With over five million transmitters installed worldwide, the Rosemount 1151 continues to offer industry leading
value. Changing customer needs and new technologies have driven product improvements, while advanced
manufacturing and testing processes have guaranteed product quality. Even today, the Rosemount 1151 is
world-reowned for proven field reliability and longevity.
Proven field performance and reliability
For over 35 years, the 1151 has provided the process
control industry with unsurpassed service and
reliability in even the harshest of environments. The
lasting customer preference results from a
combination of advanced technology, and a tradition
of field proven performance.
Commitment to continuous improvement
Through ongoing focus on continuous improvement,
±0.075% reference accuracy has been accomplished
as a result of manufacturing and engineering
enhancements. In addition, Smart electronics offer
rangeability to 50:1, reducing the number of
transmitters to specify, procure, and carry in
inventory. A modular design allows interchangeable
mechanical and electrical components, providing
backward and forward compatibility.
Rosemount Pressure Solutions
Rosemount 3051S Series of Instrumentation
Scalable pressure, flow and level measurement solutions improve
installation and maintenance practices.
Rosemount 3095 Mass Flow Transmitter
Accurately measures differential pressure, static pressure and
process temperature to dynamically calculate fully compensated
mass flow.
Rosemount 305, 306 and 304 Manifolds
Factory-assembled, calibrated and seal-tested
transmitter-to-manifold assemblies reduce installation costs.
Rosemount 1199 Diaphragm Seals
Provides reliable, remote measurements of process pressure and
protects the transmitter from hot, corrosive, or viscous fluids.
Orifice Plate Primary Element Systems: Rosemount
1495 and 1595 Orifice Plates, 1496 Flange Unions and
1497 Meter Sections
A comprehensive offering of orifice plates, flange unions and
meter sections that are easy to specify and order. The 1595
Conditioning Orifice provides superior performance in tight fit
applications.
Application flexibility
The 1151 offers a variety of configurations for
differential, gage, absolute and liquid- level
measurements including integrated solutions for
pressure, level, and flow. High pressure models allow
static line pressures up to 4500 psi (310 bar).
Multiple wetted materials, as well as alternative fill
fluids ensure process compatibility. Smart, analog
and low-power electronics are available to meet
specific application requirements.
Annubar® Flowmeter Series: Rosemount 3051SFA
®
ProBar
The state-of-the-art, fifth generation Rosemount 485 Annubar
combined with the 3051S or 3095 MultiVariable transmitter creates
an accurate, repeatable and dependable insertion-type flowmeter.
Compact Orifice Flowmeter Series: Rosemount
3051SFC, 3095MFC, and 405
Compact Orifice Flowmeters can be installed between existing
flanges, up to a Class 600 (PN100) rating. In tight fit applications,
a conditioning orifice plate version is available, requiring only two
diameters of straight run upstream and two downstream.
ProPlate® Flowmeter Series: Rosemount 3051SFP
ProPlate, 3095MFP Mass ProPlate, and 1195
These integral orifice flowmeters eliminate the inaccuracies that
become more pronounced in small orifice line installations. The
completely assembled, ready to install flowmeters reduce cost and
simplify installation.
Ranges 3 through 8, DP and GP transmitters;
Ranges 4 through 7, HP transmitters
±0.075% of calibrated span for spans from 1:1 to 10:1 of URL.
Between 10:1 and 50:1 of URL.
All other ranges and transmitters
±0.25% of calibrated span
Output Code S, square root mode
Output Codes E, G, L, and M
±0.2% of calibrated span for 1151DP Ranges 3 through 5. All
other ranges and transmitters, ±0.25% of calibrated span.
Stability
Output Code S
±0.1% of URL for 2 years for DP and GP Ranges 3 through 8.
(±0.25% for all other ranges and transmitters.)
Output Codes E and G
±0.2% of URL for six months for Ranges 3 through 5. (±0.25
for all other ranges.)
Output Codes L and M
±0.25% of URL for six months
Temperature Effect
Output Code S [–20 to 185 °F (–29 to 85 °C)]
For DP and GP transmitter Range 4 through 8;
HP transmitter Range 4 through 7:
Zero Error = ±0.2% URL per 100 °F (56 °C)
Total Error = ±(0.2% URL + 0.18% of calibrated span)
per 100 °F; For Range 3, double the stated effects. For other
ranges and transmitters follow analog temperature
specifications (Output Code E).
