Ropex RESISTRON RES-409 Operating Instructions Manual

RESISTRON
GB
RES-409
Operating
instructions
Important features
Complete control via CAN-Bus interface
Automatic zero calibration (AUTOCAL)
Automatic optimization (AUTOTUNE)
Automatic frequency adjustment
Large current and voltage range
0…10VDC analog output for ACTUAL temperature
Alarm function with fault diagnosis
Heatsealing band alloy and temperature range selectable
9.7.04
Industrie-Elektronik GmbH Tel: +49/(0)7142/7776-0 E-Mail: info@ropex.de Gansäcker 21 Fax: +49/(0)7142/7776-19 Internet: www.ropex.de D-74321-Bietigheim-Bissingen (Germany) Data subject to change

Contents

1 Safety and warning notes . . . . . . . . . . . . . . 3
1.1 Use . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Heatsealing band . . . . . . . . . . . . . . . . 3
1.3 Impulse transformer . . . . . . . . . . . . . . 3
1.4 Current transformer PEX-W2 . . . . . . . 3
1.5 Line filter . . . . . . . . . . . . . . . . . . . . . . . 4
1.6 Warranty provisions . . . . . . . . . . . . . . . 4
1.7 Standards / CE marking . . . . . . . . . . . 4
2 Application . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Principle of operation . . . . . . . . . . . . . . . . . 5
4 Description of the controller . . . . . . . . . . . 6
5 Accessories and modifications . . . . . . . . . 6
5.1 Accessories . . . . . . . . . . . . . . . . . . . . . 6
5.2 Modifications (MODs) . . . . . . . . . . . . . 7
6 Technical data . . . . . . . . . . . . . . . . . . . . . . . 8
7 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . 9
8 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . 9
8.1 Installation procedure . . . . . . . . . . . . . 9
8.2 Installation steps . . . . . . . . . . . . . . . . 10
8.3 Power supply . . . . . . . . . . . . . . . . . . . 11
8.4 Line filter . . . . . . . . . . . . . . . . . . . . . . 12
8.5 Current transformer PEX-W2 . . . . . . 12
8.6 Wiring diagram (standard) . . . . . . . . . 13
8.7 Wiring diagram with booster connection
(MOD 26) . . . . . . . . . . . . . . . . . . . . . . 14
9 Startup and operation . . . . . . . . . . . . . . . . 15
9.1 View of the controller . . . . . . . . . . . . . 15
9.2 Controller configuration . . . . . . . . . . . 15
9.3 Heatsealing band . . . . . . . . . . . . . . . . 18
9.4 Startup procedure . . . . . . . . . . . . . . . 19
10 Controller functions . . . . . . . . . . . . . . . . . 20
10.1 Indicators and controls . . . . . . . . . . . 20
10.2 CAN protocol . . . . . . . . . . . . . . . . . . . 20
10.3 Receiving CAN messages . . . . . . . . . 21
10.4 Sending CAN messages . . . . . . . . . . 24
10.5 Temperature indication (actual value
output) . . . . . . . . . . . . . . . . . . . . . . . . 25
10.6 System monitoring/alarm output . . . . 27
10.7 Error messages . . . . . . . . . . . . . . . . . 27
10.8 Fault areas and causes . . . . . . . . . . . 29
11 Factory settings . . . . . . . . . . . . . . . . . . . . . 30
12 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . 30
13 How to order . . . . . . . . . . . . . . . . . . . . . . . . 31
14 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Page 2 RES-409
Safety and warning notes

1 Safety and warning notes

This RESISTRON temperature controller is manufactured according to DIN EN 61010-1. In the course of its manufacture it passed through quality assurance, whereby it was subjected to extensive inspections and tests. It left the factory in perfect condition. The recommendations and warning notes contained in these operating instructions must be complied with, in order to guarantee safe operation. The device can be operated within the limits indicated in the "Technical Data" without impairing its operational safety. Installation and maintenance may only be performed by technically trained, skilled persons who are familiar with the associated risks and warranty provisions.

1.1 Use

RESISTRON temperature controllers may only be used for heating and temperature control of heatsealing bands which are expressly suitable for them, and providing the regulations, notes and warnings contained in these instructions are complied with.
In case of non-compliance or use contrary to
!
the intended purpose, there is a risk that safety will be impaired or that the heatsealing band, electrical wiring, transformer etc. will overheat. Ensuring such compliance is the personal responsibility of the user.
The RESISTRON temperature controller must be set and coded according to the temperature coefficient of the heatsealing band.
The use of incorrect alloys with too low a
!
temperature coefficient and incorrect coding of the RESISTRON temperature controller leads to uncontrolled heating and ultimately to burn-out of the heatsealing band!
The heatsealing bands that were originally supplied must be identified by their detailed specification, part number or some other means to ensure that all replacement bands are identical.

