Rokonet Orbit-14 Installation Manual

Page 1
Installation Manual
Page 2
Important Notice
This manual is delivered subject to the following conditions and restrictions:
This manual contains proprietary information belonging to Rokonet Electronics
Ltd. Such information is supplied solely for the purpose of assisting explicitly and properly authorized users of the system.
No part of its contents may be used for any other purpose, disclosed to any
person or firm or reproduced by any means, electronic or mechanical, without the express prior written permission of Rokonet Electronics Ltd.
The text and graphics are for the purpose of illustration and reference only. The
specifications on which they are based are subject to change without notice.
Information in this document is subject to change without notice. Corporate and
individual names and data used in examples herein are fictitious unless otherwise noted.
Copyright 2003 Rokonet Electronics Ltd. All rights reserved.
ii
Installation Manual
Page 3
Customer Information
TELEPHONE CONNECTION (Ref.: FCC Part 68)
1. This equipment, Alarm Control Panel, brand named Orbit-14 (RP214MA0000A), complies with Part 68 of the FCC Rules and the requirements adopted by the ACTA. On the bottom panel of this equipment is a label that contains among other information, a product identifier in the format US:RKEAL10BRP214MA. If requested, this number must be provided to the telephone company.
2. This equipment is designed to be connected to the telephone network using a terminal block, which is Part 68 compliant and properly installed RJ31X connector. See Installation Instructions for details.
3. The REN is used to determine the number of devices that may be connected to a telephone line. Excessive RENs on a telephone line may result in the devices not ringing in response to an incoming call. In most but not all areas, the sum of RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to a line, as determined by the total RENs, contact the local telephone company. The REN of alarm system is part of the product identifier that has the format US:RKEAL10BRP214MA.
4. If the Alarm Control Panel causes harm to the telephone network, the telephone company will notify you in advance that temporary discontinuance of service may be required. If advance notice is not practical, you will be notified as soon as possible. Also, you will be advised of your right to file a compliant with the FCC if it is necessary.
5. The telephone company may make changes in its facilities, equipment, operations or procedures that could affect the operation of the equipment. If this happens the telephone company will provide advance notice in order for you to make necessary modifications to maintain uninterrupted service.
6. If trouble is experienced with the Alarm Control Panel, for repair or warranty information please contact Rokonet Industries USA Inc 2822 NW 79th Ave. Miami, Florida 33122 USA, phone number 305 592 3820, URL: sales@rokonetusa.com. If the equipment is causing harm to the telephone network, the telephone company may request to disconnect the equipment until the problem is resolved.
7. The control panel installation is described in the Installation Manual. Connection to telephone company provided coin service is prohibited. Connection to party lines service is subject to state tariffs.
8. Alarm Control Panel must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, the alarm control panel must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line. Proper installation is depicted in the figure below. If you have any questions concerning these instructions, you should consult your telephone company or a qualified installer about installing the RJ31X jack and Alarm Control Panel for you.
Installation Manual
iii
Page 4
RJ-31X
Network
Service
Provider's
Facilities
Telephone
Line
Network
Demarcation
Point
Jack
Telephone
Customer Premises Equipment and Wiring
Alarm
Dialing
Equipment
Unused
Answering
System
RJ-11
Jack
Computer
Fax Machine
Telephone
Unused
RJ-11 Jack
Telephone
RADIO FREQUENCY INTERFERENCE (Ref.: FCC Part 15, Para. 15.105)
This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
1. Reorient or relocate the receiving antenna.
2. Increase the separation between the equipment and the receiver.
3. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
4. Consult the dealer or an experienced Radio/TV technician for help.
CHANGES OR MODIFICATIONS (Ref.: FCC Part 15, Para. 15.21 and 15.27)
Changes or modifications to this unit not expressly approved by Rokonet, Ltd., could void the user's authority to operate the equipment.
iv
Installation Manual
Page 5
CE Declaration of Conformity
We, the undersigned,
ROKONET ELECTRONICS LTD. RISHON LEZION, HACHOMA ST. 14 ISRAEL PHONE: (972) 3 9616555 FAX: (972) 3 9616584
Certify and declare under our sole responsibility that the following equipment:
Brand Type Product Description
Orbit -14 RP214MC0000A
was tested to and conforms with the requirements included in following standards:
Standard 5/1999/EC Article Note
EN 60950:00 3(1)(a) EN 301 489-3 v.1.2.1 3(1)(b) EN 50130-4:95+A1 (98) 3(1)(b) TBR21:98+ETSI EG 201 121 v.1.1.3 /
Note 1: Full Orbit 14 system. Note 2: Main unit (additionally).
and therefore complies with the requirements and provisions of the Council Directive 1999/5/EC of the European Parliament and of the council of 9 march 1999 on Radio
equipment and Telecommunications Terminal Equipment and the mutual recognition of their conformity and Annex III (Conformity Assessment procedure referred to in article 10(4)).
Control Panel with wired accessories (including cables)
1
1
1
2
20 February 2003
David Kartoun
CTO
Installation Manual
v
Page 6
vi
Installation Manual
Page 7
TABLE OF CONTENTS
Introduction to the ORBIT-14 3
Main Features 3
Technical Data 5
Installation 7
Before You Begin 7
Mounting the Control Panel 7
Wiring the Main Panel 8
Connecting to Ground (Earth) 8 Telephone Line Connection 10 Connecting AC Power 10 Zone Connections 10 Wiring Auxiliary Devices 12 Bell Tamper 12 Box Tamper 12 Utility Output Connections 13 Connecting the J4 Connector 14 Keypad Connection 15 Connecting the J3 SIG IN Connector (Signal in Voice Mail) 15
Installer Programming 16
The Keypad 16
Restoring Factory Defaults to the ORBIT-14 16
Introduction to Programming 16
Programming Your ORBIT-14 17 Viewing the Contents of a Location 17 Locations Whose Contents Occupy More Than One Digit 18 Audible Tones and Error Beeps 18 Programming Installer Parameters 18 Programming Time Out 19 Programming Tutorial 19
Programming Locations: 21
General System Parameters: Locations 000-005 21
System Codes: Locations 006-010 22
System Time Definitions: Locations 011-016 23
Installation Manual
1
Page 8
Zone Types and Sounds: Locations 017-030 24
Zone Response Time & Group Masking: Locations 031-044 27
Zone Termination & Tamper Sound: Location 045 27
Utility Outputs: Locations 046-051 28
Communication Parameters: Locations 052-055 32
Dialler Control 1: Location 052 32 Dialler Control 2: Location 053 34 Central Station Pulsed Protocols: Location 054 34 Automatic Central Station Protocols: Location 055 36
Upload/Download Rings: Location 056 37
Swinger Shutdown Limit: Location 057 37
System Controls: Locations 059-060 38
Sub Installer Restriction Level: Location 061 41
Communicator Reporting Codes: Locations 062-168 42
Reporting Codes for Alarm Events 42 Restore Codes 42 Other Reporting Codes 43 Trouble Reports and Restorals 45
Appendix 1: Installer Programming Worksheet 46
Appendix 2: Contact ID & SIA Report Codes for Orbit-14 48
Appendix 3: Summary of User’s Commands 50
2
Installation Manual
Page 9
Introduction to the ORBIT-14
The ORBIT-14 is a fully featured security system, providing solutions for alerting and reporting premises alarm signals.
The ORBIT-14 addresses the needs of many homes, offices, and small businesses. Its operation is designed around microprocessor and EEPROM (Electrically Erasable Programmable Read-Only Memory) technology, which stores the system’s operating program and its programmable parameters, without the need for a source of power.
System programming may be performed from any ORBIT-14 keypad, or from an LCD Programming Keypad designed specifically for this purpose.
Remote and local system programming is also possible through the use of Rokonet’s Upload/Download software.
Main Features
Zones
14 Programmable Intrusion Zones
12 zones on main board using zone doubling.
2 zones on keypad
3 Keypad Emergency Zones (Panic, Fire, Special Emergency)
Alarm Sounder Output
Programmable Bell/Siren or Loudspeaker Output
Capacity: 900 mA (maximum)
Auxiliary Output for Peripheral Devices
Capacity 600 mA MAX from all AUX terminals
Built-In Digital Communicator
For Central Station communications (two phone numbers), Upload/Download
functions and follow-me functions
Keypads
Up to five LED/LCD keypads can be connected
Utility Outputs
1 relay output 3A
1 transistor-driven (open-collector) 500 mA triggered output
1 transistor-driven (open-collector) 70 mA triggered output
Expandable to six outputs
Security Codes
2 Installer Codes
1 Master (User) Code
19 Codes (all may be used as duress code)
Installation Manual
3
Page 10
Periodic Testing
Daily test report to central station
Optional Peripherals
Four relay-output expansion modules
Voice Module
Event Log
Event log of 250 events
Tamper Protection
Box Tamper input (NC)
Bell Tamper input (using 2.21 K resistor)
Keypad Tamper (Wall & cover)
Automatic Arming
Daily automatic arming
Orbit 14 Main Panel Types:
P/N Description
RP214MA0000A Orbit 14 Main Panel. Telephone impedance 600. Complies
with FCC Part 68 regulation.
RP214MB0000A Orbit 14 Main Panel. Telephone impedance 900Ω.
RP214MC0000A Orbit 14 Main Panel. Complies with the TBR21: 98+ETSI EG
201 121 v.1.1.3 regulation.
RP214MZ0000A Orbit 14 Main Panel. Complies with the local Czech telephony
system requirements.
4
Installation Manual
Page 11
Technical Data
Main Panel
Input power 16.5 V AC 40 VA via transformer Rechargeable standby battery 12 V 7 A-Hours
Auxiliary Power 12 V DC 600 mA maximum Bell/LS Sounder output 12 V DC 900 mA maximum Programmable outputs 1 X Relay output 3A
1 X Open collector Active pull down 500 mA maximum 1 X Open collector Active pull down 70 mA maximum
Cabinet Dimensions: 296.2 X 262.3 X 87.5 mm ( 11.66 X 10.32 X 3.44”) Weight 2.4 kg ( 5.29lb) Main Board (dimensions / weight): 96 X 185 mm (3.77 X 7.28 “) 0.23Kg (0.51 lb)
Fuses F1: Battery Power 3.15 A AUX Automatic fuse
Bell Automatic fuse
Keypads
Current consumption:
Control panel connections:
Dimensions: 110X130X25 mm
Weight: 0.19 kg (0.42 lb) 0.19 kg (0.42 lb) 0.25kg (0.55 lb)
6 / 8-Zone Keypad 14-Zone Keypad LCD Keypad
18 mA typical, 30 mA maximum
4-wire up to 300 ft (100 m) from panel
(4.33 X 5.11 X 1“)
18 mA typical, 37 mA maximum
4 -wire up to 300 ft (100 m) from panel
110X130X25 mm (4.33 X5.11X 1“)
75mA maximum
4 -wire up to 300 ft (100 m) from panel
162 X 122 X 30 mm (6.37 X 4.8 X 1.18“)
Utility Output Expansion Module
Current consumption: 10mA typical, 50mA max
Control panel connections: 4-wire up to 300 ft (100m) from panel Contacts: 1 relay 3A, 3 relays 0.5 A, 24 V DC
Dimensions: 53X85 mm (2.1X3.35“) Weight: 80 gr (0.18 lb)
Relay row
Expansion Voice Module
Input Power: 12 V DC
Current consumption: 6 mA, typical / 26 mA maximum
Dimensions: 66 X 66 X 18 mm (2.59 X 2.59 X 0.70“)
Weight: 20.44 gr (lb)
NOTES:
For proper operation it is recommended to connect the voice module at least 20 cm from the main panel.
