Read this manual before working with the product. For personal and system safety, and for optimum product performance,
ensure you thoroughly understand the contents before installing, using, or maintaining this product.
For technical assistance, contacts are listed below:
Customer Central
Technical support, quoting, and order-related questions.
• United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)
• Asia Pacific- 65 777 8211
North American Response Center
Equipment service needs.
• 1-800-654-7768 (24 hours a day — includes Canada)
• Outside of these areas, contact your local Emerson representative.
WARNING
Failure to follow safe installation and servicing guidelines could result in death or serious injury.
Ensure the transmitter is installed by qualified personnel and in accordance with applicable code of practice.
Inspection and maintenance of this equipment shall be carried out by suitably trained personnel, in accordance with the
applicable standards and code of practice.
Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment.
Repair, e.g. substitution of components, etc. may jeopardize safety and is under no circumstances allowed.
WARNING
Process leaks could result in death or serious injury.
Handle the transmitter carefully.
Install and tighten process connectors before applying pressure.
Do not attempt to loosen or remove process connectors while the transmitter is in service.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could
be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access
by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
CAUTION
Hot surfaces
The transmitter and process seal may be hot at high process temperatures. Allow to cool before servicing.
The sections in this manual provide information on installing, operating, and maintaining
the Rosemount™ 1408A Level and Flow Transmitter – Non-Contacting Radar.
The sections are organized as follows:
Transmitter overview provides an introduction to theory of operation, a description of the
transmitter, information on typical applications, and process characteristics.
Configuration provides instructions on configuration of the transmitter.
Operation and maintenance contains operation and maintenance techniques.
Service and troubleshooting provides troubleshooting techniques for the most common
operating problems.
Specifications and reference data supplies reference and specification data.
Configuration parameters provides extended information about the configuration
parameters.
1.2Product certifications
See the Rosemount 1408A Product Certifications document for detailed information on
the existing approvals and certifications.
1.3Open source licenses
This device uses open source software. Further information can be found in the
License Information document available at Emerson.com/Rosemount.
1.4Product recycling/disposal
Recycling of equipment and packaging should be taken into consideration and disposed of
in accordance with local and national legislation or regulations.
Related information
Service support
Reference Manual5
Page 6
IntroductionReference Manual
May 202200809-0200-4480
6Rosemount 1408A Level and Flow Transmitter
Page 7
d
f
i
n
f
max
f
min
f
out
f
in
f
out
t
f
A
C
D
B
Reference ManualTransmitter overview
00809-0200-4480May 2022
2Transmitter overview
2.1Measurement principle
The Rosemount 1408A is a transmitter for continuous level measurements using fastsweep Frequency Modulated Continuous Wave (FMCW) technology.
The transmitter continuously emits signal sweeps with a constantly varying frequency
towards the product surface. Since the transmitter continuously changes the frequency of
the transmitted signal, there will be a difference in frequency between the transmitted
and the reflected signals (see Figure 2-1).
The frequency of the reflected signal is subtracted from the frequency of the signal
transmitted at that moment, resulting in a low frequency signal which is proportional to
the distance to the product surface. This signal is further processed to obtain fast, reliable,
and highly accurate level measurements.
Figure 2-1: FMCW-method
Δf∼d=distance
A. Frequency (GHz)
Time (s)
B.
C. Transmitted signal
D. Reflected signal
The Rosemount 1408A can also calculate the volume flow rate in an open channel.
2.2Process characteristics
2.2.1Dielectric constant
A key parameter for measurement performance is reflectivity. A high dielectric constant of
the media provides better reflection and enables a longer measuring range.
Reference Manual7
Page 8
Transmitter overviewReference Manual
May 202200809-0200-4480
2.2.2Foam and turbulence
Foaming liquids or turbulence may cause weak and varying surface echo amplitudes.
Surface turbulence is not normally a problem unless it is excessive.
Measurement in foamy applications depends largely on the foam properties. When the
foam is light and airy, the actual product level is measured. For heavy and dense foam, the
transmitter may measure the level of the foam’s upper surface.
2.3Vessel characteristics
2.3.1In-tank obstructions
The transmitter should be mounted so that objects such as heating coils, ladders, and
agitators are not in the radar signal path. These objects may cause false echoes resulting in
reduced measurement performance. However, the transmitter has built-in functions
designed to reduce the influence from disturbing objects where such objects cannot be
totally avoided.
Vertical and inclined structures cause minimal effect since the radar signal is scattered
rather than directed back to the antenna.
2.4Non-contacting radar technology
Non-contacting radar technology is ideal for a wide range of applications as it is
maintenance-free, has a top-down installation that reduces the risk of leakages, and is
unaffected by process conditions such as density, viscosity, temperature, pressure, and
pH.
The Rosemount 1408A uses Frequency Modulated Continuous Wave (FMCW) technology
and smart algorithms to maximize measurement accuracy and reliability, even in small
tanks and challenging fast-filling vessels.
8Rosemount 1408A Level and Flow Transmitter
Page 9
Reference ManualTransmitter overview
00809-0200-4480May 2022
2.4.1Application examples
Storage tanks
Gain insights into your tank and ensure production runs smoothly without interruption.
Plastic tanks
Monitor the inventory of your small and medium sized plastic tanks by measuring through
the plastic roof.
Open air applications
Get reliable level measurements of sumps or ponds, regardless of challenging surface and
weather conditions.
Reference Manual9
Page 10
A
D
E
F
C
B
Transmitter overviewReference Manual
May 202200809-0200-4480
Open channel flow
Use the Rosemount 1408A for volume flow measurement of water and wastewater in
open channels.
2.5Components of the transmitter
Figure 2-2: Components
A. M12 connector (A-coded)
B. Transmitter housing (polished stainless steel)
C.
Wrench size: 39 mm
D. DIN 3869 profile ring
E. ISO 228/1-G1 thread
F. Antenna (PTFE sealing)
Related information
Dimensional drawings
10Rosemount 1408A Level and Flow Transmitter
Page 11
C
A
D
E
B
Reference ManualTransmitter overview
00809-0200-4480May 2022
2.6Easy integration with IO-Link
The Rosemount 1408A provides both conventional 4-20 mA and digital switch outputs,
enabled by IO-Link connectivity. This supports easy integration into any automation
system.
Each IO-Link system consists of an IO-Link master and one or more IO-Link devices (sensors
and actuators). The connection between the master and the device is established via
unshielded standard cables using standard connectors such as M12. Process data, events
and parameters are transferred to the master via IO-Link. The IO-Link master then
transfers the data to the controller (PLC) and its fieldbus or industrial ethernet network.
Figure 2-3: Example of an IO-Link System
A. Industrial ethernet
Programmable logic controller (PLC)
B.
C.
Industrial Fieldbus
D. IO-Link master
E. IO-Link devices
Reference Manual11
Page 12
Transmitter overviewReference Manual
May 202200809-0200-4480
12Rosemount 1408A Level and Flow Transmitter
Page 13
Reference ManualMechanical installation
00809-0200-4480May 2022
3Mechanical installation
3.1Safety messages
Instructions and procedures in this section may require special precautions to ensure the
safety of the personnel performing the operations. Information that potentially raises
safety issues is indicated by a warning symbol (). Refer to the following safety messages
before performing an operation preceded by this symbol.
WARNING
Failure to follow safe installation and servicing guidelines could result in death or
serious injury.
Ensure the transmitter is installed by qualified personnel and in accordance with applicable
code of practice.
Inspection and maintenance of this equipment shall be carried out by suitably trained
personnel, in accordance with the applicable standards and code of practice.
Use the equipment only as specified in this manual. Failure to do so may impair the
protection provided by the equipment.
Repair, e.g. substitution of components, etc. may jeopardize safety and is under no
circumstances allowed.
WARNING
Process leaks could result in death or serious injury.
Handle the transmitter carefully.
Install and tighten process connectors before applying pressure.
Do not attempt to loosen or remove process connectors while the transmitter is in service.
3.2Installation considerations
Before installing the transmitter, follow recommendations for mounting position,
sufficient free space, nozzle requirements, etc.
3.2.1Mounting position
When finding an appropriate location on the tank for the transmitter, the conditions of the
tank must be carefully considered.
Consider the following guidelines when mounting the transmitter:
• For optimal performance, the transmitter should be installed in locations with a clear
and unobstructed view of the product surface.
Reference Manual13
Page 14
L
L
Mechanical installationReference Manual
May 202200809-0200-4480
• The transmitter should be mounted with as few internal structures as possible within
the signal beam.
• Do not mount close to or above the inlet stream.
