With over five million transmitters installed worldwide, the Rosemount 1151 continues to offer industry leading
value. Changing customer needs and new technologies have driven product improvements, while advanced
manufacturing and testing processes have guaranteed product quality. Even today, the Rosemount 1151 is
world-reowned for proven field reliability and longevity.
Proven field performance and reliability
For over 35 years, the 1151 has provided the process
control industry with unsurpassed service and
reliability in even the harshest of environments. The
lasting customer preference results from a
combination of advanced technology, and a tradition
of field proven performance.
Commitment to continuous improvement
Through ongoing focus on continuous improvement,
±0.075% reference accuracy has been accomplished
as a result of manufacturing and engineering
enhancements. In addition, Smart electronics offer
rangeability to 50:1, reducing the number of
transmitters to specify, procure, and carry in
inventory. A modular design allows interchangeable
mechanical and electrical components, providing
backward and forward compatibility.
Rosemount Pressure Solutions
Rosemount 3051S Series of Instrumentation
Scalable pressure, flow and level measurement solutions improve
installation and maintenance practices.
Rosemount 3095 Mass Flow Transmitter
Accurately measures differential pressure, static pressure and
process temperature to dynamically calculate fully compensated
mass flow.
Rosemount 305, 306 and 304 Manifolds
Factory-assembled, calibrated and seal-tested
transmitter-to-manifold assemblies reduce installation costs.
Rosemount 1199 Diaphragm Seals
Provides reliable, remote measurements of process pressure and
protects the transmitter from hot, corrosive, or viscous fluids.
Orifice Plate Primary Element Systems: Rosemount
1495 and 1595 Orifice Plates, 1496 Flange Unions and
1497 Meter Sections
A comprehensive offering of orifice plates, flange unions and
meter sections that are easy to specify and order. The 1595
Conditioning Orifice provides superior performance in tight fit
applications.
Application flexibility
The 1151 offers a variety of configurations for
differential, gage, absolute and liquid- level
measurements including integrated solutions for
pressure, level, and flow. High pressure models allow
static line pressures up to 4500 psi (310 bar).
Multiple wetted materials, as well as alternative fill
fluids ensure process compatibility. Smart, analog
and low-power electronics are available to meet
specific application requirements.
Annubar® Flowmeter Series: Rosemount 3051SFA
®
ProBar
The state-of-the-art, fifth generation Rosemount 485 Annubar
combined with the 3051S or 3095 MultiVariable transmitter creates
an accurate, repeatable and dependable insertion-type flowmeter.
Compact Orifice Flowmeter Series: Rosemount
3051SFC, 3095MFC, and 405
Compact Orifice Flowmeters can be installed between existing
flanges, up to a Class 600 (PN100) rating. In tight fit applications,
a conditioning orifice plate version is available, requiring only two
diameters of straight run upstream and two downstream.
ProPlate® Flowmeter Series: Rosemount 3051SFP
ProPlate, 3095MFP Mass ProPlate, and 1195
These integral orifice flowmeters eliminate the inaccuracies that
become more pronounced in small orifice line installations. The
completely assembled, ready to install flowmeters reduce cost and
simplify installation.
Ranges 3 through 8, DP and GP transmitters;
Ranges 4 through 7, HP transmitters
±0.075% of calibrated span for spans from 1:1 to 10:1 of URL.
Between 10:1 and 50:1 of URL.
All other ranges and transmitters
±0.25% of calibrated span
Output Code S, square root mode
Output Codes E, G, L, and M
±0.2% of calibrated span for 1151DP Ranges 3 through 5. All
other ranges and transmitters, ±0.25% of calibrated span.
Stability
Output Code S
±0.1% of URL for 2 years for DP and GP Ranges 3 through 8.
(±0.25% for all other ranges and transmitters.)
Output Codes E and G
±0.2% of URL for six months for Ranges 3 through 5. (±0.25
for all other ranges.)
Output Codes L and M
±0.25% of URL for six months
Temperature Effect
Output Code S [–20 to 185 °F (–29 to 85 °C)]
For DP and GP transmitter Range 4 through 8;
HP transmitter Range 4 through 7:
Zero Error = ±0.2% URL per 100 °F (56 °C)
Total Error = ±(0.2% URL + 0.18% of calibrated span)
per 100 °F; For Range 3, double the stated effects. For other
ranges and transmitters follow analog temperature
specifications (Output Code E).
Output Code E, G, L, and M
[–20 to 200 °F (–29 to 93 °C)]
For Ranges 4 through 0
Zero Error = ±0.5% URL per 100 °F.
Total Error = ±(0.5% URL + 0.5% of calibrated span) per 100
°F; double the effect for Range 3.
(1)
Static Pressure Effect – DP Transmitters
DP Transmitters
Zero Error
±0.25% of URL for 2,000 psi (13790 kPa)
for Range 4 and 5 or ±0.5% for other ranges, correctable
through rezeroing at line pressure.
Span Er ror
Correctable to ±0.25% of input reading per 1,000 psi
(6895 kPa), or to ±0.5% for Range 3.
HP Transmitters
Zero Error
±2.0% of URL for 4,500 psi (31027 kPa), correctable through
rezeroing at line pressure.
Span Er ror
Correctable to ±0.25% of input reading per 1,000 psi
(6895 kPa).
Vibration Effect
0.05% of URL per g to 200 Hz in any axis
Power Supply Effect
Output Codes S, E, and G
Less than 0.005% of output span per volt
Output Codes L, M
Output shift of less than 0.05% of URL for a 1 V power supply
shift
Load Effect
Output Codes S, E, and G
No load effect other than the change in power supplied to the
transmitter.
Output Codes L, M
Less than 0.05% of URL effect for a change in load from
100k⍀ to infinite ohms.
Short Circuit Condition (Low Power Only)
No damage to the transmitter will result when the output is shorted
to common or to power supply positive (limit 12 V).
EMI/RFI Effect
Output shift of less than 0.1% of span when tested to SAMA PMC
33.1 from 20 to 1000 MHz and for field strengths up to 30 V/m.
