TD200 AC Drive
Installation and Operation Manual
Version 1.0
0.3 to 20V RMS, 3-Phase Output
63 A (Maximum Continuous Motor Amps)
Instruction Manual
D2-3462
The information in this manual is subject to change without notice.
Throughout this manual, the following notes are used to alert you to safety considerations:
ATTENTION:Identifies information about practices or circumstances that can lead to personal
injury or death, property damage, or economic loss.
!
Important: Identifies information that is critical for successful application and understanding of the product.
ATTENTION:Only personnel familiar with the drive and associated machinery should plan or
implement the installation, start-up and subsequent maintenance of the system. Failure to comply
!
may result in bodily injury and/or damage to the equipment.
Table 2.3 – Current Rating Jumper Settings ............................................................ 2-4
Table 2.4 – External Speed Control Jumper Settings...............................................2-5
Table 2.5 – Output Frequencies for Input Voltage Reference
or External Resistance..........................................................................2-5
Table 4.1 – External Control Inputs and Ouputs.......................................................4-2
Table 4.2 – Output Power Connections....................................................................4-2
Table 4.3 – Output Power Connections....................................................................4-3
Table 6.1 – Operating the Drive................................................................................6-1
Table 7.1 – Drive Status Indicators...........................................................................7-1
Contents
V
VI
TD200 AC Drive Installation and Operation
CHAPTER 1
Introduction to the Drive
This chapter describes the drive and how to identify it using the model number matrix.
It also provides an illustration of the drive showing the locations of major components.
1.1Drive Description
The drive is powered by a nominal +28 VDC input, and provides a three-phase AC
variable frequency and voltage output to control a 63 amp AC motor (maximum
continuous amps).
1.2Identifying the Drive by Model Number
Each 2 HP AC drive can be identified by its model number. See figure 1.1. This
number appears on the shipping label and on the drive’s nameplate. The drive’s model
number includes the Power Module and the regulator version.
1 TD 20 002
Catalog Number
TD = Universal
Input Voltage
20 = +28 VDC
Horsepower Rating
002 = 2 HP
Figure 1.1 – Identifying the Drive Model Number
1.3Getting Assistance from Reliance Electric
If you have any questions or problems with the products described in this instruction
manual, contact your local Reliance Electric sales office. For technical assistance, call
1-800-726-8112.
Introduction to the Drive
1-1
1-2
TD200 AC Drive Installation and Operation
Setting the Drive Jumpers
Before the drive can be mounted and wired, you must set the drive jumpers to match
your drive application.
sensitive parts and assemblies. Static control precautions are required
!
You must remove the drive cover to provide access to the drive jumpers.
Step 1. Place the drive with the six cover screws facing up.
Step 2. Remove the six M4 machine screws that hold the cover in place.
Step 3. Remove the cover.
when installing, testing, servicing or repairing this assembly . Component
damage may result if ESD control procedures are not followed. Failure
to observe this precaution could result in damage to the equipment.
CHAPTER 2
Important: Note that the gasket inside the cover is glued to the inside of the cover . Do
not disturb the gasket.
4
5
0
1
3
2
1
2
J
J
0
1
5
3
J
6
4
J
J
S1
J7J
1
1
1
8
9
J
J
1
J
J
J
J
S2
6
8
7
1
1
1
J
J
J
9
1
1
1
J
J
J
0
1
S3
Setting the Drive Jumpers
Figure 2.1 – Location of Drive Jumpers
2-1
2.2Setting the Speed Reference Jumper (J1)
Jumper J1 is used to select between the external speed reference or the internal
speed jumpers. When this jumper is set (J1 = 1), the motor speed can be externally
adjusted from the POT1 and POT2 terminals (see section 2.6). When J1 is reset
(J1 = 0), the internal speed jumpers (J2 through J8 ) are used to set the maximum
speed. In either configuration, the "HI/LO" external input is active (see section 4.1).
Note that if the drive input power drops below a nominal 25 VDC, the speed will drop
to 3/4 of HI speed.