• Do not mount the transmitter on a manway cover.
• Do not position the transmitter directly over a side manway door.
• Multiple Rosemount 1408A transmitters can be used in the same tank without
interfering with each other.
Figure 3-1: Recommended Mounting Position
3.2.2Free space requirements
If the transmitter is mounted close to a wall or other tank obstruction such as heating coils
and ladders, noise might appear in the measurement signal. See Table 3-1 for
recommended clearance.
Figure 3-2: Free Space Requirements
Table 3-1: Distance to Tank Wall (L)
MinimumRecommended
8 in. (200 mm)½ of tank radius
14Rosemount 1408A Level and Flow Transmitter
Page 15
90°
Max. 3°
Reference ManualMechanical installation
00809-0200-4480May 2022
3.2.3Inclination
The transmitter should be mounted vertically to ensure a good echo from the product
surface. See Figure 3-3 for recommended maximum inclination.
Figure 3-3: Inclination
3.2.4Non-metallic tanks
Nearby objects outside the tank may cause disturbing radar echoes. Wherever possible,
the transmitter should be positioned so that objects close to the tank are kept outside the
signal beam.
Related information
Product certifications
Reference Manual15
Page 16
D
W
Mechanical installationReference Manual
May 202200809-0200-4480
3.2.5Beam angle and beam width
The transmitter should be mounted with as few internal structures as possible within the
signal beam.
Figure 3-4: Beam Angle and Beam Width
Beam angle (α)
10° (8° with antenna extension)
Beam width
See Table 3-2 for beam width at different distances.
Table 3-2: Beam Width (W)
Distance (D)Beam angle (α)
8°10°
6.6 ft. (2 m)0.9 ft. (0.3 m)1.2 ft. (0.4 m)
13.1 ft. (4 m)1.8 ft. (0.6 m)2.3 ft. (0.7 m)
19.7 ft. (6 m)2.8 ft. (0.8 m)3.5 ft. (1.1 m)
26.2 ft. (8 m)3.7 ft. (1.1 m)4.6 ft. (1.4 m)
32.8 ft. (10 m)4.7 ft. (1.4 m)5.8 ft. (1.8 m)
16Rosemount 1408A Level and Flow Transmitter
Page 17
D
H
Reference ManualMechanical installation
00809-0200-4480May 2022
3.2.6Nozzle requirements
To allow the microwaves to propagate undisturbed, the nozzle dimensions should be kept
within the specified limits as given in Table 3-3. The inside of the nozzle must be smooth
(i.e. avoid bad welding, rust, or deposit).
Figure 3-5: Mounting in Nozzles
Table 3-3: Nozzle Requirements
Nozzle diameter (D)Maximum nozzle height (H)
1 in. (25 mm)3.9 in. (100 mm)
1.5 in. (40 mm)5.9 in. (150 mm)
2 in. (50 mm)7.9 in. (200 mm)
3 in. (80 mm)11.8 in. (300 mm)
4 in. (100 mm)15.8 in. (400 mm)
6 in. (150 mm)23.6 in. (600 mm)
3.2.7Open air installations
The antenna extension must be fitted to the transmitter to comply with open air
requirements. The antenna extension is included in the bracket mount option.
Figure 3-6: Antenna Extension
Related information
Product certifications
Reference Manual17
Page 18
AA
Mechanical installationReference Manual
May 202200809-0200-4480
3.2.8Thread engagement length
Refer to Figure 3-7 for the required thread engagement length at the customer G1 process
connection.
Figure 3-7: Thread Engagement Length
A. 0.35 to 0.63 in. (9 to 16 mm)
Related information
Dimensional drawings
3.3Mounting preparations
3.3.1Remove the protective cap
The protective cap protects the PTFE sealing from impacts during transport and storage.
Procedure
Before installing, carefully remove the protective cap.
Note
Be careful not to scratch or otherwise damage the PTFE sealing.
18Rosemount 1408A Level and Flow Transmitter
Page 19
T30
90°
T30
Reference ManualMechanical installation
00809-0200-4480May 2022
3.3.2Cleaning the transmitter
Procedure
If needed, clean the wetted parts of the transmitter.
Use a damp cloth and a mild cleaning agent suitable for the media and wetted parts of the
transmitter.
Note
Be careful not to scratch any of the surfaces.
3.4Mount the bracket
Procedure
1. Mount the bracket on the wall/ceiling or other flat surface.
2. Ensure the adjustable holder is directed toward the ground.
Reference Manual19
Page 20
AB
46 mm
36 mm
Mechanical installationReference Manual
May 202200809-0200-4480
3. Apply lubricating paste on the transmitter thread.
Note
The paste must be approved for the application and compatible with the
elastomers used.
4. Secure the transmitter to the bracket.
Mounting options:
• (A) Antenna extension for open air installations
• (B) Lock nut
3.5Installing on a tank
3.5.1Mount on a threaded flange connection
20Rosemount 1408A Level and Flow Transmitter
Related information
Bracket hole pattern
Procedure
1. Place a suitable soft gasket on the tank flange.
Page 21
0.75 in. (19 mm)
39 mm
Torque 310 in-lb (35 N-m)
Reference ManualMechanical installation
00809-0200-4480May 2022
2. Place the flange over the gasket.
3. Tighten the bolts and nuts with sufficient torque for the flange and gasket choice.
4. Apply lubricating paste on the transmitter thread.
Note
The paste must be approved for the application and compatible with the
elastomers used.
5. Mount the transmitter on the tank.
Note
Be careful not to scratch or otherwise damage the PTFE sealing.
Reference Manual21
Page 22
41 mm
39 mm
Torque 310 in-lb (35 N-m)
Mechanical installationReference Manual
May 202200809-0200-4480
3.5.2Mount the threaded adapter version
Procedure
1. Apply anti-seize paste or PTFE tape on outer threads according to your site
procedures.
2. Mount the threaded adapter on the tank.
3. Apply lubricating paste on the transmitter thread.
Note
The paste must be approved for the application and compatible with the
elastomers used.
4. Mount the transmitter on the tank.
Note
Be careful not to scratch or otherwise damage the PTFE sealing.
22Rosemount 1408A Level and Flow Transmitter
Page 23
39 mm
Torque 310 in-lb (35 N-m)
Reference ManualMechanical installation
00809-0200-4480May 2022
3.5.3Mount on a threaded connection
Procedure
1. Apply lubricating paste on the transmitter thread.
Note
The paste must be approved for the application and compatible with the
elastomers used.
2. Mount the transmitter on the tank.
Note
Be careful not to scratch or otherwise damage the PTFE sealing.
Reference Manual23
Page 24
Mechanical installationReference Manual
May 202200809-0200-4480
24Rosemount 1408A Level and Flow Transmitter
Page 25
Reference ManualElectrical installation
00809-0200-4480May 2022
4Electrical installation
4.1Safety messages
Instructions and procedures in this section may require special precautions to ensure the
safety of the personnel performing the operations. Information that potentially raises
safety issues is indicated by a warning symbol (). Refer to the following safety messages
before performing an operation preceded by this symbol.
WARNING
Failure to follow safe installation and servicing guidelines could result in death or
serious injury.
Ensure the transmitter is installed by qualified personnel and in accordance with applicable
code of practice.
Inspection and maintenance of this equipment shall be carried out by suitably trained
personnel, in accordance with the applicable standards and code of practice.
Use the equipment only as specified in this manual. Failure to do so may impair the
protection provided by the equipment.
Repair, e.g. substitution of components, etc. may jeopardize safety and is under no
circumstances allowed.
WARNING
Process leaks could result in death or serious injury.
Handle the transmitter carefully.
Install and tighten process connectors before applying pressure.
Do not attempt to loosen or remove process connectors while the transmitter is in service.
4.2Prepare the electrical connections
4.2.1Connector type
M12 (A-coded)
4.2.2Power supply
The transmitter operates on 18-30 Vdc at the transmitter terminals.
Related information
Load limitations
Reference Manual25
Page 26
4
1
3
2BNW
H
BK
BU
1
4
2
3
OUT2
L+
L
OUT1/IO-Link
Electrical installationReference Manual
May 202200809-0200-4480
4.2.3Outputs
The transmitter provides two configurable outputs:
Output 1
Output 2
Digital output / IO-Link mode
Digital output or active 4-20 mA analog output
4.2.4Internal power consumption
< 2 W (normal operation at 24 Vdc, no outputs)
< 3.6 W (normal operation at 24 Vdc, digital and analog outputs active)
4.2.5Wiring diagram
Figure 4-1: Connection
Table 4-1: Pin Assignment
PinWire color
1BNBrownL+24 V
(1)
Signal
2WHWhiteOUT2Digital output or active 4-20 mA analog
output
3BUBlueL-0 V
4BKBlackOUT1/IO-LinkDigital output or IO-Link mode
(1) According to IEC 60947-5-2.
