Romac Industries XR501 Installation Manual

INSTALLATION INSTRUCTIONS
ROMAC INDUSTRIES, INC.
8
9
6
7
Read installation instructions rst before installing. Check parts to ensure that no damage has occurred during transit and that no parts are missing. Also check the diameter of the pipe and the range marked on the coupling to ensure you have the proper size.
Style XR501 Extended Range Couplings
For pipe ODs smaller than standard steel,
down to SDR 35 sewer, do not exceed 20 psi.
Coupling set up at factory for DI size pipe. It may be necessary to loosen coupling bolts for some A/C pipe sizes. Oversize A/C may require disassembly of coupling.
Step 1 • Check the coupling parts to insure that no damage
has occurred during transit and that no parts are missing.
Step 2 • Clean pipe ends for a distance of 2" greater than
length of the coupling when centered over the joint.
Step 3 • Check area where gaskets will seat to make sure
there are no dents, projections, gouges, etc., that will interfere with the gasket seal. Welds must be ground ush.
Step 4 • Place a reference mark on the pipe an equal
distance from each pipe end for centering coupling over joint. There should be a minimum of 3 inches of pipe insertion per coupling end.
Step 5 • Lubricate the gaskets and pipe surface with a
suitable gasket lubricant.
Step 7 • Bring the other pipe into position (recommended
pipe gap of 1 inch).
Step 8 • Center coupling over pipe ends using the reference
marks described in Step 4.
Step 9 • Tighten bolts such that the end ring anges
remain parallel and the gaskets are evenly compressed. Bolt tightening should be done evenly, alternating to diametrically opposite positions at approximately 20 ft-lbs increments. Tighten to 75 - 90 ft-lbs.
Step 6 • Slide assembled coupling completely onto one
of the pipes.
Document #20-9-0026 07/11/07
Note: Flexible Couplings do not provide protection against
possible pullout of pipe ends in unrestrained conditions.
Note: Maximum Angular Deection of 5˚.
Step 10 • After pipe is pressurized, check for leakage
and tighten as necessary.
ROMAC INDUSTRIES, INC.
INSTALLATION INSTRUCTIONS
Style XR501
Extended Range Couplings
PRECAUTIONS
1. Check diameter of pipe to make sure you are using the correct size coupling; also check gasket to make sure it is the size you think it is.
2. Clean pipe to remove dirt and corrosion from pipe surface. Lubrication and additional cleaning should be provided by brushing both the gasket and plain pipe end with soapy water or approved pipe lubricant per ANSI/AWWA C111/A21.11.
3. Make sure no foreign materials lodge between gasket and pipe.
4. Avoid loose tting wrenches, or wrenches too short to achieve proper torque.
5. Keep threads free of foreign material to allow proper tightening.
6. Take extra care to follow proper bolt tightening procedures and torque recommendations. Bolts are often not tightened enough when a torque wrench is not used.
7. Pressure test for leaks before backlling.
8. Backll and compact carefully around pipe and ttings.
9. Couplings do not provide protection against possible pullout of pipe ends in unrestrained condi­tions.
10. When reinstalling parts with stainless steel hardware there may be a loss in pressure holding ability due to worn or damaged threads during the original installation. Additional lubrication should be applied.
COMMON INSTALLATION PROBLEMS
1. Bolts are not tightened to the proper torque.
2. Rocks or debris between pipe and gasket.
3. Dirt on threads of bolts or nuts.
4. Pipe not inserted into the coupling far enough.
5. Center ring not centered evenly around pipe.
6. Too much pipe deection.
7. Using on pipe smaller than standard steel at pressures greater than 20 psi.
Loading...