Rosemount 1054A Conductivity Microprocessor Analyzer Manuals & Guides

Model 1054A C
Conductivity Microprocessor Analyzer
Instruction Manual
P/N 5101054AC
October 1996
WARNING
Making cable connections to and serv­icing this instrument require access to shock hazard level voltages which can cause death or serious injury.
Relay contacts made to separate power sources must be disconnected before servicing.
Electrical installation must be in accordance with the National Electrical Code (ANSI/NFPA-70) and/or any other applicable national or local codes.
Unused cable conduit entries must be securely sealed by non-flammable closures to provide enclosure integrity in compliance with personal safety and environmental protection require­ments.
For safety and proper performance this instrument must be connected to a properly grounded three-wire power source.
Proper relay use and configuration is the responsibility of the user.
Do not operate this instrument without front cover secured. Refer installation, operation and servicing to qualified personnel.
SS-MA54
Feb. 1992
ESSENTIAL INSTRUCTIONS
READ THIS P
AGE BEFORE PROCEEDING!
Rosemount Analytical designs, manufactures, and tests its products to meet many national and international stan­dards. Because these instruments are sophisticated tech­nical products, you must properly install, use, and main­tain them to ensure they continue to operate within their normal specifications. The following instructions must be adhered to and integrated into your safety program when installing, using, and maintaining Rosemount Analytical products. Failure to follow the proper instructions may cause any one of the following situations to occur: Loss of life; personal injury; property damage; damage to this instrument; and warranty invalidation.
• Read all instructions prior to installing, operating, and servicing the product. If this Instruction Manual is not the correct manual, telephone 1-800-654-7768 and the requested manual will be provided. Save this Instruction Manual for future reference.
• If you do not understand any of the instructions, contact your Rosemount representative for clarification.
• Follow all warnings, cautions, and instructions marked on and supplied with the product.
• Inform and educate your personnel in the proper instal­lation, operation, and maintenance of the product.
• Install your equipment as specified in the Installation Instructions of the appropriate Instruction Manual and per applicable local and national codes. Connect all products to the proper electrical and pressure sources.
• To ensure proper performance, use qualified personnel to install, operate, update, program, and maintain the product.
• When replacement parts are required, ensure that qual­ified people use replacement parts specified by Rosemount. Unauthorized parts and procedures can affect the product’s performance and place the safe operation of your process at risk. Look alike substitu­tions may result in fire, electrical hazards, or improper operation.
• Ensure that all equipment doors are closed and protec­tive covers are in place, except when maintenance is being performed by qualified persons, to prevent elec­trical shock and personal injury.
Rosemount Analytical Inc. Uniloc Division
2400 Barranca Parkway Irvine, CA 92714 USA Tel: (714) 863-1181
MODEL 1054A C TABLE OF CONTENTS
MODEL 1054A CONDUCTIVITY
MICROPROCESSOR ANALYZER
TABLE OF CONTENTS
Section Title Page
1.0 DESCRIPTION AND SPECIFICATIONS............................................................. 1
1.1 Features and Applications ................................................................................ 1
1.2 Physical Specifications - General...................................................................... 2
1.3 Analyzer Specifications..................................................................................... 2
1.4 Recommended Sensors.................................................................................... 2
1.5 Ordering Information......................................................................................... 3
2.0 INSTALLATION .................................................................................................. 5
2.1 General.............................................................................................................. 5
2.2 Unpacking and Inspection................................................................................ 5
2.3 Mechanical Installations.................................................................................... 5
2.3.1 Panel Mounting.................................................................................................. 5
2.3.2 Wall Mounting Plate with Junction Box.............................................................. 5
2.3.3 Pipe Mounting ................................................................................................... 5
2.3.4 Wall Mount Enclosure........................................................................................ 6
2.4 Electrical Wiring................................................................................................. 6
2.4.1 Power Input Wiring............................................................................................ 6
2.4.2 Output Wiring .................................................................................................... 6
2.4.3 Wall Mount Enclosure Wiring............................................................................. 6
3.0 DESCRIPTION OF CONTROLS......................................................................... 15
3.1 Keyboard Functions.......................................................................................... 15
4.0 CONFIGURATION ............................................................................................. 19
4.2 Alarm 1 and 2 ................................................................................................... 22
4.3 Interval Timer .................................................................................................... 24
4.4 Temperature ..................................................................................................... 26
4.5 Current Output .................................................................................................. 28
4.6 Defaults ............................................................................................................. 30
4.7 Alarm Setpoint................................................................................................... 32
4.8 Output Scale Expansion.................................................................................... 33
4.9 Simulate Output................................................................................................. 34
5.0 START-UP AND CALIBRATION.......................................................................... 35
5.1 Start-Up and Calibration.................................................................................... 35
5.1.1 Entering Cell Constant....................................................................................... 35
5.1.2 Temperature Calibration.................................................................................... 35
5.1.3 Initial Loop Calibration....................................................................................... 35
5.1.4 Routine Standardization.................................................................................... 37
5.1.5 Sensor Maintenance.......................................................................................... 37
6.0 KEYBOARD SECURITY..................................................................................... 38
6.1 Keyboard Security............................................................................................. 38
7.0 THEORY OF OPERATION.................................................................................. 38
7.1 Theory of Operation........................................................................................... 38
8.0 DIAGNOSTICS AND TROUBLESHOOTING...................................................... 39
8.1 Diagnostics........................................................................................................ 39
8.1.1 Fault Mnemonics............................................................................................... 39
8.1.2 Temperature Compensation.............................................................................. 39
i
MODEL 1054A C TABLE OF CONTENTS
TABLE OF CONTENTS CONT'D.
Section Title Page
8.2 Troubleshooting................................................................................................. 40
8.2.1 Installation Failure.............................................................................................. 42
8.2.2 Display Test....................................................................................................... 40
8.2.3 Software Version................................................................................................ 40
8.2.4 Sensor Troubleshooting..................................................................................... 40
8.2.5 Absolute Conductivity ....................................................................................... 40
8.2.6 Cell Factor......................................................................................................... 40
8.2.7 Simulate Output................................................................................................. 40
8.2.8 CPU Board Replacement.................................................................................. 40
8.2.9 Power Board Replacement ............................................................................... 40
8.2.10 Instrument Electronic Bench Check.................................................................. 43
9.0 RETURN OF MATERIAL..................................................................................... 44
9.1 General.............................................................................................................. 44
9.2 Warranty Repair................................................................................................. 44
9.3 Non Warranty Repair......................................................................................... 44
LIST OF FIGURES
Figure No. Title Page
2-1 Panel Mounting Cutout...................................................................................... 7
2-2 Panel Mounting Tab Installation......................................................................... 8
2-3 Input Power Select Switch................................................................................. 8
2-4 Wall Mounting J-Box Installation........................................................................ 9
2-5 Wall Mounting J-Box Wiring............................................................................... 10
2-6 Pipe Mounting Installation................................................................................. 11
2-7 Electrical Wiring................................................................................................. 12
2-8 Wall Mount Enclosure........................................................................................ 13
3-1 Keyboard Overlay ............................................................................................. 16
4-1 Menu Items........................................................................................................ 20
4-2 Alarm 1 and 2 Configuration............................................................................. 23
4-3A Timer Diagram for One Wash Cycle.................................................................. 24
4-3 Interval Timer Configuration.............................................................................. 25
4-4 Temperature Configuration................................................................................ 27
4-5 Current Output Configuration............................................................................ 29
4-6 Default Configuration......................................................................................... 31
4-7 Alarm Setpoint................................................................................................... 32
4-8 Output Scale Expansion.................................................................................... 33
4-9 Simulate Current Output.................................................................................... 34
8-1 Simulate Conductivity Input............................................................................... 43
LIST OF TABLES
Table No. Title Page
1-1 Conductivity Range........................................................................................... 2
3-1 Key Description................................................................................................. 17
3-2 Information Mnemonics..................................................................................... 18
3-3 Set Function Mnemonics................................................................................... 18
4-1 Configuration Work Sheet.................................................................................. 21
4-2 Relay States for various Alarm/Default Configurations...................................... 30
8-1 Fault Mnemonics............................................................................................... 39
8-2 RTD Resistance Values..................................................................................... 39
8-3 Troubleshooting Guide ...................................................................................... 41
8-4 Replacement Parts and Accessories................................................................ 42
ii
1
MODEL 1054A C SECTION 1.0
DESCRIPTION AND SPECIFICATIONS
SECTION 1.0
DESCRIPTION AND SPECIFICATIONS
1.1 FEATURES AND APPLICATIONS
The Model 1054A Microprocessor Analyzers, with the appropriate sensors, are designed to continuously measure and control pH, ORP, conductivity, percent concentration, dissolved oxygen, or total free chlorine in industrial and municipal processes.
The Model 1054A Conductivity Analyzers are housed in a NEMA 4X (IP65) weatherproof, corrosion-resistant, flame retardant enclo­sure suitable for panel, pipe or wall mounting. All functions are accessed through the front panel membrane keyboard which fea­tures tactile feedback. Measurement data may be read at any time. However, settings may be protected against accidental or unau­thorized changes by a user selectable security code. The display indicates the measured value in engineering units as well as tem­perature, alarm status, hold output and fault conditions.
The 1054A transmits a user selected isolated current output which is continuously expandable over the measurement range for either direct or reverse action and can be displayed in milliamps or percent. Output dampening of 0-255 secs. is user selectable.
The output and relay default settings are user selectable for hold or fault mode operation. The hold output function allows manual con­trol during routine sensor maintenance.
Continuous self diagnostics alert the operator to faults due to analyzer electronics, integral RTD failures, open wiring and process variable range problems. In the event of a fault condition or hold mode diagnosed by the analyzer, the output will be set to a pre­set or last process value and the relays will be set to their default set­tings.
Dual alarms are a standard feature on the Model 1054A and are programmable for either high or low operation. Alarm 2 may be programmed as a fault alarm. Both alarms feature independent setpoints, adjustable hysteresis and time delay action. The time delay is convenient when an alarm is used for corrective action, such as shutting down a demineralizer for regeneration. Time delay will ignore a temporary breakthrough and prevent shutting down a de-mineralizer unit prematurely. A dedicated interval timer with relay is also provided.