26Rosemount 1408A Level and Flow Transmitter
Page 27
B
4
1
3
2
2: OUT2
4: OUT1
BN
W
H
BK
BU
L+
L
A
2: OUT2
4: OUT1
2: OUT2
4: OUT1
2: OUT2
4: OUT1
4
1
3
2BNWH
BK
BU
L+
L
C
4
1
3
2BNWH
BK
BU
L+
L
D
4
1
3
2BNWH
BK
BU
L+
L
Reference ManualElectrical installation
00809-0200-4480May 2022
Figure 4-2: Example Circuits
A. 2 x Digital output PnP
B. 2 x Digital output NpN
1 x Digital output PnP / 1 x Analog output
C.
D. 1 x Digital output NpN / 1 x Analog output
Related information
Outputs
Reference Manual27
Page 28
Electrical installationReference Manual
May 202200809-0200-4480
4.3Power up transmitter
Procedure
1. Verify the power supply is disconnected.
2. Insert the M12 connector and screw tight.
See the manufacturer’s instruction manual for recommended torque.
3. Connect the power supply.
Related information
Ingress protection
28Rosemount 1408A Level and Flow Transmitter
Page 29
Reference ManualConfiguration
00809-0200-4480May 2022
5Configuration
5.1Safety messages
Instructions and procedures in this section may require special precautions to ensure the
safety of the personnel performing the operations. Information that potentially raises
safety issues is indicated by a warning symbol (). Refer to the following safety messages
before performing an operation preceded by this symbol.
WARNING
Failure to follow safe installation and servicing guidelines could result in death or
serious injury.
Ensure the transmitter is installed by qualified personnel and in accordance with applicable
code of practice.
Inspection and maintenance of this equipment shall be carried out by suitably trained
personnel, in accordance with the applicable standards and code of practice.
Use the equipment only as specified in this manual. Failure to do so may impair the
protection provided by the equipment.
Repair, e.g. substitution of components, etc. may jeopardize safety and is under no
circumstances allowed.
WARNING
Process leaks could result in death or serious injury.
Handle the transmitter carefully.
Install and tighten process connectors before applying pressure.
Do not attempt to loosen or remove process connectors while the transmitter is in service.
5.2Overview
This chapter provides information about configuration and configuration tools. Appendix
Configuration parameters provides extended information about the configuration
parameters.
Reference Manual29
Page 30
ConfigurationReference Manual
May 202200809-0200-4480
5.3Connect the transmitter to the IO-Link
IO-Link devices can be set using an IO-Link USB Communicator, through the IO-Link
master, or via the PLC.
Procedure
Start the configuration software and connect the transmitter.
Figure 5-1: Connection via the IO-Link USB Communicator
Figure 5-2: Connection via the IO-Link Master
Figure 5-3: Connection via the PLC
5.4Get started with your preferred configuration
tool
5.4.1IO-Link configuration tools
Examples:
• Rosemount IO-Link Assistant (available as accessory)
• FDT® frame applications, e.g. PACTware
5.4.2Rosemount IO-Link Assistant
Get the latest IODD files
The Rosemount IO-Link Assistant software checks and lets you download the latest IODDs
for your device catalog.
Prerequisites
For an online update, an internet connection is required.
30Rosemount 1408A Level and Flow Transmitter
Page 31
Reference ManualConfiguration
00809-0200-4480May 2022
Procedure
1. Click the icon.
The Device description files (IODD): download and install window opens.
2. In the
Vendor list, select Rosemount Inc., and then select the check box for the
devices to be installed/updated.
Alternatively, browse to an already downloaded IODD zip file, and select Open.
3. Select OK.
5.4.3FDT®/DTM framework
Download the IODD file
Procedure
1. Download the IODD from the IODDFinder portal at
2. Unzip the IODD package.
Integrate IODDs into an FDT®/DTM framework
An IODD DTM Interpreter is required to integrate IODDs into an FDT/DTM environment
(e.g PACTware).
Prerequisites
The IODD DTM Interpreter is usually included in the FDT/DTM software installation
package. It can also be downloaded from Emerson.com/Rosemount1408A.
Procedure
1. Start the IODD DTM Interpreter software.
Ioddfinder.io-link.com.
Reference Manual31
Page 32
ConfigurationReference Manual
May 202200809-0200-4480
2. Select Add IODD.
3. Browse to the IODD file (.xml) and select Open.
4. Start the configuration tool and update the device catalog.
Need help?
If the new DTM is not added automatically at start-up, then select
Catalog → Update Device Catalog.
View → Device
32Rosemount 1408A Level and Flow Transmitter
Page 33
Reference ManualConfiguration
00809-0200-4480May 2022
5.5Perform the basic setup
5.5.1Set the engineering units
Procedure
1. Under
2. In the Engineering Units list, select Metric or Imperial.
3. Select Write to device.
Related information
Engineering units
Menu, select Parameter→Basic Setup.
5.5.2Enter the reference height
Procedure
Under
1.
2. Enter the Reference Height.
3. Select Write to device.
Related information
Reference height
Menu, select Parameter→Basic Setup.
5.5.3Configure the analog output
The transmitter can be set to output the level or volume flow as a 4-20 mA signal.
Procedure
Under
1.
2. In the OUT2 Configuration list, select Analog Output 4-20 mA.
3. In the Analog Control Variable list, select Level or Volume Flow.
4. In the Alarm Mode list, select Low Alarm or High Alarm.
5. Select Analog Range Values, and then enter the desired Upper Range Value (20
6. Select Write to device.
Related information
Analog output
Reference Manual33
Menu, select Parameter→OUT2 Analog Output.
mA) and Lower Range Value (4 mA).
Page 34
ConfigurationReference Manual
May 202200809-0200-4480
5.5.4Configure the digital output
The transmitter can be set to output a switching signal for high and low limits (using the
same pin).
Procedure
1. Under
2. In the Digital Outputs P-n list, select PnP or nPn.
3. Select OUT1 Digital Output or OUT2 Digital Output.
4. In the OUT1 Configuration or OUT2 Configuration list, select Digital Output Normally
5. In the DO Control Variable list, select Level or Volume Flow.
6. Select Set Point Configuration, and then set the alarm parameters as desired.
7. Select Write to device.
Related information
Digital output
Menu, select Parameter → Basic Setup.
Open.
5.5.5Set up the volume flow measurement
Procedure
Under Menu, select Volume Flow.
1.
2. In the Volume Flow Calculation Method list, select the preferred method. Choose
from:
• Linearization table
• Parshall flume
• Khafagi-Venturi flume
3. Select Volume Flow Table/Formula, and then set the parameters as desired.
4. Select Write to device.
Related information
Volume flow
34Rosemount 1408A Level and Flow Transmitter
Page 35
Reference ManualOperation and maintenance
00809-0200-4480May 2022
6Operation and maintenance
6.1Safety messages
Instructions and procedures in this section may require special precautions to ensure the
safety of the personnel performing the operations. Information that potentially raises
safety issues is indicated by a warning symbol (). Refer to the following safety messages
before performing an operation preceded by this symbol.
WARNING
Failure to follow safe installation and servicing guidelines could result in death or
serious injury.
Ensure the transmitter is installed by qualified personnel and in accordance with applicable
code of practice.
Inspection and maintenance of this equipment shall be carried out by suitably trained
personnel, in accordance with the applicable standards and code of practice.
Use the equipment only as specified in this manual. Failure to do so may impair the
protection provided by the equipment.
Repair, e.g. substitution of components, etc. may jeopardize safety and is under no
circumstances allowed.
WARNING
Process leaks could result in death or serious injury.
Handle the transmitter carefully.
Install and tighten process connectors before applying pressure.
Do not attempt to loosen or remove process connectors while the transmitter is in service.
6.2View measurement data and events
The dashboard in Rosemount IO-Link Assistant displays the measured values, device
status, switching status for digital output (on/off), and events. The measured values and
switching states are visualized in a graph over a defined period of time.
Procedure
From the Overview screen, select Dashboard.
Reference Manual35
Page 36
Operation and maintenanceReference Manual
May 202200809-0200-4480
Figure 6-1: Dashboard
Need help?
Select the Help button for more information on the features and capabilities.
6.2.1Measurement variables
VariableDescription
LevelThe current level measurement value (from the Zero Level to the product
surface).