1.3 Impulse transformer

A suitable impulse transformer is necessary to ensure that the control loop functions perfectly. This transformer must be designed according to VDE 0570/ EN 61558 (isolating transformer with reinforced insulation) and have a one-section bobbin. When the impulse transformer is installed, suitable shock protection must be provided in accordance with the national installation regulations for electrical equipment. In addition, water, cleaning solutions and conductive fluids must be prevented from seeping into the transformer.
Incorrect installation of the impulse
!
transformer impairs electrical safety.

1.2 Heatsealing band

A basic prerequisite for reliable and safe operation of the system is the use of suitable heatsealing bands.
The resistance of the heatsealing band which
!
is used must have a positive minimum temperature coefficient in order to guarantee trouble-free operation of the RESISTRON temperature controller.
The temperature coefficient must be specified as follows:
TCR 104–×10 K
e.g. Alloy-20: TCR = 1100 ppm/K
NOREX: TCR = 3500 ppm/K
1–
RES-409 Page 3

1.4 Current transformer PEX-W2

The current transformer supplied with the RESISTRON temperature controller is an integral part of the control system.
Only the original ROPEX PEX-W2 current
!
transformer may be used. Other transformers
may cause the equipment to malfunction.
The current transformer may only be operated if it is connected to the RESISTRON temperature controller correctly (see section 9, "Startup and operation"). The relevant safety instructions contained in section 8.3, "Power supply", must be obeyed. External monitoring modules can be used in order to additionally increase operating safety. They are not included in the scope of
Application
supply of the standard control system and are described in a separate document.

1.5 Line filter

The use of an original ROPEX line filter is mandatory in order to comply with the standards and provisions mentioned in section 1.7 "Standards / CE marking" on page 4. This device must be installed and connected according to the instructions contained in section 8.3, "Power supply" as well as the separate documentation enclosed with the line filter.

1.6 Warranty provisions

The statutory provisions for warranties apply for a period of 12 months following the delivery date. All devices are tested and calibrated in the factory. Devices that have been damaged due to faulty connections, dropping, electrical overloading, natural wear, incorrect or negligent handling, chemical influences or mechanical overloading as well as devices that have been modified, relabeled or otherwise altered by the customer, for example in an attempt to repair them or install additional components, are excluded from the warranty. Warranty claims must be examined in the factory and approved by ROPEX.

1.7 Standards / CE marking

The controller described here complies with the following standards, provisions and directives:
DIN EN 61010-1 (VDE 0411-1)
DIN EN 60204-1 Electrical equipment of machines
EN 50081-1 EMC interference emissions
EN 50082-2 EMC interference immunity:
Compliance with these standards and provisions is only guaranteed if original accessories and/or peripheral components approved by ROPEX are used. If not, then the equipment is operated on the user's own responsibility. The CE marking on the controller confirms that the device itself complies with the above-mentioned standards. It does not imply, however, that the overall system also fulfils these standards. It is the responsibility of the machine manufacturer and of the user to verify the completely installed, wired and operationally ready system in the machine with regard to its conformity with the safety provisions and the EMC directive (see also section 8.3, "Power supply"). If peripheral components (e.g. the transformer or the line filter) from other manufacturers are used, no functional guarantee can be provided by ROPEX.
Safety provisions for electrical measuring, control and laboratory devices (low voltage directive). Overvoltage category III, pollution severity 2, safety class II.
(machinery directive)
according to EN 55011, group 1, class B
ESDs, RF radiation, bursts, surges.

2 Application

This RESISTRON temperature controller is an integral part of the "series 400", the outstanding feature of which is its microprocessor technology. All RESISTRON temperature controllers are used to control the temperature of heating elements (heatsealing bands, beaded bands, cutting wires, heatsealing blades, solder elements etc.), as required in a variety of heatsealing processes.
Page 4 RES-409
The controller is most commonly used for impulse­heatsealing PE films in:
Vertical and horizontal f/f/s machines
Pouch, filling and sealing machines
Film wrapping machines
Pouch-making machines
Group packaging machines
•etc.
Principle of operation
The use of RESISTRON temperature controllers results in:
Repeatable quality of the heatseals under any
conditions