2.3Setting the Maximum Speed Jumpers (J2 through J8)
Jumpers J2 through J8 set the maximum speed when jumper J1 (Speed Reference
Jumper) is in the "Speed Jumpers" position (J1 = 1). The range of values for output
frequency is 0 to 127 Hz in 1 Hz steps (see table 2.1). The speed selected by totalling
the values of these jumper settings is the nominal speed. The actual output frequency
will be within -0.5 to +1.3 Hz tolerance. Actual motor speed will depend on load and
associated slip.
Table 2.1 – Maximum Speed Jumper Settings
JumperPositionMaximum Speed Level
J21Adds 0 Hz to speed reference
0Adds 64 Hz to speed reference
J31Adds 0 Hz to speed reference
0Adds 32Hz to speed reference
J41Adds 0 Hz to speed reference
0Adds 16 Hz to speed reference
J51Adds 0 Hz to speed reference
0Adds 8 Hz to speed reference
J61Adds 0 Hz to speed reference
0Adds 4 Hz to speed reference
J71Adds 0 Hz to speed reference
0Adds 2 Hz to speed reference
J81Adds 0 Hz to speed reference
0Adds 1 Hz to speed reference
2-2
TD200 AC Drive Installation and Operation
2.4Setting the V/Hz Curve Jumpers (J9 through J12)
Jumpers J9 through J12 set the frequency break point for the V/Hz Curve . The
breakpoint is the frequency at which the output voltage reaches the maximum voltage.
Below this point the output voltage and frequency increase together. This feature is
required to allow the drive to work with motors rated at various frequencies. Figure 2.2
shows a general V/Hz curve.
2.5Setting the Current Rating Jumpers (J13 through
J16)
Jumpers J13 through J16 set the maximum continuous current rating and the
associated current limit level of the drive’s output current. The four jumpers are binary
weighted and scaled so that the current limit level is adjustable from 30 to 70 amps
RMS in approximate 3 amp RMS steps. Table 2.3.6 shows the nominal current limit
level for each possible jumper setting.
The user must verify that the application does not e xceed the maximum continous rating of 63 A RMS. Exceeding this rating could cause
overtemperature protection to shut down the drive. For maximum system protection, it is recommended that the current limit jumpers be
set to a value not greater than the application demands.
63
63
63
2
2
2
>6583148
>6787153
>7090160
2-4
TD200 AC Drive Installation and Operation
2.6Setting the Ex ternal Speed Contr o l Jumpers (J17
through J19)
The motor speed can be manually adjusted between minimum speed and full speed
with 0 to 4.5 volt voltage reference, or a 1000 ohm potentiometer. To make the
external speed control inputs (POT1, POT2) active, jumper J1 (Speed Reference
Jumper) must be in the Speed Ref position (J1 = 1), as described in section 2.2.
Jumpers J17 through J19 configure the external speed control function for either an
external 1 Kohm pot control or a 0 to 4.5 VDC voltage control (see table 2.4). Zero
ohms and zero volts are minimum speed. For the voltage control, the positive input is
into the POT1 terminal, the return being POT2. In either configuration, the "HI/LO"
external input is active.
Table 2.4 – External Speed Control Jumper Settings
Jumpers
External Speed ControlMin/Max SpeedJ1J17J18J19
1000External 1 Kohm pot0 ohm / 1 kohm
1111External 0 to 4.5 V control0 VDC / 4.5 VDC
Table 2.5 shows what the output frequency is for a given input voltage reference or
external resistance. When driving the input with an external voltage source, the source
sees a 200 Kohm input impedance. When driving an external potentiometer, the drive
input circuit sources 5 mA. When configured for external speed control (pot), an open
circuit condition will cause the drive to default to 128 Hz. For the pot control selection,
a resistor should be installed across the input if 128 Hz is beyond a safe operational
speed. For voltage source control, an open circuit will cause the drive to default to
2Hz.