Installation Manual
5
Page 12
Max. Run Length from Panel to Keypad
AWG 19 20 22 Wire
Ø (mm) 0.9 0.8 0.6
Meter 200 166 100 Length
Feet 660 547 330
Bell Loudspeaker Wiring Table (Distance in Feet)
AWG
Ø mm
Max. Current mA
100 780 238 625 190 495 151 310 95
300 260 79 208 64 165 50 103 32
650 120 37 96 30 76 23 48 15
18 19 20 22
1 0.9 0.8 0.6
Feet Meter Feet Meter Feet Meter Feet Meter
Detectors Distance in Feet
AWG
Ø mm
Max. Current mA
20 3920 1195 3100 945 2460 750 2460 472 1550 296
30 2600 793 2060 628 1640 500 1640 314 1030 197
40 1960 597 1550 472 1230 375 1230 236 775 148
18 19 20 22 24
1 0.9 0.8 0.6 0.5
Feet Meter Feet Meter Feet Meter Feet Meter Feet Meter
6
Installation Manual
Page 13
Installation
Before You Begin
Be sure the actual work is performed by experienced personnel, licensed to carry out security system installations and capable of implementing all applicable requirements of the National Fire Protection Association (NFPA-70 and NFPA-74), as well as any federal, state, and local codes – along with any safety guidelines and regulations which might apply.
Mounting the Control Panel
1. Mount the ORBIT-14’s metal cabinet at a protected dry location, near a source of unswitched AC Power, a good ground, and access to telephone service. Use the proper hardware (e.g., anchors, toggle bolts), as required, to insure a suitable mounting.
2. Thread all electrical wiring through a convenient hole in the metal cabinet. To prevent potential damage, be sure that live AC power is NOT present and that the Standby Battery is NOT connected. (Refer to page 8). Your wiring may include any and all of the following:
Connections to Hardwired Zones
Connections to devices requiring Uninterrupted Auxiliary Power (e.g., PIRs,
Glass Break Detectors)
Connections to Smoke Detectors requiring Reset table Power
Connections to any External Sounders
3. Have a Standby Battery ready (typically 12 VDC, 7 AH), but do not connect it at this time.
4. If using a Key-switch, use a momentary key-switch. The receiver (if used) must give a pulse output and not on/off.
Safety Warnings
When the panel is powered, mains voltage is present on the main PCB. To
prevent risk of electric shock, disconnect all power (AC transformer and battery) and phone cord before servicing. On no account should mains power be connected to the PCB other than the main terminal block.
For AC mains connection, a readily accessible disconnect device shall be
incorporated in the building installation wiring.
For continued protection against risk of fire, replace fuses only with fuses of
the same type and rating
There is a risk of explosion if the battery is replaced by an incorrect battery type.
Dispose of used batteries according to the instructions. (The control panel is designed to work with a 12 volt, 7 Amp-hour sealed lead battery as a back up for the primary power supply.)
Installation Manual
7
Page 14
Do not short the terminals of the transformer together. This causes the internal
fuse to blow. The transformer must be connected to a 230 VAC 24-hour outlet, which must be controlled by an approved over-current protection device.
The control is designed with reverse polarity protection on the battery charging
circuit; however, prolonged improper connection of the battery to the control panel results in damage. Power should remain disconnected until all connections have been made and checked for accuracy.
Wiring the Main Panel
Connecting to Ground (Earth)
Connect the metal box and the door of the metal box to mains earth (ground), as shown in the diagrams below. Refer also to What Makes a Good Ground, page 9.
IMPORTANT:
Connecting to ground must be performed according to the applicable local or national electrical codes.
8
Installation Manual
Page 15
Grounding the Metal Box
What Makes a Good Ground?
Grounding provides a degree of protection against lightning and induced transients for any piece of electronic equipment that may, due to lightning or static discharge, experience permanent or general malfunctions. The ideal ground is considered to be a unified earth ground in which an 8-foot copper-clad rod, located close to the existing power and telephone ground rods, is sunk several feet into the earth. Appropriate hardware and clamps are then used to electrically connect each of these rods together and then to the ground terminal of the device to be protected.
Installation Manual
9
Page 16
It may be possible to use an existing electrical ground on the premises if one is close enough to the Main Panel. Ideally, that ground can be obtained at the metal service panel where the incoming electrical power originates. When connecting the ground wire, use a solid 14-gauge wire [or larger (numerically lower) size] connected between the ORBIT-14’s GND terminal and an acceptable electrical ground connection. Keep this wire as short as possible and do not run it in conduit, coil it, bend it sharply, or run it alongside other wiring. If you must bend it or change its direction, it should have a radius of at least 8 inches at the point from which it is bent. If in doubt, you may want to enlist the help of a licensed electrician.
Telephone Line Connection
These lines are typically derived from an installed RJ31X jack. To connect telephone lines:
1. Connect the incoming telephone line to the Main Panel's LINE terminals.
2. Connect any telephone on the premises to the SET terminals.
Connecting AC Power
Connect the 230V AC to the mains fuse input terminal block (via 16.5VAC 40VA transformer) and fasten the AC cord to the metal box using adjustable clamps.
NOTES:
DO NOT apply main power at this time. Be sure to connect the live wire of the AC power through the AC fuse. Do not plug in the transformer at this time.
Zone Connections
Connect each zone to the appropriate zone terminal and its related COM terminal. Each pair of zones shares a COM terminal.
The following diagram illustrates the various possible zone connections:
10
Installation Manual
Page 17
NOTES:
For zones defined as EOL, use 2.21 K resistors (supplied). By default all zones are defined as EOL termination.
The Double End Of Line (DOEL) configuration allows a detector tamper switch, if violated, to register a tamper condition at the panel without the need for a separate connection to a designated tamper zone.
Only zones 1-6 can be defined as DEOL. Zones 9-14 are not valid in this configuration.
Double Zone Wiring
Zone doubling is used to connect two separate zones on one input. Use the following diagram for appropriate connection. The tamper alarm will be the same for both of the zones.
Zone No.1 Zone No.9
Zone No.1 Zone No.9
Tamper
To Panel
To Panel
Zone
Zone
Input
Input
Tamper
Tamper
N.C.
N.C.
Alarm
Alarm
N.C.
N.C.
3.32K
3.32K
Tamper
N.C.
N.C.
Alarm
Alarm
N.C.
N.C.
2.21K 5.62K
2.21K 5.62K
For double zone wiring use the supplied resistors.
NOTES:
The location of the resistors is crucial. Any change in the resistors' location will adversely affect the correct zone identification. Zones 1-6 must be applied with the 3.32K resistor. Zones 9-14 must be applied with the 2.21 K and 5.62 K resistors.
Zones 7 and 8 cannot be defined as double zone termination.
Installation Manual
11
Page 18
Wiring Auxiliary Devices
Use the Auxiliary Power AUX (+) COM (-) terminals to power PIRs, glass-break detectors (4-wire types), smoke detectors, audio switches, photoelectric systems and/or any device that requires a 12V DC power supply.
NOTES:
The total power from the AUX terminals should not exceed 600mA.
To connect a 4-wire smoke detector or devices that require resetting after an alarm condition, connect the Auxiliary power AUX and UO terminals (refer to page 8 for smoke detector wiring). Remember to define the UO as Switched Auxiliary (refer to page 31).
In addition, when connecting a 4-wire smoke detector observe the wiring guidelines of the local requirements applicable to smoke detectors.
To prevent a possible drop in voltage due to current requirements and distances involved, make sure to use the appropriate wire gauge.
If the auxiliary outputs are overloaded (exceed 600mA) and are shut down, you must disconnect all loads from the outputs for a period of at least 10 seconds before you reconnect any load to the auxiliary outputs.
Bell Tamper
The bell tamper is a tamper input that is terminated by an EOL resistor (2.21 K). If the line is cut or shorted, the alarm is turned on.
Connect the bell tamper to the BELL TMP and COM terminals on the main panel.
Box Tamper
The box tamper is a tamper input (NC - normally closed) for the metal box, which protects both sides of the box. This means that if the box is opened or removed from the wall, the tamper opens and turns on the alarm.
Connect the box tamper to the BOX TMP and COM terminals on the main panel.
NOTE:
For Bell and Box tamper supervision, connect the tamper switches before applying the main power to the system.
12
Installation Manual
Page 19
Utility Output Connections
The ORBIT-14 main panel includes three Utility Outputs on board: 1 relay 3Amps, 1 500mA transistor and 1 open collector 70 mA transistor which can be used for switching an external device on or off or reset a “latched” smoke detector(s). Once the Utility Output (UO) is activated the device will be connected between AUX (+12V) and ground (0V).
Wiring the external Utility Outputs:
UO1: Refer to the J4 connector instructions, described below.
UO2-UO6: Connect the positive connection of the device to AUX (+) and the negative connection to the UO's (-) terminals.
NOTES:
When activated the Utility Output is switched to the Negative Polarity.
When the UO is used to reset a “latched” smoke detector(s), the 12V power to the smoke detector is supplied via the UO (see page 8). The UO should be defined as AUX switch (see page 31).
Connecting the Utility Output Expansion Module
If more than three UOs are required, a Utility Output Expansion module is available. The UOs on the expansion module comprise four relays; three relays that allow maximum current of 500 MA each, and one relay that allows maximum current of 3A.
When the Utility Output Expansion Module is employed, UO3 on the Main Board (the UO3/ECL terminal) is no longer available. UO1 on the Utility Output expansion module becomes UO3 in the system.
To connect the Utility Output expansion module, connect the terminals as follows:
Panel BUS TERMINALS
UO Expansion Module terminals
ORBIT-14 Main BUS
AUX
RED
AUX
RED
COM
BLK
COM
BLK
ECL
YEL
UO3
ECL
DAT
GRN
DAT
GRN
NOTE:
In order to use the Utility Output Expansion, you have to define the utility module in location 059 (see page 38)
Installation Manual
13
Page 20
Connecting the J4 Connector
The J4 connector (jumper) determines the UO1 connection (behaviour), which is normally used for an external siren connection, as follows:
Positive (POS): When the J4
connector is placed on POS, the C terminal on UO1 receives
13.8V.
Negative (NEG): When the J4
connector is placed on NEG, the C terminal on UO1 receives COM.
Single pin: If the J4 connector is
placed only on 1 pin, the UO1 acts as a dry contact.
14
Installation Manual
Page 21
Keypad Connection
The ORBIT-14 can support up to five keypads. Each keypad consists of five wires and three terminal blocks (for the connection of zones 7 and 8).
NOTE:
The three terminal blocks are not applicable in a 6-LED keypad.
1. Connect four wires (Red, Black, Yellow, Green) from the keypad to the
appropriate terminals on the main panel, according to the wire colours.
2. Each keypad has an additional white wire for the connection of a panic button. To
connect the panic button, use the white wire as (+) and the black wire as (-).
NOTE:
The maximum distance between the panic button and the keypad is 30 meters.
3. Connecting zones 7 and 8: Zones 7 and 8, which are located on the keypads
(except for the 6-LED keypad), are end-of-line supervised. If more than one keypad is connected to the system and zones 7 or 8 are used, the same zones in the other keypads must be shorted. Each zone can be used only once, in one of the keypads.
NOTE:
The short of a parallel zone must be done before powering the system.
