Trademarks not belonging to Rockwell Automation are property of
their respective companies.
ControlNet Communications Option Boar d I/O
With a ControlLogix Processor
Instruction Manual D2-3483
ATTENTION:
equipment and the hazards involved should install, adjust, operate, and/or service this equipment.
!
Read and understand this instruction manual in its entirety before proceeding. Failure to observe
this precaution could result in severe bodily injury or loss of life.
ATTENTION:
the drive circuitry . This circuit must disable the system in case of improper operation. Uncontrolled
machine operation may result if this procedure is not followed. Failure to observe this precaution
could result in bodily injury.
ATTENTION:
international codes. Failure to observe this precaution could result in damage to, or destruction
of, the equipment.
Only qualified personnel familiar with the construction and operation of this
The user must provide an external, hardwired emergency stop circuit outside of
The user is responsible for conforming with all applicable local, national, and
Introduction
This manual describes how to configure WebPak 3000 ControlNet Communication Option board I/O for use
with a ControlLogix processor.
This manual is intended for use by personnel familiar with the installation and operation of the WebPak 3000
drive and the installation, programming, I/O configuration, and operation of the ControlLogix processor using
RSLogix 5000 software and RSNetWorx for ControlNet software.
Related Publications
You must be familiar with the documentation that describes your system configuration. This may include, but is
not limited to, the publications listed in table 1.
Table 1 – Related Publications
Manual No.Title
•D2-3425-2ControlNet Network Communication Option Board For Use With FlexPak 3000 and
WebPak 3000 DC Drives
•D2-3443WebPak 3000 DC Drive Hardware Reference
•D2-3444WebPak 3000 DC Drive Software Reference
Getting Assistance from Reliance Electric
If you have any questions or problems with the products described in this instruction manual, contact your local
Reliance Electric sales office. For technical assistance, call 1-800-726-8112.
ControlNet is a trademark of ControlNet International,Ltd.FlexPak,WebPak, RSLogix 5000,RSNetWorx, and ControlLogix are trademarks of
If the firmware in your ControlLogix equipment does not meet the above requirements, contact the Control and
Information Group technical support division (1-440-646-6800) to obtain a copy of the appropriate
ControlFlash upgrade kit.
1756-CNB or 1756-CNBR
915FK2101Version 2.2 or later
Series A, V1.19
Series B, V2.27 or later
Series D, V5.22
Configuring an I/O Connec tion
Before configuring an I/O connection, you must:
•Configure the WebPak 3000 drive network parameters (refer to chapter 3 in D2-3425-2), set the network
drop number appropriately, and set the control source to network.
•Verify that you have used RSNetWorx for ControlNet to configure the network containing the ControlLogix
chassis and WebPak 3000 drive.
Use the following procedure to configure an I/O connection:
Step 1. After opening the RSLogix 5000 software, verify that you are off-line with the ControlLogix processor.
You can configure an I/O connection when starting a new project or after opening an existing project,
but I/O can only be configured off-line.
2
Using WebPak 3000 ControlNet Communications Option Board I/O With a ControlLogix Pr ocessor
Step 2. Define the ControlNet bridge module in your project’s I/O Configuration folder. To do this:
a. Use the right mouse button to click on the I/O Configuration folder.
b. From the pop-up menu, select New Module.
c. From the Select Module Type dialog box, choose the ControlNet bridge of the type (1756-CNB or
1756-CNBR) and series that you are using, then click OK.
d. In the Module Properties dialog box, enter the name of the ControlNet bridge and indicate its
position in the ControlLogix chassis (where 0 indicates the left-most slot). Fill in the Revision and
Electronic Keying fields as appropriate for your application.
e. Click Finish.
Step 3. In the I/O Configuration folder, use the right mouse button to click on the ControlNet bridge, and select
New Module from the pop-up menu. The Select Module Type dialog box displays the various
ControlNet devices known to RSLogix 5000.
Note:
The WebPak 3000 ControlNet Communication Option board simulates a 1771-ACN ControlNet
board. The WebPak 3000 drive appears as a 1771 rack I/O port to ControlNet. By using this
configuration, ControlNet is able to access all the status and control words in the WebPak 3000 drive
and perform scheduled messaging.
Step 4. From the Select Module Type dialog box, select 1771-ACN15 or 1771-ACNR15, depending on
whether or not you are using redundant media, then click OK. The Module Properties dialog box
appears requesting information about the ControlNet module you are using.
Step 5. Enter the information in each of the fields of the Module Properties dialog box as shown in table 3.
Table 3 – Module Properties Configuration Fields
In this field:Enter this information:
NameGive the WebPak 3000 a name that is unique within your project. You will
use this name to direct I/O and explicit messages to the WebPak 3000.