DistanceThe distance from the Device Reference Point to the surface.
Signal strengthThe reflected signal strength from the surface.
Electronics
temperature
Min electronics
temperature
Max electronics
temperature
Volume FlowThe calculated volume flow value.
The current temperature at the electronics.
The measured minimum electronics temperature.
The measured maximum electronics temperature.
6.2.2Interpret measurement status
A “Good” or “Bad” status next to a value is an indication of the reliability or integrity of the
data being received, not an indication of whether or not the value is within the configured
upper or lower ranges. A value that triggers an alert, such as a high or low temperature
indication, will change the overall status of the device, but the measurement might still be
indicated as “Good” if the reliability of the data is good.
36Rosemount 1408A Level and Flow Transmitter
Page 37
Reference ManualOperation and maintenance
00809-0200-4480May 2022
6.3Enter the demonstration mode
In this mode, the signal processing method is optimized for demo situations when
simulating a product surface with, for example, a measurement target plate.
Note
This mode is intended for demonstration purposes only, and should not be used for
normal operations.
Prerequisites
The demonstration mode will reset the following parameters to factory settings:
• Measurement recovery time
• Damping value
When returning to Default Mode, you will therefore need to reconfigure these parameters
(if desired).
Procedure
1. Under
2. Select Enter Demonstration Mode.
Postrequisites
1. Select Exit Demonstration Mode to return to normal operation (Default Mode).
2. Verify that the Application Mode is set to Default Mode.
Instructions and procedures in this section may require special precautions to ensure the
safety of the personnel performing the operations. Information that potentially raises
safety issues is indicated by a warning symbol (). Refer to the following safety messages
before performing an operation preceded by this symbol.
WARNING
Failure to follow safe installation and servicing guidelines could result in death or
serious injury.
Ensure the transmitter is installed by qualified personnel and in accordance with applicable
code of practice.
Inspection and maintenance of this equipment shall be carried out by suitably trained
personnel, in accordance with the applicable standards and code of practice.
Use the equipment only as specified in this manual. Failure to do so may impair the
protection provided by the equipment.
Repair, e.g. substitution of components, etc. may jeopardize safety and is under no
circumstances allowed.
WARNING
Process leaks could result in death or serious injury.
Handle the transmitter carefully.
Install and tighten process connectors before applying pressure.
Do not attempt to loosen or remove process connectors while the transmitter is in service.
Reference Manual39
Page 40
Service and troubleshootingReference Manual
May 202200809-0200-4480
7.2Diagnostic messages
7.2.1Device hardware fault
Alarm classification
Event
Device status
Class
Possible cause
An electronics error has occurred.
Recommended actions
1. Restart the device.
2.
If the condition persists, replace the device.
Related information
Perform a device reset
Device hardware fault – Device exchange
Failure
Error
7.2.2Device software fault
Alarm classification
Event
Device status
Class
Device software fault – Check firmware revision
Failure
Error
Possible cause
The software has detected an internal error.
Recommended actions
1. Restart the device.
2. Restore default settings and reconfigure the device.
3. If the condition persists, replace the device.
Related information
Perform a device reset
Restore to factory settings
40Rosemount 1408A Level and Flow Transmitter
Page 41
Reference ManualService and troubleshooting
00809-0200-4480May 2022
7.2.3General power supply fault
Alarm classification
Event
Device status
Class
Possible cause
Power supply drops below 18 Vdc during transmitter start-up.
Recommended actions
Verify voltage is 18-30 Vdc at the transmitter terminal.
General power supply fault – Check availability
Failure
Error
7.2.4Parameter error
Alarm classification
Event
Device status
Class
Possible cause
The device has detected a configuration error.
Parameter error – Check data sheet and values
Failure
Error
Recommended actions
1. If analog output is used, check Upper and Lower Range Values.
2.
If digital output is used, check High and Low Alarm Set Points.
3. If volume flow table is used, check that the Level points are entered in
increasing order.
4. If condition persists, restore default settings and reconfigure the device.
Related information
Upper/lower range value
Alarm set points
Volume flow table
Restore to factory settings
Reference Manual41
Page 42
Service and troubleshootingReference Manual
May 202200809-0200-4480
7.2.5Device memory failure
Alarm classification
Event
Device status
Class
Possible cause
Configuration data has been corrupted, for example, due to a power loss during writing.
Recommended actions
1. Restore default settings, restart device, and reconfigure the device.
2.
If the condition persists, replace the device.
Related information
Restore to factory settings
Perform a device reset
Device memory failure – Restore default settings
Failure
Error
7.2.6Simulation active
Alarm classification
Event
Device status
Simulation active – Check operational mode
Functional check
Class
Possible cause
The device is in simulation mode and is not reporting actual information.
Recommended actions
1. If this behavior is not desired, stop simulation mode.
2. If the condition persists, restart the device.
Related information
Use the simulation mode
Perform a device reset
Warning
42Rosemount 1408A Level and Flow Transmitter
Page 43
Reference ManualService and troubleshooting
00809-0200-4480May 2022
7.2.7Level measurement lost
Alarm classification
Event
Device status
Class
Possible cause
No valid level reading. Reasons may be multiple:
• No valid surface echo peak in the measuring range
• Incorrect device configuration
Recommended actions
1. Analyze the Echo Peaks and check device configuration, especially General
Threshold.
3. Consider increasing Measurement Recovery Time parameter for intermittent
conditions.
4. Restore default settings, restart device, and reconfigure the device.
5. If the condition persists, replace the device.
Related information
Analyze the echo peaks
Adjust the general threshold
Measurement recovery time
Restore to factory settings
Perform a device reset
Level measurement lost – Check application
Failure
Error
Reference Manual43
Page 44
Service and troubleshootingReference Manual
May 202200809-0200-4480
7.2.8Device temperature over-run
Alarm classification
Event
Device status
Class
Possible cause
The electronics temperature is outside the operating range.
Recommended actions
1. Verify ambient temperature is within the operating range.
2.
Clear source of heat.
Related information
Ambient temperature
Device temperature over-run – Clear source of heat
Out of specification
Warning
7.2.9Device temperature under-run
Alarm classification
Event
Device status
Class
Device temperature under-run – Insulate device
Out of specification
Warning
Possible cause
The electronics temperature is outside the operating range.
Recommended actions
1. Verify ambient temperature is within the operating range.
2. Insulate device.
Related information
Ambient temperature
44Rosemount 1408A Level and Flow Transmitter
Page 45
Reference ManualService and troubleshooting
00809-0200-4480May 2022
7.2.10Short circuit
Alarm classification
Event
Device status
Class
Possible cause
Short circuit on the digital output.
Recommended actions
Check cable and connections.
Short circuit – Check installation
Out of Specification
Error
7.2.11Primary supply voltage over-run
Alarm classification
Event
Device status
Class
Possible cause
Supply voltage is too high.
Primary supply voltage over-run – Check tolerance
Out of specification
Warning
Recommended actions
Verify voltage is 18-30 Vdc at the transmitter terminal.
7.2.12Primary supply voltage under-run
Alarm classification
Event
Device status
Class
Possible cause
Supply voltage is too low.
Recommended actions
Verify voltage is 18-30 Vdc at the transmitter terminal.
Primary supply voltage under-run – Check tolerance
Out of specification
Warning
Reference Manual45
Page 46
Service and troubleshootingReference Manual
May 202200809-0200-4480
7.2.13Maintenance required
Alarm classification
Event
Device status
Class
Possible cause
Product build-up on the antenna.
Recommended actions
Clean the antenna.
Use a damp cloth and a mild cleaning agent suitable for the media and wetted parts of
the transmitter.
Note
Take care not to scratch the PTFE sealing surfaces.
Related information
Material exposed to tank atmosphere
Components of the transmitter
Maintenance required - Cleaning
Maintenance required
Notification
7.2.14Max EEPROM write cycles expired
Alarm classification
Event
Device status
Class
Possible cause
Frequent writing of parameters from master to device.
Recommended actions
1. Check the master configuration.
2.
Restart the device.
3. If error persists, contact your local Emerson representative.
Related information
Perform a device reset
46Rosemount 1408A Level and Flow Transmitter
Max EEPROM write cycles expired – Check master and restart the
device
Maintenance required
Warning
Page 47
Reference ManualService and troubleshooting
00809-0200-4480May 2022
7.2.15Measurement range over-run
Alarm classification
Event
Device status
Class
Possible cause
The level measurement is outside the configured range for the volume flow.
Recommended actions
Ensure that level values within operating range are included in the volume flow table.
