Rosemount 0085 Operating Manual

Page 1
Rosemount™ Pipe Clamp Sensor
Reference Manual
00809-0100-4952, Rev CA
May 2016
Page 2
Page 3
Reference Manual
Contents
1Section 1: Introduction
2Section 2: Installation
Contents
May 2016
1.1 Using this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Product recycling/disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.1 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Receiving and inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3.1 Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.4 Installation flowchart and checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.5 Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5.1 Tools and supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.6 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.6.1 Standard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.6.2 Rosemount X-well Technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3Section 3: Troubleshooting
3.1 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.2 Service support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.3 Return of materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
AAppendix A: Specifications and Reference Data
A.1 Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
A.2 How to order Rosemount X-well Technology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
A.3 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
BAppendix B: Product Certifications
B.1 European Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
B.2 Ordinary Location Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
B.3 Installing Equipment in North America . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
B.4 North America . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
B.5 Europe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
B.6 International . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Content s
B.7 EAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
B.8 Installation drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
iii
Page 4
Contents
May 2016
Reference Manual
00809-0100-4952, Rev CA
iv
Contents
Page 5
Reference Manual
NOTICE
00809-0100-4952, Rev CA
Rosemount™ 0085 Pipe Clamp Sensor
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
The United States has two toll-free assistance numbers and one International number.
Customer Central
1-800-999-9307 (7:00 A.M. to 7:00 P.M. CST)
International
1-(952) 906-8888
National Response Center
1-800-654-7768 (24 hours a day) Equipment service needs
Title Page
May 2016
Explosions could result in death or serious injury.
Do not remove the housing cover in explosive atmospheres when the circuit is live.Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments in
the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Verify the operating atmosphere of the sensor is consistent with the appropriate hazardous locations
certifications.
Housing cover must be fully engaged to meet explosion-proof requirements.
Failure to follow these installation guidelines could result in death or serious injury.
Make sure only qualified personnel perform the installation.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and the terminals.
The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Emerson
Process
Management Sales Representative.
This device is intended for use in temperature monitoring applications and should not be used in control and safety applications.
Title Page
v
Page 6
Title Page
May 2016
Reference Manual
00809-0100-4952, Rev CA
vi
Title Page
Page 7
Reference Manual
00809-0100-4952, Rev CA

Section 1 Introduction

1.1 Using this manual

This product manual provides installation, configuration, troubleshooting, and maintenance instructions for the Rosemount
Section 2: Installation
Installation flowchart and checklist
Receiving and inspection
Functional limitations
Mounting and installation
Wiring to transmitter/connection head
Section 3: Troubleshooting
Service support
Return of materials
0085 Pipe Clamp Sensor.
Introduction
May 2016
Appendix A: Specifications and Reference Data
Ordering information
Dimensional drawings
Appendix B: Product Certifications
Product certifications
Installation drawings

1.2 Product recycling/disposal

Recycling of equipment and packaging should be taken into consideration and disposed of in accordance with local and national legislation/regulations.
Introduction
1
Page 8
Introduction
May 2016
Reference Manual
00809-0100-4952, Rev CA
2
Introduction
Page 9
Reference Manual
00809-0100-4952, Rev CA

Section 2 Installation

Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Receiving and inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Installation flowchart and checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7

2.1 Safety messages

Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations. Refer to the following safety messages before performing any operation in this section.
Installation
May 2016
Explosions could result in death or serious injury.
Do not remove the housing cover in explosive atmospheres when the circuit is live.Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments in
the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Verify the operating atmosphere of the sensor is consistent with the appropriate hazardous locations
certifications.
Housing cover must be fully engaged to meet explosion-proof requirements.
Failure to follow these installation guidelines could result in death or serious injury.
Make sure only qualified personnel perform the installation.
Installation
3
Page 10
Installation
6-in. 6-in.
May 2016

2.2 Receiving and inspection

The Rosemount™ 0085 Pipe Clamp Sensor comes in several different types of materials and clamp sizes so it's important to inspect and verify the appropriate model was delivered before installation.
Upon receipt of the shipment, check the packing list against the material received and the purchase order. Report any damage to the carrier.