Connecting the J3 SIG IN Connector (Signal in Voice Mail)
The J3 SIG IN voice connector enables the transfer of audio data between the Voice module and the phone line. For further instruction on the voice module, refer to the “Voice Module” documentation supplied with the product.
Installation Manual
15
Page 22
Installer Programming
The Keypad
The ORBIT-14 can support up to five keypads, with a choice of four styles (LCD, 6­LED, 8-LED and 14-LED types), from which virtually all features may be accessed. In addition to the functions it provides for the user, each of the keypads can be used by an installer to program the system parameters.
An attempt to enter an incorrect series of keystrokes will result in three error beeps.
All program location values (data) are displayed by zone indicators on the keypad’s LEDs.
Restoring Factory Defaults to the ORBIT-14
1. Your ORBIT-14 and at least one LED Keypad should already be wired together and/or physically installed.
2. Remove all power from the Printed Circuit.
3. Place the ORBIT-14’s J1 (DEFAULT) jumper over both corresponding pins. (Refer to page 8).
4. Reapply power (AC and/or Standby Battery) to the PC Board.
5. After a short beep is heard, remove the J1 jumper. The ORBIT-14’s default settings are now restored.
6. Check that the POWER LED is flashing. Depending on the state of the system, the READY LED and the Zone LEDs may or may not be lit.
Introduction to Programming
First, check that the panel’s J1 (DEFAULT) jumper is NOT covering both pins on the PC Board.
The ORBIT-14 stores information in 168 programming locations. The data stored in any location is represented by numbers and/or letters. Some locations require just one digit, while most require two. Others may require several more digits (e.g. those used to store phone numbers and account numbers).
It is not necessary to enter data into all categories. Many locations have been factory­programmed with default parameters.
NOTE:
Power can be removed from the ORBIT-14, as its memory does not require a source of power to retain its information.
16
Installation Manual
Page 23
Programming Your ORBIT-14
Programming Methods
Local Requirements LED or LCD keypads
ORBIT Programmer
Easy programming of the control panel parameters with menu driven LCD display.
The programmer can store up to 10 ORBIT-14 programming sets and copy them directly to the panel.
Local ORBIT UD*
Local Up/Load Windows version from a personal computer.
Remote ORBIT UD*
Remote U/D Windows version from a personal computer.
* Compatible with Windows 95/98/2000 XP. (P/N RP128UD0000A)
The keypad must be wired to the ORBIT-14 panel.
Power must be applied to the ORBIT-14.
The programmer will be connected to and receive its power from the panel.
P/N: RP214PR00XXA* *: XX represents the programmer
language interface.
The software must be installed and an ORBIT UD Adaptor cable is connected between the panel and the computer.
P/N for the local adapters: RP214LU0000A: Local Bus Adapter. RP214USB000A: USB/RS232 Bus
Adapter.
The software and applicable modem with configured access to a telephone line must be installed.
Viewing the Contents of a Location
It is often necessary to check the data stored in a memory location to ensure that it is correct. If improper data is found, it must be corrected in order to obtain the desired system response. The data in a location can either be a number (from 0-9) or a letter (from A-F), taking advantage of the hexadecimal numbering system. For our purposes, the characters A through F will be referred to as hexadecimal digits.
Whenever the Installer Programming mode is active, the first four Zone LEDs on the keypad (1-4) are used to reveal each digit in a selected location. By adding up the values assigned to the lit LEDs, the contents of any table below.
Installation Manual
location can be determined. See the
17
Page 24
Digit
0 OFF OFF OFF OFF 8
1 OFF OFF OFF
2 OFF OFF
3 OFF OFF
4 OFF
5 OFF
6 OFF
7 OFF
Example A: If Zone 4-ON, Zone 3-OFF, Zone 2-OFF, and Zone 1 ON, then the digit equals 9.
Example B: If Zone 4-ON, Zone 3-OFF, Zone 2-ON, and Zone 1 - ON, then the digit equals 8.
ZONE LEDs
4 3 2 1
ON
ON
OFF A
ON ON
ON
OFF OFF C
ON
OFF
ON ON
ON ON ON
ON
OFF E
Digit
9
B
D
F
ZONE LEDs
4 3 2 1
ON
OFF OFF OFF
ON
OFF OFF
ON
OFF
ON
OFF
ON ON
ON ON
ON ON ON
ON ON ON ON
ON
ON ON
OFF OFF
OFF
ON
OFF
ON
OFF
Locations Whose Contents Occupy More Than One Digit
When a location contains more than one digit, they cannot be viewed simultaneously. As soon as a location is accessed, the first digit is displayed automatically. Additional digits (if they exist) can be displayed by pressing the following keys on the LED keypads.:
Used to display the next digit in a location containing at least two digits. For example, if 5-6-7-8 is stored in a location, the “5” is displayed first; when you press , the “6” will be displayed. Continue this process to display the entire contents of the chosen location. Error beeps will be emitted if you attempt to display non­existent digits.
Used to move backwards among the digits stored in a location containing at least two digits. Error beeps will be emitted if you attempt to display non-existent digits.
Audible Tones and Error Beeps
To confirm an operation, a single, long beep will be heard. However, any improper use of the keypad resulting in an error or an unacceptable response will produce three rapid beeps. If heard, repeat the operation or exit the programming mode and try again.
Programming Installer Parameters
1. To enter the Installer programming mode: Press the 4-digit Installer code followed by # (factory default 0 2 1 4)
2. To move to a new location: Press the 3-digit location code followed by ARM.
18
Installation Manual
Page 25
3. To enter data into the location: Press data digits (0 - 9 digits including hexadecimal A-F) followed by #.
Using your LED keypad, you can enter the hexadecimal digits A – F as follows:
To Enter Press
A [STAY] + [1] B [STAY] + [2] C [STAY] + [3] D [STAY] + [4] E [STAY] + [5] F [STAY] + [6]
4. To exit programming mode: Press the 4-digit installer code followed by ARM.
Programming Time Out
If after 10 minutes during the programming time, no entry is made to a keypad that has been used for the programming operations, it will produce an audible reminder, consisting of several beeps in rapid succession. Pressing on any key will stop the beeping and return to the programming mode.
Programming Tutorial
To help acquaint you with some programming basics, a short tutorial has been prepared. It involves changing the Installer Code from the factory default of 0-2-1-4 to a sequence of your own choosing. If you can master this operation, subsequent programming should be easy.
Operation Action Comments
Enter the Installer
1
Programming mode
Access the current
2
Installer Code
(stored in location “008”)
Enter a unique
3
Installer Code
(for this tutorial, use 3-0-5-7)
Store the data
4
you have entered
Enter the factory default Installer Code (0-2-1-4); followed by #.
Press [0], [0,[8], [ARM]. No confirming beep will sound.
Enter [3], [0], [5], [7].
Press [#]. A long beep will sound confirming that
A long beep will sound, confirming successful entry into Installer Programming.
No confirming beep will sound.
data has been properly stored. If a wrong number of digits entered
three (error) beeps will sound after pressing #.
Installation Manual
19
Page 26
Operation Action Comments
Check the data
5
stored in Location “008”
The first digit of the stored data is displayed.
Observe the Zone LEDs.
Press keys
Press [STAY] [STAY] to advance to the next digit.
Once all four digits have
STAY STAY
been displayed, attempts to view an additional digit will result in three (error) beeps.
If desired, press [STAY] and [ARM] to move
STAY STAY
STAY STAY
backwards.
Go to another
6
location of your
Press the desired 3-digit location and [ARM].
Press [ARM] alone to go to the next sequential location.
choice Exit programming Enter your Installer Code
7
and press [ARM]. (Only in
A long beep will confirm your actions.
the LED keypad)
Displayed
none 1st digit 2, 1 3
nd
2
3rd digit 3,1 5
4th digit 3,2,1 7
Zone LEDs
digit none 0
Value
lit
20
Installation Manual
Page 27
Programming Locations:
General System Parameters: Locations 000-005
Location: 000 Default Enable: Def: 00
To enable or disable the option of resetting the system to the factory defaults.
00
55
Location: 001 MS Lock: Def: 000000
MS Lock is a security function used in conjunction with Rokonet's Upload/Download software. It provides greater proprietary security when viewing Central Station parameters.
The 6-digit code that will be stored in the panel must also be entered into the corresponding account profile created for the installation in the Upload/Download software. If there is no match between the MS Lock Code defined in the Main Panel and the MS Lock Code defined in the Upload/Download software, the Installer will not have permission to change the following Central Station parameters from the Upload/Download software: Installer Code, MS phone numbers, the MS Lock Code, and the Default Enable jumper.
It is NOT necessary to change the MS Lock default value within Installer Programming; instead, the procedure may be performed from the Upload/Download Software and then downloaded to the ORBIT-14.
Enable the option of resetting the system to the factory defaults by shorting the default jumper on the PC board during power-up. Disable the option of resetting the system to the factory defaults by using the default jumper.
Location: 002 Phone Number: Primary Central Station (Central Station 1)
The first Central Station phone number. Up to 32 alphanumeric characters can be defined as the phone number. To enter or replace the phone number required to reach the primary Central Station, include all access digits (e.g., 0 to 9) and the area code. If required, include the following special functions to achieve the effect listed in the table:
FUNCTION SEQUENCE RESULTS
Stop dialling and wait for a new dial tone [STAY], [1] A
Wait a fixed period before continuing [STAY], [2] B
Switch from Pulse to Tone (or from Tone to Pulse) [STAY], [3] C Send the DTMF ✱ character [STAY], [✱
Send the DTMF # character [STAY], [#] #
]
When your entry is complete, press [#] to store it. To delete an existing phone number, simply press the [#] key without any other digit or character.
Installation Manual
21
Page 28
Location: 003 Phone Number: Secondary Central Station (Central Station 2)
The second Central Station phone number. The definition is the same as in Location
002.
Location: 004 Callback UD Phone Number
This is a number to which the alarm company computer, equipped with the U/D software, will be connected and to which the ORBIT-14 will call back. This provides more security for U/D operations.
When a call is made from a computer, using U/D software, to the ORBIT-14 panel, the system will hang-up and call back using this UD phone number. Up to 32 digits can be entered into the U/D phone number. Include all the digits and functions as in Location 002. To delete an existing phone number, press #.
Location: 005 Account Number Default: 0000
The system’s Central Station Account Number. The ORBIT-14 accepts hexadecimal account numbers (those using 0 through 9 and A through F); use the key combinations below (in LED keypads only) to enter hexadecimal digits “A” through “F”:
Hex digit Press Hex digit Press
A [STAY], 1 D [STAY], 4 B [STAY], 2 E [STAY], 5 C [STAY], 3 F [STAY], 6
NOTE:
Use the “0” digit only to define account numbers with less than four digits. For example, for account number 123, enter 0123. In this case the ORBIT-14 will not send the “0” digit to the Central Station.
To use an account number with “0” digit, for example “1207”, use the “A” digit instead of “0” digit. For example, for account number 1207, enter 12A7. The sequence of buttons will be: [1][2][STAY][1][7]
System Codes: Locations 006-010
Location: 006 Access Code Default: 5678
Provides data security during Upload/Download operations. This Access Code must subsequently be entered into the corresponding account profile in the Upload/Download software. For successful communication, the Access Code must be the same for the both the Upload/Download software and the Main Panel.
Location: 007 Remote ID Code Default: 0001
An ID Code that serves as an extension of the Access Code, described in the procedure above. The ID code provides data security during Upload/Download operations. This Remote ID Code must subsequently be entered into the corresponding account profile in the Upload/Download software. For successful communication, the ID Code must be the same for both the Upload/Download software and the Main Panel.