Table 2.5 – Output Frequencies for Input Voltage Reference or External Resistance
Volt Reference (V)
J17 J18 J19 = 1 1 1
0203
0.45155016
0.902810026
1.354125054
1.805430062
2.256739375
2.708050088
3.1593750113
3.60106825119
4.05118910125
4.501281000128
Output
Frequency (Hz)
External Resistance (
J17 J18 J19 = 0 0 0
Ω)
Output
Frequency (Hz)
Setting the Drive Jumpers
2-5
2.7Reattaching the Cover
Follow these steps to reattach the drive cover.
Step 1. Position the cover on the back of the drive.
Step 2. Reinstall the six M4 machine screws finger tight, beginning with the two
middle screws, then the four corner screws.
Step 3. Beginning with the two middle screws, torque all of the screws to 4 to 6 lb-in (
.45 to .68 Nm). Do not overtighten.
2-6
TD200 AC Drive Installation and Operation
3.1Planning the Installation
The drive should be installed in a location where high airflow and low ambient
temperatures are present. The jumpers must be configured before installation,
because their access is from the bottom of the unit.
3.2M ounting the Drive
Use the following steps to mount the drive.
Step 1. Prepare the mounting surface based on the dimensions shown in figure 3.1.
Step 2. Position the drive in the enclosure. Choose the mounting surface (horizontal
or vertical) to provide maximum airflow through the fin area.
Step 3. Attach the drive to the mounting surface using four fasteners.
6.50
3.00
CHAPTER 3
Mounting the Drive
3.75
0.25
Mounting the Drive
.33
4 Places
Dimensions in inches
Front View
12.95
12.25
Figure 3.1 – Drive Mounting Dimensions
4.12
Side View
0.25
3-1
3-2
TD200 AC Drive Installation and Operation
CHAPTER 4
Wiring the Drive
Figure 4.1 shows the wiring scheme for the drive’s e xternal control inputs and outputs.
Sections 4.1 through 4.3 provide information for wiring the drive circuits.
Lamp or Relay
(500 mA max.)
FAULT
+
–
Open = OFF
Closed = ON
Open = HI
Closed = LO
2
3
1K Potentiometer or
External Voltage Source
2
28 Volt Batte ry
ON/OFF
HI/LO
POT1 (+)*
1
POT2 (-)*
1
+28 V
GND
U
V
W
Drive
Drive
Wiring the Drive
T1 T2 T3
20 VAC Motor
1
When using 0 to 4.5 VDC external voltage source, POT1 is +.
2
Fuse or circuit breaker, value dependent on application.
3
Contact your local Reliance Electric sales office for motor availability.
Figure 4.1 – Drive External Wiring Diagram
3
4-1
4.1Wiring the External Control Inputs and Outputs
Table 4.1 describes the external control circuits shown in figure 4.1. All control circuits
should be wired as follows:
• use 12 to 18 AWG wire terminated with ring lugs sized for a #8 stud.
• torque all connections between 11 to 13 in-lb.
Table 4.1 – External Control Inputs and Ouputs
Terminal
LabelFunction
ON/OFFON = Closed to run motor
OFF = Open to stop motor
There is an approximate delay of 1.0 second at startup.
Peak input current = 0.2 A, approximate 0.02 A average continuous
HI/LOLO (speed) = Closed for 3/4 of maximum speed.
HI (speed) = Open for maximum speed.
Nominal input current = 50 mA
POT1
POT2
Analog speed reference input. POT1 is the signal and POT2 is the
return.
The input signal range is 0 to 4.5 VDC.
May also be used with a 1000 ohm pot between POT1 and POT2 if
appropriate jumpers are selected.
F AULTOutput fault indication. The fault output will sink up to 500 mA when
operating normally, and sink 0 A when the drive is faulted or not
activated.
4.2Wiring the Output Power to the Motor
Table 4.2 describes the drive output power connections shown in figure 4.1. All output
power connections should be wired as follows:
• Minimum 6 AWG wire terminated with ring lugs sized for a 3/8” stud (drive end).
