Your instrument purchase from Emerson is one of the finest available for your particular application.
These instruments have been designed and tested to meet many national and international standards.
Experience indicates that its performance is directly related to the quality of the installation and
knowledge of the user in operating and maintaining the instrument. To ensure its continued operation
to the design specifications, personnel should read this Quick Start Guide thoroughly before
proceeding with installation, commissioning, operation, and maintenance of this instrument. If this
equipment is used in a manner not specified by the manufacturer, the protection provided by it against
hazards may be impaired.
WARNING
Precautionary signs
Failure to observe precautionary signs may result in injury or death to personnel or cause damage to
equipment.
Follow all warnings, cautions, and instructions marked on or supplied with the product.
WARNING
Follow installation guidelines.
Failure to follow these installation guidelines could result in death or serious injury. If this equipment is
used in a manner not specified by the manufacturer, the protection it provides against hazards may be
impaired.
Install equipment as specified in this document.
Ensure that only qualified personnel perform the installation.
Inform and educate your personnel in the proper installation, operation, and maintenance of the
product.
Follow appropriate local and national codes.
If you do not understand any of the instructions, contact your Emerson representative for
clarification.
WARNING
Electrical shock
Installation and servicing of this product may expose personnel to dangerous voltages.
Electrical installation must be in accordance with the National Electrical Code (ANSI/National Fire
Protection Agency-70) and/or any other national or local codes.
The equipment is protected throughout by double insulation.
Disconnect main power, wired to separate power source, before servicing.
Ensure that all equipment doors are closed and protective covers are in place, except when
maintenance is being performed by qualified personnel.
Signal wiring must be rated at least 240 V.
Non-metallic cable strain reliefs do not provide grounding between conduit connections. Use
grounding type bushings and jumper wires.
Make sure that the instrument is connected and properly grounded through a three-wire power
source.
Proper use and configuration is the operator's responsibility.
2Emerson.com/Rosemount
February 2022Quick Start Guide
WARNING
Physical Access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end
users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your
system. Restrict physical access by unauthorized personnel to protect end users' assets. This is true for
all systems used within the facility.
NOTICE
Ensure that you have received the correct model and options from your purchase order. Verify that this
Quick Start Guide covers your model and options. If it does not, call the Emerson Customer Care
Center at +1 800 999 9307 to request the correct Quick Start Guide.
NOTICE
Use only factory documented components for repair. Tampering or unauthorized substitution of parts
and procedures can affect the performance and cause unsafe operation of your process.
NOTICE
This product generates, uses, and can radiate radio frequency energy, and this can cause radio
communication interference.
As temporarily permitted by regulation, this device has been tested for compliance within the limits of
Class A computing devices, pursuant to subpart J of part 15 of Federal Communication Commission
(FCC) rules, which are designed to take whatever measures may be required to correct the
interference.
Contents
First steps.....................................................................................................................................5
EU Declaration of Conformity.....................................................................................................43
China RoHS Table....................................................................................................................... 45
Quick Start Guide 3
Quick Start Guide February 2022
4Emerson.com/Rosemount
February 2022Quick Start Guide
1First steps
1.1Unpack and inspect
Procedure
1. Inspect the shipping container. If it is damaged, contact the shipper
immediately for instructions.
2. If there is no apparent damage, unpack the container. Be sure all
items shown on the packing list are present. If items are missing,
notify Emerson immediately.
1.2Mounting
Note
Dimensions in the following drawings show millimeters above inches.
Figure 1-1: Panel mount front
Quick Start Guide 5
Quick Start Guide February 2022
Figure 1-2: Panel mount side
A. Panel mount gasket
B. Four mounting brackets and screws provided with transmitter
C. Panel supplied by others: maximum thickness 0.375 in (9.52 mm)
6Emerson.com/Rosemount
February 2022Quick Start Guide
Figure 1-3: Panel mount bottom
A. Six conduit openings
Quick Start Guide 7
Quick Start Guide February 2022
Figure 1-4: Panel mount cut-out
A. Maximum radius
Note
Panel mounting seal integrity (4/4X) for outdoor applications is the end
user's responsibility.