(1) Accuracy for Range 9, GP transmitter at 40:1 is ±0.7%
of calibrated span.
Pressure-3
Page 4
Rosemount 1151
R
max
R
L
R
min
V
min
V
S
V
max
0
Operating
Region
Product Data Sheet
00813-0100-4360, Rev HA
Catalog 2008 - 2009
Mounting Position Effect
Zero shift of up to 1 inH2O (0.25 kPa).
With liquid level diaphragm in vertical plane, zero shift of up to 1
O (0.25 kPa). With liquid level diaphragm in horizontal plane,
inH
2
zero shift of up to 5 inH
extended units. All zero shifts can be calibrated out. No effect
on span.
O (1.25 kPa) plus extension length on
2
FUNCTIONAL SPECIFICATIONS
Service
Liquid, gas, and vapor applications
Ranges
See Table 2 for ranges. Minimum span equals the upper range
limit (URL) divided by rangedown. Rangedown varies with the
output code See Table 1.
Outputs
Code S, Smart
4–20 mA dc, user selectable for linear or square root output.
Digital process variable superimposed on 4–20 mA signal,
available to any host that conforms to the HART
Code E, Analog
4–20 mA dc, linear with process pressure
Code G, Analog
10–50 mA dc, linear with process pressure
Code L, Low Power
0.8 to 3.2 V dc, linear with process pressure
Code M, Low Power
1 to 5 V dc, linear with process pressure
Current Consumption Under Normal Operating
Conditions (Low Power Only)
Output Code L
1.5 mA dc
Output Code M
2.0 mA dc
®
protocol.
Span and Zero
Output Code S
Span and zero may be accessed with local adjustments or
remotely through a HART-compatible Interface.
Output Codes E, G, L, and M
Span and zero are continuously adjustable.
Power Supply
External power supply required. Transmitter operates according to
the following requirements:
Output Codes S, E
12 to 45 V dc with no load
Output Code G
30 to 85 V dc with no load
Output Code L
5 to 12 V dc
Output Code M
8 to 14 V dc
Where:
Code V
(1)
S
(2)
E
G308501100 R
L512Low Power Minimum Load
M814
(1) A minimum of 250 ohms is required for communication.
Zero elevation and suppression must be such that the lower
range value is greater than or equal to the (–URL) and the
upper range value is less than or equal to the (+URL). The
calibrated span must be greater than or equal to the minimum
span and less than or equal to the maximum span.
Output Code L
Zero is adjustable ±10% of URL and span is adjustable from
90 to 100% of URL.
Output Code M
Zero is adjustable ±50% of URL and span is adjustable from
50 to 100% of URL.
Pressure-4
Temperature Limits
Electronics Operating
Code S: –40 to 185 °F (–40 to 85 °C)
Code E: –40 to 200 °F (–40 to 93 °C)
Code G, L, M: –20 to 200 °F (–29 to 93 °C)
Sensing Element Operating
Silicone fill: –40 to 220 °F (–40 to 104 °C)
Inert fill: 0 to 160 °F (–18 to 71 °C)
Storage
Code S: –60 to 185 °F (–51 to 85 °C)
Codes E, G, L, M: –60 to 250 °F (–51 to 121 °C)
Page 5
Product Data Sheet
00813-0100-4360, Rev HA
Catalog 2008 - 2009
TABLE 1. Rangeability
Output CodeMinimum SpanMaximum Span
S (DP and GP, SST, Range 3–8; HP SST, Range 4–7)URL/502 ⫻ URL
S (All Others)URL/50
E, GURL/6URL
LURL/1.1URL
MURL/2URL
(1) Transmitter is capable of measuring from –URL to URL.
(2) Accuracy specification for calibrated spans from 1:1 to 6:1 of URL only.
TABLE 2. Transmitter Range Availability by Model (URL = Upper Range Limit)
D.C.® 200 Silicone–40 to 400 °F (–40 to 205 °C)0.9340.00060 (0.00108)9.5
D.C. 704 Silicone60 to 400 °F (15 to 204 °C)1.070.00053 (0.00095)44
Inert Fill–50 to 350 °F (–45 to 177 °C)1.850.0004 (0.000864)6.5
Syltherm®XLT, Silicone–100 to 300 °F (–73 to 149 °C) 0.850.000666 (0.001199)1.6
Glycerin and Water
Propylene Glycol and Water
Neobee M-20
(1) Temperature limits are reduced in vacuum service. Contact an Emerson Process Management representative for assistance.
(2) Glycerin and Water and Propylene Glycol and Water are not suitable for vacuum service.
(3) Not compatible with Buna-N or Ethylene-Propylene O-ring material.
®(3)
(2)
0 to 200 °F (–17 to 93 °C)1.130.00019 (0.00034)12.5
(3)
0 to 200 °F (–17 to 93 °C)1.020.00019 (0.00034)2.85
0 to 400 °F (–17 to 205 °C)0.9000.00056 (0.001008)9.8
(1)
Specific Gravity
Coeff. of Therm. Exp.
cc/cc/°F (cc/cc/°C)
Viscosity at 25 °C
centistokes
Pressure-5
Page 6
Rosemount 1151
Product Data Sheet
00813-0100-4360, Rev HA
Catalog 2008 - 2009
Static Pressure and Overpressure Limits
115 1DP
0 psia to 2,000 psig (0 to 13.79 MPa) on either side without
damage to transmitter. Operates within specifications from
static line pressures of 0.5 psia (3.45 kPa) to 2,000 psig
(13.79 MPa).
115 1HP
0 psia to 4,500 psig (0 to 31.02 MPa) on either side without
damage to transmitter. Operates within specifications from 0.5
psia (3.45 kPa) to 4,500 psig (31.02 MPa). Consult an
Emerson Process Management representative for higher
Static Pressure options up to 6000 psi.
115 1AP
0 psia to 2,000 psia (0 to 13.79 MPa) without damage to
transmitter. Operates within specifications from 0 psia to the
upper range limit of the transmitter.