• torque all connections between 90 to 100 in-lb.
Table 4.2 – Output Power Connections
Terminal LabelFunction
UConnect to motor terminal “U”
VConnect to motor terminal “V”
WConnect to motor terminal “W”
4-2
TD200 AC Drive Installation and Operation
4.3Wiring Input Power to the Drive
ATTENTION:The input power of this drive is not internally fused. The
user is responsible for external fusing. Failure to observe this precaution
!
Table 4.3 describes the input power connections to the drive as shown in figure 4.1. All
input power connections should be wired as follows:
• Minimum 6 AWG wire terminated with ring lugs sized for a 3/8” stud (drive end).
• torque all connections between 90 to 100 in-lb.
could result in damage to, or destruction of, the equipment.
ATTENTION:Applying reverse polarity at the drive input terminals will
allow unlimited input current to flow. A user-supplied fast-acting fuse or
circuit breaker should be installed in the drive input circuit to prevent
damage to the drive. Failure to observe this precaution could result in
damage to, or destruction of, the equipment.
Table 4.3 – Output Power Connections
Terminal LabelFunction
+28 VConnect to power source +28 VDC terminal
GNDConnect to power source ground terminal
Wiring the Drive
4-3
4-4
TD200 AC Drive Installation and Operation
CHAPTER 5
Checking the Installation
ATTENTION:Only qualified electrical personnel, familiar with the
construction and operation of this equipment and the hazards involved,
!
To ensure safe operation, check the installation with the power off before operating the
unit. When power is first applied, the direction of rotation, operator speed reference,
and operation under load should be tested.
5.1Checking the Installation with the Power Off
Perform the following installation checks of the unit with the power off:
Step 1. Disconnect DC input power to the unit.
Step 2. Check that the wiring to the power terminals and to the external control
should install, adjust, operate, and/or service this equipment. Read and
understand this manual in its entirety before proceeding. Failure to
observe this precaution could result in severe bodily injury or loss of life.
inputs and outputs are correct (refer to figure 4.1 and sections 4.1 through
4.3).
Step 3. Check that incoming DC power is correctly rated.
Step 4. Where applicable, check that a properly sized ground wire is installed and
that a suitable earth ground is used. Verify that all ground leads are run
unbroken.
5.2Checking the Direction of Motor Rotation
ATTENTION:The following procedures require rotating parts and/or
electrical circuits to be exposed. Stay clear if the motor must be running.
!
Important: If any problems occur while the drive is running, refer to chapter 7,
After verifying that the drive installation is correct, check the direction of rotation of the
motor using the following procedure:
Step 1. Disconnect DC input power to the unit.
Step 2. Uncouple the driven equipment from the motor, if possible.
Step 3. Connect input power to the unit.
Step 4. Start the drive.
Disconnect, lockout, and tag the power source if contact must be made.
Failure to observe this precaution could result in severe bodily injury or
loss of lif e.
Diagnostics and Troubleshooting.
Checking the Installation
5-1
Step 5. Visually check the direction of motor shaft rotation. If shaft rotation is correct,
proceed to the next section, Testing the Drive under Load. If shaft rotation is
incorrect, continue to step 7.
Step 6. Disconnect DC input power to the unit.
Step 7. Reverse any two of the three motor power leads (U, V, and W).
5.3Testing the Drive under Load
Use the following procedure to test the drive under load:
Step 1. Turn off, lockout, and tag power to the drive.
Step 2. Couple the driven equipment to the motor.
Step 3. Turn power on and start the drive.
Step 4. Run the drive across the required speed range under load.
Step 5. If the drive does not operate the motor properly, refer to chapter 7,
Diagnostics and Troubleshooting.
5-2
TD200 AC Drive Installation and Operation
CHAPTER 6
Operating the Drive
The following table describes how to start and stop the drive, and how to change the
motor speed. This table assumes that the drive is wired as shown in figure 4.1.