8Emerson.com/Rosemount
February 2022Quick Start Guide
Figure 1-5: Wall mount front
A. Four cover screws
Quick Start Guide 9
Quick Start Guide February 2022
Figure 1-6: Wall mount side
10Emerson.com/Rosemount
February 2022Quick Start Guide
Figure 1-7: Pipe mount bottom
A. Front panel
B. Panel and pipe mount enclosure
C. Conduit openings
D. 2 in (51 mm) pipe mount bracket
Quick Start Guide 11
Quick Start Guide February 2022
2Installation
2.1General installation information
WARNING
Electrical shock
Installation and servicing of this product may expose personnel to
dangerous voltages.
Electrical installation must be in accordance with the National Electrical
Code (ANSI/National Fire Protection Agency-70) and/or any other
national or local codes.
The equipment is protected throughout by double insulation.
Disconnect main power, wired to separate power source, before
servicing.
Ensure that all equipment doors are closed and protective covers are in
place, except when maintenance is being performed by qualified
personnel.
Signal wiring must be rated at least 240 V.
Non-metallic cable strain reliefs do not provide grounding between
conduit connections. Use grounding type bushings and jumper wires.
Make sure that the instrument is connected and properly grounded
through a three-wire power source.
Proper use and configuration is the operator's responsibility.
1. Install the transmitter with a sun shield or out of direct sunlight and
areas with extreme temperatures.
2. Install the system in an area where vibrations and electromagnetic
and radio frequency interference are minimized or absent.
3. Keep the transmitter and sensor wiring at least 1 ft (0.30 m) from
high voltage conductors. Be sure there is easy access to the
transmitter and sample conditioning system.
4. The transmitter is suitable for panel, pipe, or surface mounting.
12Emerson.com/Rosemount
February 2022Quick Start Guide
3Wiring
3.1General wiring information
The transmitter includes removable connectors and slide-out signal input
boards.The front panel is hinged at the bottom. The panel swings down for
easy access to the wiring locations.
3.1.1Removable connectors and signal input boards
The transmitter uses removable signal input boards and communication
boards to facilitate wiring and installation.
You can remove each of the signal boards either partially or completely from
the enclosure for wiring. The transmitter has three slots for placement of up
to two signal input boards and one communication board.
Slot 1 - leftSlot 2 - centerSlot 3 - right
Communication boardInput board 1Input board 2
3.1.2Wire the signal input boards
Slots 2 and 3 are for signal input measurement boards.
Procedure
1. Wire the sensor leads to the measurement board following the lead
locations marked on the board.
2. Carefully slide the wired board fully into the enclosure slot and take
up the excess sensor cable through the cable gland.
3. Tighten the cable gland nut to secure the cable and ensure a sealed
enclosure.
3.1.3Digital communication boards
HART® and Profibus® DP communication boards will be available in the
future as options for Rosemount 1056 digital communication with a host.
The HART board supports Bell 202 digital communication over an analog
4-20 mA current output. Profibus DP is an open communication protocol
that operates over a dedicated digital line to the host.
3.1.4Alarm relays
Emerson supplies four alarm relays with the switching power supply (85 to
264 Vac, 03 order code) and the 24 Vdc power supply (20 - 30 Vdc, 02 order
code). You can use all relays for process measurement(s) or temperature.
You can also configure any relay as a fault alarm instead of a process alarm.
Quick Start Guide 13
Quick Start Guide February 2022
In addition, you may configure any relay independently and program it to
activate pumps or control valves.
All process alarms, alarm logic (high or low activation or USP*), and
deadband are user-programmable. Customer-defined failsafe operation is
supported as a programmable menu function to allow all relays to be
energized or not energized as a default condition upon powering the
transmitter. You may program the USP* alarm to activate when the
conductivity is within a user-selectable percentage of the limit. USP*
alarming is available only when a contacting conductivity measurement
board is installed.
3.2Preparing conduit openings
There are six conduit openings in all configurations of the transmitter.