2.3 Considerations

Information in this manual applies to circular pipes only. Consult Emerson™ Process Management Customer Central for instruction regarding other uses.
2.3.1 Limitations
Functional
The most accurate and repeatable surface temperature measurement occurs with the following insulation best practices:
Use weather proof insulation with aluminum cladding.Apply a minimum of six inches of installation on each side of the pipe clamp sensor.Insulate the sensor extension.Install insulation with minimal gaps to isolate sensor as much as possible from ambient conditions.
Reference Manual
00809-0100-4952, Rev CA
Figure 2-1. Pipe Clamp Insulation Drawing
4
Installation
Page 11
Reference Manual
Start
Unpack instrument
Review Reference Manual
Verify proper installation location Steps 1, 2
Bench
configure?
See appropriate Reference Manual for
bench configuration information
YES
NO
Verify model indicated on tagStep 4
Remote
mounted
transmsitter?
Install hardware
YES
NO
Install transmitter
Steps 5 - 7
Steps 5 - 7
Install Pipe Clamp Sensor
Wire sensor
Remote
mounted
transmsitter?
YES
Comission the transmitter
See appropriate Reference Manual for
bench configuration information
Steps 8 - 10
NO
Finish
00809-0100-4952, Rev CA

2.4 Installation flowchart and checklist

Figure 2-2 is an installation flowchart that provides guidance through the installation process. Following
the figure, an installation checklist has been provided to verify that all critical steps have been taken in the installation process. The checklist numbers are indicated in the flowchart.
Figure 2-2. Installation Chart
Installation
May 2016
Installation
5
Page 12
Installation
May 2016
The following list is a summary of the steps required to complete a pipe clamp sensor installation.
1. Determine where the pipe clamp sensor is to be placed within the piping system.
2. Establish the proper orientation as determined by the intended application.
3. Confirm the configuration.
4. Mount the sensor and tighten the clamp bolts.
5. Check the fit-up of the instrument assembly to the pipe.
6. Check for full contact between RTD sensor tip and pipe.
7. Wire the instrument.
8. Supply power to the transmitter.
9. Commission the instrument.

2.5 Mounting

2.5.1 Tools and supplies
Reference Manual
00809-0100-4952, Rev CA
Tools required include the following:
Open end or combination wrenches (spanners) pipe clamp bolts and nuts:
16 mm (
Adjustable wrench: 40 mm (1Standard screwdrivers: 3.5 mm (#1Phillip's screwdriverHex wrench: 3 mm (Wire cutters/strippers
11
/16-in.), 18 mm (3/4-in.), 24 mm (1-in.), 30 mm (13/16-in.), 36 mm (17/16-in.)
1
/2-in.) jaw
1
/8-in.) and 6 mm (1/4-in.)
9
/64-in.)
Supplies required include the following:
Pipe compound or PTFE tape (where local piping codes allow)
6
Installation
Page 13
Reference Manual
00809-0100-4952, Rev CA