Measurement range over-run – Check application
Out of Specification
Error
Reference Manual47
Page 48
A
B
C
D
Service and troubleshootingReference Manual
May 202200809-0200-4480
7.3Troubleshooting incorrect level readings
7.3.1Reported level is too high or low
Figure 7-1: Symptom
A. Level
B. Time
C.
Actual level
D. Reported level
Possible cause
Incorrect tank geometry configuration.
Recommended actions
• Verify the tank geometry parameters are configured correctly (especially the
Reference Height).
• Analyze the Echo Peaks and check General Threshold.
• Restore default settings and reconfigure the device.
Related information
Reference height
Analyze the echo peaks
Adjust the general threshold
Restore to factory settings
48Rosemount 1408A Level and Flow Transmitter
Page 49
A
B
C
D
Reference ManualService and troubleshooting
00809-0200-4480May 2022
7.3.2Level is stuck in measuring range
Figure 7-2: Symptom
A. Level
B. Time
C.
Actual level
D. Reported level
Possible cause
Disturbing object in the tank.
Recommended actions
• Analyze the Echo Peaks and check General Threshold.
• Remove the disturbing object.
• Put an inclined metal plate on top of the disturbing object.
• Move the transmitter to another position.
Related information
Analyze the echo peaks
Adjust the general threshold
Mounting position
Reference Manual49
Page 50
A
B
C
D
Service and troubleshootingReference Manual
May 202200809-0200-4480
7.3.3Level is stuck in full tank
Figure 7-3: Symptom
A. Level
B. Time
C.
Actual level
D. Reported level
Possible cause
Disturbing object near the antenna.
Recommended actions
• Analyze the Echo Peaks and check General Threshold.
• Increase the Upper Null Zone.
• Remove the disturbing object.
• Move the transmitter to another position.
Possible cause
Product build-up on the antenna.
Recommended actions
• Clean the antenna.
Related information
Analyze the echo peaks
Adjust the general threshold
Change the upper null zone
Mounting position
50Rosemount 1408A Level and Flow Transmitter
Page 51
A
B
C
D
Reference ManualService and troubleshooting
00809-0200-4480May 2022
7.3.4Level value drops when close to antenna
Symptom
Level value drops to a lower value when product surface is close to antenna.
Figure 7-4: Symptom
A. Level
B. Time
C.
Actual level
D. Reported level
Possible cause
Product surface is within the Upper Null Zone and a disturbance echo is interpreted as the
product surface.
Recommended actions
• Check the setting of the Upper Null Zone.
Related information
Change the upper null zone
Reference Manual51
Page 52
A
B
C
Service and troubleshootingReference Manual
May 202200809-0200-4480
7.3.5Measured level fluctuates
Figure 7-5: Symptom
A. Level
Time
B.
C.
Reported level
Possible cause
Excessive foaming or turbulence.
Recommended actions
• Under turbulent conditions with low level rates, consider increasing the Damping
value.
Related information
Damping value
52Rosemount 1408A Level and Flow Transmitter
Page 53
A
B
C
D
Reference ManualService and troubleshooting
00809-0200-4480May 2022
7.3.6Measured level is occasionally unstable
Figure 7-6: Symptom
A. Level
B. Time
Actual level
C.
D. Reported level
Possible cause
The product surface is close to a suppressed false echo.
Recommended actions
• If possible, remove the disturbing object.
Related information
Analyze the echo peaks
Reference Manual53
Page 54
A
B
C
D
Service and troubleshootingReference Manual
May 202200809-0200-4480
7.3.7Lagging of measured level
Symptom
Measured level lags during rapid level changes.
Figure 7-7: Symptom
A. Level
B. Time
C.
Actual level
D. Reported level
Possible cause
Damping value is set too high.
Recommended actions
• If there is a problem with lag during rapid level changes, consider decreasing the
Damping value.
Related information
Damping value
54Rosemount 1408A Level and Flow Transmitter
Page 55
A
B
C
D
Reference ManualService and troubleshooting
00809-0200-4480May 2022
7.3.8Incorrect level at 100% (20 mA)
Symptom
Measured level is correct at 0% (4 mA) but incorrect at 100% (20 mA).
Figure 7-8: Symptom
A. Level
B. Time
C.
Actual level
D. Reported level
Possible cause
Upper Range Value is not set correctly.
Recommended actions
• Check that the Upper Range Value matches the 100% (20 mA) level in the tank.
Related information
Upper/lower range value
Reference Manual55
Page 56
A
B
C
D
Service and troubleshootingReference Manual
May 202200809-0200-4480
7.3.9Incorrect level when product surface is above 50%
Symptom
The reported level is incorrect when the product surface is above the 50% level.
Figure 7-9: Symptom
A. Level
B. Time
C.
Actual level
D. Reported level
Possible cause
A strong double bounce echo is interpreted as the product surface.
Recommended actions
• Move the transmitter to another position.
Related information
Mounting position
56Rosemount 1408A Level and Flow Transmitter
Page 57
A
B
C
D
Reference ManualService and troubleshooting
00809-0200-4480May 2022
7.3.10Dropping of level close to tank bottom
Symptom
Measured value drops to zero level in the tank bottom region.
Figure 7-10: Symptom
A. Level
B. Time
C.
Actual level
D. Reported level
Possible cause
Transmitter has locked on a strong tank bottom echo.
Recommended actions
• Verify the Reference Height is configured correctly.
Related information
Reference height
Reference Manual57
Page 58
A
B
C
D
Service and troubleshootingReference Manual
May 202200809-0200-4480
7.3.11Level measurement lost in a manway cover installation
Symptom
The transmitter reports "Level measurement lost" when opening/closing the manway
cover.
Figure 7-11: Symptom
A. Level
B. Time
Actual level
C.
D. Level measurement lost
Possible cause
If mounted on a manway cover, the transmitter may lock on a disturbance echo and report
this as surface level when the cover is opened. After closing the cover, the echo is lost and
the transmitter reports "Level measurement lost".
Recommended actions
• Before opening the manway cover, disconnect power to the transmitter.
• After closing, restart the device.
• Move the transmitter to another position.
Related information
Mounting position
Perform a device reset
58Rosemount 1408A Level and Flow Transmitter
Page 59
A
B
F
C
D
E
Reference ManualService and troubleshooting
00809-0200-4480May 2022
7.3.12Level measurement is lost in an empty tank
Symptom
The transmitter reports "Level measurement lost" in an empty tank after closing the side
manway door.
Figure 7-12: Symptom
A. Level
B. Time
Actual level
C.
D. Reported level
E. Level measurement lost
F. Manway door open
Possible cause
When the manway door is opened inward, it generates a disturbance echo which is
interpreted as the product surface echo. After closing the door, the echo is lost and the
transmitter reports "Level measurement lost". The message is cleared when start filling the
tank.
Recommended actions
• Before opening the manway door, disconnect power to the transmitter.
• After closing, restart the device.
• Move the transmitter to another position.
Related information
Mounting position
Perform a device reset
Reference Manual59
Page 60
A
B
C
D
Service and troubleshootingReference Manual
May 202200809-0200-4480
7.3.13Alarm mode close to tank bottom
Symptom
When the product surface is near the sloped tank bottom, the transmitter enters alarm
mode.
Figure 7-13: Symptom
A. Level
B. Time
Actual level
C.
D. Reported level
Possible cause
Reduction of projected surface area close to sloping tank bottom.
Recommended actions
• Verify the tank geometry parameters are configured correctly (especially the
Reference Height and Bottom Offset).
Related information
Reference height
Bottom offset
7.4Managing disturbance echoes
There are two general methods for managing disturbance echoes:
• Set general threshold to filter out weak disturbance echoes and noise.
• Increase the Upper Null Zone to block out disturbance echoes at the top of the tank.
60Rosemount 1408A Level and Flow Transmitter
Page 61
Reference ManualService and troubleshooting
00809-0200-4480May 2022
7.4.1Adjust the general threshold
If necessary, the general threshold value can be increased if a disturbance echo is
interpreted as the product surface. Alternatively, a lower threshold may be required to
handle weak surface echoes (e.g. due to excessive foaming or turbulence).
Prerequisites
The general threshold is set at factory for optimum performance and should not normally
need an adjustment.
Before changing the factory default value, study the position and amplitude of the
different echo peaks.
Procedure
1. Under
2. In the General Threshold box, enter the desired value.
3. Select Write to device.
Related information
Analyze the echo peaks
General threshold
Menu, select Parameter→Advanced Setup.
7.4.2Change the upper null zone
The Upper Null Zone defines a zone close to the transmitter where echoes are ignored.