Automatic or manual temperature compensation is keyboard selectable. The process temperature is accurately measured from an integral RTD in the sensor assembly and is read on the display. For greater accuracy, the temperature indication may be standard­ized to the process temperature. The temperature may be config­ured to read in ÞC or ÞF.
Calibration is easily accomplished by simply immersing the sen­sor in a known solution and entering the value. With a two point calibration, the Model 1054A will automatically calculate the tem­perature slope of the solution. Upon routine standardization a sen­sor cell factor value is calculated, and a trend of this value can be used to track sensor coating.
The Model 1054A Microprocessor Analyzer comes standard with an LCD display. An LED display is available as an option. An optional wall or unistrut mount enclosure is available for extra pro­tection of the analyzer in high solids or cold environments.
FM AND CSA APPROVED For Class I, Division 2, Gas Groups A, B, C, and D.
SELF DIAGNOSTICS with a user selectable fault alarm.
KEYBOARD SECURITY is user selectable.
NO BATTERY BACK-UP REQUIRED. Non-volatile EEPROM memory.
DUAL ALARMS WITH PROGRAMMABLE LOGIC. A third relay is provided with timer func­tions.
PROGRAMMABLE OUTPUT AND RELAY DEFAULTS for hold and fault modes.
NEMA 4X (IP65) WEATHERPROOF CORROSION-RESISTANT ENCLOSURE.
2
MODEL 1054A C SECTION 1.0
DESCRIPTION AND SPECIFICATIONS
1.2 PHYSICAL SPECIFICATIONS - GENERAL
Panel Mount Enclosure: Black, ABS, NEMA 4X, IP65,
CSA Enclosure 4. 144 X 144 X 192mm (5.7 X 5.7 X 7.6 inches).
Wall Mount Enclosure: Weatherproof, Thermoplastic.
300 X 330 X 190mm (11.75 X 13 X 7.5 inches).
Front Panel:Membrane keyboard with tactile feedback and user
selectable security. Black and white on grey.
Digital Display: LCD, black on grey
Optional, red LED Character Height: 18mm (0.7 inch)
Electrical Classification:
Group I Panel Mount Enclosure:
FM Class I, Div. 2, Group A thru D.
28 VDC relays - 6.0 amps resistive only 150 mA - Groups A & B; 400 mA - Group C; 540 mA - Group D; Ci - 0; Li - 0
CSA Class I, Div. 2, Group A thru D.
28 VDC, 110 VAC & 230 VAC relays
6.0 Amps resistive only
Group II Wall Mount Enclosure:General Purpose
Power:115 VAC, ± 10%, 50/60 Hz ± 6%, 4.0 W
230 VAC, ± 10%, 50/60 Hz ± 6%, 4.0 W
Current Output: Isolated, 0-20 mA or 4-20 mA
into 600 ohms maximum load, Direct or Reverse Output Dampening: 0-255 seconds.
Ambient Temperature:-20 to 65ÞC (-4 to 149ÞF) Ambient Humidity: LED max 95% RH
(LCD max 85% RH @ 50°C)
Alarms: Dual, field selectable High/Low, High/High, Low/Low
Alarm 2 configurable as a fault alarm Time Delay 0 to 254 seconds Dual Setpoints, continuously adjustable
Hysteresis is adjustable up to 25% full scale
for low side/High Alarm and high side/Low Alarm
Interval Timer: Interval: 10 min. to 2999 days
On Counts: 1 to 60 On Duration: 1 to 299.9 seconds Off Duration: 1 to 299.9 seconds Wait Duration: 1 to 299.9 seconds Controls dedicated relay
Relay Contacts: Epoxy Sealed Form A contacts, SPST, Normally
Open.
Resistive Inductive
28 VDC 6.0 Amps 3.0 Amps 115 VAC 6.0 Amps 3.0 Amps 230 VAC 3.0 Amps 1.5 Amps
Weight/Shipping Weight:1.1 kg/1.6 kg (2.5 lbs./3.5 lbs.)
The Model 1054A Conductivity Analyzer measures over the range of 0-2 µS/cm to 0-1,000 mS/cm. Temperature slope may be adjusted any- where between 0 and 5% to provide greater accuracy in chemical concentration control. The temperature slope is factory set at 2% as a rep­resentative value, but each conductive solution has its own set of temperature vs. concentration curves. The Model 1054A C will automatical­ly calculate the temperature slope for any given solution, or permit manual adjustment of the temperature slope if already known. On calibra­tion the analyzer will also automatically correct for cell constant variations for better measurement accuracy.
1.3 ANALYZER SPECIFICATIONS @ 25ÞC
Measurement Range: (See Table 1) Output Scale: Zero suppression: up to 90% full scale.
Span: from 10% to 100% full scale
Accuracy: ±0.5% of reading Repeatability: ±0.25% of reading Stability: ±0.25% month, non-cumulative Temperature Effect:0.02% of reading/ÞC Temperature Compensation: -20 to 200ÞC (-4 to 392ÞF)
(automatic or manual)
Temperature Slope Adjustment: 0-5%/ÞC
1.4 RECOMMENDED SENSORS:
Model 112 Insertion Conductivity Sensor Model 140 Retractable Conductivity Sensor Model 141 Insertion Conductivity Sensor Model 142 Insertion Conductivity Sensor Model 150 Insertion/Submersion Conductivity Sensor Model 160 Insertion/Submersion Conductivity Sensor
CONDUCTIVITY RANGE – TABLE 1-1
Conductivity Sensor 142 140 140, 141
Model Number 142 150 141 150 150 160 160 112
Cell Constant 0.01 0.1 0.2 0.5 1.0 2.0 5.0 20.0
Min. Range 1 2 4 10 200 400 1000 4000
Max. Range 200 2,000 4,000 10,000 20,000 40,000 100,000 400,000
FULL SCALE MICROSIEMENS/cm
* Uncompensated conductivity
3
MODEL 1054A C SECTION 1.0
DESCRIPTION AND SPECIFICATIONS
1.5 ORDERING INFORMATION
The Model 1054A Microprocessor Analyzer is housed in a NEMA 4X weatherproof, corrosion-resistant housing suitable for panel, pipe or wall mounting. The analyzer operates on 115 VAC, 60 Hz unless otherwise specified. Standard features include LCD digital display, isolated current outputs, dual alarms, automatic temperature compensation.
CODE GROUP II: WALL MOUNT ENCLOSURE OPTIONS (Select from either Group I or Group II, not both)
20 LCD Display, 115 VAC, 50/60 Hz 21 LCD Display, 230 VAC, 50/60 Hz 51 Enclosure heater for Code 20 52 Enclosure heater for Code 21
CODE MEASUREMENT (Required Selection)
C Conductivity
1054A C 02-21 EXAMPLE
CODE GROUP I: PANEL MOUNT ENCLOSURE OPTIONS (Select from either Group I or Group II, not both)
02 LED Display 05 230 VAC, 50/60 Hz Power
MODEL
1054A MICROPROCESSOR ANALYZER
NOTE: SELECT OPTIONS FROM GROUP I OR GROUP II, NOT BOTH.
FORMER OPTIONS
07 P/N 23053-00 Wall Mounting Plate with Junction Box 08 P/N 23054-01 Two-inch Pipe/Wall Mounting Bracket 11 P/N 2001492 Stainless Steel Tag (specify marking)
5
MODEL 1054A C SECTION 2.0
INSTALLATION
SECTION 2.0
INSTALLATION
2.1 GENERAL. This analyzer's enclosure is suitable
for outdoor use. However, it should be located in an area where temperature extremes, vibrations, electro­magnetic and radio frequency interferences are mini­mized or absent.
2.2 UNPACKING AND INSPECTION. Inspect the analyzer for shipping damage. If damaged, notify the carrier immediately. Confirm that all items shown on the packing list are present. Notify Rosemount Analytical if items are missing.
2.3 MECHANICAL INSTALLATION. Select an instal­lation site that is at least one foot from any high volt­age conduit, has easy access for operating personnel, and is not in direct sunlight. Mount the analyzer as follows:
1. Remove the four screws that secure the rear
cover of the enclosure.
2. (Not required for wall mounting configuration).
Remove the four screws holding the front panel assembly of the enclosure and carefully pull the front panel and connected printed circuit boards straight out.
3. Follow the procedure for the appropriate mount-
ing configuration: Section 2.3.1 for panel mount­ing, Section 2.3.2 for wall mounting, Section 2.3.3 for pipe mounting, or Section 2.3.4 for wall mount enclosure mounting.
2.3.1 Panel Mounting (Standard). The Model 1054A C is designed to fit into a DIN standard 137.9 mm X 137.9 mm (5.43 inch X 5.43 inch) panel cutout (Refer to Figures 2-1 and 2-2).
1. Prepare the analyzer as described in Section 2.3.
2. Install the mounting latches as described in
Figure 2-2 (latches are shown oversize for clarity). If the latches are not installed exactly as shown, they will not work correctly. The screws provided are self-tapping. Tap the screw the full depth of the mounting latch (refer to side view) leaving a gap greater than the thickness of the cutout panel.
3. Align the latches as shown and insert the analyz­er enclosure through the front of the panel cutout. Tighten the screws for a firm fit. To avoid damag­ing the mounting latches, do not use excessive force.
4. Replace the front panel assembly. Circuit boards must align with the slots on the inside of the enclosure. Replace the door and four front panel screws.
2.3.2 Wall Mounting Plate with Junction Box
(P/N 23054-01). Refer to Figures 2-4 and 2-5.
1. Prepare the analyzer as described in Section 2.3.
2. Mount the junction box and bracket to the analyz­er with the hardware provided. All wiring can be brought to the terminal strip prior to mounting the analyzer.
3. Place the metal stiffener on the inside of the ana­lyzer and mount the two 1/2 inch conduit fittings using two each weather seals as shown. Mount NEMA 4X conduit plug (included) into center con­duit hole.
4. Mount the analyzer to the junction box using the 1/2 inch conduit fittings.
5. Complete wiring from the analyzer to the junction box (Refer to Figure 2-5).
NOTE
Run sensor wiring out of the left opening (From front view) to J-Box. All others out right opening to J-Box.
2.3.3 Pipe Mounting (P/N 23053-00). The 2" pipe
mounting bracket includes a metal plate with a cutout for the analyzer (Refer to Section 2.3 for mounting the analyzer into the plate). Mounting details are shown in Figure 2-6.