22
Installation Manual
Page 29
Location: 008 Installer Code I Default: 0214
The installer code is a 4-digit code used by alarm company personnel authorized to
modify the system’s parameters. It is recommended to change the “factory default” Installer Code to one of your own choice.
Location: 009 Installer Code II Default: 1214
A 4-digit code that identifies a technician sent by the installation company to carry out restricted tasks. Using this code, the sub-installer can access only those programming locations associated with the authority level defined in location 061(refer to page 41).
Location: 010 Master Code Default: 1234
A 4-digit code used by the system's owner or chief user. The Master Code provides the following special privileges:
To enter, modify, and delete the remaining all User Codes
To set the system's internal clock
To perform certain system functions and tests
NOTE:
The Master Code cannot be seen by the installer through the zone LEDs on the keypad.
System Time Definitions: Locations 011-016
Location: 011 Exit Delay Default: 030
Establishes the system’s Exit Delay (the interval, in seconds, between entering a User Code at the keypad and when the system actually arms).
Enter the number of seconds (between 001 and 255).
Location: 012 Entry Delay Default: 060
Establishes the system’s Entry Delay (in an armed system, the interval, in seconds, between the moment an entry door is opened and an alarm is triggered).
Enter the number of seconds (between 001 and 255).
Location: 013 Bell Cutoff Time Default: 04
Sets the interval that the system’s external sounder(s) will operate during an alarm before it shuts off automatically.
Enter the number of minutes (between 01 and 90).
NOTE:
The keypad’s buzzer operation is not affected by the Bell Cutoff time definition.
Installation Manual
23
Page 30
Location: 014 Bell delay Default: 00
The time delay before the keypad sounder and the external sounder operates after the onset of an alarm.
Enter the number of minutes (between 00 and 90).
Periodic Test: Locations 015-016
The Periodic Test menu enables you to set the time period that the ORBIT-14 will automatically call the Central Station or Upload/Download phone numbers in order to check the phone line connection and the unit’s digital communicator.
NOTE:
The Periodic Test cannot occur if the value of the Start Periodic Time or Periodic Test interval is set to zero.
Location: 015 Start Periodic Test Default: 0000
Sets the start time of the periodic test. The chosen time is expressed in 24-hour format. Examples: 8:30 AM = 0830, 4:30 PM = 16:30.
NOTE:
If desired, you can disable the test transmission capability by entering the default (0000). Entering the installation mode after the indicated time will defer the test transmission until the
indicated periodic test time on the following day.
Location: 016 Periodic Test Interval Default: 00
Sets the interval for periodic test reporting. Enter two digits between 00 and 99 hours.
NOTE:
If desired, you can disable the test transmission capability by entering the default 00 as the periodic test interval.
Zone Types and Sounds: Locations 017-030
Locations 017 through 030 are identical and correspond to Zones 1 through 14. Each of these locations contains two digits.
First digit: Contains the number used to represent the Type of Zone desired.
Second digit: Contains the number used to represent the sound produced
Locations: 017-030 Zone 1-14: (1st Digit): Zone Type
1st Digit Zone Type and Comments
24
when in alarm.
Not Used
0
All unused zones should be given this designation. It is also used to disable a zone.
24-Hour
Usually assigned to protect non-movable glass, fixed skylights or cabinets for shock
1
detection systems. A violation of such a zone will always cause an instant intrusion alarm, regardless of the system’s armed/disarmed state.
Installation Manual
Page 31
Locations: 017-030 Zone 1-14: (1st Digit): Zone Type
Day Zone
Usually assigned to an infrequently used door, such as an emergency door or a movable skylight. Used to alert the system user if a violation occurs during the disarmed period (trouble by day; burglary at night), as follows:
With the system armed (either AWAY or Group), the zone acts as an instant zone.
2
A violation of this zone after the system is armed or during the Exit Delay time period causes an immediate intrusion alarm.
With the system disarmed, a violation of this zone attempts to alert the user by causing the POWER LEDs on all keypads to flash rapidly. This directs the user to view the system's TROUBLE indications.
Instant (Intrusion)
Usually intended for non-exit/entry doors, window protection, shock detection, and
3
motion detectors. Causes an immediate intrusion alarm if violated when the system is armed or during the Exit Delay time period (Only in IMQ definition).
Exit /Entry Delay
4
If violated, a zone with this designation will not cause an intrusion alarm during the Entry and Exit Delay periods.
Exit (OPEN)/Entry
Such a zone behaves as described above in Entry/Exit Delay, except that if faulted at the time the system is armed, it will be bypassed and NOT prevents system arming.
5
To avoid an intrusion alarm, however, the zone must be secured before the expiration of the Exit Delay period (Location 11).
Entry Follower
Usually assigned to motion detectors and to interior doors protecting the area between the entry door and the keypad.
6
This zone will cause an immediate intrusion alarm when violated unless an Entry/Exit zone was violated first. In such a case, an Entry Follower zone(s) will remain bypassed until the end of the Entry Delay period.
Fire Zone
Intended for smoke or other types of fire detectors. If violated, will cause an immediate
7
fire alarm. A short in the zone wiring will cause a fire alarm. A fault in the wiring to the zone will cause a Fire Trouble (fire LED blinks). A fire zone cannot be disabled or bypassed.
Panic Zone
8
Used for external panic buttons and wireless panic transmitters. If violated an immediate panic alarm will be announced.
Pulsed Key-switch Zone - Instant
If desired an external SPST spring - loaded, normally open, momentary type key
9
switch can be added for system arming and disarming. The key switch permits an instant arm and disarming of the system after tripping.
Pulsed Key-switch Zone - Delayed
A
This zone behaves similar to the Pulsed Key-switch Zone - Instant, described above, except that an exit delay will follow the arming of the system.
Latch-Key-switch Zone – Instant: If desired for system arming/disarming, connect
B
an external SPST latching type (non-momentary) key-switch to any zone terminals, given this designation.
Installation Manual
25
Page 32
Locations: 017-030 Zone 1-14: (1st Digit): Zone Type
Latch-Key-switch Zone – Delayed: This zone behaves similar to the Latched Key-
C
switch Zone - Instant, described above, except that an exit delay will follow the arming of the system.
Locations: 017-030 Zone 1-14: (2nd Digit): Zone Sound
2nd
Zone Sound and Comments
Digit
Silent
A violation during the armed period will produce no sound. The resulting alarm can still
0
be reported to the Central Station.
Bell only (Continuous)
1
Activates the external bell sounders to annunciate steadily without breaks in the sound
cadence for the duration of the Bell Timeout period, or until the system is disarmed.
Bell only (Pulses)
Activates the external bell sounders to produce a pulsed (or staggered) annunciation
2
for the duration of the Bell Timeout period, or until the system is disarmed. This sound is usually recommended for fire alarm annunciation.
Buzzer Only
3
Activates each keypad's internal buzzer to beep rapidly
Bell + Buzzer
4
Activates the bell sounders (consciously) and the keypads' buzzers simultaneously.
Bell When Armed / Buzzer When Disarmed
Related to 24H zones.
5
If an alarm occurs in disarm mode, the keypad’s buzzer will be activated. If an alarm occurs in arm mode, the external Bell will be activated.
Not Applicable
6,7
Silent: Chime on Disarm Same as the Silent option, described above, except that when in Disarm mode the
8
keypad’s buzzer makes one momentary sounds (Door Chime) whenever the zone is violated.
Bell only (Continuous): Chime on Disarm Same as the Bell only (Continuous) option, described above, except that when in
9
Disarm mode the keypad’s buzzer makes one momentary sounds (Door Chime) whenever the zone is violated.
Bell only (Pulses): Chime on Disarm Same as the Bell only (Pulses) option, described above, except that when in Disarm
A
mode the keypad’s buzzer makes one momentary sounds (Door Chime) whenever the zone is violated.
Buzzer Only: Chime on Disarm Same as the Buzzer Only option, described above, except that when in Disarm mode
B
the keypad’s buzzer makes a momentary sound (Door Chime) whenever the zone is violated.
Bell + Buzzer: Chime on Disarm Same as the Bell + Buzzer option, described above, except that when in Disarm
C
mode the keypad’s buzzer makes a momentary sound (Door Chime) whenever the zone is violated.
26
.
Installation Manual
Page 33
Zone Type and Sound Default:
Zone/s Location/s Type Sound
Z1 017 (5) (1) Z2 018 (6) (1)
Z3 – Z6 019 - 022 (3) (1)
Z7-Z8 023 - 024 (0) (0)
Z9 – Z14 025-030 (3) (1)
Zone Response Time & Group Masking: Locations 031-044
Locations 031 through 044 are identical and are corresponding to zones 1 through
14. Each of these locations contains two digits:
First digit: Contains the number used to represent the zones loop response
that sets the minimum time for which a zone violation will trigger an alarm.
Second digit: Contains the number used to represent to which group/s the
zone will be assigned.
Locations 031-044 Zone loop response + Group masking:
1st Digit Loop response
0
(Default)
1 10 ms
2nd Digit Group masking
0
(Default)
1 A 2 B 3 A + B 4 C 5 A + C 6 B + C 7 A + B + C
400 ms
None
Zone Termination & Tamper Sound: Location 045
First Digit: Determines the zone terminations. (NO – Normally Open,
NC – Normally Closed, EOL – End of Line, DEOL – Double End Of Line, DZ – Double Zone). An explanation can be found on page 11. Default: EOL.
Installation Manual
27
Page 34
NOTE:
The termination of zones 7 and 8 is always EOL. Only zones 1-6 can be defined as DEOL. In this configuration zones 9-14 are not
valid.
Second Digit: Sets the sound(s) produced by a tamper violation (Zone, Bell,
Box, Keypad). The available sounds are: Silent, Bell only – Continuous, Buzzer only, Bell + Buzzer, and Bell in Arm/ Buzzer in Disarm.
1st Digit Zone Termination
0
(Default)
1 NC 2 NO 3 DEOL 4 DZ
2nd Digit Tamper Sound
0 Silent 1 Bell Only 2 Buzzer Only 3 Bell + Buzzer
4
(Default)
Bell in Arm / Buzzer in Disarm
EOL
Utility Outputs: Locations 046-051
The ORBIT-14 main panel includes three Utility Outputs (1 3Amps relay, 1 500 mA transistor and 1 open collector 70 mA transistor). These outputs help operate external devices in response to a number of system activities related to alarms, zones, any general system event or the actions of a particular user. A total of six Utility Outputs are available when the utility module expansion module is connected. You can choose the event that will trigger a selected Utility Output (UO), as well as the manner in which the output will be applied.
NOTE:
In order to use the Utility Output Expansion you need to define the module in location 059 on page 38.
If the Utility Output Expansion Module is used, UO3 on the main board is no longer available. The 1st UO on the expansion module will be referred to as UO3 in the system.
Digit Event and Result
00 Not Active
UO offers no response to any system activity
Arm Follow (Latch)
UO is activated when the system is armed. The activation occurs after the expiration
01
of the exit/delay period. The UO remains active (latched) while the system is armed. When disarming the system the UO deactivates (unlatches).
28
Installation Manual
Page 35
Digit Event and Result
Arm Follow (Pulse)
UO is activated when the system is armed. The activation occurs after the expiration
02
of the exit/delay period. The UO is activated for several seconds (pulse), after which is deactivated.