Note
Emerson fits four of the openings with plugs upon shipment.
14Emerson.com/Rosemount
February 2022Quick Start Guide
Figure 3-1: Conduit openings
A. Front panel/keypad
B. Power leads
C. Alarm relay leads
D. Sensor 1 cable
E. 4-20 mA/HART®/Profibus® leads
F. Sensor 2 cable
G. Spare opening
NOTICE
Always use proper cable gland fittings and plugs for wire and cable
installations.
Conduit openings accept 0.5 in (13 mm) conduit fittings or PG13.5 cable
glands. To keep the case watertight, block unused openings with Type 4X or
IP66 conduit plugs.
Quick Start Guide 15
Quick Start Guide February 2022
NOTICE
Use watertight fittings and hubs that comply with your requirements.
Connect the conduit hub to the conduit before attaching the fitting to the
transmitter.
3.3Preparing sensor cable
The Rosemount 1056 is intended for use with all Rosemount sensors. Refer
to the sensor Quick Start Guide for details on preparing sensor cables.
3.4Power, output, and sensor connections
3.4.1Power wiring
Emerson offers three power supplies for the Rosemount 1056.
1. 115/230 Vac power supply (01 ordering code)
2. 24 Vdc (20-30 V) power supply (02 ordering code)
3. 85-265 Vac switching power supply (03 ordering code)
AC mains (115 or 230 V) leads and 24 Vdc leads are wired to the power
supply board, which is mounted vertically on the left side of the main
enclosure cavity. Each lead location is marked clearly on the power supply
board. Wire the power leads to the power supply board using the lead
markings on the board.
The grounding plate is connected to the earth terminal of power supply
input connector TB1 on the 01 (115/230 Vac) and 03 (85-265 Vac) power
supplies. The green screws on the grounding plate are intended for
connection to some sensors to minimize radio frequency interference. The
green screws are not intended to be used for safety purposes.
16Emerson.com/Rosemount
February 2022Quick Start Guide
Figure 3-2: 115/230 Vac power supply (01 ordering code)
NOTICE
The AC power switch is shipped in the 230 Vac position. Adjust the switch
upwards to the 115 Vac position for 110 Vac to 120 Vac operation.
Figure 3-3: 24 Vdc power supply (02 ordering code)
This power supply automatically detects DC power and accepts 20 Vdc to 30
Vdc inputs.
Four programmable alarm relays are included.
Quick Start Guide 17
Quick Start Guide February 2022
Figure 3-4: Switching AC power supply (03 ordering code)
This power supply automatically detects AC line conditions and switches to
the proper line voltage and line frequency.
Four programmable relays are included.
3.4.2Current output wiring
Emerson ships all instruments with two 4-20 mA current outputs. Wiring
locations for the outputs are on the main board, which is mounted on the
hinged door of the transmitter. Wire the relay leads on each of the
independent relays to the correct position on the main board using the lead
markings (+/positive, -/negative) on the board. Emerson provides male
mating connectors with each unit.
NOTICE
Twisted pairs are required to minimize noise pickup in the flow and current
sensor inputs. For high electromagnetic interference/radio frequency
interference (EMI/RFI) environments, use shielded sensor wire. We also
recommend using shielded sensor wire in other installations.
18Emerson.com/Rosemount
February 2022Quick Start Guide
Figure 3-5: Current output wiring
3.4.3Alarm relay wiring
Emerson supplies four alarm relays with the switching power supply (85 to
265 Vac, 03 order code) and the 24 Vdc power supply (20-30 Vdc, 02 order
code).
Wire the relay leads on each of the independent relays to the correct
position on the power supply board using the printed lead markings (NO/
Normally open, NC/Normally closed, or Com/Common) on the board. See
Figure 3-6.