2.6 Installation

2.6.1 Standard
Step 1: determine the proper orientation
The pipe clamp sensor should be mounted in a secure position to ensure there is no rotational movement after installation. The mounting best practice is to install the sensor vertically.
Step 2: install the pipe clamp sensor
Mount the pipe clamp sensor and tighten the bolts.
Step 3: install the transmitter
See appropriate transmitter reference manual for sensor-transmitter installation.
Step 4: commission the transmitter
See appropriate transmitter reference manual for transmitter commissioning instructions.
Installation
May 2016
Figure 2-3. Sensor Lead Wire Termination
Pipe clamp RTD flying leads and spring loaded
Single element 3-wire
Rosemount X-well
Red
Red
White
Single element 4-wire Dual element 3-wire
Red
Red
White White
Black
Red Red
Green
Blue Blue
Installation
7
Page 14
Installation
May 2016
2.6.2 Rosemount X-well Technology
Rosemount X-well Technology is only available as a Rosemount 648 Wireless Temperature Transmitter and Rosemount 0085 Pipe Clamp Sensor assembly. In general, pipe clamp sensor installation best practices shall be followed with Rosemount X-well Technology specific requirements noted below:
1. Direct mounting of transmitter on pipe clamp sensor is required for Rosemount X-well Technology to properly function.
2. Transmitter head shall be placed away from dynamic external temperature sources such as a boiler.
3. Insulation ( to transmitter head to prevent heat loss. Apply a minimum of six inches of insulation on each side of the pipe clamp sensor. Care should be taken to minimize air gaps between insulation and pipe.
Note
DO NOT apply insulation over transmitter head.
4. A clean contact surface is recommended to ensure sensor to pipe contact. The use of thermal grease or paste is not recommended as it may negatively impact the accuracy of the calculation.
5. Although it will come factory configures as such, ensure the pipe clamp RTD sensor is assembled in a 3-wire configuration. See Figure 2-3 for more information.
1
/2-in. thick minimum) is required over the sensor clamp assembly and sensor extension up
Reference Manual
00809-0100-4952, Rev CA
8
Installation
Page 15
Reference Manual
00809-0100-4952, Rev CA

Section 3 Troubleshooting

Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 9
Service support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 9
Return of materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 11

3.1 Safety messages

Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations. Refer to the following safety messages before performing any operation in this section.
Explosions could result in death or serious injury.
Do not remove the housing cover in explosive atmospheres when the circuit is live.Housing cover must be fully engaged to meet explosion-proof requirements.Before connecting a communicator in an explosive atmosphere, make sure the instruments in the
loop are installed in accordance with intrinsically safe or nonincendive field wiring practices.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and the terminals.
Troubleshooting
May 2016

3.2 Service support

If a malfunction is suspected despite the absence of a diagnostic message on the communicator display, follow the procedures described below to verify the Rosemount
process connections are in good working order. Always approach the most likely and easiest-to-check conditions first.
Symptom Possible source Corrective action
Tra nsmi tter does not communicate with Field Communicator
Loop wiring
Pipe Clamp Sensor, transmitter, and
Check the revision level of the transmitter device descriptors (DDs) stored in your communicator. The communicator should report Dev v4, DD v1 (improved), or reference “Field Communicator” for previous versions. Contact Emerson Customer Central for assistance.
Check for a minimum of 250 ohms resistance between the power supply and Field Communicator connection.
Check for adequate voltage to the transmitter. If a Field Communicator is connected and 250 ohms resistance is properly in the loop, then the transmitter requires a minimum of 12.0 V at the terminals to operate (over entire 3.5 to 23.0 mA operating range), and 12.5 V minimum to communicate digitally.
Check for intermittent shorts, open circuits, and multiple grounds.
Process Management
Troubleshooting
9
Page 16
Troubleshooting
May 2016
Symptom Possible source Corrective action
Connect a Field Communicator and enter the transmitter test mode to isolate a sensor failure.
Check for a sensor open circuit.
Check if the process variable is out of range.
Check for dirty or defective terminals, interconnecting pins, or receptacles.
Check the output voltage of the power supply at the transmitter terminals. It should be 12.0 to 42.4 Vdc (over entire 3.5 to 23.0 mA operating range).
Connect a Field Communicator and enter the transmitter test mode to isolate module failure.
Connect a Field Communicator and check the sensor limits to ensure calibration adjustments are within the sensor range.
Check for adequate voltage to the transmitter. It should be 12.0 to
42.4 Vdc at the transmitter terminals (over entire 3.5 to 23.0 mA operating range).
Check for intermittent shorts, open circuits, and multiple grounds.
Connect a Field Communicator and enter the loop test mode to generate signals of 4 mA, 20 mA, and user-selected values.
Connect a Field Communicator and enter the transmitter test ode to isolate module failure.
Connect a Field Communicator and enter the transmitter test mode to isolate module failure.
Check if the process variable is out of range.
Check for adequate voltage to the transmitter. It should be 12.0 to
42.4 Vdc at the transmitter terminals (over entire 3.5 to 23.0 mA operating range).
Check for shorts and multiple grounds.
Check for proper polarity at the signal terminal.
Check the loop impedance.
Connect a Field Communicator and enter the loop test mode.
Check wire insulation to detect possible shorts to ground.
High output
Erratic output
Low output or no output
Sensor input failure or connection
Loop wiring
Power supply
Electronics module
Loop wiring
Electronics module
Sensor element
Loop wiring
Reference Manual
00809-0100-4952, Rev CA
10
Electronics module
Connect a Field Communicator and check the sensor limits to ensure calibration adjustments are within the sensor range.
Connect a Field Communicator and enter the transmitter test mode to isolate an electronic module failure.
Troubleshooting
Page 17
Reference Manual
00809-0100-4952, Rev CA