115 1GP
0 psia to 2,000 psig (0 to 13.79 MPa) for ranges to 1,000 psig
(6.90 MPa), 4,500 psig (31.02 MPa) for the 3,000 psig (20.68
MPa) range, and 7,500 psig (51.71 MPa) for the 6,000 psig
(41.37 MPa) range, without damage to the transmitter.
Operates within specifications from 0.5 psia (3.45 kPa) to the
upper range limit of the transmitter.
115 1LT
TABLE 6. Flange Pressure Rating
StandardClass/RatingCarbon SteelStainless Steel
ANSI150285 psig
ANSI300740 psig
ANSI6001,480 psig
DINPN 10–4040 bar
DINPN 10/1616 bar
DINPN 25/4040 bar
(1) At 100 °F (38 °C); the rating decreases with increasing
temperature.
(2) At 248 °F (120 °C); the rating decreases with increasing
temperature.
(1)
(1)
(1)
(2)
(2)
(2)
1,440 psig
275 psig
720 psig
40 bar
16 bar
40 bar
(1)
(1)
(1)
(2)
(2)
(2)
Burst Pressure All Models
10,000 psig (68.95 MPa) proof pressure on the flanges.
Transmitter Security (Output Code S)
Activating the transmitter security function prevents changes to the
transmitter configuration, including local zero and span
adjustments. Security is activated by an internal switch.
Overpressure Saturation Value (Output Code S)
If the sensor detects a negative overpressure value, the analog
signal will be driven to 3.9 mA. If the sensor detects a positive
overpressure value, the analog signal is driven to 20.8 mA.
Damping
Numbers given are for silicone fill fluid at room temperature. The
minimum time constant is 0.2 seconds (0.4 seconds for Range 3).
Inert-filled sensor values would be slightly higher.
Output Code S
Time constant is adjustable in 0.1 second increments from
minimum to 16.0 seconds.
Output Codes E and G
Time constant continuously adjustable between minimum and
1.67 seconds.
Output Codes L, M
Damping is fixed at minimum time constant.
1151LT
Time constant continuously adjustable between 0.4 and 2.2
seconds with silicone oil fill, or 1.1 and 2.7 seconds with inert
fill for flush models and electronics codes E or G.
Turn-on Time
Maximum of 2.0 seconds with minimum damping. Low power
output is within 0.2% of steady state value within 200 ms after
application of power.
Physical Specifications,
Standard Configuration
Electrical Connections
1
/2–14 NPT conduit with screw terminals and integral test jacks
compatible with miniature banana plugs (Pomona 2944, 3690, or
equivalent). The HART Hand-Held Interface connections are fixed
to the terminal block on smart transmitters.
Humidity Limits
0 to 100% relative humidity
Volumetric Displacement
Less than 0.01 in3 (0.16 cm3)
Failure Mode Alarm (Output Code S)
If self-diagnosis detects a gross transmitter failure, the analog
signal will be driven below 3.9 mA or above 21 mA to alert the
user. High or low alarm signal is user selectable.
Level4–20 mA Saturation Value4–20 mA Alarm Value
Low3.9 mA3.75 mA
High20.8 mA21.75 mA
Pressure-6
Wetted Materials
Isolating Diaphragms
316L SST, Hastelloy C-276, or Tantalum. See ordering table
for availability per model type.
Drain/Vent Valves
316 SST or Hastelloy C-276, see ordering table for availability
per model type.
Process Flanges and Adapters
Plated carbon steel, 316 SST or Hastelloy C-276, see ordering
table for availability per model type.
Wetted O-rings
®
(other materials also available)
Viton
Page 7
Product Data Sheet
00813-0100-4360, Rev HA
Catalog 2008 - 2009
Rosemount 1151
Non-wetted Materials
Fill Fluid
Silicone oil or inert fill
Nuts and Bolts
Plated carbon steel
Blank flange (GP and AP only)
Plated carbon steel
Electronics Housing
Low-copper aluminum. NEMA 4X
Cover O-rings
Buna-N
Paint
Polyurethane
Process Connections
Rosemount 1151DP, HP, GP, AP
1
/4–18 NPT on 2.125-in. (54-mm) centers on flanges for
Ranges 3, 4, and 5.
1
/4–18 NPT on 2.188-in. (56-mm) centers on flanges for
Ranges 6 and 7.
1
/4–18 NPT on 2.250-in. (57-mm) centers on flanges for
Range 8.
1
/2–14 NPT on adapters.
For Ranges 3, 4, and 5, flange adapters can be rotated to give
centers of 2.0 in. (51 mm), 2.125 in. (54 mm), or 2.250 in. (57
mm).
Rosemount 1151LT
High pressure side: 2-, 3-, or 4-in., Class 150, 300 or 600 flange;
50, 80, or 100 mm, PN 40 or 10/16 flange.
Low pressure side: 1/4–18 NPT on flange. 1/2–14 NPT on
adapter.
Weight
12 lb (5.4 kg) for AP, DP, GP, and HP transmitters, excluding
options. Meter option: Add 2 lb (1 kg)
TABLE 7. 1151LT Weight with Flange
(1)
Flange
2-in., Class 15018 (8.2)N/AN/AN/A
3-in., Class 15023 (10.4)25 (11.3)26 (11.8)27 (12.3)
4-in., Class 15029 (13.2)32 (14.5)34 (15.4)36 (16.3)
2-in., Class 30020 (9.1)N/AN/AN/A
3-in., Class 30028 (12.7)30 (13.6)31 (14.1)32 (14.5)
4-in., Class 30038 (17.2)41 (18.6)43 (19.5)45 (20.4)
2-in., Class 60022 (10.0)N/AN/AN/A
3-in., Class 60031 (14.1)33 (15.0)34 (15.4)35 (15.9)
DN 50, PN10-4020 (9.1)N/AN/AN/A
DN 80, PN 25/4025 (11.3)27 (12.3)28 (12.7)29 (13.2)
DN 100, PN 10/1625 (11.3)28 (12.7)30 (13.6)32 (14.5)
DN 100, PN 25/4029 (13.2)32 (14.5)34 (15.4)36 (16.3)
(1) Stainless steel flange weights are listed.