Quick Start Guide 19
Quick Start Guide February 2022
Figure 3-6: Alarm relay wiring for Rosemount 1056 switching power
supply (03 ordering code)
Table 3-1: Relays
NO1 (normally open 1)
Relay 1COM1
NC1 (normally closed 1)
NO2 (normally open 2)
Relay 2COM2
NC2 (normally closed 2)
NO3 (normally open 3)
Relay 3COM3
NC3 (normally closed 3)
NO4 (normally open 4)
Relay 4COM4
NC4 (normally closed 4)
3.4.4Wire sensor to signal boards
Procedure
1. Wire the correct sensor leads to the main board using the lead
locations marked directly on the board.
2. Carefully slide the wired board fully into the enclosure slot and take
up the excess sensor cable through the cable gland.
20Emerson.com/Rosemount
February 2022Quick Start Guide
For best electromagnetic interference (EMI) and radio frequency
interference (RFI) protection, use shielded output signal cable
enclosed in an earth-grounded metal conduit. AC wiring should be
14 gauge or greater.
3. Provide a switch or breaker to disconnect the transmitter from the
main power supply. Install the switch or breaker near the transmitter
and label it as the disconnecting device for the transmitter.
WARNING
Electrical shock
Installation and servicing of this product may expose personnel to
dangerous voltages.
Electrical installation must be in accordance with the National
Electrical Code (ANSI/National Fire Protection Agency-70) and/or
any other national or local codes.
The equipment is protected throughout by double insulation.
Disconnect main power, wired to separate power source, before
servicing.
Ensure that all equipment doors are closed and protective covers
are in place, except when maintenance is being performed by
qualified personnel.
Signal wiring must be rated at least 240 V.
Non-metallic cable strain reliefs do not provide grounding
between conduit connections. Use grounding type bushings and
jumper wires.
Make sure that the instrument is connected and properly
grounded through a three-wire power source.
Proper use and configuration is the operator's responsibility.
Keep sensor and output signal wiring separate from loop power
wiring. Do not run sensor and power wiring in the same conduit or
close together in a cable tray.
NOTICE
Twisted pairs are required to minimize noise pickup in the flow and
current sensor inputs. For high electromagnetic interference/radio
frequency interference (EMI/RFI) environments, use shielded sensor
wire. We also recommend using shielded sensor wire in other
installations.
Quick Start Guide 21
Quick Start Guide February 2022
Figure 3-7: Contacting conductivity signal board and sensor cable leads
Figure 3-8: Toroidal conductivity signal board and sensor cable leads
22Emerson.com/Rosemount
February 2022Quick Start Guide
Figure 3-9: pH/ORP/ISE signal board and sensor cable leads
Figure 3-10: Chlorine, dissolved oxygen, and ozone signal boards and
sensor cable leads
Quick Start Guide 23
Quick Start Guide February 2022
Figure 3-11: Turbidity signal board with plug-in sensor connection
24Emerson.com/Rosemount
February 2022Quick Start Guide
Figure 3-12: Flow/current input signal board and sensor cable leads
Quick Start Guide 25
Quick Start Guide February 2022
Figure 3-13: Power wiring for the Rosemount 1056 115/230 Vac power
supply (01 order code)
A. To main board
B. Earth ground
C. Neutral
D. Line
26Emerson.com/Rosemount
February 2022Quick Start Guide
Figure 3-14: Power wiring for the Rosemount 1056 85-265 Vac power
supply (03 ordering code)
A. To main board
B. Earth ground
C. Neutral
D. Line
Quick Start Guide 27
Quick Start Guide February 2022
Figure 3-15: Output wiring for Rosemount 1056 main PCB
A. To power supply PCB
B. Analog output 1
C. Analog output 2
D. To digital input/output PCB
E. To sensor 1 PCB
F. To sensor 2 PCB
28Emerson.com/Rosemount
February 2022Quick Start Guide
Figure 3-16: Power wiring for Rosemount 1056 24 Vdc power supply (02
ordering code)
A. To main board
Quick Start Guide 29
Quick Start Guide February 2022
4Navigating the display
4.1User interface
The Rosemount 1056 has a large display which shows two live measurement
readouts in large digits and up to four additional process variables or
diagnostic parameters concurrently. The display is back-lit, and you can
customize the format to meet your requirements.