This zone can be extended to block out disturbing echoes at the top of the tank.
Prerequisites
Note
Make sure the Upper Range Value (100%/20 mA) value is below the Upper Null Zone.
Measurements are not performed within the Upper Null Zone.
Procedure
1. Identify desired Upper Null Zone by analyzing the echo peaks.
Under Menu, select Diagnosis→Echo Peaks.
a)
b) View the echo peaks to find out if there are disturbing echoes close to tank
top.
2. Set the desired Upper Null Zone value.
a) Under Menu, select Parameter→Geometry→Advanced.
b) Enter the desired Upper Null Zone value.
c) Select Write to device.
Reference Manual61
Page 62
A
C
E
m
0
mV
0.5
1.0
1.5
2.0
2.5
3.0
0
150
300
450
600
750 900
D
B
Service and troubleshootingReference Manual
May 202200809-0200-4480
Figure 7-14: Upper Null Zone
A. Upper Null Zone
B. Disturbance echo
100% (20 mA)
C.
D. General threshold
E. Product surface echo
Related information
Upper null zone
7.5Service and troubleshooting tools
7.5.1Analyze the echo peaks
Measurement problems can be understood by studying the position and amplitude of the
different peaks.
Procedure
Under Menu, select Diagnosis→Echo Peaks.
62Rosemount 1408A Level and Flow Transmitter
Page 63
Reference ManualService and troubleshooting
00809-0200-4480May 2022
Echo peaks
See Table 7-1 for a list of possible echo peaks.
Table 7-1: Echo Peak Types
TypeDescription
SurfaceEcho tracked as the current surface echo
UnknownEcho identified as unknown (can be a surface candidate)
SuppressedEchoes that are identified but suppressed by the device
Tank bottom echoEcho considered as an echo from the tank bottom
7.5.2Perform a device reset
The function is used to reset/restart the electronics without re-cycling the power.
Procedure
1. Under
2. Select Device Reset.
Menu, select Parameter→Service Tools→Maintenance.
7.5.3Restore to factory settings
This function restores the transmitter to factory settings (user configuration is
overwritten).
Procedure
Under
1.
2. Select Restore Factory Settings.
Menu, select Parameter→Service Tools→Maintenance.
7.5.4Use the simulation mode
It is possible to set the level to a simulated value for testing purposes. The simulated value
affects both digital and analog output.
Procedure
Under
1.
2. In the Simulated Level box, enter the desired value.
Menu, select Parameter→Service Tools→Simulation.
This value will also be used for the volume flow calculation.
3. Select Write to device.
4. Select Start simulation (60 min).
Reference Manual63
Page 64
Service and troubleshootingReference Manual
May 202200809-0200-4480
7.5.5Calibrate analog out
Use this function to calibrate the analog output by comparing the actual output current
with the nominal 4 mA and 20 mA currents. Calibration is done at factory and the analog
output does not normally need to be recalibrated.
Prerequisites
Connect a calibrated ampere meter to the analog output loop.
Procedure
1. Under
2. Perform the calibration of 4 mA.
3. Perform the calibration of 20 mA.
Menu, select Parameter→Service Tools→Analog Out Calibration.
a) Select Enter 4 mA Fixed Current Mode to set the analog out to 4 mA.
b) Measure the analog output with the ampere meter.
c) In the 4 mA Measured Current box, enter the measured current.
d) Select Write to device.
e) Select Calibrate 4 mA.
f) Measure the analog output with the ampere meter and verify it is within
4±0.01 mA.
a) Select Enter 20 mA Fixed Current Mode to set the analog out to 20 mA.
b) Measure the analog output with the ampere meter.
c) In the 20 mA Measured Current box, enter the measured current.
d) Select Write to device.
e) Select Calibrate 20 mA.
f) Measure the analog output with the ampere meter and verify it is within
20±0.01 mA.
4. Select Exit Fixed Current Mode.
7.6Service support
To expedite the return process, contact the nearest Emerson representative.
CAUTION
Individuals who handle products exposed to a hazardous substance can avoid injury if they
are informed of and understand the hazard. Returned products must include a copy of the
required Safety Data Sheet (SDS) for each substance.
Emerson representatives will explain the additional information and procedures necessary
to return goods exposed to hazardous substances.
64Rosemount 1408A Level and Flow Transmitter
Page 65
Reference ManualSpecifications and reference data
00809-0200-4480May 2022
ASpecifications and reference data
A.1Performance specifications
A.1.1General
Reference conditions
• Measurement target: Stationary metal plate, no disturbing objects
• Temperature: 59 to 77 °F (15 to 25 °C)
• Ambient pressure: 14 to 15 psi (960 to1060 mbar)
• Relative humidity: 25-75%
• Damping: Default value, 2 s
Instrument accuracy (under reference conditions)
±0.08 in. (±2 mm)
(1)
Repeatability
±0.04 in. (±1 mm)
Ambient temperature effect
±0.04 in. (±1 mm)/10 K
Sensor update rate
Minimum 1 update per second (typically 5 updates per second)
Maximum level rate
200 mm/s
A.1.2Measuring range
Maximum measuring range
33 ft. (10 m)
(2)
(1) Refers to inaccuracy according to IEC 60770-1 when excluding installation dependent offset. See the IEC 60770-1 standard
for a definition of radar specific performance parameters and if applicable corresponding test procedures.
(2) Measurement is possible up to 49 ft. (15 m) if there is good reflection of the product surface (dielectric constant >10, i.e.
water based media). Note though that a combination of adverse process conditions, such as heavy turbulence, foam, and
condensation, together with products with poor reflection may affect the measuring range.
Reference Manual65
Page 66
B
±0.08
(±2)
±0.4
(±10)
5.9 (150)
C
A
B
±0.08
(±2)
±0.4
(±10)
0.8 (20)
5.9 (150)
C
A
Specifications and reference dataReference Manual
May 202200809-0200-4480
Accuracy over measuring range
Figure A-1 illustrates the accuracy over measuring range at reference conditions.
Figure A-1: Accuracy Over Measuring Range
A. Device Reference Point
B. Accuracy in inches (millimeters)
Distance in inches (millimeters)
C.
A.1.3Environment
Vibration resistance
2 g at 10-1000 Hz according to IEC 61298-3, level “field with general application”
Electromagnetic compatibility (EMC)
• EMC Directive (2014/30/EU): EN 61326-1
• NAMUR recommendations NE21 (only 4-20 mA output)
Pressure Equipment Directive (PED)
Complies with 2014/68/EU article 4.3
66Rosemount 1408A Level and Flow Transmitter
Page 67
Reference ManualSpecifications and reference data
00809-0200-4480May 2022
Radio approvals
• Radio Equipment Directive (2014/53/EU) and Radio Equipment Regulations (S.I.
2017/1206):
— ETSI EN 302 372 (without antenna extension)
— ETSI EN 302 729 (with antenna extension)
— EN 62311
• Part 15 of the FCC Rules
• Industry Canada RSS 211
Related information
Product certifications
A.2Functional specifications
A.2.1General
Field of application
Continuous measurement of level and open channel flow.
Minimum dielectric constant
2
Measurement principle
Frequency Modulated Continuous Wave (FMCW)
Frequency range
77 to 81 GHz
Maximum output power
3 dBm (2 mW)
Internal power consumption
< 2 W (normal operation at 24 Vdc, no outputs)
< 3.6 W (normal operation at 24 Vdc, digital and analog outputs active)
Humidity
0 - 100% relative humidity, non-condensing
Turn-on time
(3)
< 15 s
Reference Manual67
Page 68
Specifications and reference dataReference Manual
May 202200809-0200-4480
A.2.2Outputs
The transmitter provides two configurable outputs:
Output 1
Output 2
Digital output / IO-Link mode
Digital output or active 4-20 mA analog output
A.2.3Digital output
Switching signal for high and low limits (using the same pin)
Output type
PNP/NPN configurable
Switching function
Normally open
Permanent current rating
< 50 mA
Maximum voltage drop
2.5 V
A.2.44-20 mA analog output
Load limitations
Maximum loop resistance is determined by the voltage level of the external power supply:
Maximum Loop Resistance = 43.5 × (External Power Supply Voltage - 18) + 600 Ω
(3) Time from when power is applied to the transmitter until performance is within specifications.
68Rosemount 1408A Level and Flow Transmitter
Page 69
18
19 20 21 22 2325 26 27 28 29
700
600
1100
1000
900
800
1200
3024
B
A
860
1
121
Reference ManualSpecifications and reference data
00809-0200-4480May 2022
Figure A-2: Load Limits
A. Loop Resistance (Ω)
External Power Supply Voltage (Vdc)
B.
