Roscid Technologies H-STAT Specifications

The H-STAT is a low voltage microprocessor based humidistat ideal for controlling humidification and dehumidification in both residential and commercial applications. It offers an temperature sensor used to lower the
optional
humidity set point to prevent condensation buildup on windows or structures.
Features:
Large LCD showing humidity reading or set point
Menu access using the push button on the front panel display
Proven humidity sensor with extraordinary performance in repeatability and durability
User friendly installation/
replacement with
plug-in electronic module and base plate
SPECIFICATIONS
www.roscid.com
Specifications:
Measurement range: 10-95% RH Operating Temperature: 5°C to 50°C Control Range: 10-95%RH Power equipment: 24Vdc or 24Vac
Accuracy@25C: +/-2% RH from 30-80% Repeatability +/-0.3%RH Relay Contact: 1 Λ@125VAC Stability: +/-1%@50% RH, 5yr Temp Effect: 0.05%RH/°F Enclosure: ABS *Non-Condensing
www.roscid.com