Press MENU to access calibration, hold (of current outputs), programming,
and display functions. In addition, a dedicated DIAGNOSTIC button is
available to provide access to useful operational information on installed
sensor(s) and any problematic conditions that might occur. The display
flashes Fault and/or Warning when these conditions occur. The transmitter
displays Help screens for most fault and warning conditions to guide you in
troubleshooting. During calibration and programming, key presses cause
different displays to appear. The displays are self-explanatory and guide you
step-by-step through the procedure.
4.2Keypad
Press MENU to access menus for programming and calibrating the
transmitter. There are four function keys and four selection keys on the
keypad.
Function keys
Four top-level menu items appear when you press MENU.
• Calibrate: Calibrate the attached sensor(s) and analog output(s).
• Hold: Suspend analog output(s).
• Program: Program outputs, measurement, temperature, security, and
reset.
30Emerson.com/Rosemount
February 2022Quick Start Guide
• Display: Program display format, language, warnings, and contrast.
Press MENU to display the main menu screen. Press MENU followed by EXIT
to display the main display.
Press DIAG to display active Faults and Warnings and detailed transmitter
information and sensor diagnostics, including: faults, warnings, Sensor 1 and
2 information, Out 1 and Out 2 live current values, transmitter software
version, and AC frequency used.
Press ENTER on Sensor 1 or Sensor 2 to display useful diagnostics and
information (as applicable): measurement, sensor type, raw signal value, cell
constant, zero offset, temperature, temperature offset, selected
measurement range, cable resistance, temperature sensor resistance, and
signal board software version.
Press ENTER to store numbers and settings and move the display to the next
screen.
Press EXIT to return to the previous screen without storing changes.
Selection keys
Surrounding the ENTER key, four selection keys (Up, Down, Right, and Left)
move the cursor to all areas of the screen while using the menus.
Selection keys are used to:
1. Select items on the menu screens.
2. Scroll up and down the menu lists.
3. Enter or edit numeric values.
4. Move the cursor to the right or left.
5. Select measurement units during operation.
4.3
Quick Start Guide 31
Main display
The Rosemount 1056 displays one or two primary measurement values, up
to four secondary measurement values, a fault and warning banner, alarm
relay flags, and a digital communications icon.
Process measurements
Two process variables are displayed if two signal boards are installed. One
process variable and process temperature are displayed if one signal board is
installed with one sensor. The upper display area shows the Sensor 1 process
reading. The center display area shows the Sensor 2 process reading. For
dual conductivity, you can assign the upper and center display areas to
different process variables as follows:
Quick Start Guide February 2022
Process variables for upper displayProcess variables for center display
Measure 1Measure 1
% RejectMeasure 2
% Pass% Reject
Ratio% Pass
Ratio
Blank
For single input configurations, the upper display area shows the live process
variable, and you can assign the center display area to Temperature or blank.
Secondary values
Up to four secondary values are shown in display quadrants at the bottom
half of the screen. You can program all four secondary value positions to any
displayable parameter available.
Possible secondary values include:
• Slope 1
• Reference off 1
• GI impedance 1
• Reference impedance 1
• Raw
• mV input
• Temperature 1
• Manual temperature 1
• Manual temperature 2
• Output 1 mA
• Output 2 mA
• Output 1%
• Output 2%
• Measure 1
• Blank
Fault and warning banner
If the transmitter detects a problem with itself or the sensor, the word Fault
or Warning will appear at the bottom of the display. A fault requires
32Emerson.com/Rosemount
February 2022Quick Start Guide
immediate attention. A warning indicates a problematic condition or an
impending failure. For troubleshooting assistance, press DIAG.
Formatting the main display
You can program the main display screen to show primary process variables,
secondary process variables, and diagnostics.
1. Press MENU.
2. Scroll down to Display. Press ENTER.
3. Main Format is highlighted. Press ENTER.
4. The Sensor 1 process value is highlighted in reverse video. Press the
selection keys to navigate down to the screen sections that you wish
to program. Press ENTER.
5. Choose the desired display parameter or diagnostic for each of the
four display sections in the lower screen.
