SDS-T8840
TM
Trusted
Industrial Control System
TrustedTM Temperature Input FTA - T8840
GENERAL ASSEMBLY
DESCRIPTION
The Trusted
system and up to eight temperature, voltage or current devices using a
range of available plug in conditioning units. The FTA excludes the
conditioning units to allow maximum configurability. More than one type of
conditioning unit can be used on the same FTA. Compatible conditioning
unit include the 7B series of units from Analog Devices and SCM7B series
from Dataforth.
The Trusted
(CJC) resistor for each of the inputs. This makes the FTA compatible with
Thermocouple conditioning units.
The Trusted
Module using either Companion cables TC-211/212 or Smart Slot cables
TC-511/512. The Output can also be connected to the Analogue Input
module via a VFTA if necessary to be compatible with an existing
installation.
The VFTA is designed to be mounted on either of the TS32 or TS35 DIN
rails in the horizontal or vertical positions as required.
TM
Temperature FTA is designed to interface between a Trusted
TM
Temperature FTA includes a Cold Junction Compensation
TM
Temperature FTA can connect direct to an Analogue Input
FEATURES
Eight Input channels per
Trusted Temperature FTA
Flexible user defined
conditioning
Standard DIN rail
compatibility
Configurable 2 or 3-wire
RTD inputs
Dual 24V Supply
Issue 3 Aug 2006
SDS-T8840
Trusted
TM
Industrial Control System
TrustedTM Temperature Input FTA - T8840
ELECTRICAL SPECIFICATION
Voltage Range
Maximum Input Current
Number of Inputs
Possible Input Types
(dependant on conditioning unit
fitted)
Accuracy, resolution
15 to 28V dc
2.5A
8
Isolated Voltage
Isolated Current
Isolated RTD Pt 100ohm
Isolated RTD Ni 120ohm
Powered Isolated 2 wire 4-20mA
transmitter
Isolated Potentiometer
Isolated Thermocouple J,K
Dependant on conditioning unit
MECHANICAL
SPECIFICATION
Dimensions (HxWxD):
110mm x 145mm x 68mm
(4.3ins x 5.7ins x 2.6ins)
Depth with conditioning
unit fitted:
90mm
(3.6ins)
Weight (fully populated)
248gms
(0.55lbs)
ENVIRONMENTAL
Operating Temperature:
-5°C to 60°C
(23°F to 140°F)
Operating Humidity:
5 to 95%, noncondensing
Vibration:
10 to 57Hz ±0.075mm
57 to 150Hz 1.0g
Shock:
15g, ½ sine wave, 11ms
EMI (IEC 801):
ESD
Air discharge to 15kV.
Contact discharge to 8kV
Radiated Fields
10V/m, 27MHz to
500MHz
Transients and Bursts
2kV, 2.5kHz for
t=60 seconds
ICS Triplex
Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Websi te:- www.icstr iple x.com