600 mm)) Installation
A. Nuts F. Pipe Section B. Jackscrew G. Stud C. Jackscrew Nut H. Gasket D. Rosemount 1595 E. Alignment Tools
1
(1)
I. Transmitter
Quick Start Guide
1. The installation drawings applies when using the Rosemount 2051C, Rosemount 3051C, Rosemount 3051S and Rosemount 3051SMV. See the following documents for quick installation instruction of the transmitters. Rosemount 2051C: document number 00825-0100-4101 Rosemount 3051C: document number 00825-0100-4001 Rosemount 3051S: document number 00825-0100-4801 Rosemount 3051SMV: document number 00825-0100-4803
Note
To ensure the best possible flow measurement accuracy, Rosemount provides an Official DP Calculation Sheet with every 1595 Conditioning Orifice Plate. The Official DP Calculation sheet uses the calibration factor which is unique to that device and is also stamped on the orifice plate. The Official DP Calculation Sheet displays the expected full scale flow value and the calculated full scale DP value and is corrected for the unique calibration factor which is also displayed on the sheet. This full scale DP value should be used to range a DP transmitter for the referenced application. Or, the calibration factor should be used as a correction factor when configuring a flow computer for the Rosemount Conditioning Orifice Plate.
9
Page 10

Product Certifications

Approved Manufacturing Locations
Rosemount Inc. — Chanhassen, Minnesota USA
European Directive Information
The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www.rosemount.com. A hard copy may be obtained by contacting our local sales office.
European Pressure Equipment Directive (PED) (97/23/EC)
Rosemount 1595 Conditioning Orifice Plate — Sound Engineering Practice (SEP) Pressure Transmitter — See appropriate Pressure Transmitter QIG
Hazardous Locations Certifications
For information regarding the electronics product certification, see the appropriate transmitter QIG:
Rosemount 3051SF Series Flowmeter Electronics with HART Protocol (document
number 00825-0100-4801)
Rosemount 3095MF Mass Flowmeter Electronics (document number
00825-0100-4716)
July 2014
10
Page 11
July 2014
File ID: DSI C E Marking Page 1 of 3 DSI 1000I-DoC
EC Declaration of Conformity
No: DSI 1000 Rev. I
We,
Emerson Process Management Heath Place - Bognor Regis West Sussex PO22 9SH England
declare under our sole responsibility that the products,
Primary Element Models 405 / 1195 / 1595 & Annubar®
Models 485 / 585
manufactured by,
Rosemount / Dieterich Standard, Inc. 5601 North 71
st
Street Boulder, CO 80301 USA
to which this declaration relates, is in conformity with the provisions of the European Community Directives as shown in the attached schedule.
Assumption of conformity is based on the application of the harmonized standards and, when applicable or required, a European Community notified body certification, as shown in the attached schedule.
As permitted by 97/23/EC, Annex 7, the authorized signatory for the legally binding declaration of
conformity for Rosemount/Dieterich Standard, Inc. is Vice President of Quality, Timothy J. Layer.
20-Oct-2011
Timothy J. Layer
Vice President, Quality
(signature)
(date of issue)
Quick Start Guide
11
Page 12
File ID: DSI C E Marking Page 2 of 3 DSI 1000I-DoC
Schedule
EC Declaration of Conformity DSI 1000 Rev. I
PED Directive (97/23/EC)
Models: 405 / 485 / 585/ 1195 / 1595
QS Certificate of Assessment – CE-0041-H-RMT-001-10-USA
IV* Flo Tap - 485/3051SFA/3095MFA: Sensor Size 3 600# 60" to 72" Line (Category IV Flo Tap will require a B1 Certificate for design examination and H1 Certificate for special surveillance)
All other models: Sound Engineering Practice
Summary of Classifications
Model/Range
PED Category
Group 1
Fluid
Group 2
Fluid
585M - 2500# All Lines
N/A
SEP
585S - 1500# & 2500# All Lines
III
SEP
MSL46 - 2500# All Lines
N/A
SEP
MSR: 1500# & 2500# All Lines
III
SEP
1195, 3051SFP, 3095MFP: 150# 1-1/2
I
SEP
1195, 3051SFP, 3095MFP: 300# & 600# 1-1/2
II
I
1195, 3051SFP, 3095MFP: 1-1/2 Threaded & Welded
II
I
DNF - 150# 1-1/4”, 1-1/2” & 2
I
SEP
DNF - 300# 1-1/4”, 1-1/2” & 2
II
I
DNF, DNT, & DNW: 600# 1-1/4”, 1-1/2” & 2”
II
I
Flanged  485/3051SFA/3095MFA: 1500# & 2500# All Lines
II
SEP
FloTap  485/3051SFA/3095MFA: Sensor Size 2 150# 6to 24 Line
I
SEP
FloTap  485/3051SFA/3095MFA: Sensor Size 2 300# 6to 24 Line
II
I
FloTap  485/3051SFA/3095MFA: Sensor Size 2 600# 6to 16 Line
II
I
FloTap  485/3051SFA/3095MFA: Sensor Size 2 600# 18to 24 Line
III
II
FloTap  485/3051SFA/3095MFA: Sensor Size 3 150# 12to 44 Line
II
I
FloTap  485/3051SFA/3095MFA: Sensor Size 3 150# 46to 72 Line
III
II
FloTap  485/3051SFA/3095MFA: Sensor Size 3 300# 12 to 72 Line
III
II
FloTap  485/3051SFA/3095MFA: Sensor Size 3 600# 12to 48 Line
III
II
FloTap  485/3051SFA/3095MFA: Sensor Size 3 600# 60 to 72 Line
IV*
III
July 2014
12
Page 13
File ID: DSI C E Marking Page 3 of 3 DSI 1000I-DoC
Schedule
EC Declaration of Conformity DSI 1000 Rev. I
Pressure Equipment Directive (93/27/EC) Notified Body:
Bureau Veritas UK Limited
[Notified Body Number: 0041] Parklands, Wilmslow Road, Didsbury Manchester M20 2RE United Kingdom
July 2014
Quick Start Guide
13
Page 14
00825-0100-4828,RevDC
Quick Start Guide
00825-0100-4828, Rev DC
July 2014
Emerson Process Management Rosemou nt Inc.
8200 Market Boulevard Chanhassen, MN USA 55317 T (US) (800) 999-9307 T (Intnl) (952) 906-8888 F (952) 906-8889
Emerson Process Management Asia Pacific Priva te Limited
1 Pandan Crescent Singapore 128461 T (65) 6777 8211 F (65) 6777 0947/65 6777 0743
Emerson Process Management GmbH & Co. OHG
Argelsrieder Feld 3 82234 Wessling Germany T 49 (8153) 9390, F49 (8153) 939172
Beijing Rosemount Far East Instrument Co., Limited
No. 6 North Street, Hepingli, Dong Cheng Distric t Beijing 100013, China T (86) (10) 6428 2233 F (86) (10) 6422 8586
00825-0100-4828, Rev DC, 07/14
Emerson Process Management Latin America
1300 Concord Terrace, Suite 400 Sunrise Florida 33323 USA Tel + 1 954 846 5030 www.rosemount.com
© 2014 Rosemount Inc. All rights reserved. All marks property of owner. The Emerson logo is a trade mark and service mark of Emerson Electric Co Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.
Loading...