Alarm Follow (Latched – Restore on Bell Time out)
UO is immediately activated when the system goes into any type of alarm
03
(i.e., intrusion, fire, keypad-initiated panic). UO deactivates at after the system’s bell “times out”.
Alarm Follow (Latched - Restore on user Disarm)
UO is immediately activated when the system goes into any type of alarm (i.e. intrusion, fire, keypad-initiated panic). UO remains active (latched) for the
04
duration of the alarm-even after the system’s bell “times out” UO is deactivated when the system is disarmed.
Alarm Follow (Pulse)
UO is immediately activated for several seconds and then deactivated whenever the
05
system goes into any type of alarm (i.e., intrusion, fire, keypad-initiated panic).
Zone 1 Alarm Follow (Latched)
UO is immediately activated when an alarm occurs on Zone 1. UO remains active
06
(latched) for the duration of the alarm - even after the system sounder "times out". UO is deactivated when Zone 1 goes into normal condition.
Zone 1 Alarm Follow (Pulsed)
UO is immediately activated for several seconds (pulsed) and then deactivated
07
whenever Zone 1 goes into alarm.
Zone 2 Alarm Follow (Latched)
08
Zone 2 Alarm Follow (Pulsed)
09
Zone 3 Alarm Follow (Latched)
0A
Zone 3 Alarm Follow (Pulsed)
0B
Zone 4 Alarm Follow (Latched)
0C
Zone 4 Alarm Follow (Pulsed)
0D
Zone 5 Alarm Follow (Latched)
0E
Zone 5 Alarm Follow (Pulsed)
0F
Zone 6 Alarm Follow (Latched)
10
Zone 6 Alarm Follow (Pulsed)
11
Zone 7 Alarm Follow (Latched)
12
Zone 7 Alarm Follow (Pulsed)
13
Zone 8 Alarm Follow (Latched)
14
Zone 8 Alarm Follow (Pulsed)
15
Zone 9 Alarm Follow (Latched)
16
Zone 9 Alarm Follow (Pulsed)
17
Zone 10 Alarm Follow (Latched)
18
Zone 10 Alarm Follow (Pulsed)
19
Zone 11 Alarm Follow (Latched)
1A
Zone 11 Alarm Follow (Pulsed)
1B
Zone 12 Alarm Follow (Latched)
1C
Installation Manual
29
Page 36
Digit Event and Result
Zone 12 Alarm Follow (Pulsed)
1D
Zone 13 Alarm Follow (Latched)
1E
Zone 13Alarm Follow (Pulsed)
1F
Zone 14 Alarm Follow (Latched)
20
Zone 14 Alarm Follow (Pulsed)
21
Panic Follow (Latched)
UO is activated immediately when a PANIC alarm is triggered by a violation of a
22
zone, defined as Panic, or by pressing the keypad’s [1] and [2] keys simultaneously for two seconds. UO is deactivated when the system is disarmed.
Panic Follow (Pulse)
UO is activated for several seconds when a PANIC alarm is triggered by a violation
23
of a zone, defined as Panic, or by pressing the keypad’s [1] and [2] keys simultaneously for two seconds.
Special Emergency Keying Follow (Latched) UO is activated immediately when pressing the keypad’s [7] and [8] keys
24
simultaneously for two seconds. UO is deactivated when the system is disarmed.
Special Emergency Keying Follow (Pulsed) UO is activated for several seconds when pressing the keypad’s [7] and [8] keys
25
simultaneously for two seconds.
Fire Keying Follow (Latched)
UO is activated immediately when a Fire alarm is triggered by a violation of zone 5,
26
defined as Fire, or by pressing the keypad’s [4] and [5] keys simultaneously for two seconds. UO is deactivated when the system is disarmed.
Fire Keying Follow (Pulse)
UO is activated when a Fire alarm is triggered by a violation of zone 5, defined as
27
Fire, or by pressing the keypad’s [4] and [5] keys simultaneously for two seconds.
User Activated (Toggle)
UO may be activated by the user through the entry of [*]+[2]+[User Code]+[X], where X refers to the Utility Output number.
28
The first entry of the above sequence activates the UO and causes it to latch in the opposite of its current state. The system briefly lights the Zone LED corresponding to the selected UO and produces a single confirming beep. Subsequent entries toggle the response between ON and OFF.
User Activated (Pulse)
UO may be activated by the user through the entry of [*]+[2]+[User Code]+[X], where X refers to the Utility Output number.
29
The entry activates the UO for several seconds (pulse). The system briefly lights the Zone LED corresponding to the selected UO and produces a single confirming beep. Subsequent entries repeat this pattern.
30
Installation Manual
Page 37
Digit Event and Result
AUX POWER Switch (Fire)
Until triggered, UO is normally activated and is designed to be a part of the circuit supplying power to the smoke detector(s); see page 8.
After a Fire Alarm is disarmed, it may be necessary to reset any smoke detector(s), which may be “latched” in alarm. A “latched” smoke detector will cause the
2A
keyboard’s Fire LED to remain lit, even though the panel may be disarmed. To reset a Smoke Detector, a “UO” used in this manner must be momentarily deactivated. This action is performed by the user, who must enter [*]+[2]+[User Code]+[X], where [X] refers to the UO number in the circuit providing Smoke Detector power. If this is not done, it will be impossible to arm the panel. Please advise your customer of this contingency, as stated in the ORBIT-14’s User's Manual.
Duress Code Follow (Latched)
UO is activated when any duress code is entered. The UO is deactivated either when
2B
arming the system or disarming the system due to an alarm that was activated from the emergency keypad keys, 24-hour zone violation or tamper zone violation.
Duress Code Follow (Pulse)
UO is activated for several seconds (and is then deactivated) when any duress code
2C
is entered.
AC Loss Follow (Latched)
UO is activated due to a lack of power from the commercial AC. UO is deactivated
2D
when the system is operating properly from commercial (AC) power.
AC Loss Follow (Pulse)
UO is activated for several seconds (and is then deactivated) due to a lack of power
2E
from the commercial AC.
Low Battery Follow (Latched)
UO is activated when the rechargeable standby battery has insufficient reserve
2F
capacity and the voltage decreases to 11.5V. The UO is deactivated when the battery is in good condition.
Low Battery Follow (Pulse)
UO is activated for several seconds when the rechargeable standby battery has
30
insufficient reserve capacity and the voltage decreases to 11.5V.
Phone line trouble (Latched)
UO is activated when a telephone line fault is detected. The UO is deactivated after
31
the telephone line fault has been corrected.
Phone line trouble (Pulsed)
32
UO is activated for several seconds when a telephone line fault is detected.
Voice Module Enable
The UO is activated after FM phone number dialling has been made due to alarm
33
and causes to a repeatedly pre-recorded message announcement. The UO is deactivated after the FM period termination.
Chime Follow (Pulse)
34
UO is activated for several seconds whenever a keypad sounds its chime. Bell Follow Latched NO
UO is activated whenever the bell is activated. UO is deactivated at the bell cut-off
35
time.
Bell Follow Latched NC
UO is deactivated whenever the bell is activated. UO is activated at the bell cut-off
36
time.
Installation Manual
31
Page 38
Digit Event and Result
Ready Follow NO (Latched)
37
UO is activated whenever the system is in the ready state.
Ready follow NO (Pulsed)
38
UO is activated for several seconds whenever the system is in the ready state.
Ready follow, NC (latched)
39
UO is deactivated whenever the system is in the ready state.
Ready follow, NC (Pulsed)
3A
UO is deactivated for several seconds whenever the system is in the ready state.
Utility Outputs Default:
Utility Output Location Type
UO1 046 04 UO2 047 03
UO3 – UO6 048 - 051 00
Communication Parameters: Locations 052-055
Locations 052 to 055 allow you to define the manner in which the ORBIT-14 communicates with the Central Station when it reports alarms, restorals, troubles, openings/closings, and tests.
Locations 054 and 055 allow you define the communication format as defined by the Central Station (CS).
Dialler Control 1: Location 052
First digit: Determines the number corresponding to the Dialling Method,
Duty Cycle and Central Station retries.
Second digit: Determines the number corresponding to the Redial Wait,
Answering Machine Override and Stop Follow Me authorization.
Comments on Dialler Control 1: (Location 052: 1
Dialling Method Duty Cycle MS Retries
Used to select the dialling method, Pulsed or DTMF. When selecting the dialling method, your choice must be compatible with the type of phone service available at the protected premises.
For pulse dialling method 2 option are available: 10 PPS (Pulse Per Second) or 20 PPS.
For pulse dialling, choose the proper dialling duty cycle.
67/33%: Typically used in European telephone systems.
61/39%: Typically used in USA telephone systems.
st
Digit)
The number of times the ORBIT-14 redials the Central Station after failing to establish a successful communication.
32
Installation Manual
Page 39
Comments on Dialler Control 1: (Location 052: 2nd Digit)
Redial Wait
The number of seconds between attempts at redialling the same phone number when it is busy or unresponsive. Applies to both the MS Retries and FM Retries parameters.
Answering Machine Override
Yes: The Answering Machine
Override is enabled, as follows:
The Upload/Download software at the alarm company calls the account. The software hangs up after one ring by the U/D operator.
Within one minute, the software calls again. The ORBIT-14 is programmed to pick up this second call on the first ring, thus bypassing any interaction with the answering machine.
NOTE:
This feature is used to prevent interference from an answering machine with remote Upload/Download operations.
No: The Answering Machine Override is disabled, and communication takes place in the standard manner.
Follow Me Enable
Yes: Enables Follow Me
communication.
In addition to reporting to the Central Station, the ORBIT-14 has a Follow-Me feature, in which a standard phone call is made to a designated phone number, reporting a system event. The Follow Me can convey a series of tones representing an alarm; it can send numeric or alphanumeric data to a page to display a specific event; or it can send pre-recorded voice messages using the voice module.
No: Disables Follow Me communication.
NOTE:
If both MS phones and FM phones are defined, the system will first call the MS phones and then the FM phones.
Location: 052 Dialler Controls 1: (1st Digit):
1st Digit Dialling Method Duty Cycle MS Retries
0 DTMF N/A 3 1 Pulse @ 20 pps 67/33 3 9 Pulse @ 20 pps 67/33 8
8 (Default) DTMF N/A 8
5 Pulse @ 20 pps 61/39 3 D Pulse @ 20 pps 61/39 8 3 Pulse @ 10 pps 67/33 3 B Pulse @ 10 pps 67/33 8 7 Pulse @ 10 pps 61/39 3 F Pulse @ 10 pps 61/39 8
Location: 052 Dialler Controls 1: (2nd Digit):
2nd Digit Redial Wait Answering Machine Follow Me Enable
0 Immediate No No
1 20 No No
2 30 No No
Installation Manual
33
Page 40
Location: 052 Dialler Controls 1: (2nd Digit):
2nd Digit Redial Wait Answering Machine Follow Me Enable
3 60 No No 4 Immediate Yes No 5 20 Yes No 6 30 Yes No 7 60 Yes 8 Immediate No Yes
9 20 No Yes A 30 No Yes B 60 No Yes C Immediate Yes Yes D 20 Yes Yes
E
(Default)
F 60 Yes Yes
30
Yes
Dialler Control 2: Location 053
First digit: Not applicable, Always “0”
Second digit: Determines whether:
1. The ORBIT-14 is connected to a telephone and if the line is supervised. If the telephone line is cut for more than four minutes, supervision causes phone line trouble.