Output Code E, G, L, and M
[–20 to 200 °F (–29 to 93 °C)]
For Ranges 4 through 0
Zero Error = ±0.5% URL per 100 °F.
Total Error = ±(0.5% URL + 0.5% of calibrated span) per 100
°F; double the effect for Range 3.
(1)
Static Pressure Effect – DP Transmitters
DP Transmitters
Zero Error
±0.25% of URL for 2,000 psi (13790 kPa)
for Range 4 and 5 or ±0.5% for other ranges, correctable
through rezeroing at line pressure.
Span Er ror
Correctable to ±0.25% of input reading per 1,000 psi
(6895 kPa), or to ±0.5% for Range 3.
HP Transmitters
Zero Error
±2.0% of URL for 4,500 psi (31027 kPa), correctable through
rezeroing at line pressure.
Span Er ror
Correctable to ±0.25% of input reading per 1,000 psi
(6895 kPa).
Vibration Effect
0.05% of URL per g to 200 Hz in any axis
Power Supply Effect
Output Codes S, E, and G
Less than 0.005% of output span per volt
Output Codes L, M
Output shift of less than 0.05% of URL for a 1 V power supply
shift
Load Effect
Output Codes S, E, and G
No load effect other than the change in power supplied to the
transmitter.
Output Codes L, M
Less than 0.05% of URL effect for a change in load from
100k⍀ to infinite ohms.
Short Circuit Condition (Low Power Only)
No damage to the transmitter will result when the output is shorted
to common or to power supply positive (limit 12 V).
EMI/RFI Effect
Output shift of less than 0.1% of span when tested to SAMA PMC
33.1 from 20 to 1000 MHz and for field strengths up to 30 V/m.
(1) Accuracy for Range 9, GP transmitter at 40:1 is ±0.7%
of calibrated span.
Pressure-3
Rosemount 1151
R
max
R
L
R
min
V
min
V
S
V
max
0
Operating
Region
Product Data Sheet
00813-0100-4360, Rev HA
Catalog 2008 - 2009
Mounting Position Effect
Zero shift of up to 1 inH2O (0.25 kPa).
With liquid level diaphragm in vertical plane, zero shift of up to 1
O (0.25 kPa). With liquid level diaphragm in horizontal plane,
inH
2
zero shift of up to 5 inH
extended units. All zero shifts can be calibrated out. No effect
on span.
O (1.25 kPa) plus extension length on
2
FUNCTIONAL SPECIFICATIONS
Service
Liquid, gas, and vapor applications
Ranges
See Table 2 for ranges. Minimum span equals the upper range
limit (URL) divided by rangedown. Rangedown varies with the
output code See Table 1.
Outputs
Code S, Smart
4–20 mA dc, user selectable for linear or square root output.
Digital process variable superimposed on 4–20 mA signal,
available to any host that conforms to the HART
Code E, Analog
4–20 mA dc, linear with process pressure
Code G, Analog
10–50 mA dc, linear with process pressure
Code L, Low Power
0.8 to 3.2 V dc, linear with process pressure
Code M, Low Power
1 to 5 V dc, linear with process pressure
Current Consumption Under Normal Operating
Conditions (Low Power Only)
Output Code L
1.5 mA dc
Output Code M
2.0 mA dc
®
protocol.
Span and Zero
Output Code S
Span and zero may be accessed with local adjustments or
remotely through a HART-compatible Interface.
Output Codes E, G, L, and M
Span and zero are continuously adjustable.
Power Supply
External power supply required. Transmitter operates according to
the following requirements:
Output Codes S, E
12 to 45 V dc with no load
Output Code G
30 to 85 V dc with no load
Output Code L
5 to 12 V dc
Output Code M
8 to 14 V dc
Where:
Code V
(1)
S
(2)
E
G308501100 R
L512Low Power Minimum Load
M814
(1) A minimum of 250 ohms is required for communication.
Zero elevation and suppression must be such that the lower
range value is greater than or equal to the (–URL) and the
upper range value is less than or equal to the (+URL). The
calibrated span must be greater than or equal to the minimum
span and less than or equal to the maximum span.
Output Code L
Zero is adjustable ±10% of URL and span is adjustable from
90 to 100% of URL.
Output Code M
Zero is adjustable ±50% of URL and span is adjustable from
50 to 100% of URL.