6
MODEL 1054A C SECTION 2.0
INSTALLATION
2.3.4 Wall Mount Enclosure (Options 20/21). In this
configuration, the analyzer is housed in a NEMA 4X heavy duty enclosure. This may be mounted on a wall or handrail (see Figure 2-8 for mounting details). Installation procedures as outlined in Section 2.3 should be followed when installing the wall mounted enclosure. Sufficient clearance should be provided in front of the enclosure to permit opening of the door which is hinged on the left side.
2.4 ELECTRICAL WIRING. The Model 1054A has three conduit openings in the bottom rear of the ana­lyzer housing which will accommodate 1/2 inch con­duit fittings. From the front view, the conduit opening on the left is for sensor wiring; the center is for signal output and the opening on the right is for timer, alarm, and AC connections. Sensor wiring should always be run in a separate conduit from power wiring.
2.4.1 Power Input Wiring. The Model 1054A C has been configured at the factory for either 115 VAC or 230 VAC power. Operating power can be changed by a selector switch located on the power supply board (P/N 23056-02/03). To access this switch, remove the four screws from the front keyboard and pull the elec­tronic assembly straight out (See Figure 2-3).
Connect AC power to TB1-7 and -8, ground to the ground terminal at TB3-8 (refer to Figure 2-7).
CAUTION
The sensitivity and stability of the analyzer will be impaired if the input wiring is not grounded. DO NOT apply power to the analyzer until all electrical connections are verified and secure. The following precau­tions are a guide using UL 508 as a safe­guard for personnel and property.
1. AC connections and grounding must be in com­pliance with UL 508 and/or local electrical codes.
2. The metal stiffener is required to provide support and proper electrical continuity between conduit fittings.
3. This type 4/4X enclosure requires a conduit hub or equivalent that provides watertight connect, REF UL 508-26.10.
4. Watertight fittings/hubs that comply with the requirements of UL 514B are to be used.
5. Conduit hubs are to be connected to the conduit before the hub is connected to the enclosure, REF UL 508-26.10.
6. If the metal support plate is not used, plastic fit­tings must be used to prevent structural damage to the enclosure. Also, appropriate grounding lug and awg conductor must be used with the plastic fittings.
2.4.2 Output Wiring. The signal output and alarm
connections are made to terminals 1 through 6 of TB1 and TB3-1 and 2. (Refer to Figure 2-7).
2.4.3 Wall Mount Enclosure Wiring (Refer to
Figure 2-4). The wall mount enclosure has three 3/4-
inch conduit openings, two with 3/4-inch fittings and one with a NEMA 4X conduit plug. From a front view, the conduit opening on the left is for sensor wiring; the center is for signal output and the opening on the right is for timer alarm and AC power supply connections.
7
MODEL 1054A C SECTION 2.0
INSTALLATION
FIGURE 2-1. Panel Mounting Cutout
WHEN INCH AND METRIC DIMS
ARE GIVEN
MILLIMETER
INCH
DWG. NO. REV.
41054A01 B
8
MODEL 1054A C SECTION 2.0
INSTALLATION
FIGURE 2-2. Panel Mounting Tab Installation
FIGURE 2-3. Input Power Select Switch
DWG. NO. REV.
41054A29 A
DWG. NO. REV.
41054A26 A
9
MODEL 1054A C SECTION 2.0
INSTALLATION
FIGURE 2-4.Wall Mounting J-Box Installation
DWG. NO. REV.
41054A27 A
10
MODEL 1054A C SECTION 2.0
INSTALLATION
FIGURE 2-5.Wall Mounting J-Box Wiring
WHEN INCH AND METRIC DIMS
ARE GIVEN
MILLIMETER
INCH
DWG. NO. REV.
41054A08 B
11
MODEL 1054A C SECTION 2.0
INSTALLATION
FIGURE 2-6. Pipe Mounting Installation
WHEN INCH AND METRIC DIMS
ARE GIVEN
MILLIMETER
INCH
DWG. NO. REV.
41054A02 C
12
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
DRIVE, BLACK
N/C
CURRENT IN,WHITE
N/C
RTD IN, GREEN
REF GROUND, SHIELD
RTD SENSE, RED
EARTH GROUND
CURRENT
LOOP
OUTPUT1
N/C
EARTH
GROUND
ALARM
1
(N.O.)
ALARM
2
(N.O.)
TIMER
HOT 11 5/230 V AC NEUTRAL
FIELD TERMINAL BOARD CONNECTIONS
TB1
TB3
+
TB2
MODEL 1054A C SECTION 2.0
INSTALLATION
FIGURE 2-7. Electrical Wiring
DWG. NO. REV.
41054A05 A
13
MODEL 1054A C SECTION 2.0
INSTALLATION
FIGURE 2-8.Wall Mount Enclosure
DWG. NO. REV.
41054A12 C
WHEN INCH AND METRIC DIMS
ARE GIVEN
MILLIMETER
INCH
15
Configuration is all accomplished through a series of menus located within the set mode menu. To access these set mode menus the ACCESS keypad is pressed T
WICE in RAPID succession.
Once inside the Set mode menu, use the scroll key­pad to scroll through the menu list. When the menu desired is displayed, release the scroll keypad.
To enter the submenus press the SELECT keypad. If the submenu allows editing, the item will flash that can be edited. If not, use the scroll keypad to scroll through the next list of submenus . SELECT will enter this submenu and if it is editable, the field will flash.
To exit the menu and SAVE the new value, press the ENTER keypad.
To exit the menu without saving the edited value, press the COND keypad to jump out of the set menu program with out saving value. To change other parameters will require re-entering the set menu program.
Figure 3-4 explains the various fields surrounding the Primary process on the LC display.
Table 3-1 describes the functions accessible with the 8 keypads, the number of times to press the keypad to access, and its’ function when used with the select keypad and set menu.
Table s 3-2 and 3-3 describe the meaning of the vari­ous mnemonics used on the display. They are cate­gorized by their use in either menus, or as process information.
MODEL 1054A C SECTION 3.0
DESCRIPTION OF CONTROLS
SECTION 3.0
DESCRIPTION OF CONTROLS
3.1 KEYBOARD FUNCTIONS. All operations of the
Model 1054 A C microprocessor Analyzer are con­trolled by the 8 keypads on the front of the instrument. These keypads are used to :
1. Display parameters other than the primary parameter.
2. Edit setpoints for alarms, set up specific output current value for simulation, calibrate tempera­ture, conductivity, etc.
3. Configure display for temperature units, for auto­matic temperature compensation, alarm usage, setting timer functions, security , and output range.
To view, and not change parameters, other than the primary parameter requires only a simple keystroke routine. As shown in Figure 3-1, a single keypress accesses the lower function printed on the keypad. Quick, double keypresses access the top function printed on the keypad.
To edit any of these parameters, requires one more
operation. After displaying the value associated with the parameter selected, press the SELECT keypad. As seen in Figure 3-2, this will display the numerical value, and the first digit will be flashing to indicate this value may be edited.
All changes to the operating program that set-up the instrument display are made through the set menu program. See Figure 3-5 at the end of this section.
FIGURE 3-1. Function Select on Keypad.
Single press of the keypad will access the present Conductivity reading. Read only.
1. Press Key.
2. Adj shows briefly.
3. Numbers show with digit flashing.
1 .Press Key twice.
2. Lo shows briefly.
3. Zero point is displayed.
SELECT
ZERO
ALARM
1
OUTPUT
COND
FIGURE 3-2. Accessing Editing Function.
1. Press twice in rapid succession.
2. See SEt on display. Confirms entry into set mode menu.
3.First menu item is displayed. Analyzer now ready to configure.
4. Use the SCROLL keypad to rotate through the available menus.
ACCESS
ENTER
SEt
Cin
FIGURE 3-3. Accessing Configuration Menus
Quick double press will access the current output current value in mA or %. Read only.
16
MODEL 1054A C SECTION 3.0
DESCRIPTION OF CONTROLS
FIGURE 3-4. LCD Display
3.1.1 Item Selection and Value Adjustment Keys.
The three keys located on the lower right side of the keypad are used for menu navigation, value adjust­ment and entry, and item selection. These keys per­form the following functions:
A. SELECT/Shift (Ô) Key. This key is used to select the displayed menu, or for shifting to the next digit in the Numeric Display.
B. SCROLL Key (). This key is used to scroll through menu when selected, or scroll through digits on the active (flash­ing) Numeric Display, or move the deci­mal point and µS/mS display. Holding
key down auto scrolls display.
C. ACCESS/ENTER Key. This key is used to ACCESS the Set Mode (Section
4.1.2) and to ENTER the displayed value into memory (from Numeric Display).
SELECT
ACCESS
ENTER
17
TABLE 3-1. Key Description
Displays - current output (mA or % full scale).
Set Function (w/SELECT) - Simulates current output.
Displays - low current setpoint. Set Function (w/SELECT) - Sets low
current point.
Displays - full scale output setpoint. Set Function (w/SELECT) - Sets full
scale output point.
Select sub menu (mnemonic display). Shift to next digit (numeric display).
Scroll through menu (mnemonic display). Scroll digits (numeric display). Scroll decimal position, µS/mS display. Holding key down auto scrolls the main set menu and each digit in the numeric display.
Press twice to access set-up menu. Enter displayed value into memory. Enter displayed menu item (flashing) into memory.
Two Point temperature slope calibra­tion.
Displays - Alarm 1 setpoint. Set Function (w/SELECT) - Sets
Alarm 1 setpoint.
Displays - conductivity. Set Function (w/SELECT) - One point
standardization of conductivity.
Initiates or removes analyzer from hold con­dition.
Displays - process temperature (ÞC or Þ F).
Set Function (w/SELECT) - One point standardization of temperature.
Displays - Alarm 2 setpoint. Set Function (w/SELECT) - Sets
Alarm 2 setpoint.
HOLD
TEMP
OUTPUT
COND
ZERO
ALARM 1
F.S.
ALARM 2
SLOPE
CAL
SELECT
ACCESS
ENTER
Displays - temperature slope in percent. Set Function (w/SELECT) - manually sets tem-
perature slope.