2. The dialler waits for a dial tone before it starts dialling.
Location: 053 Dialler Controls 2: (2nd Digit):
2nd Digit Wait for Dial Tone
0 No No
1 No Yes
2 Yes No 3
(Default)
Yes
Telephone Connection and
Supervision
Yes
No
Yes
Central Station Pulsed Protocols: Location 054
The code format of the central station protocols is based on the following information.
First digit: Determines the number corresponding to the desired combination
of: Kissoff/Handshake Freq / Message Validation / Extended-Non-Extended Format.
Second digit: Determines the number (or letter) corresponding to the desired
combination of: Dialling Rate / Intrepidity Time / Data Frequency.
NOTE:
The pulsed protocol definition is only applicable if the value “00”, which represents a “Pulsed Protocol” format, is entered in location 55.
34
Installation Manual
Page 41
Location: 054 Pulsed CS Protocols: (1st Digit):
1st Digit Format Kissoff/Handshake Freq Message Validation
0
(Default)
Non-Extended
1400 Hz
Dual Round Compare
1 Non-Extended 2300 Hz Dual Round Compare
2 Non-Extended 1400 Hz Parity
3 Non-Extended 2300 Hz Parity
4 Extended 1400 Hz Dual Round Compare
5 Extended 2300 Hz Dual Round Compare
6 Extended 1400 Hz Parity
7 Extended 2300 Hz Parity
Location: 054 Pulsed CS Protocols: (2nd Digit):
2nd Digit Data Rate Interdigit Time Data Frequency
0
(Default)
40 pulses/sec
390 ms
1800 Hz
1 33 pulses/sec 390 ms 1800 Hz
2 20 pulses/sec 390 ms 1800 Hz
3 10 pulses/sec 390 ms 1800 Hz
4 40 pulses/sec 650 ms 1800 Hz
5 33 pulses/sec 650 ms 1800 Hz
6 20 pulses/sec 650 ms 1800 Hz
7 10 pulses/sec 650 ms 1800 Hz
8 40 pulses/sec 390 ms 1900 Hz
9 33 pulses/sec 390 ms 1900 Hz
A 20 pulses/sec 390 ms 1900 Hz
B 10 pulses/sec 390 ms 1900 Hz
C 40 pulses/sec 650 ms 1900 Hz
D 33 pulses/sec 650 ms 1900 Hz
E 20 pulses/sec 650 ms 1900 Hz
F 10 pulses/sec 650 ms 1900 Hz
Central Station Pulsed Protocols Communication Formats
Refer to the information in the table below and enter a 2-digit format code corresponding to the pulsed communication protocol required by the central station receiver associated with the MS telephone number.
Installation Manual
35
Page 42
Format Name
Silent Knight/
ADEMCO Slow
Silent Knight/
ADEMCO Slow Extended
Radionics/DCI/ Franklin slow 10 2300 Hz Dual round 650 17
Silent Knight Fast 20 1400 Hz Dual round 650 0E
Silent Knight Fast Extended 20 1400 Hz Dual round 650 4E
Sescoa/Franklin/Vertix/ DCI fast
Sescoa/Franklin/Vertix/DCI Extended
Universal high speed 20 2300Hz Dual round 390 12
Radionics 20 1400 Hz Dual round 390 02
Radionics 20 2300Hz Dual round 390 12
Radionics Extended 20 1400 Hz Dual round 390 42
Radionics Extended 20 2300Hz Dual round 390 52
Radionics 40 1400 Hz Dual round 390 00
Radionics 40 2300Hz Dual round 390 10
Radionics Extended 40 1400 Hz Dual round 390 40
Radionics Extended 40 2300Hz Dual round 390 50
Radionics 40 1400 Hz Parity 390 20
Radionics 40 2300Hz Parity 390 30
Radionics Extended 40 1400 Hz Parity 390 60
Radionics Extended 40 2300Hz Parity 390 70
PPS
(pulses
/sec)
10 1400Hz Dual round 650 0F
10 1400Hz Dual round 650 4F
20 2300Hz Dual round 650 16
20 2300Hz Dual round 650 56
Kissoff/
Handshake
Validation
InterDigit
Time
Code
Format
For example, enter 0F in location 054 to use ADEMCO Slow.
Automatic Central Station Protocols: Location 055
When selecting any of the formats, all the reporting codes will be automatically applied to the locations of the reporting codes.
To change a code, enter a new code (according to the type of event – see page 48) to the corresponding location.
When selecting the Pulsed Protocol, the default for all the reported codes will be “00” and any other code should be entered manually.
To remove a particular reporting code from any of the seven Protocols, enter “00” into the corresponding location.
IMPORTANT:
Choose the code format only after defining the zone parameters. Changing a zone type after selecting the code format WILL NOT change the zone’s reporting code and a faulty report will be sent to the central station.
36
Installation Manual
Page 43
Location: 055 Automatic CS Protocols:
Digit Format Name Inter digit Time
00
(Default)
01 Contact ID NA NA -
02
03 SIA (Level 1) 390 ms 1800 Hz -
04 SIA - Domestic 390 ms 1800 Hz
05
06 Ademco 4/2 Express NA NA -
Pulsed Protocol
Contact ID -
Domestic
Ademco 4/2 Express
South Africa
NA NA
NA NA
Data
Frequency
Remarks
No Open/Close reports)
No Open/Close reports)
Special values for the South
African market.
Upload/Download Rings: Location 056
Location 056 sets the number of rings that the ORBIT-14 will wait before automatically answering an incoming call. If such a call was initiated by the alarm company’s Upload/Download software, a process begins which allows a Remote Programming session to take place.
Location: 056 Number of Rings Default: 08
Choose a number of rings greater than that which the customer will normally wait to answer an incoming call. Enter the number of rings (between 00-15).
NOTE:
If an Answering Machine is in use and so programmed, entries made in this location will be ignored (see Location 052 / 2nd Digit). 00 indicates an immediate connection without any rings.
Swinger Shutdown Limit: Location 057
Location: 057 Swinger Shutdown Limit Default: 00
A swinger is a repeated violation of the same zone, often resulting in a nuisance alarm, and usually due to a malfunction, an environmental problem, or the incorrect installation of a detector or sensor.
This parameter specifies the number of violations of the same zone reported during a single armed period, before the zone is automatically bypassed.
Range: 00-15 times.
NOTE:
Enter 00 to disable the swinger shutdown.
Location: 058 Not Applicable
Installation Manual
37
Page 44
System Controls: Locations 059-060
Locations 059-060 allow you to specify some additional parameters, which determine how the ORBIT-14 will operate.
Location: 059 System Control 1 Default: 53
The location contains two digits:
First digit: Determines the digit corresponding to the choices involving Quick
Arm / Quick Bypass / Bypass Enable / Loudspeaker / Bell-Siren.
Second digit: Determines the digit corresponding to the use of Silent Panic /
Bell Squawk on Arming / UO Expander/ Voice Module.
st
Digit)
Loudspeaker: If the
external sounder(s) is NOT equipped with a built-in sound driver; doing so causes the ORBIT-14 to produce an oscillating frequency for the device.
Bell/Siren: If the external sounder(s) is a bell or a buzzer or equipped with a built-in electronic sound driver.
Yes: Voice messages will be sent.
No: Tones will be used to represent an active alarm.
Comments on System Control 1 (Location 059: 1
Quick Arm Quick Bypass Bypass Enable Loudspeaker/Bell-Siren
Yes: Eliminates the
need to enter a User Code when arming to the Away or Group modes. No: A valid User Code is required for arming in AWAY or Group modes.
Yes: Eliminates the need for a valid User Code when bypassing zones.
No: Qualified users must enter a valid User Code to bypass zones.
Yes: Permits zone bypassing by authorized system users after entering a valid User Code.
No: Zone bypassing is NOT permitted.
Comments on System Control 1 (Location 059: 2nd Digit)
Silent Panic Bell Squawk on Arming UO Extender Voice Module
Yes: The panic alarm
will be INAUDIBLE at the External Sounder and invisible on the keypad.
No: The panic alarm will be AUDIBLE at the External Sounder and visual on the keypad.
Yes: Bell Squawk on Arming will produce a
brief confirmation “chirp” from the system’s external sounder(s) once the system is armed and the Exit Delay expires.
No: No confirmation chirp from the system external sounders when arming the system.
Yes: A Utility Output Expansion Module is installed. The maximum number of Utility Outputs in the system is 6.
No: A Utility Output expansion module is not installed. The maximum number of Utility Outputs in the system is 3.
38
Installation Manual
Page 45
Location: 059 System Controls 1: (1st Digit):
1st Digit Loudspeaker/Bell-
0 Bell-Siren No No No
1 Bell-Siren No No Yes
2 Bell-Siren No Yes No
3 Bell-Siren No Yes Yes
4 Bell-Siren Yes No No
5
Default
6 Bell-Siren Yes Yes No
7 Bell-Siren Yes Yes Yes
8 Loudspeaker No No No
9 Loudspeaker No No Yes
A Loudspeaker No Yes No
B Loudspeaker No Yes Yes
C Loudspeaker Yes No No
D Loudspeaker Yes No Yes
E Loudspeaker Yes Yes No
F Loudspeaker Yes Yes Yes
Siren
Bell-Siren
Bypass Enable Quick Bypass Quick Arm
Yes
No
Yes
Location: 059 System Controls 1: (2nd Digit):
2nd Digit Voice Module UO Extender Bell Squawk on
0 Disabled No No No 1 Disabled No No Yes 2 Disabled No Yes No
3
(Default)
4 Disabled Yes No No 5 Disabled Yes No Yes 6 Disabled Yes Yes No 7 Disabled Yes Yes Yes 8 Enabled No No No
9 Enabled No No Yes A Enabled No Yes No B Enabled No Yes Yes C Enabled Yes No No D Enabled Yes No Yes E Enabled Yes Yes No
F Enabled Yes Yes Yes
Disabled
No
Arm
Yes
Silent Panic
Yes
Installation Manual
39
Page 46
Location: 060 System Control 2 Default: 11
The location contains two digits:
First digit: Determines the digit corresponding to the choices involving 3-
minute bypass / IMQ Installation bit / Czech installation bit / UL installation bit.
Second digit: Determines the digit corresponding to the use of Auto arming
Pre-Warning / Alarm restore.
Comments on System Control 2 (Location 060: 1
3 Minute Bypass IMQ Installation Czech installation UL installation
Yes: All zones will
be automatically bypassed for 3 minutes when power is restored to an “unpowered” system. This prevents potential false alarms by allowing time for the stabilization of motion and/or smoke detectors.
No: No bypassing occurs.
Yes: Causes the following parameters to function as follows:
An open zone during Auto
Arming will activate an alarm and the system will not be armed.
UO Arm Follow (Pulsed or
Latched). UO will be activated immediately, regardless of the Exit Delay time.
AC loss report and UO
follow AC loss are activated after a delay of 30 minutes.
No:
Auto Arming – An open
zone during auto-arming will be bypassed and the system will be armed.
UO arm follow (Pulsed or
Latched). UO will be activated after the Exit Delay time.
AC loss report and UO
follow AC loss will be activated immediately.
st
Digit)
Yes: The ORBIT-14
is installed in accordance with the Czech telephony requirements.
No: No features are changed.
Yes: The ORBIT-14 is installed in accordance with UL requirements for a Residential Installation (UL 1641). Operation of the unit’s Digital Communicator must be modified to disable features which are inappropriate for UL listed installations. This feature disables the use of Upload/ Download and permits a status display only when remotely accessed.
No: No features are disabled.