6. Continue to navigate and program all desired screen selections. Press
MENU and EXIT. The screen returns to the main display.
For single sensor configurations, the default display shows the live process
measurement in the upper display area and temperature in the center
display area. You can elect to disable the display of temperature in the
center display area using the Main Format function. For dual sensor
configurations, the default display shows Sensor 1 live process
measurement in the upper display area and Sensor 2 live process
measurement in the center display area.
Quick Start Guide 33
Quick Start Guide February 2022
Figure 4-1: Formatting the main display
4.4Menu system
The transmitter uses a scroll and select menu system. Press MENU at any
time to open the top-level menu, including Calibrate, Hold, Program, and
Display functions.
To find a menu item, scroll with the Up and Down keys until the item is
highlighted. Continue to scroll and select menu items until the desired
function is chosen. To select the menu item, press ENTER. To return to a
previous menu level or to enable the main live display, press EXIT
repeatedly. To return immediately to the main display from any menu level,
press MENU and then EXIT.
The selection keys have the following functions:
• The Up key (above ENTER) increments numerical values, moves the
decimal point one place to the right, or selects units of measurement.
• The Down key (below ENTER) decrements numerical values, moves the
decimal point one place to the left, or selects units of measurement.
• The Left key (left of ENTER) moves the cursor to the left.
• The Right key (right of ENTER) moves the cursor to the right.
During all menu displays (except main display format and Quick Start), the
live process measurements and secondary measurement values are
34Emerson.com/Rosemount
February 2022Quick Start Guide
displayed in the top two lines of the upper display area. This conveniently
allows display of the live values during important calibration and
programming operations.
Menu screens time out after two minutes and return to the main display.
Quick Start Guide 35
Quick Start Guide February 2022
5Start up the transmitter
Procedure
1. Wire sensor(s) to the signal boards.
Refer to the sensor Quick Start Guide for additional details. Make
current output, alarm relay, and power connections.
2. Once connections are secured and verified, apply power to the
transmitter.
WARNING
Electrical shock
Installation and servicing of this product may expose personnel to
dangerous voltages.
Electrical installation must be in accordance with the National
Electrical Code (ANSI/National Fire Protection Agency-70) and/or
any other national or local codes.
The equipment is protected throughout by double insulation.
Disconnect main power, wired to separate power source, before
servicing.
Ensure that all equipment doors are closed and protective covers
are in place, except when maintenance is being performed by
qualified personnel.
Signal wiring must be rated at least 240 V.
Non-metallic cable strain reliefs do not provide grounding
between conduit connections. Use grounding type bushings and
jumper wires.
Make sure that the instrument is connected and properly
grounded through a three-wire power source.
Proper use and configuration is the operator's responsibility.
When the transmitter is powered up for the first time, Quick Start
screens appear. Quick Start operating tips are as follows:
a. A back-lit field shows the position of the cursor.
b. To move the cursor left or right, use the keys to the left or
right of the ENTER key. To scroll up or down or to increase or
decrease the value of a digit, use the keys above and below
the ENTER key. Use the Left or Right keys to move the
decimal point.
36Emerson.com/Rosemount
February 2022Quick Start Guide
c. Press ENTER to store a setting. Press EXIT to leave without
storing changes. Press EXIT during Quick Start to return the
display to the initial startup screen (Select language).
3. Complete the steps as shown in the Figure 5-1.
Figure 5-1: Quick start flow diagram
Quick Start Guide 37
Quick Start Guide February 2022
After the last step, the main display appears. The outputs are
assigned to default values.
4. To change output and temperature-related settings, go to the MainMenu and choose Program. Follow the prompts.
Figure 5-2: Rosemount 1056 menu tree
5. To return the transmitter to the factory default settings, go to
Program→Reset.
Call the Emerson Customer Support Center at +1-800-999-9307 if
you need further support.
38Emerson.com/Rosemount
February 2022Quick Start Guide
6Approvals
Pollution degree
Installation
category
Altitude
Humidity
2
II
6,561.7 ft (2,000 m)
80 percent to temperatures up to 88 °F (31 °C)
decreasing linearly to 50 percent relative humidity
at 104 °F (40 °C). Maximum 80 percent relative
humidity, non-condensing.