Analog signal on alarm
The transmitter automatically and continuously performs self-diagnostic routines. If a
failure or a measurement error is detected, the analog signal will be driven offscale to alert
the user. High or low failure mode is user-configurable.
Table A-1: Signal on Alarm
LevelCustom levelsNAMUR NE43 (default)
Low3.5 to 4.0 mA3.5 mA (NAMUR ≤ 3.6 mA)
High20.0 to 22.5 mA21.5 mA (NAMUR ≥ 21.0 mA)
Analog saturation levels
The transmitter will continue to set a current that corresponds to the measurement until
reaching the associated saturation limit (and then freeze).
Table A-2: Saturation Levels
LevelCustom levelsNAMUR NE43 (default)
Low3.5 to 4.0 mA3.8 mA
High20.0 to 22.5 mA20.5 mA
A.2.5IO-Link specifications
IO-Link revision
1.1
Transfer type
COM2 (38.4 kBaud)
Reference Manual69
Page 70
Specifications and reference dataReference Manual
May 202200809-0200-4480
SIO mode
Yes
IO-Link master port
Class A
Minimum cycle time
6 ms
A.2.6Configuration
IO-Link configuration tools
Examples:
• Rosemount IO-Link Assistant (available as accessory)
• FDT® frame applications, e.g. PACTware
Damping
User selectable (default is 2 s, minimum is 0 s)
Output units
• Level: in., m
• Temperature: °F, °C
• Volume flow: US gal/h, m3/h
• Signal strength: mV
Output variables
Variable4-20 mADO1 and DO2Digital, service
tools using
IODD
Level✓✓✓✓
Distance (ullage)N/AN/A✓N/A
Volume flow✓✓✓✓
Electronics temperature N/AN/A✓N/A
Signal strengthN/AN/A✓N/A
IO-Link PDIn
(to the PLC)
70Rosemount 1408A Level and Flow Transmitter
Page 71
A
B
104
(40)
176 (80)
302
(150)
176
(80)
-40
(-40)
-40 (-40)
Reference ManualSpecifications and reference data
00809-0200-4480May 2022
Volume flow calculations
• Linearization table
• Parshall flume
• Khafagi-Venturi flume
A.2.7Process pressure
-15 to 116 psig (-1 to 8 bar)
Atmospheric pressure at temperatures below -4 °F (-20 °C)
Note
The flanges must be used only in non-pressurized applications.
A.2.8Temperature limits
Process temperature
-40 to 302 °F (-40 to 150 °C)
Ambient temperature
-40 to 176 °F (-40 to 80 °C)
The ambient temperature limits may be further restricted by the process temperature as
described by Figure A-3.
Figure A-3: Ambient Temperature vs. Process Temperature
A. Ambient temperature °F (°C)
B. Process temperature °F (°C)
Storage temperature
-40 °F to 194 °F (-40 °C to 90 °C)
Reference Manual71
Page 72
Specifications and reference dataReference Manual
May 202200809-0200-4480
A.3Physical specifications
A.3.1Material selection
Emerson provides a variety of Rosemount products with various product options and
configurations, including materials of construction that can be expected to perform well in
a wide range of applications. The Rosemount product information presented is intended
as a guide for the purchaser to make an appropriate selection for the application. It is the
purchaser’s sole responsibility to make a careful analysis of all process parameters (such as
all chemical components, temperature, pressure, flow rate, abrasives, contaminants,
etc.), when specifying product, materials, options, and components for the particular
application. Emerson is not in a position to evaluate or guarantee the compatibility of the
process fluid or other process parameters with the product, options, configuration, or
materials of construction selected.
A.3.2Housing and enclosure
Process connection
ISO 228/1-G1 thread with a wide choice of adapters and flanges
Materials
Polished stainless steel 316L (EN 1.4404)
Transmitter weight
1.1 lb (0.5 kg)
Ingress protection
• IP66/68
• IP6K9K (ISO 20563:2013)
• NEMA® 4X
The stated ingress protection only applies when plugged in using a suitable M12
connector that has the appropriate ingress protection.
(4)
/69 (IEC 60529)
A.3.3Mounting bracket
Materials
• Bracket and device holder: Stainless steel 316L
• Antenna extension for open air: Stainless steel 316L, polyacetal copolymer (POM-C
ELS), stainless steel EN 10270-3-1.4310
• Lock nut: Stainless steel A4
(4) IP68 at 9.8 ft. (3 m) for more than 30 minutes.
72Rosemount 1408A Level and Flow Transmitter
Page 73
Reference ManualSpecifications and reference data
00809-0200-4480May 2022
A.3.4Flanges
Materials
316L
A.3.5Threaded adapters
Materials
316/316L (EN 1.4404)
A.3.6Material exposed to tank atmosphere
• PTFE sealing: PTFE fluoropolymer
• O-ring: FVMQ
• G1 thread: 316L (EN 1.4404)
• Profile ring: FKM
• Flange: 316L
• NPT threaded and D50 weld adapters: 316/316L (EN 1.4404)
Reference Manual73
Page 74
Ø 2.32 (59)
2.99 (76)
4.76
(121)
5.79
(147)
B
A
Specifications and reference dataReference Manual
May 202200809-0200-4480
A.4Dimensional drawings
Figure A-4: Rosemount 1408A
A. ISO 228/1-G1 thread
B. M12 connector (A-coded)
Dimensions are in inches (millimeters).
74Rosemount 1408A Level and Flow Transmitter
Page 75
0.32 (8)
0.75 (19)
D
1.18
(30)
A
Reference ManualSpecifications and reference data
00809-0200-4480May 2022
Figure A-5: Flanges for Non-pressurized Applications
SizeOuter diameter
(D)
2-in.6.50 (165)2-in. ASME B16.5 Class 150/300, EN1092-1 DN50 PN16/40,
3-in.7.87 (200)3-in. ASME B16.5 Class 150/300, EN1092-1 DN80 PN16/40, and
4-in.9.25 (235)4-in. ASME B16.5 Class 150/300, EN1092-1 DN100 PN16/40, and
Hole pattern
and JIS B2220 50A 10K/20K
JIS B2220 80A 10K/20K
JIS B2220 100A 10K/20K
Dimensions are in inches (millimeters).
Figure A-6: NPT Threaded Adapters
A. 1½-, 2-in. NPT thread
Dimensions are in inches (millimeters).
Reference Manual75
Page 76
1.38
(35)
Ø 1.97 (50)
Ø 2.05 (52)
0.39 (10)
3.29 (83.5)5.89 (149.5)
4.72 (120)
6.18
(157)
8.35
(212)
7.95
(202)
A
Specifications and reference dataReference Manual
May 202200809-0200-4480
Figure A-7: D50 Weld Adapter
Dimensions are in inches (millimeters).
Figure A-8: Mounting Bracket
A. Antenna extension for open air installations
Dimensions are in inches (millimeters).
76Rosemount 1408A Level and Flow Transmitter
Page 77
0.28 (7)
0.43 (11)
1.97
(50)
Ø 0.28 (7)
30°
Reference ManualSpecifications and reference data
00809-0200-4480May 2022
A.4.1Bracket hole pattern
Figure A-9: Hole Pattern
Dimensions are in inches (millimeters).
Related information
Type 1 Drawing
Reference Manual77
Page 78
Menu > ParameterBasic Setup
OUT1 Digital Output
OUT2 Digital Output
*
OUT2 Analog Output
Engineering Units
Reference Height
Write Protection
Digital Outputs P-n
GeometryReference Height
AdvancedCalibration Offset
Upper Null Zone
Bottom Offset
Measurement Recovery Time
Damping Value
General Threshold
Service Tools
Maintenance
Device Reset
Restore Factory Settings
Advanced Setup
Simulation
Analog Out Calibration
OUT1 Configuration
DO Control Variable
Alarm Configuration
OUT2 Configuration
Analog Control Variable
Volume Flow
Volume Flow Calculation Method
Volume Flow Table/Formula
Alarm Mode
Analog Range Values
Upper Range Value (20 mA)
Lower Range Value (4 mA)
Alarm On/Off Delay
Analog Alarm LimitsHigh Alarm Value
High Saturation Value
Low Saturation Value
Low Alarm Value
Set Point ConfigurationHigh Alarm
SP1-High Alarm Set Point
SP2-Low Alarm Set Point
Low Alarm
SP1-Hysteresis High Alarm
SP2-Hysteresis Low Alarm
Application Mode
Configuration parametersReference Manual
May 202200809-0200-4480
BConfiguration parameters
B.1Menu tree
Figure B-1: Parameter
78Rosemount 1408A Level and Flow Transmitter
* Contains the same sub-menus as OUT1 Digital Output.
