Roper C340 Owner's Manual

I
1
-. -
/’
‘-~
r.
i;
CONTENTS
USE AND CARE
Important Instructions for Your Safety Your Counter Unit and Its Features Using Your Counter Unit Favorite American Recipes Cleaning lips Removable Control Knobs
SERVICE
What To Do Before Calling For Service
WARRANTY
ECrnll

INSTALLATION

IMPORTANT: Save these instruction for the local electrical inspector’s use.
TOOL LIST
The following tools are needed to install your new coun­ter unit.
0%” drill bit *Electric or hand drill *Flat bladed screwdriver @Pencil *Ruler or tape measure and straight edge #Hand saw or sabre saw
LOCATION
See Figures 1 and 2 and Table 1 for all rough-in and spacing dimensions. These dimensions must be met for safe use of your range.
MINIMUM CLEARANCES TO BE MAINTAINED:
1” between counter unit rear edge and wall behind unit. 2%” between counter unit front edge and counter front
edge. 30” between cooktop and nearest overhead surface 1” on the right and 2” on the left side of the counter unit
to a height of 18”
CUTOUT AND COUNTER UNIT MINIMUM CLEARANCES TO
L
DIMENSIONS
TABLE
DIMENSIONS
1
29%” 20%”
28%”
19%” 1 Y/16”’ 28g/r6”’ 14%2”
33’A”
3 % ’ ’
Fig. 1
ADJACENT CONSTRUCTION
IMPORTANT:
fire when reaching over hot surface elements, cabinet storage space above the cooktop should be avoided. If cabinet storage space is to be provided above the cooktop, the rrsk can be reduced by installing a range hood that sticks out at least 5” beyond the front of the cabinets. Cabinets installed above a cooktop may be no deeper than 13”.
‘For ex~stlng, standard cutou1s: unll may 111 Into an
exlstlng cutout of 28%” x 19’h”.
To eliminate the risk of burns or
Fig. 2
EiNSC4
We recommend that you have the electrical hookuo of your counter unit done by a qualified electrician. Have the electrician show you where your disconnect is located.
The electrical power to the range supply line must be shut off while line connectlons are belng made. Failure to do so could result In serlous InJury or death.
When making the wire connections, use the entire length ’ of conduit provided (3 ft). The conduit must not be cut.
Call your Electric Company and ask which codes apply in your area. If there are no codes, you must follow the
NATIONAL ELECTRICAL CODE, ANSI/NFPA NO. 70-
1987. You can get a copy by writing: National Fire Protection Association
Batterymarch Park
Quincy, MA 02269
I
If you fail to wire your counter unit in accordance with
governing codes, you may create a hazardous condition.
I
You must use a three-wire, single-phase AC 120/240 Volt
or 208Y/120 Volt, 60 Hertz electrical system.
Use a minimum wire size of No. 10 copper wire protected with a 30 Amp. fuse or circuit breaker for both 208Y/120 Volt and 120/240 Volt electrical systems,
Do not use aluminum wiring to connect your counter unit to the household circuit.
Before installing the counter unit or moving it to another location, have the electrician verify:
l That your home is provided with adequate electrical
service.
Connect the red and black leads from the counter unit conduit to the corresponding leads in the junction box.
The bare ground wire in the conduit is connected to the counter unit frame. Connect the other end of this wire to a properly grounded cold water pipe or use another approved grounding method.
A white (neutral) wire is not needed for this unit. The white lead from the household electrical supply can be taped and terminated in the junction box.
BE SURE THIS CUT DOES NOT
INTERFERE WITH CABINET
STRUCTURE AT FRONT
MIN.
l That the addition of the counter unit will not overload
the household circuit on which it is used.
Cut the opening in the counter top. Be sure to maintain cutout dimensions and minrmum clearances as shown on previous page. To minimize chipping of the counter­top you can apply maskrng tape before you make the cut.
Install an approved junction box where it will be easily reached through the front of the cabinet where the coun­ter unit will be located. The counter unit has 3 feet of conduit.
IMPORTANT: The junction box must be located where It will allow conslderable slack In the conduit for service-
eblllty. See Fig. 3.
Install the counter unit in the cutout opening. Note: If the unit is being installed in a blind counter (one with no
cabinet opening below), wire connections must be made before putting the unit into the cutout.
To attach the unit to the counter, insert the side retainers in the slot on each stde of the unit. Use the screws and washers supplied to attach unit to counter as shown in figure 3.
SIDE RETAINER
Fig. 3
SUGGESTED MOUNTING OF
AN APPROVED JUNCTION BOX
Loading...
+ 8 hidden pages