Flush
lb. (kg)
2-in (50mm) Ext.
lb. (kg)
4-in. (100mm) Ext.
lb. (kg)
6-in. (150mm) Ext.
lb. (kg)
Pressure-7
Page 8
Rosemount 1151
Product Data Sheet
00813-0100-4360, Rev HA
Catalog 2008 - 2009
Product Certifications
Approved Manufacturing Locations
Rosemount Inc. — Chanhassen, Minnesota, USA
Emerson Process Management GmbH & Co. — Wessling,
Germany
Emerson Process Management Asia Pacific
Private Limited — Singapore
Beijing Rosemount Far East Instrument Co., Limited – Beijing,
China
European Directive Information
The EC declaration of conformity for all applicable European
directives for this product can be found on the Rosemount website
at www.rosemount.com. A hard copy may be obtained by
contacting our local sales office.
ATEX Directive (94/9/EC)
Emerson Process Management complies with the ATEX
Directive.
European Pressure Equipment Directive (PED) (97/23/EC)
All other 1151 Pressure Transmitters
— Sound Engineering Practice
Transmitter Attachments: Diaphragm Seal - Process Flange Manifold
— Sound Engineering Practice
Electro Magnetic Compatibility (EMC) (2004/108/EC)
All models
— EN 61326: 1997 with Amendments A1, A2, and A3
Hazardous Locations Certifications
North American Certifications
Ordinary Location Certification for Factory Mutual
As standard, the transmitter has been examined and tested
to determine that the design meets basic electrical,
mechanical, and fire protection requirements by FM, a
nationally recognized testing laboratory (NRTL) as
accredited by the Federal Occupational Safety and Health
Administration (OSHA).
Factory Mutual (FM) Approvals
FM Explosion-Proof tag is standard. Appropriate tag will be
substituted if optional certification is selected.
Explosion-Proof: Class I, Division 1, Groups B, C, and D.
Dust-Ignition Proof: Class II, Division 1, Groups E, F, and G;
Class III, Division 1. Indoor and outdoor use. NEMA 4X.
Factory Sealed.
I5Intrinsically safe for Class I, II, and III Division 1, Groups A,
B, C, D, E, F, and G hazardous locations in accordance with
entity requirements and Control drawing 01151-0214 and
00268-0031. Non- incendive for Class I, Division 2, Groups
A, B, C and D hazardous locations.
For entity parameters see control drawing 01151-0214.
Canadian Standards Association (CSA) Approvals
E6Explosion-Proof for Class I, Division 1, Groups C and D;
Class II, Division 1, Groups E, F, and G; Class III, Division 1
Hazardous Locations. Suitable for Class I, Division 2, Groups
A, B, C, and D; CSA enclosure type 4X. Factory Sealed.
I6Intrinsically safe for Class I, Division 1, Groups A, B, C, and
D hazardous locations when connected per Drawing
01151-2575. For entity parameters see control drawing
01151-2575. Temperature Code T2D.
Pressure-8
European Certifications
I1 ATEX Intrinsically Safe and Combustible Dust
(1151 Smart only)
Certificate No.: BAS99ATEX1294X
ATEX Marking II 1 GD
EEx ia IIC T5 (-60°C ≤
EEx ia IIC T4 (-60°C ≤
118 0
IP66
TABLE 8. IS Entity Parameters
Ui = 30 V
Ii = 125 mA
Pi = 1.0 W (T4) or 0.67 W (T5)
Ci = 0.034 μF
Li = 20 µH
Special Conditions for Safe Use (X)
The apparatus, is not capable of withstanding the 500V test
as required by EN 50020: 1994. This must be taken into
account when installing the apparatus.
Ta ≤ 40°C)
Ta ≤ 80°C)
Page 9
Product Data Sheet
00813-0100-4360, Rev HA
Catalog 2008 - 2009
Rosemount 1151
N1ATEX Type n and Combustible Dust
(1151 Smart only)
Certificate No.: BAS 99ATEX3293X
ATEX marking: II 3 GD
EEx nL IIC T5 (-40°C ≤
EEx nL IIC T4 (-40°C ≤
Dust Rating: T90 °C (Ta = -20°C to 40°C)
= 45 Vdc Max
U
i
IP66
Special Conditions for Safe Use (x)
The apparatus is not capable of withstanding the 500V
insulation test required by EN 50021: 1999. This must be
taken into account when installing the apparatus.
E8ATEX Flame-Proof
Certification Number CESI03ATEX037
ATEX Marking II 1/2 G
EEx d IIC T6 (–40 ≤ Ta ≤ 40 °C)
EEx d IIC T4 (–40 ≤ Ta ≤ 80 °C)
1180
V = 60 Vdc maximum
Ta ≤ 40°C)
Ta ≤ 80°C)
Australian Certifications
Standards Association of Australia (SAA) Certification
E7SAA Flame-proof
Certificate Number Ex 494X
Ex d IIB + H
DIP T6
IP65
Special Conditions for safe use (x):
For transmitters having NPT, PG or G cable entry threads,
an appropriate flame-proof thread adaptor shall be used to
facilitate application of certified flame-proof cable glands or
conduit system.
T6
2
I7SAA Intrinsically Safe
Certificate Number: Ex 122X
Ex ia IIC T5 (T
Ex ia IIC T4 (T
Special Conditions for Safe Use (x):
The equipment has been assessed to the entity concept and
accordingly the following electrical parameters must be
taken into account during installation.
amb
amb
= 40 °C)
= 60 °C)
TABLE 9. Entity Parameters
Ui = 30V
= 125 mA
I
i
Pi = 1.0 W (T4) or 0.67W (T5)
= 14.8 nF
C
i
Li = 20 μH
N7SAA Type n
Certificate Number: Ex 887X
Ex n IIC T6 (T
Ex n IIC T5 (T
IP66
Special Conditions for safe use (x):
The equipment must be connected to a supply voltage
which does not exceed the rated voltage. The enclosure end
caps must be correctly fitted whilst the equipment is
energized.
amb
amb
= 40 °C)
= 80 °C)
Combination Certifications
Stainless steel certification tag is provided when optional approval
is specified. Once a device labeled with multiple approval types is
installed, it should not be reinstalled using any other approval
types. Permanently mark the approval label to distinguish it from
unused approval types.