3.3 Return of materials

To expedite the return process, call the Rosemount National Response Center toll-free at 800-654-7768. This center, available 24 hours a day, will assist you with any needed information or materials.
The center will ask for the following information:
Product modelSerial numbersThe last process material to which the product was exposed
The center will provide:
A return material authorization (RMA) numberInstructions and procedures that are necessary to return goods that were exposed to hazardous
substances
Note
If a hazardous substance is identified, a Material Safety Data Sheet (MSDS), required by law to be available to people exposed to specific hazardous substances, must be included with the returned materials.
Troubleshooting
May 2016
Troubleshooting
11
Page 18
Troubleshooting
May 2016
Reference Manual
00809-0100-4952, Rev CA
12
Troubleshooting
Page 19
Reference Manual
00809-0100-4952, Rev CA
Specifications and Reference Data
May 2016

Appendix A Specifications and Reference Data

Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 13
How to order Rosemount X-well Technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 16
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 18

A.1 Ordering information

Table A-1. Rosemount™ Pipe Clamp Sensor Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
The Expanded offering is subject to additional delivery lead time.
Model Product description
0085 Non Intrusive Pipe Clamp Sensor
Code Connection head IP rating Conduit entry
C Connection head Rosemount, aluminum 66/68 M20 1.5
D Connection head Rosemount, aluminum 66/68
1
/2-in. NPT
G Connection head Rosemount, stainless steel 66/68 M20 1.5
H Connection head Rosemount, stainless steel 66/68
1
/2-in. NPT
N No connection head 66/68 N/A
1 Connection head Rosemount, aluminum with LCD display cover 66/68 M20 1.5
2 Connection head Rosemount, aluminum with LCD display cover 66/68
1
/2-in. NPT
3 Connection head Rosemount, stainless steel with LCD display cover 66/68 M20 1.5
4 Connection head Rosemount, stainless steel with LCD display cover 66/68
1
/2-in. NPT
Sensor connection
3 Spring loaded adapter
5 Spring loaded adapter with terminal block
Sensor type Temperature range
P1 RTD, single element, 4-wire, silver tip -50 to 300 °C (-58 to 572 °F)
P2 RTD, dual element, 3-wire, silver tip -50 to 300 °C (-58 to 572 °F)
P3 RTD, single element, 4-wire, nickel tip -200 to 300 °C (-328 to 572 °F)
P4 RTD, dual element, 3-wire, nickel tip -200 to 300 °C (-328 to 572 °F)
Extension type Head connection
J Nipple-union None
N No extension (sensor only option)
Instrument connection
1
/2-in. NPT Stainless steel
Material
Extension length (N) in mm
0080 80 mm
0150 150 mm
XXXX Non standard lengths 200–500 mm (available in 50 mm increments)
Specifications and Reference Data
13
Page 20
Specifications and Reference Data
May 2016
Reference Manual
00809-0100-4952, Rev CA
Table A-1. Rosemount™ Pipe Clamp Sensor Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