SECOND FUNCTION (PRESS TWICE QUICKLY)MAIN FUNCTION (PRESS ONCE)
MODEL 1054A C SECTION 3.0
DESCRIPTION OF CONTROLS
18
MODEL 1054A C SECTION 3.0
DESCRIPTION OF CONTROLS
TABLE 3-2. Information Mnemonics
MNEMONIC DESCRIPTION
AdJ Adjustment to value reading bAd Incorrect entry Con Conductivity Display dOC Displays conductivity output (mA) HLd Analyzer in Hold Position
HI Displays high range value for current output itr Interval timer activated LO Displays low range value for current output
LOC Access locked – enter security code Pct Displays conductivity output (percent)
SEt Set mode S iP Simulates current output (percent) S iC Simulates current output (mA)
SLP Displays temperature slope in percent
SP1 Displays Alarm 1 setpoint SP2 Displays Alarm 2 setpoint Std Standardize conductivity
tP1 Calibration Point 1 tP2 Calibration Point 2
AL1 Alar m 1 setup AL2 Alarm 2 setup Atc Automatic temp. comp. CEL Cell Constant
DC Temperature ÞC
Cin Display Sensor input COd Security Code cnt Timer count CUr Config. current output Cur Config. fault output cur Default current setpoint dAY Days dFt Fault Configuration d-O Display output d-t Display temperature doc Display output in mA doF Delay off time
don Delay on time dPn Dampen output dtS LCD/LED Display test dur Timer duration
DF Temperature ÞF Fct Calibration Factor FLt Use alarm as fault alarm
Hi Relay action - high
H-L Alarm logic
Hr Hours HYS Hysteresis
int Interval period
Int Timer setup
Lo Relay action - low non No action on fault oFF Relay open on fault OFF Alarm not used
ont Timer on time
on Relay closed on fault
On Use alarm as pr ocess alarm OFt Timer off time OUt Current output
Pct
Display output in percent
rL1 Relay 1 fault setup rL2 Relay 2 fault setup SEC Seconds SHO Show fault history t-C Temperature config.
tiL Timer - time remaining tOn Timer status UEr User version
uin Minutes 420 4mA to 20mA output 020 0mA to 20mA output
TABLE 3-3. Set Function Mnemonics
19
MODEL 1054A C SECTION 3.0
DESCRIPTION OF CONTROLS
H-L
HYS
don
doF
On
OFF
Cin CEL Fct
AL1
AL2
Int
t-C
OUt
UEr
dFt
dtS
COd
SEt
Hi
Lo
tOn
int
cnt
ont
OFt
dur
tiL
oFF
on
SEC
uin
hr
dAY
DF
DC
doc
Pct
on
oFF
non
non
cur
rL1
rL2
Cur
SHO
on
oFF
On
FLt
OFF
420
020
d-t
Atc
dPn
CUr
d-O
FIGURE 3-5. Set Menu Items
21
MODEL 1054A C SECTION 4.0
CONFIGURATION
SECTION 4.0
CONFIGURATION
4.1 GENERAL. This section details all of the items avail-
able in the Set Mode to configure the analyzer to a spe­cific application.
4.1.1. Configuration Worksheet. The configuration worksheet on page 19 should be filled out before pro­ceeding with the analyzer’s configuration. This sheet gives a brief parameter description, the factory setting, and a space for user setting.
4.1.2 Set Mode Display Mnemonic SEt. Most of the analyzer's configuration is done while in the Set Mode. Please refer to Figure 4-1 for the layout of all menu items. All menu variables are written to the ana­lyzer's EEPROM (memory) when selected and remain there until changed. As these variables remain in memory even after the analyzer's power is removed, the analyzer configuration may be performed prior to installing it.
1. Power up the analyzer. Only power input wiring is required for analyzer configuration (Refer to Section 2.4.1). The analyzer's display will begin showing values and/or fault mnemonics. All fault mnemonics will be suppressed while the analyz­er is in Set Mode (the fault flag will continue to blink).
2. Enter Set Mode. Pressing the ACCESS key twice in rapid succession will place the analyzer in Set Mode. The display will show “SEt” to confirm that it is in Set Mode. It will then display the first item in the set menu “Cin.’’ The analyzer is now ready for user configuration.
NOTE:
If “LOC” displays, the Keyboard Security Code must be entered to access the Set Mode. (Refer to Section 6.0.)
3. Analyzer variables can be entered in any order. On initial configuration, however, it is recom­mended that the variables be entered in the order shown on the worksheet. Refer to the configura­tion worksheet (Table 4-1). This will reduce the chance of accidentally omitting a needed vari­able.
22
MODEL 1054A C SECTION 4.0
CONFIGURATION
TABLE 4-1.
CONFIGURA TION WORKSHEET
Use this worksheet to assist in the configuration of the analyzer. Date: _________________
RANGE FACTORY SET USER SET
A. Alarm 1 Setup (AL1)
1. Alarm Configuration (On/OFF) On _________
2. High or Low (H-L) (Hi/Lo) Lo _________
3. Hysteresis (HYS) 0-25 % of setpoint 0.00% _________
4. Delay Time On (don) 0-255 sec. 000 Seconds _________
5. Delay Time Off (doF) 0-255 sec. 000 Seconds _________
B. Alarm 2 Setup (AL2)
1. Alarm Configuration (On/FLt/OFF) On _________
2. High or Low (H-L) (Hi/Lo) Hi _________
3. Hysteresis (HYS) 0-25 % of setpoint 0.00% _________
4. Delay Time On (don) 0-255 sec 000 Seconds _________
5. Delay Time Off (doF) 0-255 sec 000 Seconds _________
C. Interval Timer (Int)
1. Active Status (tOn) (oFF/on) oFF _________
2. Interval Time (int) minimum 10 minutes 1 Day _________
3. Count (cnt) 1 to 60 5 _________
4. On Time (ont) 0 to 299.9 sec 1 Second _________
5. Off Time (OFt) 0 to 299.9 sec 1 Second _________
6. Duration (dur) 0 to 299.9 sec 2 Seconds _________
D.Temperature Setup (t-C)
1. Display Temperature (d-t) (DC/DF) DC _________
2. Automatic Temperature Compensation on _________ (Atc) (on/oFF)
a. Manual Temp. Value -20ÞC to 200ÞC _________
E. Current Output Setup (OUt)
1. mA Output (CUr) (020/420) 420 _________
2. Display Current Output (d-O) (Pct/doc) doc _________
3. Dampen Current Output (dPn) 0-255 sec. 0.0 Seconds _________
F. Default Setup (dFt)
1. Relay 1 Default (rL1) (non/oFF/on) non _________
2. Relay 2 Default (rL2) (non/oFF/on) non _________
3. Current Output Default (Cur) (non/cur) non _________
G. Keyboard Security Setup (COd)
1. Keyboard Security Required 001-999 _ _________
2. Keyboard Security Not Required 000 000 _________
Alarm Set Points
1. Alarm 1 (SP1) 0-1999 mS 0.00 mS _________
2. Alarm 2 (SP2) 0-1999 mS 1,000 mS _________
Current Output
1. Zero (0 or 4 mA) (Lo) 0-1,000 mS 0.00 mS _________
2. F.S. (20 mA) (HI) 0-1,000 mS 1,000 mS _________
23
MODEL 1054A C SECTION 4.0
CONFIGURATION
4.2. ALARM 1 AND 2. Display Mnemonic “AL1” or “AL2”.
Used to set alarm relay logic. The alarms may be used to perform on-off process control. See note below .
A. ON.Display Mnemonic “On”. Select this item if Alarm 1 or 2 is to be used as a process alarm. See Steps D through G for further configuration.
B. OFF. Mnemonic “OFF”. Select this item if alarm 1 or 2 will not be used or to temporarily disable the alarm. Alarm 1 or 2 setpoint will display “oFF” if this item is selected. Omit Steps D through G.
C. Fault. Display Mnemonic “FLt”. (Alarm 2 only). Select to make Alarm 2 a fault alarm. Relay 2 will ener­gize when the unit shows a fault condition. See Table 8-1 for a listing of the fault mnemonics and their descriptions. Alarm 2 setpoint will display “F1 t ” if this item is selected. Omit Steps D through G.
D. Alarm Logic. Mnemonic “H-L”. Select this item for high or low alarm logic. High logic activates the alarm when the reading is greater than the set point value. Low logic activates the alarm when the reading is less than the set point value.
E. Relay Hysteresis. Display Mnemonic “HYS”. Sets the relay hysteresis (dead band) for deactivation after read­ing has passed the alarm set point. May be set from 0 to 25%. Use hysteresis when a specific conductivity should be reached before alarm deactivation.
F . Delay Time On. Display Mnemonic “don”. Sets time delay for relay activation after alarm set point is reached. May be set from 0 to 255 seconds.
G. Delay Time Off.Display Mnemonic “doF”. Sets time delay for relay deactivation after alarm set point is reached. May be set from 0 to 255 seconds. Alarm state restarts time from zero. Use when a fixed time should pass before relay deactivation occurs.
NOTE
Alarm logic may be changed from normal­ly open (N.O.) to normally closed (N.C.). by cutting bowties on the power supply PCB and adding a jumper between W4 and W5, and or W6 and W7, and or W8 and W9.
4.2.1 Alarm Configuration (AL1/AL2). Refer to Figure 4-1.
1. Enter Set Mode by pressing ACCESS key twice.
2. SCROLL () until “AL1” or “AL2” appears on the display.
3. SELECT to move to the next menu level. “On”, “OFF”or (AL2 only) “FLt” will display.
4. SCROLL () to display desired item then SELECT.
5. If “OFF” is selected, display will show “oFF”to acknowledge. Press ENTER key to return to “AL1” or “AL2”, concluding routine. Skip to Step 11.
If “On” is selected, display will show “on” to ack­nowledge, then display “H-L”. Proceed to Step 6.
If “FLt” is selected, display will show “Flt” to ack­nowledge. Press ENTER key to return to “AL2”.
6. SELECT H-L”. “Hi” or “Lo” will display (flashing).
7. SCROLL () to the desired item and ENTER it into memory. Display will return to “H-L”. If changes to relay activation logic are desired, proceed to Step 8, otherwise Step 12.