C6Combination of I6 and E6,
K5Combination of FM Approvals Explosion-Proof and I5.
K6Combination of E6, I6, I1, and E8
Pressure-9
Page 10
Rosemount 1151
Flange Distance “A” Center to Center
Rangeinchesmm
3, 4, 52.12554
6, 72.18856
82.25057
92.28158
02.32859
Meter
Housing
Terminal Connections
this Side
¼–18 NPT on
Flanges for Pressure
Connection without
Flange Adapters
½–14 NPT
on Flange
Adapters
A
(See Table)
4.5 (114)
Max.
7.5 (191) Max.
with Optional Meter
0.75 (19)
Clearance for
Cover Removal
(Typical)
Transmitter
Circuitry
this Side
1.625
(41)
Blank Flange
Used on
AP and GP
Transmitters
Flange
Adapter
4.5
(114)
3.375
(86)
Flanges Can
Be Rotated
3.69
(94)
4.5 (114)
Max.
Permanent
Tag (Optional)
Nameplate
Wired-on Tag
(Standard)
Drain/Vent
Valve
¼–18 NPT for
Side Drain/Vent
(Optional Top
or Bottom)
NOTE
Dimensions are in inches (millimeters).
½–14 NPT
Conduit
Connection
(2 Places)
9.0
(229)
Max.
Product Data Sheet
00813-0100-4360, Rev HA
Catalog 2008 - 2009
Dimensional Drawings
1151 Transmitter
Pressure-10
Page 11
Product Data Sheet
Smart
Electronics
Terminal Eyelets
Transmitter Security and Failure
Mode Alarm Switches
Zero and Span Buttons
Board
Spacers
Blank Flange
for AP and GP
Process
Flange
␦-Cell
™
Sensing
Module
00813-0100-4360, Rev HA
Catalog 2008 - 2009
Typical Transmitter Exploded View with Smart Electronics
Rosemount 1151
Pressure-11
Page 12
Rosemount 1151
C
B
DIAPHRAGM ASSEMBLY
AND MOUNTING FLANGE
NOTE
Dimensions are in inches (millimeters).
Meter
Housing
Terminal Connections
This Side
Nameplate (Remove for
Span and Zero Adjust)
Transmitter
Circuitry
This Side
½–14 NPT for
Conduit Connection
(2 places)
0.75 (19) Clearance
for Cover Removal
(typical)
½–14 NPT
on Flange
Adapters
¼–18 NPT on Flanges
for Pressure Connection
without the Use of Flange
Adapters
SST Non-wetted Parts on Transmitter without Meter••••
(12)
SST Non-wetted Parts on Transmitter with Meter••••
H3SST Housing, Covers, Conduit Plug, Lock-nut, without Meter••••
H4SST Housing, Covers, Conduit Plug, Lock-nut, with Meter••••
R1Integral Transient Protection (Only available with Option Code S and E electronics
CodeBolts for Flanges and Adapters (optional - select one)DPHPGPAP
L3ASTM A193-B7 Flange and Adapter Bolts••••
L4316 SST Flange and Adapter Bolts••••
L5ASTM A193-B7M Flange and Adapter Bolts••••
CodeProcess Connections (optional
D1Side Drain/ Vent, Top316 SST
(14)
)MaterialsDPHPGPAP
•••
Hastelloy C-276••••
D2Side Drain/ Vent, Bottom316 SST
•••
Hastelloy C-276••••
DF ½–14 NPT Flange adapter(s)- Material determined by flange materialCarbon Steel
316 SST
Hastelloy C-276
D4
D5
(15)
Conformance to DIN EN61518 Ranges 3, 4, 5 with ¼ NPT Process Connections
Thread (Available in Germany Only)
(15)
Conformance to DIN EN61518 Ranges 6, 7, 8, without ¼ NPT Process Connections
•
•
•
•
•
•
•
•
•
••——
••——
Thread (Available in Germany Only)
D6316 SST Low Side Blank Flange—— ••
D9JIS Process Connection–RC ¼ Flange with RC ½ Flange
Adapter
Carbon Steel
316 SST
Hastelloy C-276
•
•
•
•
•
•
•
•
•
G1DIN Spacing (Single Entry Port, No Side V/D Hole Flange)••••
G2DIN Spacing (Single Entry Port, Two Side V/D Hole Flange)••••
G3DIN Spacing (Dual Entry Port, No Side V/D Hole Flange)••••
G4DIN Spacing (Dual Entry Port, One Top Side V/D Hole Flange)••••
G5DIN Spacing (Dual Entry Port, One Bottom Side V/D Hole Flange)••••
G6DIN Spacing (Dual Entry Port, Two Side V/D Hole Flange)••••
•
•
•
•
•
•
•
•
Pressure-17
Page 18
Product Data Sheet
00813-0100-4360, Rev HA
Rosemount 1151
(16)
K1
K2
(17)(18)
S1
(17)(18)
S2
(18)(19)
S4
S6
CodeWetted O-ring Material (optional - select one)DPHPGPAP
W2Buna-N••••
W3Ethylene-Propylene••••
W4Aflas••••
W6
W7
CodeSpecial Configuration (Software)DPHPGPAP
(23)(24)
CN
(23)(24)
C4
C9
CodeSpecial CertificationsDPHPGPAP
Q8
Q16Surface Finish Certification for Sanitary Remote Seals••••
CodeToolkit Total System Performance ReportsDPHPGPAP
CodeProcedures (optional - select one)DPHPGPAP
P1
P2
CodeOutputs (optional - select one)DPHPGPAP
V1
V2
V3
Typical Model Number: 1151DP 4 S 52 B3 M4
(1) Output Code G is not available with CE Mark.
(2) Meter or SST housing not valid with this option.
(3) Bolts and conduit plugs are plated carbon steel.
(4) On GP and AP transmitters, the low-side flange is plated carbon steel. For a stainless-steel low-side flange, order process connection Option Code D6.
(5) These selections meet NACE material recommendations per MR 01-75.