Pressure-4
Temperature Limits
Electronics Operating
Code S: –40 to 185 °F (–40 to 85 °C)
Code E: –40 to 200 °F (–40 to 93 °C)
Code G, L, M: –20 to 200 °F (–29 to 93 °C)
Sensing Element Operating
Silicone fill: –40 to 220 °F (–40 to 104 °C)
Inert fill: 0 to 160 °F (–18 to 71 °C)
Storage
Code S: –60 to 185 °F (–51 to 85 °C)
Codes E, G, L, M: –60 to 250 °F (–51 to 121 °C)
Product Data Sheet
00813-0100-4360, Rev HA
Catalog 2008 - 2009
TABLE 1. Rangeability
Output CodeMinimum SpanMaximum Span
S (DP and GP, SST, Range 3–8; HP SST, Range 4–7)URL/502 ⫻ URL
S (All Others)URL/50
E, GURL/6URL
LURL/1.1URL
MURL/2URL
(1) Transmitter is capable of measuring from –URL to URL.
(2) Accuracy specification for calibrated spans from 1:1 to 6:1 of URL only.
TABLE 2. Transmitter Range Availability by Model (URL = Upper Range Limit)
D.C.® 200 Silicone–40 to 400 °F (–40 to 205 °C)0.9340.00060 (0.00108)9.5
D.C. 704 Silicone60 to 400 °F (15 to 204 °C)1.070.00053 (0.00095)44
Inert Fill–50 to 350 °F (–45 to 177 °C)1.850.0004 (0.000864)6.5
Syltherm®XLT, Silicone–100 to 300 °F (–73 to 149 °C) 0.850.000666 (0.001199)1.6
Glycerin and Water
Propylene Glycol and Water
Neobee M-20
(1) Temperature limits are reduced in vacuum service. Contact an Emerson Process Management representative for assistance.
(2) Glycerin and Water and Propylene Glycol and Water are not suitable for vacuum service.
(3) Not compatible with Buna-N or Ethylene-Propylene O-ring material.
®(3)
(2)
0 to 200 °F (–17 to 93 °C)1.130.00019 (0.00034)12.5
(3)
0 to 200 °F (–17 to 93 °C)1.020.00019 (0.00034)2.85
0 to 400 °F (–17 to 205 °C)0.9000.00056 (0.001008)9.8
(1)
Specific Gravity
Coeff. of Therm. Exp.
cc/cc/°F (cc/cc/°C)
Viscosity at 25 °C
centistokes
Pressure-5
Rosemount 1151
Product Data Sheet
00813-0100-4360, Rev HA
Catalog 2008 - 2009
Static Pressure and Overpressure Limits
115 1DP
0 psia to 2,000 psig (0 to 13.79 MPa) on either side without
damage to transmitter. Operates within specifications from
static line pressures of 0.5 psia (3.45 kPa) to 2,000 psig
(13.79 MPa).
115 1HP
0 psia to 4,500 psig (0 to 31.02 MPa) on either side without
damage to transmitter. Operates within specifications from 0.5
psia (3.45 kPa) to 4,500 psig (31.02 MPa). Consult an
Emerson Process Management representative for higher
Static Pressure options up to 6000 psi.
115 1AP
0 psia to 2,000 psia (0 to 13.79 MPa) without damage to
transmitter. Operates within specifications from 0 psia to the
upper range limit of the transmitter.
115 1GP
0 psia to 2,000 psig (0 to 13.79 MPa) for ranges to 1,000 psig
(6.90 MPa), 4,500 psig (31.02 MPa) for the 3,000 psig (20.68
MPa) range, and 7,500 psig (51.71 MPa) for the 6,000 psig
(41.37 MPa) range, without damage to the transmitter.
Operates within specifications from 0.5 psia (3.45 kPa) to the
upper range limit of the transmitter.
115 1LT
TABLE 6. Flange Pressure Rating
StandardClass/RatingCarbon SteelStainless Steel
ANSI150285 psig
ANSI300740 psig
ANSI6001,480 psig
DINPN 10–4040 bar
DINPN 10/1616 bar
DINPN 25/4040 bar
(1) At 100 °F (38 °C); the rating decreases with increasing
temperature.
(2) At 248 °F (120 °C); the rating decreases with increasing
temperature.
(1)
(1)
(1)
(2)
(2)
(2)
1,440 psig
275 psig
720 psig
40 bar
16 bar
40 bar
(1)
(1)
(1)
(2)
(2)
(2)
Burst Pressure All Models
10,000 psig (68.95 MPa) proof pressure on the flanges.