8. SCROLL () to display “HYS”, “don” or “doF” then SELECT desired item. Numerical display will flash to indicate that a value is required.
9. Use SCROLL () and SHIFT (Ô) to display the desired value.
10. ENTER value into memory. The analyzer will acknowledge and return to display of last item selected. Repeat Step 8 if further changes are desired, otherwise Step 12.
11. Repeat Step 3 for the other Alarm's settings as required.
12. To return to the first level of the Set Mode, Press the ACCESS key.
Figure 4-1. Alarm 1 and Alar m 2 Configuration
On
OFF
On
FLt
OFF
AL1
AL2
H-L
HYS
don
doF
Hi
Lo
SEt
24
MODEL 1054A C SECTION 4.0
CONFIGURATION
Figure 4-2. Interval Timer Configuration
4. SCROLL () to display “on” or “oFF” and ENTER it into memory. If interval configuration is
required, proceed to Step 5, otherwise Step 10.
5. SCROLL () to display desired menu item. If “int” is selected, go to Step 6, otherwise Step 10.
6. SCROLL () to display desired interval period and SELECT it. Numerical Display will flash.
7. SCROLL () and SHIFT (Ô) to display the desired value and ENTER it into memory. Display will return to interval period menu.
8. Repeat Steps 6 and 7 as needed.
9. Press the ENTER key to return to the main timer menu.
10. SELECT the desired item. The Numerical Display will flash.
11. SCROLL () and SHIFT (Ô) to display the desired value and ENTER it into memory.
12. Repeat Steps 5, 10, and 11 as required.
13. Press the ENTER key to return to Set Menu.
4.3 INTERVAL TIMER. Display Mnemonic “Int”. This item is used to set the interval timer's relay logic. The timer can be used for sensor maintenance, such as a wash cycle to clean the sensor in a bypass line. Choices are:
A. Interval Timer Enable/Disable. Display Mnemonic “
tOn”. Select this item to begin interval cycle “on” or
disable interval cycle “oFF”. B. Interval Period. Display Mnemonic “int”. Select
this item to set the time period between control cycles. “SEC” for seconds, uin” for minutes, hr for hours, and “dAY” for days. May be set from a mini­mum of 10 minutes.
C. “On” Periods Per Cycle. Display Mnemonic “cnt”. Select this item to enter the number of on periods per cycle. May be set from 1 to 60 on periods.
D. Duration of “On” Periods. Display Mnemonic “ont”. Select this item to enter the relay activation time for each on period. May be set from 0.1 to 299.9 seconds.
E. Duration of “Off” Periods. Display Mnemonic “OFt”. Select this item to enter the relay deactivation time between each “on” period during the control cycle. Valid when “cnt” is 2 or greater. May be set from 0 to 299.9 seconds.
F. Sensor Recovery Time. Display Mnemonic “dur”. Select this option to enter the duration time after the last “on” period in a cycle. May be set from 0 to 299.0 seconds. The wait duration can be used for electrode recovery after a wash cycle.
G. Interval Time remaining. Display Mnemonic “tiL”. Select this item to display the time remaining to the next control cycle. If selected during the control cycle, display will show "---".
NOTE
The Model 1054A is placed
on hold
during the control cycle (from first “on” period through the wait duration). The analyzer will simulate a fault condition and briefly show “itr” every eight seconds. The display will continue to show the measured value.
4.3.1 Interval Timer Configuration (Int). Refer to Figures 4-2 and 4-2A.
1. Enter Set Mode by pressing ACCESS Key twice.
2. SCROLL () until “Int” appears on the display.
3. SELECT to move to the next menu level. “tOn”, will display.
SEt
OFF
On
tOn
int
cnt
ont
OFt
dur
tiL
SEC
uin
hr
dAY
Int
FIGURE 4-2A.
Timer Diagram for One Cycle
RELAY
ACTIVATION
TIME
int
ont
dur
cnt = 1 OFt = 0
25
MODEL 1054A C SECTION 4.0
CONFIGURATION
4.4 TEMPERATURE. Display Mnemonic “t-C”. Select this item
for temperature reading and compensation choices. A. Temperature Display. Display Mnemonic “d-t”.
Select this item to toggle between ÞF and ÞC tempera­ture display. The analyzer will show all temperatures in units selected until the selection is changed.
B. Automatic Temperature Compensation. Display Mnemonic “Atc”. The analyzer will use the temperature input from the sensor for temperature correction when “on” is selected. When “oFF” is selected, the analyzer will use the value entered by the user for temperature correc­tion. This manual temperature option is useful if the tem­perature sensor is faulty or not on line. Temperature spe­cific faults will be disabled (refer to Section 1.2).
4.4.1 Temperature Configuration t-C. Refer to Figure 4-3.
Figure 4-3. Temperature Configuration
1. Enter Set Mode by pressing ACCESS key twice
2. SCROLL () until “t-C” appears on the display.
3. SELECT to move to the next menu level. “d-t” will display.
4. SCROLL () to display desired item then SELECT it.
5. If “d-t” is selected, display will show “DC” or “DF”. If “Atc” is selected, display will show “on” or “oFF”.
6. SCROLL () then ENTERdesired item into memory.
7. If “DC”, “DF” or “ on” are entered, display will return to the previous level (proceed to Step 9).
If “oFF” is selected, numerical display will flash indi­cating that a process temperature value is required (proceed to Step 8).
8. Use SCROLL () and SHIFT (Ô) to display the desired value. ENTER value into memory.
9. Repeat Steps 4-8 as required for other item.
10. Press the ENTER key to return to Set Menu.
4.5 CURRENT OUTPUT. Display Mnemonic is “OUt”. This item is used to configure the output signal.
A. Output Dampening. Display Mnemonic “dPn”. Dampens the response of the signal output. This option is useful to minimize the effect of a noisy reading. The number entered is the sample time (in seconds) for an averaged output. Zero to 255 seconds may be entered.
B. mA Output Range. Display Mnemonic “CUr”. Selection of this item will allow choice of 0 to 20 mA or 4 to 20 mA output range.
C. Display Output. Display Mnemonic “d-O”. This item is used to select logic of output display. Selecting this item will allow the analyzer to display current output as mA (“doc”) or as a percent of full scale output range (“Pct”).
4.5.1 Current Output Configuration “OUt. Refer to Figure 4-4.
Figure 4-4. Current Output Configuration
1. Enter Set Mode by pressing the ACCESS key twice.
2. SCROLL () until “OUt” appears on the display.
3. SELECT to move to the next menu level. “dPn” will display.
4. SCROLL () then SELECT desired item.
5. If “dPn” is selected, numerical display will flash indi­cating that a value is required (proceed to Step 6).
If “CUr” or “d-O” is selected, proceed to Step 7.
6. SCROLL () then SHIFT (Ô) to display the desired value. ENTER into memory
7. SCROLL () then ENTER desired item.
8. Repeat Steps 4-7 as required.
9. Press the ENTER key to return to the Set Menu.
t-C
SEt
Out
SEt
d-t
Atc
on
oFF
Df
DC
dPn
CUr
d-O
doc
Pct
420
020
26
MODEL 1054A C SECTION 4.0
CONFIGURATION
4.6 DEFAULTS. Display Mnemonic “dFt”. This item is
used to set the configuration of relays and output default conditions during fault or hold status. See Table 8-1 for a listing of the possible fault conditions which can be diagnosed by the analyzer. A hold sta­tus is initiated by pressing the HOLD key twice. (Press twice again to remove the hold.)
A. Relay 1 and 2. Display Mnemonic “rL1” and “rL2”. The relays can be set to activate “on”, deactivate “oFF”, or hold present status “non”. See Table 4-2.
B. Current Output. Display Mnemonic “Cur”.The cur- rent output is held “non” or goes to a specified value “cur” during a fault condition. “cur” will probably be the most informative selection.
C. Fault History. Display Mnemonic “SHO”. Selecting this item will display the most recent detected faults. Press the SCROLL key once for each previous fault history. Pressing ACCESS will clear “SHO” history.
4.6.1 Default Configuration (dFt). dFt” Refer to
Figure 4-5.
Figure 4-5. Default Configuration
1. Enter Set Mode by pressing the ACCESS key twice.
2. SCROLL () until “dFt” appears on the display.
3. SELECT to move to the next menu level. “rL1” will display.
4. SCROLL () then SELECT desired item.
5. Display will show next item selection. SCROLL () and ENTER desired item.
6. Repeat Steps 4 and 5 as required for other default settings “rL2” and “Cur”. If “cur” is select­ed for “Cur”, press ENTER then use the SCROLL () and SHIFT (Ô) keys to enter the desired cur­rent value in mA.
7. Press the ENTER key to return to Set Menu.
ANALYZER CONDITION
NORMAL HOLD FAULT
Set menu AL1/AL2 setting Set menu AL1/AL2 setting Set menu AL1/AL2 setting
On OFF FLt On OFF FLt On OFF FLt
(Alarm 2 (Alarm 2 (Alarm 2
only) only) only)
on Proc. det. + + +
off Proc. det. +
non Proc. det. Proc. det. Proc. det. +
Set Menu
default
(dFt)
setting
rL1/rL2
Proc. det.: Alarm state is deter mined by
the process value.
+:Relay will activate.
–:Relay will not activate.
Example: If you want the analyzer to activate relay 1 in
hold mode during calibration, set "AL1" to "On" in Section 4.3, and set "rL1" to "on".
TABLE 4-2. Relay States for Various Conditions and Alarm/Default Configurations
SEt
dFt
rL1
rL2
Cur
SHO
on
oFF
non
non
cur
27
MODEL 1054A C SECTION 4.0
CONFIGURATION
4.7 ALARM SETPOINT. The alarm setpoints should
be adjusted after completing the configuration proce­dure outlined in Sections 4.1 to 4.6. (Refer to Figure 4-7.)
1. Press the COND key to ensure that the analyzer is not in Set Mode.
2. Press the ALARM 1 or ALARM 2 key. “SP1” or “SP2” will show briefly, followed by the Alarm 1 or Alarm 2 Setpoint.
NOTE:
If the alarm is set to OFF or FAULT (Alarm 2 only), the analyzer will display “oFF” or “F1 t ” respectively. (Refer to Section 4.2, Alarm Configuration.)
