Rockwell Automation T8843 User Manual

TrustedTM
PD-T8843
Introduction
Trusted
TM
40 Channel Digital Input
The TrustedTM 40 Channel Digital Input Versatile FTA T8843 is designed to act as the main interface between a field device generating a digital signal and the Trusted T8403, or the Trusted
Features
40 input channels per VFTA.
Industry standard field device connections (3-wire).
Standard DIN rail compatibility.
Simple installation and connection.
24/120V dc operation.
SmartSlot connection for ‘one to many’ hot replacement of input modules.
Fused field power supply per channel.
M
T
TMR 120V dc Digital Input Module T8423.
TM
TMR 24V dc Digital Input Module
Issue 4 Sep 05 PD-T8843 1
Trusted
Issue Record
Issue
Number Date Revised by Technical CheckAuthorised by Modification
4 Sep 05 J W Clark Format
TM
Digital Input Versatile FTA T8843
Issue 4 Sep 05 PD-T8843 2
Trusted
TM
Digital Input Versatile FTA T8843
Figure 1 T8843 Layout
Issue 4 Sep 05 PD-T8843 3
Trusted
TM
Digital Input Versatile FTA T8843
Table of Contents
1. Description ...................................................................................................................................7
2. Installation....................................................................................................................................8
3. Associated Cable Selection .........................................................................................................8
4. Assembly Pinout Connections .....................................................................................................9
4.1. TBFP1 to TBFP5 Connections ....................................................................................................9
4.2. TBG1 Connections ......................................................................................................................9
4.3. TBG2 Connections ....................................................................................................................10
4.4. TBG3 Connections ....................................................................................................................10
4.5. TBG4 Connections ....................................................................................................................11
4.6. TBG5 Connections ....................................................................................................................11
4.7. TBSS Connections.....................................................................................................................12
4.8. TB1 to TB40 Connections..........................................................................................................12
5. Specifications.............................................................................................................................13
Figures
Figure 1 T8843 Layout..............................................................................................................................3
Figure 2 Single Channel Schematic .........................................................................................................7
Table s
Table 1 TBFP1 to TBFP5 Connections ....................................................................................................9
Table 2 TBG1 Connections ......................................................................................................................9
Table 3 TBG2 Connections ....................................................................................................................10
Table 4 TBG3 Connections ....................................................................................................................10
Table 5 TBG4 Connections ....................................................................................................................11
Table 6 TBG5 Connections ....................................................................................................................11
Table 7 TBSS Connections ....................................................................................................................12
Table 8 TB1 to TB40 Connections .........................................................................................................12
Issue 4 Sep 05 PD-T8843 4
Trusted
TM
Digital Input Versatile FTA T8843
Notice
The content of this document is confidential to ICS Triplex Technology Ltd. companies and their partners. It may not be given away, lent, resold, hired out or made available to a third party for any purpose without the written consent of ICS Triplex Technology Ltd.
his document contains proprietary information that is protected by copyright. All rights are reserved.
T
Microsoft, Windows, Windows 95, Windows NT, Windows 2000, and Windows XP are registered trademarks of Microsoft Corporation.
The information contained in this document is subject to change without notice. The reader should, in all cases, consult ICS Triplex Technology Ltd. to determine whether any such changes have been made. From time to time, amendments to this document will be made as necessary and will be distributed by ICS Triplex Technology Ltd.
Information in this documentation set may be subject to change without notice and does not represent a commitment on the part of ICS Triplex Technology Ltd.
The contents of this document, which may also include the loan of software tools, are subject to the confidentiality and other clause(s) within the Integrator Agreement and Software License Agreement.
No part of this documentation may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, for any purpose, without the express written permission of ICS Triplex Technology Ltd.
Disclaimer
The illustrations, figures, charts, and layout examples in this manual are intended solely to illustrate the text of this manual.
The user of, and those responsible for applying this equipment, must satisfy themselves as to the acceptability of each application and use of this equipment.
This document is based on information available at the time of its publication. While efforts have been made to be accurate, the information contained herein does not purport to cover all details or variations in hardware or software, nor to provide for every possible contingency in connection with installation, operation, or maintenance. Features may be described herein which are present in all hardware or software systems. ICS Triplex Technology Ltd. assumes no obligation of notice to holders of this document with respect to changes subsequently made.
ICS Triplex Technology Ltd. makes no representation or warranty, expressed, implied, or statutory with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein. No warranties of merchantability or fitness for purpose shall apply.
Issue 4 Sep 05 PD-T8843 5
Trusted
TM
Digital Input Versatile FTA T8843
Revision and Updating Policy
All new and revised information pertinent to this document shall be issued by ICS Triplex Technology Ltd. and shall be incorporated into this document in accordance with the enclosed instructions. The change is to be recorded on the Amendment Record of this document.
Precautionary Information
WARNING
Warning notices call attention to the use of materials, processes, methods, procedures or limits which must be followed precisely to avoid personal injury or death.
CAUTION
Caution notices call attention to methods and procedures which must be followed to avoid damage to the equipment.
Notes:
Notes highlight procedures and contain information to assist the user in the understanding of the information contained in this document
Warning
RADIO FREQUENCY INTERFERENCE
Most electronic equipment is influenced by Radio Frequency Interference (RFI). Caution should be exercised with regard to the use of portable communications equipment around such equipment. Signs should be posted in the vicinity of the equipment cautioning against the use of portable communications equipment.
MAINTENANCE
Maintenance must be performed only by qualified personnel, otherwise personal injury or death, or damage to the system may be caused.
Caution
HANDLING
Under no circumstances should the module housing be removed.
Associated Documents
Product Descriptions (PD) provide product specific information.
The Safety Manual contains the recommended safety requirements for the safety system design.
The PD8082B – Toolset Suite provides specific guidance on system configuration and application generation.
The Operator and Maintenance Manual contains general guidelines on maintenance and diagnostic procedures.
For technical support email: support@icstriplex.com
Issue 4 Sep 05 PD-T8843 6
Trusted
TM
Digital Input Versatile FTA T8843
1. Description
The TrustedTM 40 Channel Digital Input Versatile FTA T8843 provides termination for a maximum of 40
nput channels from various types of field devices which generate a digital input. The 40 channels are
i arranged in five power groups each comprising eight identical channels. Figure 2 below shows the configuration of a single channel within a group.
Figure 2 Single Channel Schematic
Each power group is supplied from dual 24V dc (or 120V dc dependent upon input module type) feeds which are ‘commoned’ via diodes on the VFTA. The supply is then fed to each channel within the group.
The supply voltage to the field is fed via the 315mA fuse. The incoming signal (digital) from the field device is fed through the 50mA fuse which effectively limits the input signal. Line monitoring components (if required) provide the necessary thresholds used by the input module to detect the field loop/device status, i.e. open/short circuit, alarm etc.
The cable linking the 40 channels on the input module to the VFTA is terminated at five 10-way connectors (TBG1 to TBG5). SmartSlot (Version 1) signals from the module are connected to a single 7-way connector (TBGSS). The dual dc field power supplies are connected to the VFTA via five 4-way connectors (TBFP1 to TBFP5). Forty 3-way connectors are used for the field loops (TB1 to TB40).
Issue 4 Sep 05 PD-T8843 7
Trusted
TM
Digital Input Versatile FTA T8843