Comments on System Control 2 (Location 060: 2nd Digit)
Arm Pre-Warning Alarm Restore
Yes: When the system is Auto Armed, an
audible Exit Delay (warning) countdown will commence 4 minutes prior to the automatic arming. During this period, Exit Delay beeps will be heard in the keypads.
No: There is no Arm Pre-Warning for the Auto Arming feature.
Yes: The system will send an alarm restore after the audible alarm “times out” (BTO=Bell Time Out).
No: The system will send an alarm restore when the zone responsible for the alarm returns to its non-violated (secured) state.
40
Installation Manual
Page 47
Location: 060 System Controls 2: (1st Digit):
1st Digit
0 No No No No
1
(Default)
2 No No Yes No 3 No No Yes Yes 4 No Yes No No 5 No Yes No Yes 6 No Yes Yes No 7 No Yes Yes Yes 8 Yes No No No
9 Yes No No Yes A Yes No Yes No B Yes No Yes Yes C Yes Yes No No D Yes Yes No Yes E Yes Yes Yes No
F Yes Yes Yes Yes
Location: 060 System Controls 2: (2nd Digit):
UL installation Czech
No
2nd Digit Alarm Restore Auto Arm Pre-Warning
0 BTO No
1 (Default) BTO Yes
2 Zone Restore NO
3 Zone Restore Yes
installation
No
IMQ Installation 3 Minute Bypass
No
Yes
Sub Installer Restriction Level: Location 061
The Sub Installer can be defined with two different authority levels. Each level restricts him from programming different locations in the ORBIT-14.
Location: 061 Sub Installer Restriction Level Default: 01
Digit Description
Low: The Sub installer is unable to modify the following locations: 000-008,
00
01
(Default)
056-058,061 High: Use this option for greater restriction of the sub installer programming
options. The Sub installer is unable to modify the following locations: 000-008, 046-058, 061-161.
Installation Manual
41
Page 48
Communicator Reporting Codes: Locations 062-168
Locations 062 -168 enable you to program the codes that will be transmitted by the ORBIT-14 to the Central Station.
To prevent the corresponding event from being reported, use a “double-zero” (00, the default) in the location.
Reporting Codes for Alarm Events
Location Description
062 Zone 1 Alarm Reporting code 2 00
063 Zone 2 Alarm Reporting code 2 00
064 Zone 3 Alarm Reporting code 2 00
065 Zone 4 Alarm Reporting code 2 00
066 Zone 5 Alarm Reporting code 2 00
067 Zone 6 Alarm Reporting code 2 00
068 Zone 7 Alarm Reporting code 2 00
069 Zone 8 Alarm Reporting code 2 00
070 Zone 9 Alarm Reporting code 2 00
071 Zone 10 Alarm Reporting code 2 00
072 Zone 11 Alarm Reporting code 2 00
073 Zone 12 Alarm Reporting code 2 00
074 Zone 13 Alarm Reporting code 2 00
075 Zone 14 Alarm Reporting code 2 00
076 Keypad Fire Alarms Reporting code 2 00
077 Keypad Panic Reporting code 2 00
078 Keypad Special Emergency Reporting code 2 00
079 Tamper Alarm in zone 1 / 9 2 00
080 Tamper Alarm in zone 2 / 10 2 00
081 Tamper Alarm in zone 3 / 11 2 00
082 Tamper Alarm in zone 4 / 12 2 00
083 Tamper Alarm in zone 5 / 13 2 00
084 Tamper Alarm in zone 6 / 14 2 00
085 General tamper alarm (Box / Bell /Keypad) 2 00
Digits Default Report
Code
Restore Codes
An ORBIT-14 Restoral Report informs the Central Station that the external sounder’s operation, initially triggered by the respective alarm condition, has either “timed out” or been silenced by the act of system disarming. Be sure to check with Central Station personnel if restorals are permitted and, if so, what codes are required.
42
Installation Manual
Page 49
Reporting Codes for Restore Alarm Events
Location Description
086 Zone 1 Restoral Code 2 00
087 Zone 2 Restoral Code 2 00
088 Zone 3 Restoral Code 2 00
089 Zone 4 Restoral Code 2 00
090 Zone 5 Restoral Code 2 00
091 Zone 6 Restoral Code 2 00
092 Zone 7 Restoral Code 2 00
093 Zone 8 Restoral Code 2 00
094 Zone 9 Restoral Code 2 00
095 Zone 10 Restoral Code 2 00
096 Zone 11 Restoral Code 2 00
097 Zone 12 Restoral Code 2 00
098 Zone 13 Restoral Code 2 00
099 Zone 14 Restoral Code 2 00
100 Keypad Fire Restoral Code 2 00
101 Keypad Panic Restoral Code 2 00
102 Keypad Special Emergency Restoral Code 2 00
103 Restore tamper from zones 1 / 9 2 00
104 Restore tamper from zones 2 / 10 2 00
105 Restore tamper from zones 3 / 11 2 00
106 Restore tamper from zones 4 / 12 2 00
107 Restore tamper from zones 5 / 13 2 00
108 Restore tamper from zones 6 / 14 2 00
109 General tamper restore (Box / Bell / Keypad) 2 00
Digits Default Report
Code
Other Reporting Codes
Location Description
Report code used when the system’s periodic
110
central station (CS) test transmission take place User 0 arm (the “Master” Code, “Quick Arm”,
111
“Keyswitch” Arm or Remote arming) 112 User 1 arm Reporting code 2 00 113 User 2 arm Reporting code 2 00 114 User 3 arm Reporting code 2 00 115 User 4 arm Reporting code 2 00 116 User 5 arm Reporting code 2 00 117 User 6 arm Reporting code 2 00 118 User 7 arm Reporting code 2 00 119 User 8 arm Reporting code 2 00
Installation Manual
Digits Default Report
2 00
2 00
Code
43
Page 50
Location Description
120 User 9 arm Reporting code 2 00 121 User 10 arm Reporting code 2 00 122 User 11 arm Reporting code 2 00 123 User 12 arm Reporting code 2 00 124 User 13 arm Reporting code 2 00 125 User 14 arm Reporting code 2 00 126 User 15 arm Reporting code 2 00 127 User 16 arm Reporting code 2 00 128 User 17 arm Reporting code 2 00 129 User 18 arm Reporting code 2 00 130 User 19 arm Reporting code 2 00
131
132 Group/s arming Reporting code 2 00 133 Auto arm reporting code 2 00
134
135 User 1 disarm Reporting code 2 00 136 User 2 disarm Reporting code 2 00 137 User 3 disarm Reporting code 2 00 138 User 4 disarm Reporting code 2 00 139 User 5 disarm Reporting code 2 00 140 User 6 disarm Reporting code 2 00 141 User 7 disarm Reporting code 2 00 142 User 8 disarm Reporting code 2 00 143 User 9 disarm Reporting code 2 00 144 User 10 disarm Reporting code 2 00 145 User 11 disarm Reporting code 2 00 146 User 12 disarm Reporting code 2 00 147 User 13 disarm Reporting code 2 00 148 User 14 disarm Reporting code 2 00 149 User 15 disarm Reporting code 2 00 150 User 16 disarm Reporting code 2 00 151 User 17 disarm Reporting code 2 00 152 User 18 disarm Reporting code 2 00 153 User 19 disarm Reporting code 2 00 154 Duress Disarm 2 00
Forced arm Reporting code (when the system is armed with a bypassed zone)
User 0, disarm Reporting code by master code, quick arm, key-switch or remote arming.
Digits Default Report
Code
2 00
2 00
44
Installation Manual
Page 51
Trouble Reports and Restorals
Location Description
155 Low Battery Reporting code 2 00 156 Loss of AC Power (for at least 15 min) 2 00 157 Fire zone trouble 2 00 158 Bell Loop Interrupted 2 00 159 Clock not set 2 00 160 Phone line cut 2 00 161 Day zone trouble 2 00 162 Low Battery restore 2 00 163 Loss of AC Power restore 2 00 164 Fire zone trouble Restore 2 00 165 Bell Loop Restore 2 00 166 Clock not set restore 2 00 167 Phone line cut Restore 2 00 168 Day zone trouble Restore 2 00
Digits Default Report
Code
Installation Manual
45
Page 52
Appendix 1: Installer Programming Worksheet
Customer _____________________________________ Address ______________________________________ City _________________ State _________ Zip _______ Customer Phone No: ( ) _________________________ Comments: ___________________________________
Loca-
Description
tion
000 Default Disable 042 Zone 12: Loop R. + Level 001 MS LOCK 043 Zone 13: Loop R. + Level 002 Phone No. CS 1 See below 044 Zone 14: Loop R. + Level
003 Phone No. CS 2 See below 045
004 UD Call back See below 046 Utility Output 1 type 005 Account No. 047 Utility Output 2 type 006 Access Code 048 Utility Output 3 type 007 Remote ID Code 049 Utility Output 4 type 008 Installer Code 1 050 Utility Output 5 type 009 Installer Code 2 051 Utility Output 6 type 010 Master Code 052 Dialler Control 1 011 Exit Delay 053 Dialler Control 2 012 Entry Delay 054 MS Pulsed protocol 013 Bell Cutoff Time 055 MS Auto protocol 014 Bell Delay 056 U/D Rings 015 Periodic test time 057 Swinger Shut down 016 Periodic test interval 058 NA 017 Zone 1: type + sound 059 System Control 1 018 Zone 2: type + sound 060 System Control 2 019 Zone 3: type + sound 061 Sub Installer level 020 Zone 4: type + sound 062 Zone 1 Alarm 021 Zone 5: type + sound 063 Zone 2 Alarm 022 Zone 6: type + sound 064 Zone 3 Alarm 023 Zone 7: type + sound 065 Zone 4 Alarm 024 Zone 8: type + sound 066 Zone 5 Alarm 025 Zone 9: type + sound 067 Zone 6 Alarm 026 Zone 10: type + sound 068 Zone 7 Alarm 027 Zone 11: type + sound 069 Zone 8 Alarm 028 Zone 12: type + sound 070 Zone 9 Alarm 029 Zone 13: type + sound 071 Zone 10 Alarm 030 Zone 14: type + sound 072 Zone 11 Alarm 031 Zone 1: Loop R. + Level 073 Zone 12 Alarm 032 Zone 2: Loop R. + Level 074 Zone 13 Alarm 033 Zone 3: Loop R. + Level 075 Zone 14 Alarm 034 Zone 4: Loop R. + Level 076 Keypad Fire Alarm 035 Zone 5: Loop R. + Level 077 Keypad Panic Alarm 036 Zone 6: Loop R. + Level 078 Keypad Special Alarm 037 Zone 7: Loop R. + Level 079 Tamper zone 1 / 9 038 Zone 8: Loop R. + Level 080 Tamper zone 2 / 10 039 Zone 9: Loop R. + Level 081 Tamper zone 3 / 11 040 Zone 10: Loop R. + Level 082 Tamper zone 4 / 12 041 Zone 11: Loop R. + Level
Entry
Central Station Account No: ___________ Date of Installation: __________________ Installer(s): ________________________ Comments: ________________________
__________________________________
Loca-
Description
tion
Zone termination + tamper sound
083 Tamper zone 5 / 13
Entry
46
Installation Manual
Page 53