(6) Not available with Output Codes L or M, or Option Codes V2 or V3.
(7) Limited availability. Contact your Emerson Process Management representative.
(8) Specify the range, mode, and engineering units. Also, the 20 mA value must be greater than the 4 mA value.
(9) Not available with Output Codes G.
(10) Not available with Output Codes E, G, L, or M.
(11) Limited availability depending on transmitter type and range. Contact an Emerson Process Management representative.
(12) Option includes SST housing, covers, conduit plug, locknut, L4 bolting, and D6 low side blank flange for GP and AP transmitters.
(13) Not available with Output Codes L or M.
(14) Allowable combinations are: D1, D3, D6; D2, D3, D6; and D6, S1.
(15) Material Traceability Certificate Option Q8 available.
(16) The maximum working pressure on this option is 300 psig. Available only with materials of construction Option Code 2x.
(17) This option may only be used on Ranges 4–8.
(18) “Assemble-to” items are specified separately and require a completed model number.
(19) This option has a maximum static pressure rating of 3,000 psi, and is available for factory assembly only without associated piping and is available only for
(20) Contains a Hastelloy spring that is wetted by the process; consult factory for PTFE O-ring without a spring.
(21) Available for all the ranges of DP (3-8), HP (4-7), and AP (4-8), but it is only available for GP ranges 3-8.
(22) PTFE O-ring has seal property limitations; Consult an Emerson Process Management representative for more information.
(23) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field.
(24) Available with Output Code S only.
(25) This option is available for the transmitter flange and adapters.
(26) Hydrostatic testing for Range 0, 125% maximum working pressure.
(27) Fluorolube
(28) Reverse output option is not needed with smart electronics; configured via HART-based communicator.
(29) Not available with Output Codes L or M.
Kynar insert, ¼–18 NPT•—••
(16)
Kynar insert, ½–14 NPT•—••
Assemble to one Rosemount diaphragm seal •—•—
Assemble to two Rosemount diaphragm seals •———
Assemble to Rosemount 1195 Integral Orifice•———
(18)
Assemble to Rosemount 304 Manifold or Connection System••••
(20)(21)
Spring-loaded PTFE•—••
(21)(22)
PTFE•—••
Analog Output Levels Compliant with NAMUR Recommendation NE43: 27-June-1996 and Low Alarm Level••••
Analog Output Levels Compliant with NAMUR Recommendation NE43: 27-June-1996 and High Alarm
Level
(24)
Software Configuration (Requires completed Configuration Data Sheet)••••
Q4Calibration Certificate••••
(25)
Material Traceability per EN 10204 3.1••••
QZRemote Seal System Performance Calculation Report••••
(26)
Hydrostatic Testing, 150% Maximum Working Pressure••••
(27)
Cleaning for Special Service••••
P3Cleaning for <1 PPM Chlorine/Fluorine••••
(28)
Reverse Output——•—
(29)
4–20 mV Test Signal••••
(29)
20–100 mV Test Signal••••
Option Codes L4 and D6 parts are included with housing Option Codes H1 and H2.
Ranges 2, 3, 4, and 5.
®
grease on wetted O-rings.
Catalog 2008 - 2009
••••
Pressure-18
Page 19
Product Data Sheet
00813-0100-4360, Rev HA
Catalog 2008 - 2009
ModelProduct Description
115 1LT Flange-Mounted Liquid Level Transmitter
CodePressure Range
4150 inH2O (0–635 to 0–3,810 mmH2O)
5750 inH2O (0–3,175 to 0–19,050 mmH2O)
62,770 inH2O (0–11.96 to 0–70.36 mmH2O)
CodeOutput
S4–20 mA with Digital Signal based on HART Protocol (Smart)
E4–20 mA, Linear with Input
(1) (2)
G
CodeSizeMaterialExtension Length
CodeSizeRatingMaterial
10–50 mA, Linear with Input
G02 in./DN 50316L SSTFlush Mount OnlyWhen specifying these option codes, a lower
H02 in./DN 50Hastelloy C-276Flush Mount Only
J02 in./DN 50TantalumFlush Mount Only
A03 in./DN 80316L SSTFlush Mount
A23 in./DN 80316L SST2 in./50 mm
A43 in./DN 80316L SST4 in./100 mm
A63 in./DN 80316L SST6 in./150 mm
B04 in./DN 100316L SSTFlush Mount
B24 in./DN 100316L SST2 in./50 mm
B44 in./DN 100316L SST4 in./100 mm
B64 in./DN 100316L SST6 in./150 mm
C03 in./DN 80Hastelloy C-276Flush Mount
C23 in./DN 80Hastelloy C-2762 in./50 mm
C43 in./DN 80Hastelloy C-2764 in./100 mm
C63 in./DN 80Hastelloy C-2766 in./150 mm
D04 in./DN 100Hastelloy C-276Flush Mount
D24 in./DN 100Hastelloy C-2762 in./50 mm
D44 in./DN 100Hastelloy C-2764 in./100 mm
D64 in./DN 100Hastelloy C-2766 in./150 mm
E03 in./DN 80TantalumFlush Mount Only
F04 in./DN 100TantalumFlush Mount Only
CodeProcess Fill - High Pressure SideTemperature Limits
ASyltherm XLT–100 to 300 °F (–73 to 135 °C)
CD. C. Silicone 70460 to 400 °F (15 to 205 °C)
DD. C. Silicone 200–40 to 400 °F (–40 to 205 °C)
HInert–50 to 350 °F (–45 to 177 °C)
GGlycerin and Water0 to 200 °F (–17 to 93 °C)
NNeobee M-200 to 400 °F (–17 to 205 °C)
PPropylene Glycol and Water 0 to 200 °F (–17 to 93 °C)
CodeOptions
Low-Side Flange
(3)(4)
S1
M1
M3
M4
M7
Assemble to one Rosemount diaphragm seal
METERS
(5)
Linear Meter, 0–100% Scale
(5)
Special Scale Meter, Specify Range
(5)(6)
LCD Display, 0–100%
(5)(7)
LCD Display, Linear, Special Configuration
TERMINAL BLOCKS
R1Integral Transient Protection (Available with output codes S and E only)
HARZARDOUS LOCATIONS CERTIFICATIONS
E8ATEX Flameproof
(8)
I1
N1
I5
K5
C6
I6
K6
ATEX Intrinsic Safety
(8)
ATEX Type n
(8)
FM Intrinsically Safe, Division 2
(8)
FM Explosion-Proof, Dust Ignition-proof, Intrinsically Safe, Division 2
Q16Surface Finish Certification for Sanitary Remote Seals (all options)
Typical Model Number: 1151LT 4 S A0 A 52 D F1
(1) Not available with Output Codes E and G.