3 Principle of operation

The resistance of the heatsealing band, which is temperature-sensitive, is monitored 50x per second (60x at 60Hz) by measuring the current and voltage. The temperature calculated with the help of these measurements is displayed and compared with the set point. The primary voltage of the impulse transformer is adjusted by phase-angle control if the measured values deviate from the set point. The resulting change in the current through the heatsealing band leads to a change in the band temperature and thus also its resistance. This change is measured and evaluated by the RESISTRON temperature controller. The control loop is closed: ACTUAL temperature = SET temperature. Even minute thermal loads on the heatsealing band are detected and can be corrected quickly and precisely. The thermoelectric control loop which is formed has a highly dynamic response because purely electrical variables are measured at a high sampling rate. A high secondary current can be controlled because power is controlled on the primary side of the transformer. This
Increased machine capacity
Extended life of the heatsealing bands and teflon coatings
Simple operation and control of the sealing process
allows optimum adaptation to the load and to the required dynamic range despite the exceptionally compact dimensions of the controller.
PLEASE NOTE!
RESISTRON temperature controllers play a significant role in enhancing the performance of modern machines. However, the full benefit can only be obtained from the advanced technology offered by this control system if all the system components, in other words the heatsealing band, the impulse transformer, the wiring, the timing signals and the controller itself, are compatible with one another and interrelated.
We will be pleased to
contribute our many
years of experience
towards optimizing your
heatsealing system.
Heatsealing band R = f (T)
U
2
sec.
Impulse transformer
Current transformer
U
1
prim.
RESISTRON controller
URI
R
R=f(T)
LINE
_
+
Actual value
Start
Set point
RES-409 Page 5
Indicators
and
controls
or
bus interface

4 Description of the controller

Description of the controller
The microprocessor technology endows the RESISTRON temperature controller RES-409 with previously unattainable capabilities:
Very simple operation thanks to AUTOCAL, the automatic zero calibration function.
Good dynamic response of the control system thanks to AUTOTUNE, which adapts automatically to the controlled system.
High precision thanks to further improved control accuracy and linearization of the heatsealing band characteristic.
High flexibility: the secondary voltage range from 1 V to 120V is covered with only 3 DIP switches, with 2 DIP switches for the current range from 30 A to 400A.
Automatic adjustment to the line frequency in the range from 47 Hz to 63Hz.
Increased protection against dangerous conditions, such as overheating of the heatsealing band.
The RESISTRON temperature controller RES-409 is equipped with a CAN-Bus interface. This interface can
be used to control all the controller functions and interrogate controller information. The ACTUAL temperature of the heatsealing band is supplied to the CAN-Bus interface and to an analog 0 to 10V DC output. The real heatsealing band temperature can thus be displayed on an external temperature meter (e.g. ATR-x). The RES-409 features an integrated fault diagnosis function, which tests both the external system (heatsealing band, wiring etc.) and the internal electronics and outputs a selective error message in case of a fault. To increase operational safety and interference immunity, all CAN-Bus signals are electrically isolated from the controller and the heating circuit. Either coding switches on the temperature controller itself or the CAN-Bus interface can be used to adapt to different heatsealing band alloys (Alloy-20, NOREX etc.) and set the required temperature range (0…300°C, 0…500 °C etc.). The compact design of the RESISTRON temperature controller RES-409 and the plug-in connections make this controller easy to install.

5 Accessories and modifications

A wide range of compatible accessories and peripheral devices are available for the RESISTRON temperature controller RES-409. They allow it to be optimally adapted to your specific heatsealing application and to your plant's design and operating philosophy.
Analog temperature meter ATR-x
For front panel mounting or mounting on a top hat rail (DIN TS35 rail). Analog indication of the ACTUAL temperature of the heatsealing band in °C. The meter damping of the unit is optimized for the abrupt temperature changes that occur in impulse mode.
Digital temperature meter DTR-x
For front panel mounting or mounting on a top hat rail (DIN TS35 rail). Digital indication of the ACTUAL temperature of the heatsealing band in °C, with HOLD function.
Line filter LF-xx480
Essential in order to ensure CE conformity. Optimized for the RESISTRON temperature controller.

5.1 Accessories

The products described below are only a few of the wide range of accessories available for RESISTRON temperature controllers (ª "Accessories" leaflet).
Page 6 RES-409
Accessories and modifications
Impulse transformer ITR-x
Designed according to VDE 0570/EN 61558 with a one-section bobbin. Optimized for impulse operation with RESISTRON temperature controllers. Specified according to the heatsealing application (ª ROPEX Application Report).
Booster B-xxx400
External switching amplifier, necessary for high primary currents (continuous current > 5 A, pulsed current > 25 A).
Monitoring current transformer MSW-1
For detecting frame short-circuits on the heatsealing band. Used as an alternative to the standard PEX-W2 current transformer.