Loca­tion
Description
Entry Loca-
tion
Description
Entry
084 Tamper zone 6 / 14 127 User 16 arm 085 Tamper Box / Bell / KP 128 User 17 arm 086 Zone 1 Restore 129 User 18 arm 087 Zone 2 Restore 130 User 19 arm 088 Zone 3 Restore 131 Forced Arm 089 Zone 4 Restore 132 Level arming 090 Zone 5 Restore 133 Auto Arm 091 Zone 6 Restore 134 User 0 Disarm 092 Zone 7 Restore 135 User 1 Disarm 093 Zone 8 Restore 136 User 2 Disarm 094 Zone 9 Restore 137 User 3 Disarm 095 Zone 10 Restore 138 User 4 Disarm 096 Zone 11 Restore 139 User 5 Disarm 097 Zone 12 Restore 140 User 6 Disarm 098 Zone 13 Restore 141 User 7 Disarm 099 Zone 14 Restore 142 User 8 Disarm 100 Keypad Fire Restore 143 User 9 Disarm 101 Keypad Panic Restore 144 User 10 Disarm 102 Keypad Special Restore 145 User 11 Disarm 103 Tamp. zone 1/ 9 restore 146 User 12 Disarm 104 Tamp. zone 2/10 restore 147 User 13 Disarm 105 Tamp. zone 3/11 restore 148 User 14 Disarm 106 Tamp. zone 4/12 restore 149 User 15 Disarm 107 Tamp. zone 5/13 restore 150 User 16 Disarm 108 Tamp. zone 6 /14 restore 151 User 17 Disarm
Tamp. Box /Bell /Keypad
109
restore
152 User 18 Disarm
110 Periodic Time Test 153 User 19 Disarm 111 User 0 arm 154 Duress Disarm 112 User 1 arm 155 Low Battery 113 User 2 arm 156 AC Loss 114 User 3 arm 157 Fire Trouble 115 User 4 arm 158 Bell Loop trouble 116 User 5 arm 159 Clock not set 117 User 6 arm 160 Phone line cut trouble 118 User 7 arm 161 Day zone trouble 119 User 8 arm 162 Low Battery restore 120 User 9 arm 163 AC Loss restore 121 User 10 arm 164 Fire Trouble restore 122 User 11 arm 165 Bell Loop trouble restore 123 User 12 arm 166 Clock not set restore 124 User 13 arm 166 Clock not set restore 125 User 14 arm 167 Phone line cut restore 126 User 15 arm
168 Day zone restore
Location Description Phone Number (32 Digit max)
02 MS Phone 1
03 MS Phone 2
04 UD Call back
Installation Manual
47
Page 54
Appendix 2: Contact ID & SIA Report Codes for Orbit-14
Event Reporting Format Contact ID SIA (Level 1)
Zones Alarms/Disarm Program Digit Code Program Digit Code
Exit/Entry Alarm 01 134 01 BA
Exit/Entry Restore 01 134 02 BH
Burglary Zone Alarm 03 130 03 BA
Burglary Zone Restore 03 130 04 BH
24 Hour Zone Alarm 05 133 05 BA
24 Hour Zone Restore 05 133 06 BH
Tamper Zone Alarm 07 137 07 TA
Tamper Zone Restore 07 137 08 TR
Smoke Zone Alarm/Restore 09 111
Combustion Zone Alarm/Restore 1A 112
Water Flow Zone Alarm/Restore 11 113 11 WA
Heat Zone Alarm 12 114 12 KA
Heat Zone Restore 12 114 13 KH
Duct Zone Alarm/Restore 14 116
Flame Zone Alarm/Restore 15 117
Panic Zone Alarm Restore
Silent Alarm 16 122
Audible Alarm 17 123
Perimeter Zone Alarm/Restore 18 131 18 NL
Interior Zone Alarm/Restore 19 132
Day/Night Zone Alarm/Restore 2A 135
Outdoor Zone Alarm/Restore 21 136
General Alarm/Restore 22 140
Sensor Tamper Alarm 23 144 23 TA
Sensor Tamper Restore 23 144 24 TR
24 Hour Non Burg Alarm/Restore 24 150
Gas Detected Alarm 25 151 25 GA
Gas Detected Restore 25 151 26 GH
Refrigeration Zone Alarm/Restore 27 152
Loss of Heat Alarm/Restore 28 153
Water Leakage Alarm 29 154 29 WA
Water Leakage Restore 29 154 3A WH
Foil Break Alarm/Restore 31 155
Low Battled Gas level Alarm/Restore 32 157
High Temperature Alarm/Restore 33 158 33 DA
48
Installation Manual
Page 55
Event Reporting Contact ID SIA (Level 1)
Zones Alarms/Disarm Program Digit Code Program Digit Code
Low Temperature Alarm/Restore 34 159 34 DA
Loss of Air Flow 35 161 35 DB
Special
Special Emergency Key Alarm 4A 100 4A MA
Special Emergency Key Restore 4A 100 41 MH
Fire Zone Alarm 42 110 42 FA
Fire Zone Restore 42 110 43 FH
Fire Key Alarm 44 115 44 FA
Fire Key Restore 44 115 45 FH
Panic Key Alarm 46 120 46 PA
Panic Key Restore 46 120 47 PH
Duress Alarm 48 121 48 HA
Duress Restore 48 121 49 HH
Troubles
AC Trouble 5A 301 5A AT
AC Restore 5A 301 51 AR
Low Battery Trouble 52 302 52 YT
Low Battery Restore 52 302 53 YR
Main Bell Trouble 54 321 54 YA
Main Bell Restore 54 321 55 YH
Fire Trouble 56 373 56 FT
Fire Restore 56 373 57 FJ
Clock Not Set 00 - 00 -
Clock Set 00 - 00 -
Phone Line Trouble 58 351 58 LT
Phone Line Restore 58 351 59 LR
Day Zone Trouble 5C 156 5C UT
Day Zone Restore 5C 156 5D UJ
O/C Access
User Arm 6A 401 6A CL
User Disarm 6A 401 61 OP
Quick Arm/Disarm - User 0 62 408 6A CL
Forced Arm 63 574 63 CF
Periodic Test 64 602 64 RP
Auto Arm 65 403 65 CA
Installation Manual
49
Page 56
Appendix 3: Summary of User’s Commands
Function Procedure
System Arming [User Code] + [Arm] Group Arming [User Code] + [Stay] + [Group #: 1,2, 3, 0=All Groups] System Disarming [User Code] Duress Disarming [Duress Code] Silencing an Alarm [User Code] Bypassing / Unbypassing a
Zone
Quick Bypassing Zone Reset Smoke Detector(s) [ ] + [ 2 ] + [User Code ] + [Smoke Output No.]
Utility Output Operation [ ] + [ 2 ] + [User Code ] + [ Utility Output No. ] Display Troubles [ ] + [ 3 ] Display Memory [ ] + [ 4 ] Setting/Changing a User Code
Setting User Authority Level
Set Date [ ] + [ 6 ] + [ 1 ] + [Master Code] + [MM] [DD] [YY] Set Time [ ] + [ 6 ] + [ 2 ] + [Master Code] + [HH] [MM] Set Auto Arm Time [ ] + [ 6 ] + [ 3 ] + [Master Code] + [HH] [MM] Set Follow-Me Phone No. 1 [ ] + [ 7 ] + [ 1 ] + [Master Code] + Phone No. + [#] Set Follow-Me Phone No. 2 [ ] + [ 7 ] + [ 2 ] + [Master Code] + Phone No. + [#] Set Follow-Me Phone No. 3 [ ] + [ 7 ] + [ 3 ] + [Master Code] + Phone No. + [#] Set Follow-Me Phone No. 4 [ ] + [ 7 ] + [ 4 ] + [Master Code] + Phone No. + [#] Erase Follow-Me Phone No. [ ] + [ 7 ] + [ 1 / 2 / 3 / 4 ] + [Master Code] + [#] Maintenance: On/Off Buzzer On/Off Door Chime On/Off Audible Kiss-Off Get Event From Event Logger
(Only from LCD Keypad) Test System [ ] + [ 0 ] + [Master Code]
Trouble Table
[ ] + [ 1 ] + [User Code ] + [ 2-digit zone number to be bypassed / unbypassed]
[ ] + [ 1 ] + [ 2-digit zone number to be bypassed / unbypassed]
[ ] + [ 5 ] + [1] + [Master Code] + [ 2-digit User No. to be set/changed] + [New Code]
[ ] + [ 5 ] + [2] + [Master Code] + [2-digit User Number to be set/changed] + [Authority Level No.] 0 = User, 1 = User Un-Bypass, 2 = Maid, 3 = Service
[ ] + [ 8 ] + [Master Code] + [ 1 ] [ ] + [ 8 ] + [Master Code] + [ 2 ] [ ] + [ 8 ] + [Master Code] + [ 3 ]
[ ] + [ 9 ] + [Master Code]
LED Trouble
1 Low Battery 2 AC Power Loss 3 Clock Not Set 4 Communication Trouble 5 Bell Loop Trouble 6 Phone line cut 7 General Tamper (Bell/ Box/ Keypad) 8 Day Zone Trouble
50
Installation Manual
Page 57
Notes
Page 58
Notes
Page 59
Rokonet Limited Warranty
Rokonet Electronics, Ltd. and its subsidiaries and affiliates ("Seller") warrants its products to be free from defects in materials and workmanship under normal use for 12 months from the date of production. Because Seller does not install or connect the product and because the product may be used in conjunction with products not manufactured by the Seller, Seller cannot guarantee the performance of the security system which uses this product. Seller's obligation and liability under this warranty is expressly limited to repairing and replacing, at Seller's option, within a reasonable time after the date of delivery, any product not meeting the specifications. Seller makes no other warranty, expressed or implied, and makes no warranty of merchantability or of fitness for any particular purpose.
In no case shall seller be liable for any consequential or incidental damages for breach of this or any other warranty, expressed or implied, or upon any other basis of liability whatsoever.
Seller's obligation under this warranty shall not include any transportation charges or costs of installation or any liability for direct, indirect, or consequential damages or delay.
Seller does not represent that its product may not be compromised or circumvented; that the product will prevent any persona; injury or property loss by burglary, robbery, fire or otherwise; or that the product will in all cases provide adequate warning or protection. Buyer understands that a properly installed and maintained alarm may only reduce the risk of burglary, robbery or fire without warning, but is not insurance or a guaranty that such will not occur or that there will be no personal injury or property loss as a result.
Consequently seller shall have no liability for any personal injury, property damage or loss based on a claim that the product fails to give warning. However, if seller is held liable, whether directly or indirectly, for any loss or damage arising from under this limited warranty or otherwise, regardless of cause or origin, sellers maximum liability shall not exceed the purchase price of the product, which shall be complete and exclusive remedy against seller.
No employee or representative of Seller is authorized to change this warranty in any way or grant any other warranty.
WARNING: This product should be tested at least once a week.
Page 60
Contacting Rokonet
Rokonet Electronics Ltd. is committed to customer service and product support. You can contact us through our website (www.rokonet.com) or at the following telephone and fax numbers:
USA
Tel: +1 (305) 592-3820
Fax: +1 (305) 592-3825
United Kingdom
Tel: +44 (1527) 576-765 Fax: +44 (1527) 576-816
Italy
Tel: +39 (02) 392-5354
Fax: +39 (02) 392-5131
Israel
Tel: +972 (3) 9616555 Fax: +972 (3) 9616584
Brazil
Tel: +55 (21) 2496-3544
Fax: +55 (21) 2496-3547
Thailand
Tel: +66 (0) 38723736
Mob: 06 8361823
Fax: +66 (0) 38723736
© ROKONET ELECTRONICS LTD. 04/03 5IN214IM
Loading...