(2) Output Code G is not available with CE Mark.
(3) For welded capillary assemblies, order sensor module and low-side materials of construction Option Code 22 (refer to 00813-0100-4016 for more information).
(4) “Assemble-to” items are specified separately and require a completed model number.
(5) Not available with Option Codes Zx, V2, or V3.
(6) Limited availability. Contact an Emerson Process Management representative.
(7) Specify the Range, Mode, and Engineering Units. Also, the 20 mA value must be greater than the 4 mA value.
(8) Not available with Output Codes E and G.
(9) Limited availability depending on transmitter type and range. Contact an Emerson Process Management representative.
(10) Available for the diaphragm, upper housing, flange, adapter, extension, and lower housing.
Material Traceability per EN 10204 3.1B
QZRemote Seal System Performance Calculation Report
V1Reverse Output
V24–20 mV Test Signal
V320–100 mV Test Signal
F_Select One Code from Flushing Connections Lower Housing Option. See Table 11.
(1) Not available with high pressure side Option Codes A0, B0, and G0.
Flushing
Connections
• = Applicable— = Not Applicable
Diaphragm Size
Size
1
/4 - 18 NPT•••
1
/4 - 18 NPT•••
1
/4 - 18 NPT•••
1
/4 - 18 NPT•••
1
/2 - 14 NPT•••
1
/2 - 14 NPT•••
1
/2 - 14 NPT•••
1
/2 - 14 NPT•••
2-in.3-in.4-in.
Pressure-21
Page 22
Rosemount 1151
Product Data Sheet
00813-0100-4360, Rev HA
Catalog 2008 - 2009
Standard Accessories
All models are shipped with drain/vent valves, and one instruction
manual per shipment.
Tagging
The transmitter will be tagged, at no charge, in accordance with
customer requirements. All tags are stainless steel. The standard
tag is wired to the transmitter, however a permanently attached tag
is available upon request. Tag character height is 0.125 in. (0.318
cm).
Calibration
Transmitters are factory calibrated to the customer’s specified
range. If calibration is not specified, the transmitters are calibrated
at maximum range. Calibration is performed at ambient
temperature and pressure.
Options
The following sections describe a variety of available options for
the 1151 Transmitter. These options permit greater application
flexibility.
Optional Manifolds
Refer to Manifold Product Data Sheet (document number
00813-0100-4839).
Optional Diaphragm and Sanitary Seals
Refer to Product Data Sheet (document numbers
00813-0100-4016 or 00813-0201-4016)
Mounting Brackets
B1 Bracket for 2-in. Pipe Mounting
• Bracket for mounting transmitter on 2-in. pipe
• Constructed of carbon steel with carbon steel U-bolt
• Coated with polyurethane paint
B4 Bracket for 2-in. Pipe with 316 SST Bolts
• Same bracket as Option Code B1 with 316 SST bolts
B7 304 SST Bracket and 316 SST Bolts for 2-in. Pipe Mounting
• Same bracket as Option Code B1 with all SST materials
B2 Bracket for Panel Mounting
• Bracket for mounting transmitter on panel or wall
• Constructed of carbon steel with
carbon steel bolts
• Coated with polyurethane paint
B5 Bracket for Panel with 316 SST Bolts
• Same bracket as Option Code B2
with 316 SST bolts
B3 Flat Bracket for 2-in. Pipe Mounting
• Bracket for vertical mounting of transmitter on 2-in. pipe
• Constructed of carbon steel with
carbon steel U-bolt
• Coated with polyurethane paint
B6 Flat Bracket for 2-in. Pipe with 316 SST Bolts
• Same bracket as Option Code B3
with 316 SST bolts
B9 304 SST Flat Bracket and 316 SST Bolts for 2-in. Pipe
Mounting
• Same bracket as Option Code B3 with all 316 SST materials
Bolts and Nuts for Flanges and Adapters
Options permit bolts and nuts for flanges and adapters in the
specified material.
• L3 ANSI/ASTM A - 193-B7
• L4 Austenitic 316 SST
• L5 ANSI/ASTM A193-B7M
Meters
Analog
• Meters have 2-in. (50.8 mm) scale
• Plug-in mounting configuration
• Indication accuracy ±2%
• Operating temperature limit: –40 to 150 °F (–40 to 65 °C)
• Meters are enclosed in a housing certified by Factory Mutual
as Explosion-Proof for Class I, Division 1, Groups B, C, and D;
Class II, Division 1, Groups E, F, and G and Class III, Division
1
• For optional CSA explosion-proof approval, see certification
Option Code E6
• M1 Linear Analog Meter, 0–100% Scale
• M2 Square Root Analog Meter, 0–100% Flow Scale
• M3 Special Scaling Analog Meter (Specify Range)
• M6 Square Root Analog Meter, 0–
LCD
• 4-digit display
• Indication accuracy ±0.25% of calibrated span ±1 digit
• Display resolution at ±0.5% of calibrated span ±1 digit
• Operating temperature limit: –4 to 158 °F (–20 to 70 °C)
• Plug-in mounting configuration
• Meters are enclosed in a housing certified by FM as
Explosion-Proof for Class I, Division 1, Groups B, C, and D;
Class II, Division 1, Groups E, F, and G and Class III, Division 1
• For Optional CSA explosion-proof approval, see certification
Option Code E6
• Reverse output not available with LCD Display
• M4 Linear LCD Meter, 0 to 100%
• M7 Special Scale LCD Display
(Specify Range, Mode, and Engineering Units)
• M8 Square Root LCD Display, 0 to 100%
• M9 Square Root LCD Display, 0–10
NOTES
Meter Options are not available with Output Codes L or M, or
Option Codes V2 or V3. Meter Options M4, M7, M8, and M9 are
not available with Output Code G.
