Rockwell Automation T8871 User Manual

TrustedTM
PD-T8871
Trusted
Introduction
M
The Trusted between the Trusted the output module is digital at 120V ac.
Features
T
16 Channel 120Vac Digital Output FTA T8871 is designed to act as the main interface
TM
TMR 120V ac Digital Output Module T8472 and a field device. The signal from
16 output channels per FTA.
TM
16 Channel 120Vac
Industry standard field device connections (3-wire).
Standard DIN rail compatibility.
Simple installation and connection.
120V ac operation.
Transient protection on each channel.
Field terminal wire size allowance 12-24 AWG
Issue 2 Feb 08 PD-T8871 1
Trusted
Issue Record
ssue
I
Number Date Revised by Technical CheckAuthorised by Modification
1 Sep 05 N Owens Initial Issue
2 Feb 08 N Owens A Holgate P Stock Voltage warning
TM
120Vac Digital Output FTA T8871
Issue 2 Feb 08 PD-T8871 2
Trusted
TM
120Vac Digital Output FTA T8871
Figure 1 T8871 Layout
Issue 2 Feb 08 PD-T8871 3
Trusted
TM
120Vac Digital Output FTA T8871
Table of Contents
1. Description...................................................................................................................................7
2. Installation....................................................................................................................................8
3. Associated Cable Selection .........................................................................................................8
4. Assembly Pinout Connections .....................................................................................................9
4.1. SK1 Connections from module....................................................................................................9
4.2. SK3 Connections from module....................................................................................................9
4.3. SK2 Power connection to module..............................................................................................10
4.4. SK4 Power connection to module..............................................................................................10
4.5. TB1 Field Connections...............................................................................................................11
4.6. TB3 Field Connections...............................................................................................................11
4.7. TB2 Power supply connection ...................................................................................................12
4.8. TB4 Power supply connection ...................................................................................................12
5. Specifications.............................................................................................................................13
Figures
Figure 1 T8871 Layout..............................................................................................................................3
Figure 2 Single Channel Schematic .........................................................................................................7
Figure 3 TB1 and TB3 Connections (example) ......................................................................................11
Tab l es
Table 1 SK1 Connections .........................................................................................................................9
Table 2 SK3 Connections .........................................................................................................................9
Table 3 SK2 Connections .......................................................................................................................10
Table 4 SK4 Connections .......................................................................................................................10
Table 5 TB1 Connections .......................................................................................................................11
Table 6 TB3 Connections .......................................................................................................................11
Table 7 TB2 Connections .......................................................................................................................12
Table 8 TB4 Connections .......................................................................................................................12
Issue 2 Feb 08 PD-T8871 4
Trusted
TM
120Vac Digital Output FTA T8871
Notice
The content of this document is confidential to ICS Triplex Technology Ltd. companies and their partners. It may not be given away, lent, resold, hired out or made available to a third party for any purpose without the written consent of ICS Triplex Technology Ltd.
This document contains proprietary information that is protected by copyright. All rights are reserved.
icrosoft, Windows, Windows 95, Windows NT, Windows 2000, and Windows XP are registered
M trademarks of Microsoft Corporation.
The information contained in this document is subject to change without notice. The reader should, in all cases, consult ICS Triplex Technology Ltd. to determine whether any such changes have been made. From time to time, amendments to this document will be made as necessary and will be distributed by ICS Triplex Technology Ltd.
Information in this documentation set may be subject to change without notice and does not represent a commitment on the part of ICS Triplex Technology Ltd.
The contents of this document, which may also include the loan of software tools, are subject to the confidentiality and other clause(s) within the Integrator Agreement and Software License Agreement.
No part of this documentation may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, for any purpose, without the express written permission of ICS Triplex Technology Ltd.
Disclaimer
The illustrations, figures, charts, and layout examples in this manual are intended solely to illustrate the text of this manual.
The user of, and those responsible for applying this equipment, must satisfy themselves as to the acceptability of each application and use of this equipment.
This document is based on information available at the time of its publication. While efforts have been made to be accurate, the information contained herein does not purport to cover all details or variations in hardware or software, nor to provide for every possible contingency in connection with installation, operation, or maintenance. Features may be described herein which are present in all hardware or software systems. ICS Triplex Technology Ltd. assumes no obligation of notice to holders of this document with respect to changes subsequently made.
ICS Triplex Technology Ltd. makes no representation or warranty, expressed, implied, or statutory with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein. No warranties of merchantability or fitness for purpose shall apply.
Issue 2 Feb 08 PD-T8871 5
Trusted
TM
120Vac Digital Output FTA T8871
Revision and Updating Policy
All new and revised information pertinent to this document shall be issued by ICS Triplex Technology Ltd. and shall be incorporated into this document in accordance with the enclosed instructions. The change is to be recorded on the Amendment Record of this document.
Precautionary Information
WARNING
Warning notices call attention to the use of materials, processes, methods, procedures or limits which must be followed precisely to avoid personal injury or death.
CAUTION
Caution notices call attention to methods and procedures which must be followed to avoid damage to the equipment.
Notes:
Notes highlight procedures and contain information to assist the user in the understanding of the information contained in this document
Warning
HIGH VOLTAGE
This unit contains high voltage. Do not operate the unit without a protective cover.
RADIO FREQUENCY INTERFERENCE
Most electronic equipment is influenced by Radio Frequency Interference (RFI). Caution should be exercised with regard to the use of portable communications equipment around such equipment. Signs should be posted in the vicinity of the equipment cautioning against the use of portable communications equipment.
MAINTENANCE
Maintenance must be performed only by qualified personnel, otherwise personal injury or death, or damage to the system may be caused.
Caution
HANDLING
Under no circumstances should the module housing be removed.
Associated Documents
Product Descriptions (PD) provide product specific information.
The Safety Manual contains the recommended safety requirements for the safety system design.
The PD8082B – Toolset Suite provides specific guidance on system configuration and application generation.
The Operator and Maintenance Manual contains general guidelines on maintenance and diagnostic procedures.
For technical support email: support@icstriplex.com
Issue 2 Feb 08 PD-T8871 6
Trusted
TM
120Vac Digital Output FTA T8871