3. Press SELECT to adjust the value. The display will acknowledge briefly with “AdJ” followed by the Numeric Display with digit flashing.
4. SCROLL () and SHIFT (Ô) to display the desired value.
5. ENTER value into memory.
6. Repeat Steps 2 to 5 for the second setpoint.
NOTE
Selection of µS/mS and decimal posi­tions is achieved by pressing SHIFT (Ô) until the µS/mS flag flashes, then SCROLL () until the desired combina- tion of decimal position and mS (quick flashing)/µS (slow flashing) flag are dis­played.
ZERO
ALARM
1
F.S.
ALARM
2
ACCESS
SELECT
AdJ
SP1/2
SELECT
ENTER
Press
Once
Press Once
Displays
Briefly
Displays
Briefly
Numeric
Display
Change to
desired
value
Press Once
Numeric
Display
of
Setpoint
FIGURE 4-7. Alarm Setpoint
28
MODEL 1054A C SECTION 4.0
CONFIGURATION
4.8 OUTPUT SCALE EXPANSION. This section should
be followed if it is desired to scale the current output range other than the factory setting of 0-20 millisiemen. The output zero and full scale value should be adjusted after completing the configuration procedure as out­lined in Sections 4.1 to 4.6. (Refer to Figure 4-8.)
A. ZERO POINT (0 mA or 4 mA) LO
1. Press the COND key to ensure that the unit is not in Set Mode.
2. Press the ALARM 1 key twice. The display will show “LO” briefly then display the ZERO point.
3. Press SELECT to adjust the value. The display will acknowledge briefly with “AdJ” followed by the Numeric Display with digit flashing.
4. SCROLL () and SHIFT (Ô) to display the desired value.
5. ENTER value into memory. The display will showLO” and display the entered value.
B. Full Scale (F.S.) Point (20 mA) HI
1. Press the COND key to ensure that the analyzer is not in Set Mode.
2. Press the ALARM 2 key twice. The display will show HI briefly then display the FULL SCALE point.
3. Press SELECT to adjust the value. The display will acknowledge briefly with “AdJ” followed by the Numeric Display with digit flashing.
4. SCROLL () and SHIFT (Ô) to display the desired value.
5. ENTER value into memory. The display will show
HI and display the entered value.
NOTE
For a reverse output, enter the higher value for zero, and the lower value for the Full Scale.
NOTE
Selection of µS/mS and decimal positions is achieved by pressing SHIFT (Ô) until the µS/mS flag flashes, then SCROLL () until the desired combination of deci­mal position and mS (quick flashing)/µS (slow flashing) flag are displayed.
ZERO
ALARM
1
F.S.
ALARM
2
ACCESS
SELECT
AdJ LO/HI
SELECT
ENTER
Press Twice
Press Once
Displays
Briefly
Displays
Briefly
Numeric
Display
Change to
desired
value
Press Once
Numeric
Display
of
Setpoint
FIGURE 4-8. Output Scale Expansion
29
4.9 SIMULATE CURRENT OUTPUT. The output can
be simulated to check the operation of devices such as valves, pumps, or recorders. The output can be simulated in either current (mA) or percent of full scale, depending on how the output display “d-O” was configured in Section 4-5. (Refer to Figure 4-9.)
A. Simulate Output in Percent SiP”. The output can be simulated in percent if “d-O” in Section 4.5 was configured to display percent “Pct”.
1. Press the COND key once to insure that the analyz­er is not in the Set Mode.
2. Press the OUTPUT key twice. The display will show “Pct” briefly, then display the output value in percent of full scale.
3. Press SELECT to simulate the output. The dis­play will briefly acknowledge with “SiP” followed by the Numeric Display with digit flashing.
4. SCROLL () and SHIFT to display the desired value.
5. ENTER value into memory. The display will showPct” and display the entered value. Also, the dis­play will flash to acknowledge that the analyzer is placed on hold “HLd”. In hold mode the relays will be set as determined in Section 4-6.
6. To remove the analyzer from hold, press the HOLD key twice. The hold flag on the display will be removed and the display will stop flashing.
B. Simulate Output in Current SiC”. The output can be simulated in mA units if “d-O” in Section 4.5 was configured to display current “doc”.
1. Press the COND key once to insure that the analyzer is not in the Set Mode.
2. Press the OUTPUT key twice. The display will show “dOC” briefly, then display the output value in mA.
3. Press SELECT to simulate the output. the display will briefly acknowledge with “Sic” followed by the Numeric Display with digit flashing.
4. SCROLL () and SHIFT (Ô) to display the desired value.
5. ENTER value into memory. The display will showdOC” and display the entered value. Also, the dis­play will flash to acknowledge that the analyzer is placed on hold “HLd”. In hold mode the relays will be set as determined in Section 4-6.
6. To remove the analyzer from hold, press the HOLD key twice. The hold flag on the display will be removed and the display will stop flashing.
MODEL 1054A C SECTION 4.0
CONFIGURATION
OUTPUT
COND
ACCESS
SELECT
SiC/SiP
Pct/dOC
SELECT
ENTER
Press Twice
Press Once
Displays
Briefly
Displays
Briefly
Numeric
Display
Change to
desired
value
Press Once
Numeric
Display
of Output
(Analyzer in
hold)
FIGURE 4-9. Simulate Current Output
31
MODEL 1054A C SECTION 5.0
START-UP AND CALIBRATION
SECTION 5.0
START-UP AND CALIBRATION
5.1 START-UP AND CALIBRATION. Calibration and
operation of the Model 1054A C should begin only after completion of the configuration of the analyzer. The sensor must be wired (including J-box and inter­connecting cable) as it will be in operation.
NOTE READ THE ENTIRE CALIBRATION SECTION TO DETERMINE THE CALI­BRATION PLAN MOST SUITABLE FOR Y OUR NEEDS.
5.1.1 Entering the Cell Constant. The first time the
analyzer is calibrated and any time there is a sensor change, the sensor cell constant must be entered into memory. Entering a cell constant into memory will reset the cell factor “Fct” to 1.0 and will initiate the analyzer (the cell factor gives an indication of sensor scaling. Refer to Section 8.2.6).
1. Enter the Set Mode. Press the ACCESS key twice in rapid succession. The analyzer will dis­play “SEt” briefly then display “Cin”.
2. SCROLL (Ð) the menu until “CEL” is displayed, then SELECT it. The Numerical display will flash to indicate that a value is desired.
3. Use SCROLL (Ð) and SHIFT (Ô) to display the correct sensor cell constant and ENTER it into memory. This value can be found on the cable label, i.e.; Sensor K= 1.00.
NOTE
Only adjust the cell constant when the con­ductivity sensor is replaced or serviced. Then always perform a restandardization. See Section 5.1.4.
5.1.2 Temperature Calibration. For accurate temper-
ature correction, the temperature reading may need adjusting. The following steps must be performed with the sensor in the process or in a grab sample. For the most accurate results, standardization should be performed at or near operating temperature.
1. Observe the analyzer temperature reading by pressing the TEMP key. Allow the reading to sta­bilize to insure that the sensor has acclimated to the process temperature.
2. Compare the analyzer reading to a calibrated temperature reading device. If the reading requires adjusting, proceed to Step 3, otherwise, go to Section 5.1.3.
3. Press the TEMP key then the SELECT key to correct the temperature display. The analyzer will display “AdJ” briefly, then the Numeric Display will show with digit flashing.
4. SCROLL (Ð) and SHIFT (Ô) to display the cor­rect value and ENTER it into memor y. Proceed to Section 5.1.3.
5.1.3 Initial Loop Calibration. Please read the entire
calibration section before proceeding to determine the best plan to follow.
A. Two Point Calibration - Standard Method. This is the recommended procedure for the initial calibration if the process's temperature slope is unknown. If any of the steps below are impossible or impractical, refer to the alternate Section 5.1.3 B.
1. Obtain a grab sample of the process to be meas­ured.
2. Determine the sample's conductivity using a cali­brated bench or portable analyzer. The analyzer must be able to reference the conductivity to 25ÞC, or the solution must be measured at 25ÞC. Note the reading. Insure that the analyzer is in hold. Press the HOLD key twice and observe the solid flag.
3. Immerse the analyzer's sensor into the process solution. The sensor body must be held away from the bottom and sides of the sample's con­tainer and the sensor cable must not be allowed to contact the solution. Shake the sensor to ensure that no air bubbles are present.
4. Adjust the sample's temperature to either the nor­mal high or normal low temperature of the process. To raise the sample's temperature, a hot plate with stirrer is recommended. To lower the process temperature, place the grab sample's container in an ice bath or let it slowly cool down.
32
MODEL 1054A C SECTION 5.0
START-UP AND CALIBRATION
A.Two Point Calibration. (continued)
5. Allow the sensor to acclimate to the solution. (The temperature reading should be stable.)
6. Press the CAL key. 15t displays briefly (if 2nd dis- plays, press CAL again), then the Numeric Adjustment window displays.
7. SCROLL (Ð) and SHIFT (Ô) to display the grab sample's conductivity value at 25ÞC as noted in Step 2, then ENTER into memory.
8. Adjust the sample's temperature to the other nor­mal temperature extreme of the process. To raise the sample's temperature, a hot plate with stirrer is recommended. To lower the process temperature, place the grab sample container in an ice bath.
9. Allow the sensor to acclimate to the solution. (The temperature reading should be stable.)
10. Press the CAL key. 15t displays briefly (If “2nd” dis- plays, press CAL again), then the Numeric Adjustment window displays.
11. SCROLL (Ð) and SHIFT (Ô) to display the grab sample's conductivity value 25ÞC as noted in Step 2, then ENTER into memory.
The analyzer will then calculate the true cell constant and the temperature slope then return to reading con­ductivity. The temperature slope of the process can now be read. Press the SLOPE key twice. The display will show “SLP” briefly then the calculated slope for the two calibration points. Place the sensor in the process, then remove the analyzer from hold by pressing the HOLD key twice again.
The slope may be calculated from the following formula:
% SLOPE/ÞC=
Conductivity T
max
(
Conductivity T
min
—1
)
³T
X100
Where: Conductivity T
max
is the conductivity at the
maximum process temperature, Conductivity T
min
is the conductivity at the lower process temperature, and the ³T is the difference between the maximum and minimum process temperature.
