This document provides detailed information for the TC-800 series of TrustedTM I/O Cables. These types of cable provide connection facilities between the Trusted modules and field terminations, for cases which do not fit into the other I/O cable series.
TM
The types of TC-800 Trusted
Cable Type Description
TC-801-02-xmx I/O Companion Slot, Speed Monitor Module to Speed FTAs
The cables are manufactured to user’s requirements, therefore length and type of cable insulation must be specified. Length must be specified to the nearest 0.5m in the format xmx, e.g. 2m0 for a cable length of 2.0m. This detail must be added to the end of the part number. The type of cable insulation forms part of the cable part number and is denoted by 02 for Low Smoke Low Halogen (LSLH), flame retardant to IEC 60332-3 Cat A. PVC covered cables are not available. When ordering cables, it is recommended that the user supplies the details as shown in Table 1.
The maximum recommended I/O cable length is 15m. Cables longer than this may be specified if necessary but may suffer from voltage drop, offset, crosstalk and noise and will present materials handling problems.
Internal cables are designed for cables where they are terminated in adjacent enclosures. If the cable needs to leave the enclosure environment, the External cable has more protection. Note that the ‘External’ cables are not armoured and are not suitable for truly external use and must still be treated with care. These cables will need protection when drawn through a cable route, and should also not be pulled by the connector(s). They should enter cabinets through transit/compression blocks and can not be glanded.
Cables currently available are listed in Table 1 below.
Table 1 TrustedTM I/O Companion Slot Cables
M
T
analogue and digital input/output
Issue 01 Feb 08 PD-TC800 1
Trusted
Issue Record
ssue
I
Number Date Revised by Technical CheckAuthorised by Modification
1 Feb 08 N Owens A Holgate P Stock First Release
TM
Special I/O Cables TC-800
Issue 01 Feb 08 PD-TC800 2
Trusted
TM
Special I/O Cables TC-800
Table of Contents
1. I/O Companion Slot Cable Type TC-801 .....................................................................................6
Figures
Figure 1 I/O Companion Slot Cable Type TC-801-02 ..............................................................................6
Tab le s
M
Table 1 Trusted
T
I/O Companion Slot Cables ........................................................................................1
Issue 01 Feb 08 PD-TC800 3
Trusted
TM
Special I/O Cables TC-800
Notice
The content of this document is confidential to ICS Triplex Technology Ltd. companies and their partners. It may not be given away, lent, resold, hired out or made available to a third party for any purpose without the written consent of ICS Triplex Technology Ltd.
This document contains proprietary information that is protected by copyright. All rights are reserved.
icrosoft, Windows, Windows 95, Windows NT, Windows 2000, and Windows XP are registered
M trademarks of Microsoft Corporation.
The information contained in this document is subject to change without notice. The reader should, in all cases, consult ICS Triplex Technology Ltd. to determine whether any such changes have been made. From time to time, amendments to this document will be made as necessary and will be distributed by ICS Triplex Technology Ltd.
Information in this documentation set may be subject to change without notice and does not represent a commitment on the part of ICS Triplex Technology Ltd.
The contents of this document, which may also include the loan of software tools, are subject to the confidentiality and other clause(s) within the Integrator Agreement and Software License Agreement.
No part of this documentation may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, for any purpose, without the express written permission of ICS Triplex Technology Ltd.
Disclaimer
The illustrations, figures, charts, and layout examples in this manual are intended solely to illustrate the text of this manual.
The user of, and those responsible for applying this equipment, must satisfy themselves as to the acceptability of each application and use of this equipment.
This document is based on information available at the time of its publication. While efforts have been made to be accurate, the information contained herein does not purport to cover all details or variations in hardware or software, nor to provide for every possible contingency in connection with installation, operation, or maintenance. Features may be described herein which are present in all hardware or software systems. ICS Triplex Technology Ltd. assumes no obligation of notice to holders of this document with respect to changes subsequently made.
ICS Triplex Technology Ltd. makes no representation or warranty, expressed, implied, or statutory with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein. No warranties of merchantability or fitness for purpose shall apply.
Issue 01 Feb 08 PD-TC800 4
Trusted
TM
Special I/O Cables TC-800
Revision and Updating Policy
All new and revised information pertinent to this document shall be issued by ICS Triplex Technology Ltd. and shall be incorporated into this document in accordance with the enclosed instructions. The change is to be recorded on the Amendment Record of this document.
Precautionary Information
WARNING
Warning notices call attention to the use of materials, processes, methods, procedures or limits which must be followed precisely to avoid personal injury or death.
CAUTION
Caution notices call attention to methods and procedures which must be followed to avoid damage to the equipment.
Notes:
Notes highlight procedures and contain information to assist the user in the understanding of the information contained in this document
Warning
RADIO FREQUENCY INTERFERENCE
Most electronic equipment is influenced by Radio Frequency Interference (RFI). Caution should be exercised with regard to the use of portable communications equipment around such equipment. Signs should be posted in the vicinity of the equipment cautioning against the use of portable communications equipment.
MAINTENANCE
Maintenance must be performed only by qualified personnel, otherwise personal injury or death, or damage to the system may be caused.
Caution
HANDLING
Under no circumstances should the module housing be removed.
Associated Documents
Product Descriptions (PD) provide product specific information.
The Safety Manual contains the recommended safety requirements for the safety system design.
The PD8082B – Toolset Suite provides specific guidance on system configuration and application generation.
The Operator and Maintenance Manual contains general guidelines on maintenance and diagnostic procedures.
For technical support email: support@icstriplex.com
Issue 01 Feb 08 PD-TC800 5
odule
T8442
Trusted
TM
Special I/O Cables TC-800
1. I/O Companion Slot Cable Type TC-801
This type of cable, and the modules/field termination assemblies it is used with, is shown in Figure 1
elow.
b
Figure 1 I/O Companion Slot Cable Type TC-801-02
TM
This type of Trusted
I/O Companion Slot Cable is designed for use with the T8442 Speed Monitor module and is required for connections to a T8846 Speed Input FTA and up to three T8891 Speed Output FTAs. This is an internal low smoke low halogen cable. There is no SmartSlot version of this cable.
The chassis end of the multi-core cable is fitted with a 96-way type ‘C’ connector housed in a double-width hood. The other ends of the cable are fitted with six 20-way screw-fit 3.5mm pitch female header connectors; three to the T8846 and one to each T8891. The cable is only available with three T8891 tails in the arrangement shown in the figure above.
The cables are assembled from individual cores and screened twisted pairs and are shrouded in nylon Megamide sheathing. The ends of the sheathing are fitted with heat-shrink sleeving to prevent fraying.
At the chassis end, a sheathed braid allows the connector hood to be wired to safety earth.