The Expanded offering is subject to additional delivery lead time.
Pipe clamp material
N No clamp (sensor only option)
P ASTM 304 SST (1.4301)
B Duplex F51 (1.4462)
C Carbon steel (1.0037)
Inner diameter (D)
0022 22 mm
(1)
Suitable pipe size (inch)
1
/2-in. DN15 30 5 mm, M10
Suitable pipe size (DIN)
Clamp/bolt dimensions
0034 34 mm 1-in. DN25 30 5 mm, M10
0061 61 mm 2-in. DN50 40 6 mm, M12
0089 89 mm 3-in. DN80 40 6 mm, M12
0115 115 mm 4-in. DN100 50 8 mm, M16
0140 140 mm 5-in. DN125 50 8 mm, M16
0169 169 mm 6-in. DN150 50 8 mm, M16
0220 220 mm 8-in. DN200 50 8 mm, M16
0273 273 mm 10-in. DN250 60 8 mm, M20
0027 27 mm
3
/4-in. DN20 30 5 mm, M10
0030 30 mm N/A DN25 30 5 mm, M10
0043 43 mm 11/4-in. DN32 30 5 mm, M10
0049 49 mm 11/2-in. DN40 30 5 mm, M10
0077 77 mm 21/2-in. DN65 40 6 mm, M12
0159 159 mm N/A DN150 50 8 mm, M16
0306 306 mm N/A N/A 60 8 mm, M20
0324 324 mm 12-in. DN300 60 8 mm, M20
0356 356 mm 14-in. DN350 60 8 mm, M20
0368 368 mm N/A DN350 60 8 mm, M20
0407 407 mm 16-in. DN400 60 8 mm, M20
0458 458 mm 18-in. DN450 70 10 mm, M24
0508 508 mm 20-in. DN500 70 10 mm, M24
0521 521 mm N/A DN500 70 10 mm, M24
0610 610 mm 24-in. DN600 70 10 mm, M24
0660 660 mm 26-in. N/A 70 10 mm, M24
0720 720 mm N/A N/A 70 10 mm, M24
0762 762 mm 30-in. N/A 70 10 mm, M24
0813 813 mm 32-in. DN790 70 10 mm, M24
0915 915 mm 36-in. DN900 70 10 mm, M24
1016 1016 mm 40-in. DN1000 70 10 mm, M24
14
Specifications and Reference Data
Page 21
Reference Manual
Specifications and Reference Data
00809-0100-4952, Rev CA
Table A-1. Rosemount™ Pipe Clamp Sensor Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
The Expanded offering is subject to additional delivery lead time.
1070 1070 mm 42-in. N/A 70 10 mm, M24
1219 1219 mm 48-in. N/A 70 10 mm, M24
Corrosion protection inlay
May 2016
N None
A Material NBR
Options (include with selected model number)
Sensor options
A1 Single element class A sensor from -50 to 300 °C (-58 to 572 °F)
A2 Dual element class A sensor from -50 to 300 °C (-58 to 572 °F)
Assemble to option
XA Assemble sensor to specific temperature transmitter
Cable gland options
G2 Cable gland, Ex d, brass, 7.5–11.9 mm
G7 Cable g land, M20 1.5, Ex e, blue, polyamide, diam 5–9 mm
Product certifications
E1 ATEX Flam eproof
E7 IECEx Flameproof and Dust
E5 FM Explosion-proof
E6 CSA Explosion-proof
EM Technical Regulations Customs Union (EAC) Flameproof
Cover chain option
G3 Cover chain (only available with Rosemount connection head material codes C, D, G, and H)
Product certifications
LT Special material to meet extended temperature rage of -51 °C
Typical pipe clamp model number: 0085 C 3 P 1 J 0080 P 0061 N
Replacement sensor only model number: 0085 N3 P 1 N 0080 N 0061 N
1. When selecting this option in regards to Rosemount X-well Technology, refer to “How to order Rosemount X-well Technology” on page 16.
Specifications and Reference Data
15
Page 22
Specifications and Reference Data
May 2016
Reference Manual
00809-0100-4952, Rev CA