5.2 Modifications (MODs)

Owing to its universal design, the RESISTRON temperature controller RES-409 is suitable for a very wide range of heatsealing applications. Two modifications (MOD) are available for the RESISTRON temperature controller RES-409 for implementing special applications.
MOD 01
Amplifier for low secondary voltages (U
= 0.25…16VAC). This modification is necessary,
R
for example, for very short or low-resistance heatsealing bands.
MOD 26
Additional terminal for connecting an external switching amplifier (booster). This modification is necessary for high primary currents (continuous current > 5 A, pulsed current > 25A).
RES-409 Page 7

6 Technical data

Type of construction Housing for installation in the electrical cabinet
Snaps onto a standard top hat rail (DIN TS35 rail, 35mm) acc. to DIN EN 50022 Dimensions: 90 x 75 mm; height: 135mm (incl. terminals)
Line voltage All controllers manufactured as of January 2004:
115VAC version: 115VAC -15 %…120VAC +10% (equivalent to 98…132 VAC) 230VAC version: 230VAC -15 %…240VAC +10% (equivalent to 196…264VAC) 400VAC version: 400VAC -15 %…415VAC +10% (equivalent to 340…456VAC)
All controllers manufactured up to December 2003: 115VAC, 230 VAC or 400VAC, tolerance: +10% / -15 %
depending on device version (ª section 13 "How to order" on page 31)
Line frequency 47…63Hz, automatic adjustment to frequencies in this range
CAN interface Baud rates: 10kBaud; 50 kBaud; 125kBaud; 205 kBaud;
250kBaud; 500 kBaud; 800kBaud; 1 MBaud
2 x 3-pole M8 circular connector acc. to IEC 947-5-2
Technical data
Heatsealing band type and temperature range
Six ranges selectable via the CAN interface:
Temperature coefficient 1100ppm, 0…200°C (e.g. Alloy A20) Temperature coefficient 1100ppm, 0…300°C (e.g. Alloy A20) Temperature coefficient 1100ppm, 0…400°C (e.g. Alloy A20) Temperature coefficient 1100ppm, 0…500°C (e.g. Alloy A20) Temperature coefficient 3500ppm, 0…200 °C (e.g. NOREX) Temperature coefficient 3500ppm, 0…300 °C (e.g. NOREX)
Analog output
(actual value)
0…10V DC, Imax = 5 mA Equivalent to 0…300 °C or 0…500°C
Terminals 17+18
Alarm relay
U
max
=50VDC, I
= 0.2A, changeover contact, potential-free
max
Terminals 12, 13, 14
Maximum load
(primary current of
= 5A (duty cycle = 100%)
I
max
= 25A (duty cycle = 20 %)
I
max
impulse transformer)
Ambient
+5…+45°C
temperature
Degree of protection IP20
Installation If several controllers are installed on one top hat
rail (DIN TS35 rail), a clearance of at least 20mm should be allowed between them.
Weight Approx. 0.7 kg (incl. connector plug-in parts)
Page 8 RES-409
Dimensions
Housing material Plastic, UL-94-1, self-extinguishing
Connecting cables
Type / cross-sections

7 Dimensions

Rigid or flexible; 0.2…2.5mm² (AWG 24…12) Plug-in connectors
135.0
113.0
75.0 90.0

8 Installation

ª See also section 1 "Safety and warning notes" on page 3.
Installation and startup may only be
!
performed by technically trained, skilled persons who are familiar with the associated risks and warranty provisions.

8.1 Installation procedure

Proceed as follows to install the RESISTRON temperature controller RES-409:
1. Switch off the line voltage and verify that all circuits are deenergized.
2. The supply voltage specified on the nameplate of the RESISTRON temperature controller must be identical to the line voltage that is present in the plant or machine. The line frequency is automatically detected by the temperature controller in the range from 47 Hz to 63Hz.
3. Install the RESISTRON temperature controller in the electrical cabinet on a standard top hat rail (DIN TS35 rail, according to DIN EN 50022). If several controllers are installed on one top hat rail, the minimum clearance specified in section 6 "Technical data" on page 8 must be allowed between them.
RES-409 Page 9
Installation
4. Wire the system in accordance with the instructions in section 8.3 "Power supply" on page 11, section 8.6 "Wiring diagram (standard)" on page 13 and the ROPEX Application Report. The information provided in section 8.2 "Installation steps" on page 10 must be heeded additionally.
5. Connect the RESISTRON temperature controller to the CAN master using a cable according to IEC 947-5-2.

8.2 Installation steps

Use heatseal bands with
Heatseal element
with coppered ends
suitable temperature coefficient
Heatsealing band R= f (T)
Check the tightness of all the system
!
connections, including the terminals for the
impulse transformer windings.
6. Make sure that the wiring conforms to the relevant national and international installation regulations.
No push-on connectors
Sufficient wire
cross-section
Avoid long
cables
Dimension transformer correctly
- Secondary voltage
- Power
- Duty cycle
F
U (sec.)
2
No additional
resistance
in secondary
circuit
A
Impulse
transformer
Note number of turns
Current transformer
U (prim.)
1
20mm clearance if several
controllers installed on
PEX-W2
Temperature
meter
ATR -x
Note
polarity
one top hat rail
Controller
Connect U measuring
heatsealing band ends
Twi sted
Current measuring
R
wires directly to
wires I
R
Line
Line filter
LF-xx480
Note
direction
of rotation
Digital potentiometer PD-x
Configure
DIP switches