EXAMPLE:
% SLOPE/ÞC=
45K
(
35K
—1
)
X100
60-50=10
=2.8%/ÞC
B. Single Point Calibration - Slope Known. This is the recommended procedure for the initial calibration if the temperature slope of the process is known.
If you do not know the exact temperature slope value, but wish to approximate it, refer to the following guide. However, the conductivity reading may have reduced accuracy compared to the value if the procedure in Section A is performed.
Acids: 1.0 to 1.6% per ÞC Bases: 1.8 to 2.2% per ÞC Salts: 2.2 to 3.0% per ÞC Water: 2.0% per ÞC
1. Press the SLOPE key twice. The analyzer will dis- play “SLP” briefly, then show the temperature slope in memory.
2. SELECT to change the value. The analyzer will display “AdJ” briefly, then show the Numeric Display window.
3. SCROLL (Ð) and SHIFT (Ô) to display the proper temperature slope for the process to be meas­ured, then ENTER into memory.
4. Obtain a grab sample of the process to be measured.
5. Determine the conductivity of the sample using a calibrated bench instrument or portable analyzer. The instrument must be able to reference the con­ductivity to 25ÞC or the solution must be meas­ured at 25ÞC. Note the reading. Insure that the analyzer is in hold. Press the HOLD key twice and observe the solid flag.
6. Press the COND key once then press the SELECT key once. “Std” will display followed by the Numeric Display with digit flashing.
7. SCROLL (Ð) and SHIFT (Ô) to display the con­ductivity value you noted in Step 5, then ENTER it into memory.
8. Install the sensor in the process, then remove the analyzer from hold by pressing the HOLD key twice.
The analyzer will calculate the true cell constant after the initial calibration.
33
5.1.4 Routine Standardization. The sensor should
be standardized routinely if it is suspected that the process might degrade or coat the sensor. When a sensor cell constant is entered CEL is set to this value and the cell factor Fct is set to 1.000. The first stan­dardization recalculates the cell constant CEL. Subsequent standardizations will change the cell fac­tor Fct. Refer to Section 8.2.6 for a description of the cell factor.
To perform a standardization do the following:
1. Take a grab sample which is as close to the sen­sor as possible. Write down the value the analyz­er is reading at this time (C1).
2. Measure the conductivity of the grab sample using a calibrated bench analyzer referenced to 25ÞC/77ÞF or measured at 25ÞC. Write down this value (C2).
3. Before entering the reference value, note the value the analyzer is reading now (C3) and com­pare it to the value in Step 1. This accounts for the change while the grab sample is being meas­ured.
4. Press the COND key once, then press SELECT. Std will display briefly followed by the Numeric display with flashing digit.
5. The corrected conductivity reference value may be determined by multiplying the value in Step 2 (C
2
) by the value noted in Step 3 (C3) and dividing the product by the analyzer value from Step 1 (C1):
C2x C
3
= CRV
C
1
Enter this corrected reference value in the ana­lyzer using the SCROLL (Ð) and SHIFT (Ô) keys. Then press ENTER.
6. Note the cell factor value Fct. Press the ACCESS key twice quickly. SCROLL (Ð) to Fct press SELECT and note this value. Keep track of this value to determine a sensor cleaning schedule.
5.1.5 Sensor Maintenance. Before performing main­tenance or cleaning of the sensor, the Model 1054A C should be placed in hold. This will place the current output and relays in the states determined in Section 4-6. Before removing the sensor from the process, press the HOLD key twice. The HOLD flag will show to indicate the hold condition.
Always reenter the cell constant and restandardize (Sections 5.1.1 and 5.1.4) after cleaning or replace­ment of the sensor.
Replace the sensor back into the process and press the HOLD key twice again to remove the analyzer from hold. The hold flag will disappear.
MODEL 1054A C SECTION 5.0
START-UP AND CALIBRATION
34
MODEL 1054A C SECTION 6.0
KEYBOARD SECURITY
SECTION 6.0
KEYBOARD SECURITY
7.1 THEORY OF OPERATION. This section is a gen-
eral description of how the analyzer operates. This section is for those users who desire a greater under­standing of the analyzer’s operation.
A square wave measurement circuit in the Model 1054A C Analyzer replaces the typical bridge circuit used in most conductivity analyzers, resulting in improved linearity, accuracy and a broad measure­ment range. The analyzer measures the absolute con­ductivity of the measured process. The analyzer then corrects the conductivity to 25ÞC by accurately meas­uring the process temperature by means of a PT-100 RTD located in the conductivity sensor. The micro­processor also adjusts the amount of correction required for temperature compensation by means of a temperature slope adjustment.
The slope may be adjusted between 0-5%/ÞC either manually via the keyboard or automatically during bench or process calibration. This slope controls the amount of correction required in the temperature compensation circuit, and is specific to the process, giving you the most accurate conductivity reading possible.
The Model 1054A C analyzer can provide conductivi­ty measurements as low as 1 uS/cm and as high as 1000 mS/cm full scale over a process temperature range of 0 to 200ÞC.
Rosemount Analytical also offers a booklet titled “Conductance Data for Commonly Used Chemicals.” This booklet includes measurement theory and conduc­tance information for commonly used chemicals.
6.1 KEYBOARD SECURITY. Display Mnemonic “COd”. Select this feature to display the user defined security code. Any three digit number may be used for this code. “000” will disable the security feature. This item is used to prevent accidental changes to the calibration and configuration of the analyzer. When activated, the analyzer will allow all read functions to read normally. If an attempt is made to change a value, “LOC” will dis­play followed by the Numeric Display ready for the code to be entered. A proper code will unlock the ana­lyzer and the analyzer will return to the last function attempted. Any incorrect value will result in “bAd” briefly displaying. The analyzer will then return to numeric display and await the entry of the code. Once unlocked, the analyzer will allow access to all functions until the analyzer is either powered down or no key­strokes are made for a period of 2 minutes. If the code should be forgotten, pressing and holding the ACCESS key for 5 seconds will result in display of the code. Releasing the ACCESS key, then pressing
ENTER will unlock the analyzer.
6.1.2 Keyboard Security (“COd).
1. Enter Set Mode by pressing ACCESS key twice.
2. SCROLL () until “COd” appears on the display.
3. Press SELECT.
4. SCROLL () and SHIFT (Ô) to display the desired value, then ENTER it into memory.
NOTE
Entering “000” disables the keyboard secu­rity.
NOTE
Security feature will not activate until 2 minutes without keyboard activity or power is removed from the analyzer then restored.
SECTION 7.0
THEORY OF OPERATION
35
MODEL 1054A C SECTION 8.0
DIAGNOSTICS AND TROUBLESHOOTING
SECTION 8.0
DIAGNOSTICS AND TROUBLESHOOTING
Display Description
EEP EEPROM write error (bad EEPROM chip).CHS ROM failure (check sum error) (bad ROM chip).Orn Overrange.SEn Sensor line error or wire length error.
COP Computer not operating properly.
tcH High temperature compensation error. tcL Low temperature compensation error.
Ein Input shorted. rin Sensor miswired.
FAC Factory calibration required.
8.1 DIAGNOSTICS. The Model 1054A C analyzer has a diagnostic feature which automatically searches for fault conditions that would cause an error in the measured conductivity value. If such a condition occurs, the current output and relays will act as con­figured in default and the fault flag and display will flash. A fault code mnemonic will display at frequent intervals. If more than one fault condition exists, the display will sequence the faults at one second inter­vals. This will continue until the cause of the fault has been corrected. Display of fault mnemonics is sup­pressed when in Set Mode. Selecting the “SHO” item will display a history of the two most recent fault con­ditions unless “SHO” was cleared (Refer to Section
4.6).
NOTE
If the analyzer is in hold and a fault occurs, the mnemonic “HLd” will display during the fault sequence.
8.1.1 Fault Mnemonics. Table 8-1 lists the fault mnemonics and describes the meaning of each.
8.1.2 Temperature Compensation. Table 8-2 is a
ready reference of RTD resistance values at various temperatures. These are used for test and evaluation of the sensor.
NOTE
Ohmic values are read across the T.C. element and are based on the stated values (R
O
± .12%). Allow enough time for the T.C. element to stabilize to the surrounding temperature. Each 1ÞC change corresponds to a change of
0.385 ohms.
TABLE 8-1. Fault Mnemonics
TABLE 8-2. RTD Resistance Values
Temperature Resistance
0ÞC 100 ohms
10ÞC 103.90 ohms 20ÞC 107.70 ohms 25ÞC 109.62 ohms 30ÞC 111.67 ohms 40ÞC 115.54 ohms
50ÞC 119.40 ohms
60ÞC 123.24 ohms 70ÞC 127.07 ohms 80ÞC 130.89 ohms 90ÞC 134.70 ohms
100ÞC 138.50 ohms
110ÞC 142.29 ohms 120ÞC 146.06 ohms 130ÞC 149.82 ohms 140ÞC 153.58 ohms
150ÞC 157.31 ohms
160ÞC 161.04 ohms 170ÞC 164.76 ohms 180ÞC 168.46 ohms 190ÞC 172.16 ohms
200ÞC 175.84 ohms
MODEL 1054A C SECTION 8.0
DIAGNOSTICS AND TROUBLESHOOTING
8.2 TROUBLESHOOTING. The Model 1054A C ana-
lyzer is designed with the state of the art micro­processor circuitry. This design incorporates pro­grammed features that provide constant monitoring for fault conditions, and the reporting of these faults via Mnemonics on the instrument display screen. This aids in determining where to start checking for the cause of failures, and in some instances, the ability to see changes that can be used to predict future degen­eration of assemblies before their complete failure.
8.2.1 Analyzer Installation. After completion of instal­lation the instrument should be checked for operation. Normally this would consist of Powering up the instru­ment and checking for:
1. A self diagnostic fault display. Refer to Table 8-1 for brief description of problem indicated by mnemonic. Table 8-3 provides a more compre­hensive problem explanation and actions that may help solve the problem.
2. A conductivity reading that is approximately cor­rect. (Depending upon sensor installation in either air or process.) Refer to Section 8.2.2 for sensor checks.
3. Pressing several of the keypads to determine whether programming appears to be operational. Table 8-3 explains problems and actions that may be helpful in solving them.