10√ Scale
√ Scale
Process Connections
D1 Side Drain/Vent-Top
• Drain/vent valve mounted in side of flange.
• Top position used to vent gas buildup in liquid process
applications with transmitter mounted vertically.
Pressure-22
• Plug of same material as requested flange inserted in end of
flange opposite adapter.
Page 23
Product Data Sheet
00813-0100-4360, Rev HA
Catalog 2008 - 2009
Rosemount 1151
D2 Side Drain/Vent-Bottom
• Drain/vent valve mounted in side of flange.
• Bottom position used to drain liquid buildup in gas process
applications with transmitter mounted vertically.
• Plug of same material as requested flange inserted in end of
flange opposite adapter.
D6 316 SST Low Side Flange (1151GP and 1151AP Only)
1
/2–14 NPT flange adapters
DF
• Options provide
rather than
1
/4–18 NPT Kynar™ Process Flange Insert
K1
1
/2–14 NPT Kynar Process Flange Insert
K2
• Options provide Kynar plastic process flange insert that
prevents process from coming in contact with the metal of the
flange. One process insert for the 1151GP and LT; two inserts
for the 1151DP.
• Process connections are from the side.
• Available with carbon steel and stainless steel process flanges
only.
• Pressure Maximum: 200 psi at 200 °F with Kynar impulse
piping; 300 psi at 200 °F with metal impulse piping.
S1 Assembled with One Remote Diaphragm Seal
S2 Assembled with Two Remote Diaphragm Seals
• Options provide for the assembly of one or two remote
diaphragm seals.
S4 Assembled with 1195 Integral Orifice
• Designed for highly accurate, small-bore flow measurement
of any clean gas, liquid, or vapor.
• Reduce the costs associated with traditional orifice plate
installations.
• Several configurations are available factory assembled to
Rosemount differential pressure transmitters.
• Wide orifice bore/flow range capability.
• Wide choice of process connections, including threaded,
socket weld, and ANSI flanges.
• Static pressure maximum limit is 3,000 psig.
• Wetted materials are available that comply with NACE MR
01-75(90).
• Available only with Ranges 2, 3, 4, and 5.
(1) Applicable only to orifice assemblies without piping.
1
/2–14 NPT process connection on flanges
1
/4–18 NPT
(1)
Wetted O-rings
• Standard: Viton®
• W2 Buna N
• W3 Ethylene-Propylene
•W4 Aflas
• W5 Copper O-ring for Vacuum Service (Nonwetted - 1151LT
only)
• W6 Spring-Loaded PTFE
•Contains a Hastelloy spring that is in contact with the
• W7 PTFE
®
process fluid. Consult factory if Hastelloy is unacceptable.
Procedures
Standard Configuration
Unless otherwise specified, transmitter will be shipped as
follows:
Ranges 3–82,000 psi
Range 94,500 psi
Range 07,500 psi
1151LT
Class 150 Flange450 psi
Class 300 Flange1,100 psi
P1 Hydrostatic Testing
• Each transmitter is hydrostatic tested according to Table 12.
• Test medium is water.
• This option provided for transmitters with remote diaphragm
seal on application only.
• Rosemount Procedure 1746 outlines the testing procedure.
P2 Cleaning for Special Service
• This option minimizes contaminants to the process system by
cleaning wetted surfaces with a suitable detergent.
• Rosemount Procedure 97412 outlines the cleaning procedure.
P3 Cleaning for <1 PPM Chlorine/Fluorine
Outputs
V1 Reverse Output
• This option permits reversing of pressure input so that
electrical output will increase as pressure input decreases.
• This option applies only to 1151GP and 1151LT. When this
option is selected, the process flange, adapter, drain/vent
valve, appropriate O-rings, and bolting are installed on low
side of transmitter. Not available for Ranges 9 and 0.
• Not available with 1151AP. Reverse output on 1151DP and
1151HP can be obtained by connecting high-pressure input to
low side of transmitter and vice versa.
• This option should not be ordered with smart transmitters
(Output Code S). The 1151 Smart transmitter can be
configured for reverse output through a HART-Compatible
Interface.
V2 1 ⍀ Test Resistor
•A 1 ⍀ precision resistor is mounted across the test terminals
to provide 4–20 mV output or a 10–50 mV output if 10–50 mA
output is used.
• This option cannot be used with any meter options or Option
Codes I5 or I6.
V3 5 ⍀ Test Resistor
•A 5 ⍀ precision resistor is mounted across test terminals to
provide 20–100 mV output or a 50–250 mV output if 10–50
mA output is used.
• This option cannot be used with any meter options or Option
Codes I5 or I6.
Pressure-24
Page 25
Product Data Sheet
00813-0100-4360, Rev HA
Catalog 2008 - 2009
Rosemount 1151
Pressure-25
Page 26
Rosemount 1151
Product Data Sheet
00813-0100-4360, Rev HA
Catalog 2008 - 2009
Standard Terms and Conditions of Sale can be found at www.rosemount.com\terms_of_sale
The Emerson logo is a trademark and service mark of Emerson Electric Co.
Rosemount, Annubar, ProPlate, and the Rosemount logotype are registered trademarks of Rosemount Inc.
HART is a registered trademark of the HART Communication Foundation. δ-Cell is a trademark of Rosemount Inc.
Fluorolube is a registered trademark of Hooker Chemical Co.
Viton is a registered trademark of E.I. du Pont de Nemours & Co.
Neobee M-20 is a registered trademark of Stepan Chemical Co.
Syltherm and D.C. are registered trademarks of Dow Corning Corp.
Aflas is a registered trademark of Asahi Glass Co., Ltd.
Kynar is a trademark of Pennwalt Inc..
Emerson Process Management
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN 55317 USA
T (U.S.) 1 800 999 9307
T (International) (952) 906 8888
F (952) 949 7001
www.rosemount.com