Transmitter Security (Output Code S)
Activating the transmitter security function prevents changes to the
transmitter configuration, including local zero and span
adjustments. Security is activated by an internal switch.
Overpressure Saturation Value (Output Code S)
If the sensor detects a negative overpressure value, the analog
signal will be driven to 3.9 mA. If the sensor detects a positive
overpressure value, the analog signal is driven to 20.8 mA.
Damping
Numbers given are for silicone fill fluid at room temperature. The
minimum time constant is 0.2 seconds (0.4 seconds for Range 3).
Inert-filled sensor values would be slightly higher.
Output Code S
Time constant is adjustable in 0.1 second increments from
minimum to 16.0 seconds.
Output Codes E and G
Time constant continuously adjustable between minimum and
1.67 seconds.
Output Codes L, M
Damping is fixed at minimum time constant.
1151LT
Time constant continuously adjustable between 0.4 and 2.2
seconds with silicone oil fill, or 1.1 and 2.7 seconds with inert
fill for flush models and electronics codes E or G.
Turn-on Time
Maximum of 2.0 seconds with minimum damping. Low power
output is within 0.2% of steady state value within 200 ms after
application of power.
Physical Specifications,
Standard Configuration
Electrical Connections
1
/2–14 NPT conduit with screw terminals and integral test jacks
compatible with miniature banana plugs (Pomona 2944, 3690, or
equivalent). The HART Hand-Held Interface connections are fixed
to the terminal block on smart transmitters.
Humidity Limits
0 to 100% relative humidity
Volumetric Displacement
Less than 0.01 in3 (0.16 cm3)
Failure Mode Alarm (Output Code S)
If self-diagnosis detects a gross transmitter failure, the analog
signal will be driven below 3.9 mA or above 21 mA to alert the
user. High or low alarm signal is user selectable.
Level4–20 mA Saturation Value4–20 mA Alarm Value
Low3.9 mA3.75 mA
High20.8 mA21.75 mA
Pressure-6
Wetted Materials
Isolating Diaphragms
316L SST, Hastelloy C-276, or Tantalum. See ordering table
for availability per model type.
Drain/Vent Valves
316 SST or Hastelloy C-276, see ordering table for availability
per model type.
Process Flanges and Adapters
Plated carbon steel, 316 SST or Hastelloy C-276, see ordering
table for availability per model type.
Wetted O-rings
®
(other materials also available)
Viton
Product Data Sheet
00813-0100-4360, Rev HA
Catalog 2008 - 2009
Rosemount 1151
Non-wetted Materials
Fill Fluid
Silicone oil or inert fill
Nuts and Bolts
Plated carbon steel
Blank flange (GP and AP only)
Plated carbon steel
Electronics Housing
Low-copper aluminum. NEMA 4X
Cover O-rings
Buna-N
Paint
Polyurethane
Process Connections
Rosemount 1151DP, HP, GP, AP
1
/4–18 NPT on 2.125-in. (54-mm) centers on flanges for
Ranges 3, 4, and 5.
1
/4–18 NPT on 2.188-in. (56-mm) centers on flanges for
Ranges 6 and 7.
1
/4–18 NPT on 2.250-in. (57-mm) centers on flanges for
Range 8.
1
/2–14 NPT on adapters.
For Ranges 3, 4, and 5, flange adapters can be rotated to give
centers of 2.0 in. (51 mm), 2.125 in. (54 mm), or 2.250 in. (57
mm).
Rosemount 1151LT
High pressure side: 2-, 3-, or 4-in., Class 150, 300 or 600 flange;
50, 80, or 100 mm, PN 40 or 10/16 flange.
Low pressure side: 1/4–18 NPT on flange. 1/2–14 NPT on
adapter.