Page 79
A
B
C
D
A
B
C
Reference ManualConfiguration parameters
00809-0200-4480May 2022
B.2Basic setup
B.2.1Engineering units
Sets the unit of measure for length, temperature, and volume flow.
OptionLength unitTemperature unitVolume flow unit
Metricm°Cm3/h
Imperialinch°FUS gal/h
After appropriate units have been selected, all configuration parameters and transmitter
variables will be expressed in these units.
B.2.2Reference height
Distance between the Device Reference Point and Zero Level.
Figure B-2: Reference Height
A. Device Reference Point
B. Reference Height
Zero Level
C.
D. 0.6 in. (15 mm)
Ensure the Reference Height is set as accurate as possible. The transmitter measures the
distance to the product surface and subtracts this value from the Reference Height to
Reference Manual79
determine the level.
Page 80
A
B
C
EF
D
Of
f
On
Configuration parametersReference Manual
May 202200809-0200-4480
Related information
Enter the reference height
B.2.3Digital output P-n
The output polarity for the switching outputs (PnP or nPn).
B.2.4Write protection
The transmitter can be software write protected to prevent unintentional configuration
changes.
B.3Digital output
B.3.1DO control variable
Select between volume flow or level to control the digital output.
B.3.2Alarm configuration
Alarm delays
Alarm on delay
The time delay for when the digital output transfers from normal to alarm state.
Alarm off delay
The time delay for when the digital output transfers from alarm state to normal.
Figure B-3: Example - High Alarm with Alarm Delays
A. Level
B. Time
SP1 - High alarm set point
C.
D. SP1 - Hysteresis high alarm
E. Alarm on delay
F. Alarm off delay
80Rosemount 1408A Level and Flow Transmitter
Page 81
A
B
C
Of
f
On
DD
E
A
B
C
Of
f
On
D
E
Reference ManualConfiguration parameters
00809-0200-4480May 2022
Options for alarm on delay
Table B-1: Alarm On Delay
OptionDescription
AlwaysAlarm on delay is always used.
Lost surfaceAlarm on delay is used only for lost surface alarms. This may be useful in
applications when there are small and local rapid level changes caused by
surface turbulence.
Hardware faults and measurement values that exceed the alarm set
points will trigger alarm without any delay.
Figure B-4: Behavior of the Alarm On Delay
Always
Lost surface
A. Level
Time
B.
C.
SP1 - High alarm set point
D. Alarm on delay
E. Lost surface (invalid level)
B.3.3Set point configuration
High alarm
Enable or disable the high alarm.
Reference Manual81
Page 82
Configuration parametersReference Manual
May 202200809-0200-4480
Low alarm
Enable or disable the low alarm.
Alarm set points
SP1 - High alarm set point
If the measured value is above this set point, the digital output is set to alarm state.
SP2 - Low alarm set point
If the measured value is below this set point, the digital output is set to alarm state.
Hysteresis
The hysteresis is a buffer zone so the alerts do not toggle on and off when the
measurement value fluctuates around the alarm limit. The alarm is set when the value
exceeds the alarm limit. The alarm is then cleared when the value falls outside the
hysteresis zone.
SP1 - Hysteresis high alarm
Hysteresis zone for the high alarm.
SP2 - Hysteresis low alarm
Hysteresis zone for the low alarm.
B.4Analog output
B.4.1Analog control variable
Select between volume flow or level to control the analog output.
B.4.2Upper/lower range value
Enter the range values that correspond to the analog output values 4 and 20 mA. In
normal operation, the transmitter will drive the output in response to volume flow or level
from the lower to upper saturation points.
Note
The 20 mA point should be set below the reduced accuracy zone at the top of the tank.
82Rosemount 1408A Level and Flow Transmitter
Page 83
B
E
C
D
A
Reference ManualConfiguration parameters
00809-0200-4480May 2022
Figure B-5: Example of Range Value Settings
A. Reduced accuracy zone
B. 100% (20 mA)
Zero Level
C.
D. Level measurement range 0-100%
E. 0% (4 mA)
Related information
Accuracy over measuring range
B.4.3Alarm mode
The transmitter automatically and continuously performs self-diagnostic routines. If a
failure or a measurement error is detected, the transmitter drives the output to selected
alarm limit (high or low).
B.4.4Analog alarm limits
High/low alarm value
The high/low alarm current for the analog output when the device enters the alarm mode.
Related information
Analog signal on alarm
High/low saturation value
Reference Manual83
The device will continue to set a current that corresponds with the measurement until
reaching the upper/lower limit (and then freeze).
Page 84
A
C
D
B
Configuration parametersReference Manual
May 202200809-0200-4480
Related information
Analog saturation levels
B.5Geometry
B.5.1Advanced
Calibration offset
Difference between surface distance measured by transmitter and the same distance
measured by, for example, hand-dipping with a measurement tape. A positive Calibration
Offset value will increase the presented level value.
Figure B-6: Calibration Offset
A. Positive Calibration Offset value
B. Negative Calibration Offset value
C. Reported level
D. Actual level
Upper null zone
The Upper Null Zone defines how close to the device's reference point a level value is
accepted. You can extend this value to block out disturbing echoes close to the antenna,
for example from the tank nozzle.
Note
Make sure the 20 mA value is below the Upper Null Zone. Measurements are not
performed within the Upper Null Zone (UNZ).
Related information
84Rosemount 1408A Level and Flow Transmitter
Change the upper null zone
Page 85
A
B
C
D
+
Reference ManualConfiguration parameters
00809-0200-4480May 2022
Bottom offset
The Bottom Offset is defined as the distance between Zero Level and the tank bottom. The
default value is zero.
If the Zero Level is not located at the tank bottom, then enter a Bottom Offset. It is needed
for the transmitter to know the position of the tank bottom.
Figure B-7: Bottom Offset
A. Device Reference Point
B. Reference Height
C.
Zero Level
D. Bottom Offset
B.6Volume flow
B.6.1Volume flow calculation method
Select the preferred volume flow calculation method. The are three options to choose
from:
• Linearization table
• Parshall flume
• Khafagi-Venturi flume
Related information
Set up the volume flow measurement
Reference Manual85
Page 86
Configuration parametersReference Manual
May 202200809-0200-4480
B.6.2Volume flow table
The volume flow table is used to convert the measured level into a volume flow rate. Up to
30 level-volume flow pairs can be entered. The level points must be entered in increasing
order.
B.6.3Volume flow formula
Parshall Flume
The volume flow is calculated from the formula:
Q = K × H
Table B-2: Parshall Flume Parameters
ParameterDescription
QCalculated volume flow in m3/h
HMeasured level in m
n
Constant KFlume specific factor K
Exponent nFlume specific factor n
Maximum level valueFlume maximum Level (weir height)
Khafagi-Venturi Flume
The volume flow is calculated from the formula:
Q = K × H
Table B-3: Khafagi-Venturi Flume Parameters
ParameterDescription
QCalculated volume flow in m3/h
HMeasured level in m
Constant KFlume specific factor K
Maximum level valueFlume maximum Level (weir height)
1.5
B.7Advanced setup
B.7.1Measurement recovery time
The Measurement Recovery Time (Echo Timeout) parameter controls the maximum time
from when measurement is lost (e.g. due to process conditions such as foam or
turbulence) until it is annunciated. If measurement is recovered within the time specified
by this parameter, then it will not be annunciated.
86Rosemount 1408A Level and Flow Transmitter
Page 87
B
m
0
mV
0.5
1.0
1.5
2.0
2.5
3.0
0150 300 450 600 750 900
A
Reference ManualConfiguration parameters
00809-0200-4480May 2022
B.7.2Damping value
This parameter defines how fast the transmitter reacts to a change of the level value (step
response). The default value is 2 seconds.
A high value makes the level reading steady, while a low value allows the transmitter to
respond to rapid level changes (but the presented level value may be less steady).
B.7.3General threshold
The general threshold is used to filter out noise and disturbing echoes from the product
surface echo. The transmitter uses certain criteria to decide which type of echo peak that
is detected. Only echoes above the general threshold might be considered the product
surface.
Emerson Terms and Conditions of Sale are available upon
request. The Emerson logo is a trademark and service mark of
Emerson Electric Co. Rosemount is a mark of one of the
Emerson family of companies. All other marks are the property
of their respective owners.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.