TrustedTM Temperature Input FTA - T8840

GENERAL ASSEMBLY

The Trusted system and up to eight temperature, voltage or current devices using a range of available plug in conditioning units. The FTA excludes the conditioning units to allow maximum configurability. More than one type of conditioning unit can be used on the same FTA. Compatible conditioning unit include the 7B series of units from Analog Devices and SCM7B series from Dataforth.
The Trusted (CJC) resistor for each of the inputs. This makes the FTA compatible with Thermocouple conditioning units.
The Trusted Module using either Companion cables TC-211/212 or Smart Slot cables TC-511/512. The Output can also be connected to the Analogue Input module via a VFTA if necessary to be compatible with an existing installation.
The VFTA is designed to be mounted on either of the TS32 or TS35 DIN rails in the horizontal or vertical positions as required.
TM
Temperature FTA is designed to interface between a Trusted
TM
Temperature FTA includes a Cold Junction Compensation
TM
Temperature FTA can connect direct to an Analogue Input

FEATURES

Eight Input channels per Trusted Temperature FTA
Flexible user defined
conditioning
Standard DIN rail
compatibility
Configurable 2 or 3-wire
RTD inputs
Dual 24V Supply
Issue 3 Aug 2006
SDS-T8840
Trusted
TM
Industrial Control System
TrustedTM Temperature Input FTA - T8840

ELECTRICAL SPECIFICATION

Voltage Range Maximum Input Current Number of Inputs Possible Input Types (dependant on conditioning unit fitted)
Accuracy, resolution
15 to 28V dc
2.5A 8 Isolated Voltage Isolated Current
Isolated RTD Pt 100ohm Isolated RTD Ni 120ohm Powered Isolated 2 wire 4-20mA transmitter Isolated Potentiometer Isolated Thermocouple J,K Dependant on conditioning unit
MECHANICAL SPECIFICATION
Dimensions (HxWxD):
110mm x 145mm x 68mm (4.3ins x 5.7ins x 2.6ins)
Depth with conditioning unit fitted:
90mm (3.6ins)
Weight (fully populated)
248gms (0.55lbs)
ENVIRONMENTAL
Operating Temperature:
-5°C to 60°C (23°F to 140°F)
Operating Humidity:
5 to 95%, non­condensing
Vibration:
10 to 57Hz ±0.075mm 57 to 150Hz 1.0g
Shock:
15g, ½ sine wave, 11ms
EMI (IEC 801):
ESD Air discharge to 15kV. Contact discharge to 8kV
Radiated Fields 10V/m, 27MHz to 500MHz
Transients and Bursts 2kV, 2.5kHz for t=60 seconds