A.2 How to order Rosemount X-well Technology

Rosemount X-well Technology is only available as a Rosemount 648 Wireless Temperature Transmitter and Rosemount 0085 Pipe Clamp Sensor direct mount assembly.
The Rosemount 648 Wireless option code requirements are:
PT Temperature measurement assembled with Rosemount X-well Technology
XA Sensor specified separately and assembled to transmitter
C1 Custom configuration of date, descriptor, message, and wireless parameters (requires CDS with order)
The Rosemount 0085 Pipe Clamp Sensor option code requirements are:
N No connection head
3 Sensor connection
P1 Sensor type
J Extension type
0080 Extension length
XA Assemble sensor to specific temperature transmitter
Rosemount X-well assemblies are available in most Rosemount 0085 Pipe Clamp sensor diameter sizes depending on the pipe schedule. The pipe diameters that correspond to the pipe schedules are:
Pipe schedule 40 and 80 Pipe schedule 40 and 80
Code
0022
0027
0034 1-in. DN 25 0407 16-in. DN 400
0043 11/4-in. DN 32 0458 18-in. DN 450
0049 11/2-in. DN 40 0508 20-in. DN 500
0061 2-in. DN 50 0610 24-in. DN 600
0077 21/2-in. DN 65 0660 26-in. N/A
0089 3-in. DN 80 0762 30-in. DN 790
0115 4-in. DN 100 0813 32-in. DN 900
0140 5-in. DN 125 0915 36-in. DN 1000
0169 6-in. DN 150 1016 42-in. N/A
0220 8-in. DN 200 1070 42-in. N/A
Suitable pipe size
inch DIN inch DIN
1
/2-in. DN15 0324 12-in. DN 300
3
/4-in. DN 20 0356 14-in. DN 350
Code
Suitable pipe size
0273 10-in. DN 250 1219 48-in. N/A
16
Specifications and Reference Data
Page 23
Reference Manual
00809-0100-4952, Rev CA
Pipe schedule 120
Specifications and Reference Data
May 2016
Code
0115 4-in. DN 100
0140 5-in. DN 125
0169 6-in. DN 150
0220 8-in. DN 200
0273 10-in. DN 250
0324 12-in. DN 300
0356 14-in. DN 350
0407 16-in. DN 400
0458 18-in. DN 450
0508 20-in. DN 500
0610 24-in. DN 600
Suitable pipe size
inch DIN
Note
For pipe schedules larger than 120, consult factory for more information.
Typical model number of the assembly: 648 D X 1 D 1 NA WA3 WK1 M5 PT C1 XA
0085 N 3 P1 J 0080 C 0169 N XA
Specifications and Reference Data
17
Page 24
Specifications and Reference Data
80 mm
A
ØD
May 2016

A.3 Dimensional drawings

Figure A-1. Pipe Clamp Sensor Assembly
Reference Manual
00809-0100-4952, Rev CA
A. 1/2-in. NPT spring loaded adapter
18
Specifications and Reference Data
Page 25
Reference Manual
00809-0100-4952, Rev CA

Appendix B Product Certifications

Rev 1.1
European Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19
Ordinary Location Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19
Installing Equipment in North America . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19
North America . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19
Europe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19
International . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 20
EAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 20
Installation drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 21
Product Certifications
May 2016

B.1 European Directive Information

A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC Declaration of Conformity can be found at
EmersonProcess.com/Rosemount
.

B.2 Ordinary Location Certification

As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
B.3 Installing Equipment in North
America
The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.