2. Installation

TrustedTM Versatile FTA 40 Channel Digital Input T8843 is designed to be mounted on either of the
S32 or TS35 DIN rails in the horizontal or vertical positions as required.
T

3. Associated Cable Selection

Refer to the product descriptions detailed below:
PD-TC000 Trusted
PD-TC200 Trusted
PD-TC500 Trusted
TM
Power Cables
TM
I/O Companion Slot Cables
M
T
I/O SmartSlot Cables
Issue 4 Sep 05 PD-T8843 8
Trusted
TM
Digital Input Versatile FTA T8843

4. Assembly Pinout Connections

4.1. TBFP1 to TBFP5 Connections

The pin connections of TBFP1 to TBFP5 are identical and are detailed below:
Pin Service
1 24V-1 or 120V-1
2 0V
3 0V
4 24V-2 or 120V-2
Table 1 TBFP1 to TBFP5 Connections

4.2. TBG1 Connections

Pin Service
1 0V
2 Channel 1
3 Channel 2
4 Channel 3
5 Channel 4
6 Channel 5
7 Channel 6
8 Channel 7
9 Channel 8
10 Not used
Table 2 TBG1 Connections
Issue 4 Sep 05 PD-T8843 9
Trusted
TM
Digital Input Versatile FTA T8843

4.3. TBG2 Connections

Pin Service
1 0V
2 Channel 9
3 Channel 10
4 Channel 11
5 Channel 12
6 Channel 13
7 Channel 14
8 Channel 15
9 Channel 16
10 Not used
Table 3 TBG2 Connections

4.4. TBG3 Connections

Pin Service
1 0V
2 Channel 17
3 Channel 18
4 Channel 19
5 Channel 20
6 Channel 21
7 Channel 22
8 Channel 23
9 Channel 24
10 Not used
Table 4 TBG3 Connections
Issue 4 Sep 05 PD-T8843 10
Trusted
TM
Digital Input Versatile FTA T8843

4.5. TBG4 Connections

Pin Service
1 0V
2 Channel 25
3 Channel 26
4 Channel 27
5 Channel 28
6 Channel 29
7 Channel 30
8 Channel 31
9 Channel 32
10 Not used
Table 5 TBG4 Connections

4.6. TBG5 Connections

Pin Service
1 0V
2 Channel 33
3 Channel 34
4 Channel 35
5 Channel 36
6 Channel 37
7 Channel 38
8 Channel 39
9 Channel 40
10 Not used
Table 6 TBG5 Connections
Issue 4 Sep 05 PD-T8843 11
Trusted
TM
Digital Input Versatile FTA T8843

4.7. TBSS Connections

Pin Service
1 Not used
2 Not used
3 SmartSlot link
4 SmartSlot link
5 SmartSlot link
6 Channel 41
7 Channel 0
Table 7 TBSS Connections

4.8. TB1 to TB40 Connections

The pin connections of TB1 (Channel 1) to TB40 (Channel 3) are identical and are detailed below:
Pin Service
1 Field power
2 Signal in
3 0V
Table 8 TB1 to TB40 Connections
Issue 4 Sep 05 PD-T8843 12
Trusted
TM
Digital Input Versatile FTA T8843

5. Specifications

Voltage Range
Fuses
Maximum Current (Field Supply)
Power Consumption (Field Supply)
Operating Temperature
Non-operating Temperature
Operating Humidity
Environmental Specifications
Dimensions
Height Width Depth
Weight
18 to 120V dc
40-off 315mA 40-off 50mA
315mA per power group
9W maximum per power group
-50C to 600C (230F to 1400F)
-250C to 700C (-130F to 1580F)
5 to 95% RH
Refer to Document 552517
110mm (4.33ins) 360mm (14.17ins) 68mm (2.67ins)
950gms (2.1lbs)
Issue 4 Sep 05 PD-T8843 13
Loading...