Table 6.1 – Operating the Drive
FunctionProcess
Start the driveApply 28 VDC to the ON/OFF terminal.
Stop the driveRemove 28 VDC to the ON/OFF terminal.
Adjust motor speedMotor speed can be controlled by:
• jumper settings (see section 2.3).
• speed potentiometer (see section 2.6).
• external voltage control (see section 2.6).
• application of 28 VDC to HI/LO terminal. This will
reduce motor speed by 75%.
Operating the Drive
6-1
6-2
TD200 AC Drive Installation and Operation
CHAPTER 7
Diagnostics and Troubleshooting
7.1Drive Faults and Corrective Actions
The drive has two status LEDs that can be used to diagnose drive faults. Table 7.1
lists some possible drive faults and their corrective actions.
Table 7.1 – Drive Status Indicators
Status
Drive is
running
Drive runs,
but not at
commanded
speed
Drive is
stopped
Motor
LED
(M)
ONONDrive is running (normal status).
ONONInternal speed reference set
ONONOvertemperature - result of
ONOFFInternal Drive FaultCycle power. If fault repeats, replace drive.
OFFONOvercurrent - sustained overload
Drive
LED
(D)Possible CauseCorrective Action
improperly
External peed refere nce not present
HI/LO input has voltage applied
Current limit set too low
V/Hz jumpers set improperly
Excessive load
Input voltage too low (< 25 VDC,
nominal)
Power source not delivering enough
current
inadequate air flow, excessive
ambient temperature, and/or
excessive load current
Overvoltage - voltage exceeds 32
VDC
exceeding limits in table 2.3.
Check jumper settings (J1 - J8).
Check speed r ef erenc e jum pers (J 1, J17 - J19),
POT1 and POT2.
Remove input voltage.
Increase J13 - J16 settings.
Set J9 - J12 to proper motor setting.
Reduce load.
Increase input voltage.
Supply app ropriate input current.
Let drive cool down, then cycle ON/OFF input.
Unit will automatically restart when voltage
returns to normal input levels.
Reduce current load.
OFFOFFInput power is too low or ON/OFF
To reset a fault, toggle the ON/OFF switch to OFF. When the switch is returned to the
ON position, the drive will attempt to restart.
Diagnostics and Troubleshooting
Instantaneous Overcurrent (IOC) short circuit or other fault applied to
the output
Nominal: +28 VDC
Operating Range: +20 to +32 VDC
Maximum Non-operating Transient: +60 V peak., 0.1 seconds
Source: battery, battery & alternator, stand-alone alternator, or DC power supply
Note: Negative voltage should not be applied to the drive.
Input Current
Nominal: +65 A DC (@ 28 VDC input and rated HP)
Output Voltage
Nominal: 0.3 to 20 V RMS, 3-phase (@ 28 VDC input)
Output Current (per phase)
Maximum Continuous: 63 A RMS, (jumper-selectable range from 30 A to 63 A)
Instantaneous Overcurrent Trip (IOC Trip):160 A peak @ 63 A jumper setting (any
phase). This value is proportional to jumper setting.
Horsepower Rating
Maximum motor size: 2 HP. Maximum continuous output current must not be
exceeded.
Efficiency
Minimum: 93% (@ 28 V input and maximum continuous output current)
Humidity and Water Splash
The drive is suitable for wash down. The drive is not submersible.
A-1
Shock and Vibration
Will withstand 3-axis sinusoidal vibration from 20 to 200 Hz @ 2 g.
Will withstand 3-axis, 10 g shock pulse with a duration of 8 msec.
Cooling Air Requirements
Minimum air velocity: 1000 linear ft/min (LFM) referenced to standard conditions of
° C and 760 mm Hg, directed through base areas of the unit’s cooling fins.
25
Electromagnetic Interference (EMI)
This product has been tested for immunity to electrostatic discharges, radiated
interference, and electrical fast transients. The IEC1000-4- 2, 3, 4 standards were
used to establish compliance.