1. Description

The TrustedTM 16 Channel 120Vac Digital Output FTA T8871 provides termination for a maximum of 16 output channels. Figure 2 below shows the configuration of a single channel.
MODULE CONNECTIONS
VARISTORS 150VAC 50A
100uH
FIELD CONNECTIONS
L N CHANNEL E
L N DISTRIBUTION E
Figure 2 Single Channel Schematic
The supply for the field is connected via terminal blocks TB2 and TB4 on the FTA. This is supplied to the module on sockets SK2 and SK4 via harmonic and transient protective devices as shown.
The output signals to the field (16-off) are connected from the module on sockets SK1 and SK3. These connect to the field by 3-wire arrangements terminated on 2-off 24-way terminal blocks TB1 and TB3.
Issue 2 Feb 08 PD-T8871 7
Trusted
TM
120Vac Digital Output FTA T8871

2. Installation

TrustedTM 16 Channel 120Vac Digital Input FTA T8871 is designed to be mounted on either of the TS32 or TS35 DIN rails in the horizontal or vertical positions as required.

3. Associated Cable Selection

Refer to the product descriptions detailed below:
TM
PD-TC000 Trusted
PD-TC200 Trusted
Note that SmartSlot operation is not available with this FTA.
Power Cables
TM
I/O Companion Slot Cables
Issue 2 Feb 08 PD-T8871 8
Trusted
TM
120Vac Digital Output FTA T8871

4. Assembly Pinout Connections

4.1. SK1 Connections from module

Pin Service
1 Channel 1
2 Channel 2
3 Channel 3
4 Channel 4
5 Channel 5
6 Channel 6
7 Channel 7
8 Channel 8
Table 1 SK1 Connections

4.2. SK3 Connections from module

Pin Service
1 Channel 9
2 Channel 10
3 Channel 11
4 Channel 12
5 Channel 13
6 Channel 14
7 Channel 15
8 Channel 16
Table 2 SK3 Connections
Issue 2 Feb 08 PD-T8871 9
Trusted
TM
120Vac Digital Output FTA T8871

4.3. SK2 Power connection to module

Pin Service
1 Live
2 Unused
3 Neutral
4 Unused
5 Earth
Table 3 SK2 Connections

4.4. SK4 Power connection to module

Pin Service
1 Live
2 Unused
3 Neutral
4 Unused
5 Earth
Table 4 SK4 Connections
Issue 2 Feb 08 PD-T8871 10
Trusted
TM
120Vac Digital Output FTA T8871

4.5. TB1 Field Connections

Group Column Service
Ch 1 L1,N1,E1
Ch 2 L1,N1,E1 Field device connection channel 2
Ch 3 L1,N1,E1 Field device connection channel 3
Ch 4 L1,N1,E1 Field device connection channel 4
Ch 5 L1,N1,E1 Field device connection channel 5
Ch 6 L1,N1,E1 Field device connection channel 6
Ch 7 L1,N1,E1 Field device connection channel 7
Ch 8 L1,N1,E1 Field device connection channel 8

4.6. TB3 Field Connections

Group Column Service
Ch 9 L2,N2,E2
Ch 10 L2,N2,E2 Field device connection channel 10
Ch 11 L2,N2,E2 Field device connection channel 11
Ch 12 L2,N2,E2 Field device connection channel 12
Ch 13 L2,N2,E2 Field device connection channel 13
Ch 14 L2,N2,E2 Field device connection channel 14
Ch 15 L2,N2,E2 Field device connection channel 15
Ch 16 L2,N2,E2 Field device connection channel 16
Field device connection channel 1 (Live,Neutral, Earth)
Table 5 TB1 Connections
Field device connection channel 9 (Live,Neutral, Earth)
Table 6 TB3 Connections
Channel 1
L1
E1
N1
Figure 3 TB1 and TB3 Connections (example)
Issue 2 Feb 08 PD-T8871 11
Trusted
TM
120Vac Digital Output FTA T8871

4.7. TB2 Power supply connection

Pin Service
1 Live
2 Unused
3 Neutral
4 Unused
5 Earth
Table 7 TB2 Connections

4.8. TB4 Power supply connection

Pin Service
1 Live
2 Unused
3 Neutral
4 Unused
5 Earth
Table 8 TB4 Connections
Issue 2 Feb 08 PD-T8871 12
Trusted
TM
120Vac Digital Output FTA T8871

5. Specifications

Voltage Range
Maximum Current (Field Supply)
ower Consumption (Field Supply)
P
Operating Temperature
Non-operating Temperature
Operating Humidity
Environmental Specifications
Dimensions
Width Depth
Weight
Height
90 to 150V ac
0.5A
<9W excluding transients
0
-5
C to 600C (230F to 1400F)
0
-25
C to 700C (-130F to 1580F)
5 to 95% RH
Refer to Document 552517
125mm (4.9ins) 216mm (8.5ins) 69mm (2.7ins)
700gms (1.5lbs)
Issue 2 Feb 08 PD-T8871 13