4. Checking output for 4-20 mA output current.
8.2.2 After Operation. Troubleshooting this instrument
after previous operation should follow normal trou­bleshooting procedures. Check display. If power is O.K. the display mnemonic will direct you to the basic area of malfunction (Sensor, Printed Circuit Boards, calibration, or temperature compensation).
Use Tables 8-1 and 8-3 to determine area, possible problem and actions to take to remedy fault.
Evaluate instrument electronics. This can be accomplished by simulating a known conductivity input and observation of instrument operation. To sim­ulate sensor operation with known conductivity inputs, use the following procedures.
1. Disconnect the Sensor input leads from TB2-1, 3, 6, and 7.
2. Install decade box or resistor leads to TB2-1 and 3. (If decade box is not available, simulate desired conductivity input by either calculating using the formula given in Figure 8-1, or by using the Conductivity vs. resistance Table in Figure 8-1.)
3. Install a jumper between TB2-6 and 7. Check
wiring with Figure 8-1.
4. Power up instrument and enter “SEt” menu.
5. Turn “Atc” to “off”.
6. Set manual temperature compensation to 25°C (See Section 4.4 and Figure 4-4).
7. Set Cell constant to 1.0 (See Section 5.1.1).
8. Evaluate analyzer response with previous responses.
Faulty display. If a faulty display is suspected, enter the SET menu and scroll through to the “dtS” option. This option will activate all display segments. See Figure 3-1, Keyboard Overlay).
Output Circuit Testing. To check for problems in the output circuit, bypass the sensor input and analyzer calculations by setting a known output current and checking item driven by output current and checking the operation of valves, pumps, recorders, etc. For directions on how to set output current, refer to Section
4.9.
8.2.2 Sensor Troubleshooting. In addition to the sen-
sor fault mnemonics, the analyzer can display infor­mation pertinent to determining if sensor has become coated, or if there is a conductivity versus temperature problem, or an application problem.
Sensor Coated. As the cell becomes coated, or affected by the process, the cell factor will change. Tracking this change in cell factor will prevent use of a sensor that has lost its sensitivity because of contam­ination or damage.
CAUTION
Standardizing the instrument results in the cell factor being returned to 1.0.
This instrument tracks the change in calculated cell factor from the initial cell factor value of 1.0 every time the unit is standardized. The cell factor should be checked and tracked to set up a regular maintenance schedule and can be seen in the following manner:
1. Press ACCESS key twice.
2. SEt” will be displayed briefly followed by “Cin”.
3. SCROLL () to display “Fct” and press SELECT.
4. To return to normal operation, press COND.
36
37
MODEL 1054A C SECTION 8.0
DIAGNOSTICS AND TROUBLESHOOTING
Absolute Conductivity. As an aid in determining
whether a problem exists in the conductivity section of the sensor or analyzer, or the temperature compensating circuits, the absolute conductivity (the uncorrected con­ductivity value, without temperature compensation) of the process can be displayed. To do so:
1. Press ACCESS key twice.
2. SEt” will be displayed briefly followed by “Cin”.
3. SELECT Cin” to read the absolute conductivity.
4. To return to normal operation, press COND. Temperature Sensor accuracy. If the temperature
sensor in the conductivity sensor is suspect, measur­ing the resistance across the T.C. element and com­paring the corresponding temperature reading can be used in the evaluation of the sensor. Allow enough time for the T.C. element to stabilize to the surrounding temperature. Each 1°C change corresponds to a change of 0.385 ohms.
8.2.3 Subassembly replacement considerations. CPU Board Replacement. If a problem exists on the
CPU board, and replacement is required, specific pro­cedures included with the new board must be followed or the microprocessor will be improperly programmed. Should this occur , it will be necessary to return the ana­lyzer to the factory for reprogramming.
Power Board Replacement. If it becomes necessary to replace the power board, the CPU board will need to be recalibrated following the specific procedures that are included with the power board. Failure to fol­low these procedures exactly will cause the micro­processor to be improperly programmed and require the return of the analyzer to the factory for reprogram­ming.
38
MODEL 1054A C SECTION 8.0
DIAGNOSTICS AND TROUBLESHOOTING
TABLE 8-3. Troubleshooting Guide
SYMPTOM PROBLEM ACTION
Fct” below 0.5 or above 2.0. 1. Old or coated sensor. 1. Clean or replace sensor. Actual range determined by user.
Analyzer value not the same 1. Grab sample incorrect. 1. Re-evaluate sample technique as grab sample of process. and equipment.
2. Unclear what is correct. 2. Bench test analyzer.
3. Analyzer out of calibration. 3. Recalibrate per Start-up and Calibration Section.
Fault code “tcH”/“tcL”/“rin”. 1. Miswire. 1. Check wiring between the
sensor and analyzer.
2. Open or shorted RTD. 2. Replace sensor.
Fault code “Orn”. 1. Process conductivity 1. Replace sensor with a sensor
too high for sensor in use. which has a higher cell constant
2. Process upset. (see Table 1-1).
2. Check for process control problem.
Fault code “SEn”. 1. Open wire between sensor 1. Repair wire/check connection.
and analyzer.
2. Cable length has been exceeded. 2. Locate analyzer within 250 ft.
Maximum cable length 250 ft. of sensor. Fault code “EEP”. 1. Defective EEPROM. 1. Replace CPU PCB. Fault code “CHS”. 1. Defective CPU. 1. Replace CPU PCB. No alarm relay closure. 1. Defective power card. 1. Replace power PCB.
2. Defective CPU. 2. Replace CPU PCB.
No output current. 1. Defective power board. 1. Replace power PCB.
2. M i swired. 2. Check for short.
Low output current. 1. Circuit loading with excessive 1. Consult output loading limits
resistance on output. Model 1054A C specifications
(600 ohms max load).
Zero conductivity reading. 1. Sensor miswired. 1. Repair wire/connection.
2. Solids coating sensor. 2. Clean sensor.
3. Open wire in sensor. 3. Replace sensor or tube.
Fault code “Ein”. 1. Sensor miswired. 1. Repair wire connection. Very high conductivity reading. 2. Shorted sensor. 2. Replace sensor or tube.
23053-00 Mounting Bracket, 2-inch Pipe 23054-01 Mounting Bracket, Wall, with Junction box 2001492 Stainless Steel Tag (specify marking)
39
MODEL 1054A C SECTION 8.0
DIAGNOSTICS AND TROUBLESHOOTING
P/N DESCRIPTION QUANTITY
22966-00 PCB, LCD Digital Display 23025-01 Panel Mounting Kit 1 23056-02 PCB, 115V Power Supply 23056-03 PCB, 230V Power Supply 23124-07 PCB, CPU, Conductivity 23245-01 PCB, LED Digital Display 23268-01 Heater Kit, 115V, Wall Mounting Enclosure 23268-02 Heater Kit, 230V, Wall Mounting Enclosure 23316-00 PCB, Motherboard 23319-00 Keyboard Overlay, Conductivity, LCD Version 23319-01 Keyboard Overlay, Conductivity, LED Version 32934-00 Enclosure 32936-00 Enclosure, Rear Cover 32937-00 Gasket, Rear Cover 9100153 Fuse, 0.125, 2AG, 250V 2 9100157 Fuse, 0.1A, 3AG, 250V, Slo Blo 2
TABLE 8-4. Replacement Parts
Accessories
40
MODEL 1054A C SECTION 8.0
DIAGNOSTICS AND TROUBLESHOOTING
8.2.10 Instrument Electronic Check. This procedure
will allow the operation of the analyzer to be evaluated by simulating a known conductivity input.
1. Disconnect the conductivity sensor input leads from TB2-1, 3, 6 and 7. Install decade box or resistor leads to TB2-1 and 3 and a jumper to TB2-6 and 7 (see Figure 8-1).
2. With instrument power on, enter the SEt menu and turn Atc to oFF. Set manual temperature compen­sation to 25°C (see Section 4.4 and Figure 4-4).
3. Set cell constant to 1.0 (see Section 5.1.1).
4. To simulate a desired conductivity input, an appropriate resistance value may be calculated by Formula or selected from the conductivity (µmhos) vs resistance (ohms) table (see Figure 8-
1).
5. Simulate conductivity input and evaluate the ana­lyzer response.
Formula:
1
Conductivity =
____________
X 1,000,000
Resistance
Table:
Conductivity (µmhos) vs Resistance (ohms)
10 100,000
100 10,000
1,000 1,000 10,000 100 20,000 50
FIGURE 8-1. Simulate Conductivity Input
41
Model 1054A C SECTION 9.0
RETURN OF MATERIAL
SECTION 9.0
RETURN OF MATERIAL
9.1 GENERAL. To expedite the repair and return of
instruments, proper communication between the cus­tomer and the factory is important. A return material authorization (RMA) number is required. Call 714 863-1181. The "Return of Materials Request" form is provided for you to copy and use in case the situation arises. The accuracy and completeness of this form will affect the processing time of your materials.
9.2 WARRANTY REP AIR. The following is the proce­dure for returning instruments still under warranty.
1. Contact the factory for authorization.
2. Complete a copy of the “Return of Materials Request” form as completely and accurately as possible.
3. To verify warranty, supply the factory sales order number or the original purchase order number. In the case of individual parts or sub-assemblies, the serial number on the mother unit must be sup­plied.
4. Carefully package the materials and enclose your “Letter of Transmittal” and the completed copy of the “Return of Materials Request” form. If possi­ble, pack the materials in the same manner as it was received.
IMPORTANT
Please see second section of “Return of Materials Request Form”. Compliance to the OSHA requirements is mandatory for the safety of all personnel. MSDS forms and a certification that the instruments have been disinfected or detoxified are required.
5. Send the package prepaid to: Rosemount Analytical Inc.
2400 Barranca Parkway Irvine, CA 92714
Attn: Factory Repair Mark the package: Returned for Repair
RMA# __________________ Model No. ______________
9.3 NON WARRANTY REPAIR.
1. Contact the factory for authorization.
2. Fill out a copy of the “Return of Materials Request” form as completely and accurately as possible.
3. Include a purchase order number and make sure to include the name and telephone number of the right individual to be contacted should additional information be needed.
4. Do Steps 4 and 5 of Section 6.2.
NOTE
Consult the factory for additional infor­mation regarding service or repair.
Loading...