Quick Start Guide 39
Quick Start Guide February 2022
7Product certifications
Rev 1.4
7.1European Directive information
A copy of the EU Declaration of Conformity can be found at the end of this
guide. The most recent revision of the EU Declaration of Conformity can be
found at Emerson.com/Rosemount.
7.2Ordinary location certification
As standard, the transmitter has been examined and tested to determine
that the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health Administration (OSHA).
7.3Installing equipment in North America
The US National Electrical Code® (NEC) and the Canadian Electrical Code
(CEC) permit the use of Division marked equipment in Zones and Zone
marked equipment in Divisions. The markings must be suitable for the area
classification, gas, and temperature class. This information is clearly defined
in the respective codes.
40Emerson.com/Rosemount
February 2022Quick Start Guide
7.4USA
7.4.1USA hazardous locations
Certificate
Standards
Markings
Special Conditions for Safe Use (X):
1. For use with sensors in accordance with drawing 1700463.
2. Sensors having exposed electrodes in the process shall be used in a
non-flammable liquid process only.
3. The panel mount gasket has been tested for Type 4X installation.
Type 4X refers to the enclosure only.
4. Turbidity sensors shall be used in a non-flammable liquid process
only.
FM16US0180X
FM Class 3600: 2011
FM Class 3611: 2004
FM Class 3810: 2005
ANSI/NEMA 250: 2003
Nonincendive for use in Class I, II, and III, Division 2,
Groups A, B, C, D, E, F and G; temperature class T4A
Tamb = -20 °C to +50 °C; hazardous (classified)
locations; enclosure Type 4X
Nonincendive for use in Class I, II, and III, Division 2,
Groups A, B, C, D, E, F and G; temperature class T4A
Tamb = -20 °C to +50 °C; when installed per control
Drawing 1400324; hazardous (classified) locations;
enclosure Type 4X
7.4.2USA hazardous locations
Certificate
Standards
Markings
Quick Start Guide 41
70173522
CSA Standard C22.2 No. 25-1966, CSA Standard C22.2
No.94.4:20, CSA Standard C22.2 No. 213-M1987, CAN/
CSA-C22.2 No. 61010-1-12 AMD 1 CSA Standard C22.2
No. 60529:05 (Reaffirmed 2015), ANSI/IEC 60529-2004
(Reaffirmed 2011), ANSI/ISA 12.12.01:2007, UL
Standard 50E, 3rd edition, UL 61010-1, 3rd edition
Class I, Division 2, Groups A, B, C, and D;
Class II, Division 2, Groups E, F, and G;
Class III
Maximum ambient 55 °C; temperature code T4A;
enclosure Type 4X; IP66
Quick Start Guide February 2022
7.4.3USA ordinary locations
Certificate
Standards
Markings
20170327-E207618
UL 61010-1, CAN/CSA-C22.2 No. 61010-1
Ordinary locations
7.5Canada
7.5.1Canada hazardous locations
Certificate
Standards
Markings
70173522
CSA Standard C22.2 No. 25-1966, CSA Standard C22.2
No.94.4:20, CSA Standard C22.2 No. 213-M1987, CAN/
CSA-C22.2 No. 61010-1-12 AMD 1 CSA Standard C22.2
No. 60529:05 (Reaffirmed 2015), ANSI/IEC 60529-2004
(Reaffirmed 2011), ANSI/ISA 12.12.01:2007, UL
Standard 50E, 3rd edition, UL 61010-1, 3rd edition
Class I, Division 2, Groups A, B, C, and D;
Class II, Division 2, Groups E, F, and G;
Class III
Maximum ambient 55 °C; temperature code T4A;
Emerson Terms and Conditions of Sale are
available upon request. The Emerson logo
is a trademark and service mark of
Emerson Electric Co. Rosemount is a mark
of one of the Emerson family of
companies. All other marks are the
property of their respective owners.
Emerson.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.