Weight
12 lb (5.4 kg) for AP, DP, GP, and HP transmitters, excluding
options. Meter option: Add 2 lb (1 kg)
TABLE 7. 1151LT Weight with Flange
(1)
Flange
2-in., Class 15018 (8.2)N/AN/AN/A
3-in., Class 15023 (10.4)25 (11.3)26 (11.8)27 (12.3)
4-in., Class 15029 (13.2)32 (14.5)34 (15.4)36 (16.3)
2-in., Class 30020 (9.1)N/AN/AN/A
3-in., Class 30028 (12.7)30 (13.6)31 (14.1)32 (14.5)
4-in., Class 30038 (17.2)41 (18.6)43 (19.5)45 (20.4)
2-in., Class 60022 (10.0)N/AN/AN/A
3-in., Class 60031 (14.1)33 (15.0)34 (15.4)35 (15.9)
DN 50, PN10-4020 (9.1)N/AN/AN/A
DN 80, PN 25/4025 (11.3)27 (12.3)28 (12.7)29 (13.2)
DN 100, PN 10/1625 (11.3)28 (12.7)30 (13.6)32 (14.5)
DN 100, PN 25/4029 (13.2)32 (14.5)34 (15.4)36 (16.3)
(1) Stainless steel flange weights are listed.
Flush
lb. (kg)
2-in (50mm) Ext.
lb. (kg)
4-in. (100mm) Ext.
lb. (kg)
6-in. (150mm) Ext.
lb. (kg)
Pressure-7
Rosemount 1151
Product Data Sheet
00813-0100-4360, Rev HA
Catalog 2008 - 2009
Product Certifications
Approved Manufacturing Locations
Rosemount Inc. — Chanhassen, Minnesota, USA
Emerson Process Management GmbH & Co. — Wessling,
Germany
Emerson Process Management Asia Pacific
Private Limited — Singapore
Beijing Rosemount Far East Instrument Co., Limited – Beijing,
China
European Directive Information
The EC declaration of conformity for all applicable European
directives for this product can be found on the Rosemount website
at www.rosemount.com. A hard copy may be obtained by
contacting our local sales office.
ATEX Directive (94/9/EC)
Emerson Process Management complies with the ATEX
Directive.
European Pressure Equipment Directive (PED) (97/23/EC)
All other 1151 Pressure Transmitters
— Sound Engineering Practice
Transmitter Attachments: Diaphragm Seal - Process Flange Manifold
— Sound Engineering Practice
Electro Magnetic Compatibility (EMC) (2004/108/EC)
All models
— EN 61326: 1997 with Amendments A1, A2, and A3
Hazardous Locations Certifications
North American Certifications
Ordinary Location Certification for Factory Mutual
As standard, the transmitter has been examined and tested
to determine that the design meets basic electrical,
mechanical, and fire protection requirements by FM, a
nationally recognized testing laboratory (NRTL) as
accredited by the Federal Occupational Safety and Health
Administration (OSHA).
Factory Mutual (FM) Approvals
FM Explosion-Proof tag is standard. Appropriate tag will be
substituted if optional certification is selected.
Explosion-Proof: Class I, Division 1, Groups B, C, and D.
Dust-Ignition Proof: Class II, Division 1, Groups E, F, and G;
Class III, Division 1. Indoor and outdoor use. NEMA 4X.
Factory Sealed.
I5Intrinsically safe for Class I, II, and III Division 1, Groups A,
B, C, D, E, F, and G hazardous locations in accordance with
entity requirements and Control drawing 01151-0214 and
00268-0031. Non- incendive for Class I, Division 2, Groups
A, B, C and D hazardous locations.
For entity parameters see control drawing 01151-0214.
Canadian Standards Association (CSA) Approvals
E6Explosion-Proof for Class I, Division 1, Groups C and D;
Class II, Division 1, Groups E, F, and G; Class III, Division 1
Hazardous Locations. Suitable for Class I, Division 2, Groups
A, B, C, and D; CSA enclosure type 4X. Factory Sealed.
I6Intrinsically safe for Class I, Division 1, Groups A, B, C, and
D hazardous locations when connected per Drawing
01151-2575. For entity parameters see control drawing
01151-2575. Temperature Code T2D.
Pressure-8
European Certifications
I1 ATEX Intrinsically Safe and Combustible Dust
(1151 Smart only)
Certificate No.: BAS99ATEX1294X
ATEX Marking II 1 GD
EEx ia IIC T5 (-60°C ≤
EEx ia IIC T4 (-60°C ≤
118 0
IP66
TABLE 8. IS Entity Parameters
Ui = 30 V
Ii = 125 mA
Pi = 1.0 W (T4) or 0.67 W (T5)
Ci = 0.034 μF
Li = 20 µH
Special Conditions for Safe Use (X)
The apparatus, is not capable of withstanding the 500V test
as required by EN 50020: 1994. This must be taken into
account when installing the apparatus.
Ta ≤ 40°C)
Ta ≤ 80°C)