B.4 North America

E5 FM Explosionproof and Dust-Ignitionproof
Certificate: 0R7A2.AE Standards: FM Class 3600- 2011, FM Class 3615-2006,
FM Class 3810-2005, ANSI/NEMA 250-1991
Markings: XP CL I, DIV 1, GP B, C, D, T6; DIP CL II/III, DIV 1, GP
E, F, G, T6; Type 4X; Installed per 00068-0013
E6 CSA Explosionproof, Dust-Ignitionproof
Certificate: 1063635 Standards: CAN/CSA C22.2 No. 0-M91,
CSA Std. C22.2 No. 25-1966, CSA Std. C22.2 No. 30-M1986, CSA Std. C22.2 No. 94-M91, CSA Std. C22.2 No. 142-M1987, CSA Std. C22.2 No. 213-M1987
Markings: XP Class I Groups B, C, and D; DIP Class II Groups E,
F, G; Class III; Class I Div. 2 Groups A, B, C, D; Class I Zone 1 Group IIB+H2; Class I Zone 2 Group IIC; Installed per 00068-0033

B.5 Europe

E1 ATE X Fl amepr oof
Certificate: FM12ATEX0065X Standards: EN60079-0:2012, EN60079-1:2007 Markings: II 2 G Ex d IIC T6…T1 Gb
Product Certifications
Special Conditions for Safe Use (X):
1. See certificate for ambient temperature range.
2. The non-metallic label may store an electrostatic charge and become a source of ignition in Group III environments.
3. Guard the LCD display cover against impact energies greater than 4 joules.
4. Consult the manufacturer if dimensional information on the flameproof joints is necessary.d
19
Page 26
Product Certifications
May 2016

B.6 International

E7 IECEx Flameproof
Certificate: IECEx FMG 12.0022X Standards: IEC60079-0:2011, IEC60079-1:2007 Markings: Ex d IIC T6…T1 Gb
Special Conditions for Safe Use (X):
1. See certificate for ambient temperature range.
2. The non-metallic label may store an electrostatic charge and become a source of ignition in Group III environments.
3. Guard the LCD display cover against impact energies greater than 4 joules.
4. Consult the manufacturer if dimensional information on the flameproof joints is necessary.

B.7 EAC

EM Explosionproof/ Flameproof
Certificate: TC RU C-US.GB05.B.00895 Standards: GOST R IEC 60079-0:2011,
GOST IEC 60079-1:2011
Markings: 1Ex d IIC T6...T1 Gb X; T6 (-50 °C to 40 °C),
T5...T1 (-50 °C to 60 °C) IP66
Reference Manual
00809-0100-4952, Rev CA
Special Condition for Safe Use (X):
1. See certificate.
20
Product Certifications
Page 27
Reference Manual
00809-0100-4952, Rev CA
Product Certifications

B.8 Installation drawings

Figure B-1. FM Explosionproof Temperature Measurement Assembly (E5) 00068-0013, Rev AG
May 2016
Product Certifications
21
Page 28
Product Certifications
May 2016
Figure B-2. CSA Explosionproof Temperature Measurement Assembly (E6) 00068-0033, Rev AG
00809-0100-4952, Rev CA
Reference Manual
22
Product Certifications
Page 29
Page 30
Global Headquarters
Emerson Process Management
6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@EmersonProcess.com
North America Regional Office
Emerson Process Management
8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com
Latin America Regional Office
Emerson Process Management
1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@EmersonProcess.com
Reference Manual
00809-0100-4952, Rev CA
May 2016
Europe Regional Office
Emerson Process Management Europe GmbH
Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@EmersonProcess.com
Asia Pacific Regional Office
Emerson Process Management Asia Pacific Pte Ltd
1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.EmersonProcess.com
Middle East and Africa Regional Office
Emerson Process Management
Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465 RFQ.RMTMEA@Emerson.com
Linkedin.com/company/Emerson-Process-Management
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/RosemountMeasurement
Google.com/+RosemountMeasurement
Standard Terms and Conditions of Sale can be found at:
www.Emerson.com/en-us/pages/Terms-of-Use.aspx
The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount X-well Technology, Rosemount, and Rosemount logotype are trademarks of Emerson Process Management. NEMA is a registered trademark and service mark of the National Electrical Manufacturers Association. National Electrical Code is a registered trademark of National Fire Protection Association, Inc. All other marks are the propert y of their respective owners. © 2016 Emerson Process Management. All rights reserved.
Loading...