DescriptionEnter a more detailed description of the WebPak 3000 drive’s purpos e,
location, etc., if desired.
Comm FormatSelect Rack Optimization.
NodeEnter the ControlNet address of the WebPak 3000 drive you wish to use.
Input SizeEnter the number of words of drive feedback data that you want the
programmable controller to
receive from
the drive (1 to 8). Refer to
section 4.2.3 of the ControlNet Network Communication Option board
manual (D2-3425-2) for information about the type of data that is sent.
Output SizeEnter the number of words of drive reference data that you want the
programmable controller to
send to
the drive (1 to 8). See section 4.2.2 in
the ControlNet Network Communication Option board manual (D2-3425-2)
for information about the type of data that is sent.
Electronic KeyingSelect Disable Keying. Note that the Revision option will become grayed
out.
Step 6. When you have completed entering all the of the information, click Next. The next Module Properties
dialog box in the configuration sequence appears.
Using WebPak 3000 ControlNet Communications Option Board I/O With a ControlLogix Processor
3
Step 7. In the field named Requested Packet Interval (RPI), enter the number of milliseconds desired
between each I/O message between the ControlLogix processor and the WebPak 3000 drive.
Step 8. Click Finish to complete the configuration of the I/O connection using RSLogix 5000 software.
Step 9. Verify that all other I/O in your system is configured.
Step 10. Save the configuration.
Step 11. Download the configuration to the ControlLogix processor.
Step 12. Exit the RSLogix 5000 application (or minimize it).
Scheduling the I/O
Use the following procedure to schedule the I/O:
Step 1. Open RSNetworx for ControlNet application.
Step 2. Verify that you are on-line with the previously configured using the RSNetworx application.
Step 3. Turn on the Enable Edits check box.
Step 4. Save the network. This causes the I/O connection created in the RSLogix 5000 application to be
scheduled in the ControlLogix processor. Select the appropriate save type at the Save Configuration
screen.
After a few seconds, the I/O LED on the ControlLogix processor should stop flashing and remain steadily on
(green). The Control Source Select status (Network) on the WebPak OIM should stop flashing and remain
steadily on.
Troubleshooting Guidelines
If the I/O LED on the ControlLogix processor keeps blinking and/or the Control Source Select status keeps
flashing, it could indicate a number of I/O related problems. Use the following guidelines to isolate the problem:
•If the WebPak OIM Network status remains steadily on, the I/O connection has been made. The flashing
green I/O LED on the ControlLogix processor indicates that another I/O connection did not start correctly.
•A flashing Network status on the WebPak OIM may be the result of a previous error condition on the
network. T ry cycling power on the WebPak 3000 drive and notice if the Network status remains steadily on.
•The I/O may need to be scheduled in the RSNetWorx for ControlNet again. Repeat the scheduling
procedure.
If the above guidelines do not get the I/O connection opened, please contact technical support for the
ControlLogix processor or the WebPak 3000 drive for assistance.
Viewing and Assigning Controller Tag Values
After the I/O connection is open, you can view and assign contoller tag values. Use the following procedure:
Step 1. Open the RSLogix 5000 application.
Step 2. Select the Controller Tags entry.
4
Using WebPak 3000 ControlNet Communications Option Board I/O With a ControlLogix Pr ocessor
The name of the controller tag reflects the name assigned to the WebPak 3000 drive during module
configuration. Figures 1 and 2 assume that the name Webpak1 was assigned.
The O subgroup contains one entry for each word of output data you configured and the I subgroup contains
one entry for each word of input data you configured. Refer to sections 4.2.2 and 4.2.3 in the ControlNet
Network Communication Option board instruction manual (D2-3425-2) for descriptions of output and input
words and their associated bits. Sample output and input configurations are shown in figures 1 and 2.
Corresponds to Word 0
Drive Control Word
Corresponds to Bit 00
Section Run
Corresponds to Word 1
Speed/Torque Reference
Figure 1 – Sample Output Configuration
Using WebPak 3000 ControlNet Communications Option Board I/O With a ControlLogix Processor
5
Corresponds to Word 0
Drive Status Word
Corresponds to Bit 00
Ready
Corresponds to Word 2
Speed Feedback
Creating Aliases
Figure 2 – Sample Input Configuration
For ease of programming, you may wish to create aliases for the Control and Status words and bits based on
the corresponding word or bit name used in the ControlNet manual)
Step 1. From the Controller Tags screen, select the Edit Tags tab.
Step 2. Right click on the item for which you wish to create an alias.
Step 3. From the dialog box, select Create Tag Which Aliases ‘xxxxx.’
Step 4. Type in the desired name for that word or bit, then press Enter.
Step 5. Repeat the process for all the Control and Status words and bits.
Publication D2-3483 February 2001 2001 Rockwell International Corporation.All rights reserved. Printed in USA.