Rockwell Automation T8833 User Manual

TrustedTM
PD-T8833
TM
Trusted
20 Channel Isolated AI/DI
Introduction
The TrustedTM 20 Channel Isolated AI/DI FTA (Field Termination Assembly) T8833 is designed to act as the main interface between a field device generating a 4-20mA signal and the Isolated Analogue Input Module T8433.
Features
20 isolated input channels per FTA.
Standard DIN rail compatibility.
Simple installation and connection.
Loop Powered operation.
Issue 3 Aug 06 PD-T8833 1
Trusted
Issue Record
Issue
Number Date Revised by Technical CheckAuthorised by Modification
2 Sep 05 J W Clark Format
3 Aug 06 N Owens I Vince P Stock Termination
TM
AI/DI FTA Loop Power T8833
Issue 3 Aug 06 PD-T8833 2
Trusted
TM
AI/DI FTA Loop Power T8833
Figure 1 T8833 Layout
Issue 3 Aug 06 PD-T8833 3
Trusted
TM
AI/DI FTA Loop Power T8833
Table of Contents
1. Description ...................................................................................................................................7
2. Installation....................................................................................................................................8
3. Associated Cable Selection .........................................................................................................8
4. Assembly Pinout Connections .....................................................................................................9
4.1. CON1 Connections......................................................................................................................9
4.2. TB1 Connections .......................................................................................................................10
5. Specifications.............................................................................................................................11
Figures
Figure 1 T8833 Layout..............................................................................................................................3
Figure 2 Single Channel Schematic .........................................................................................................7
Figure 3 Connector locations....................................................................................................................8
Table s
Table 1 CON1 Connections......................................................................................................................9
Table 2 TB1 Connections .......................................................................................................................10
Issue 3 Aug 06 PD-T8833 4
Trusted
TM
AI/DI FTA Loop Power T8833
Notice
The content of this document is confidential to ICS Triplex Technology Ltd. companies and their partners. It may not be given away, lent, resold, hired out or made available to a third party for any purpose without the written consent of ICS Triplex Technology Ltd.
his document contains proprietary information that is protected by copyright. All rights are reserved.
T
Microsoft, Windows, Windows 95, Windows NT, Windows 2000, and Windows XP are registered trademarks of Microsoft Corporation.
The information contained in this document is subject to change without notice. The reader should, in all cases, consult ICS Triplex Technology Ltd. to determine whether any such changes have been made. From time to time, amendments to this document will be made as necessary and will be distributed by ICS Triplex Technology Ltd.
Information in this documentation set may be subject to change without notice and does not represent a commitment on the part of ICS Triplex Technology Ltd.
The contents of this document, which may also include the loan of software tools, are subject to the confidentiality and other clause(s) within the Integrator Agreement and Software License Agreement.
No part of this documentation may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, for any purpose, without the express written permission of ICS Triplex Technology Ltd.
Disclaimer
The illustrations, figures, charts, and layout examples in this manual are intended solely to illustrate the text of this manual.
The user of, and those responsible for applying this equipment, must satisfy themselves as to the acceptability of each application and use of this equipment.
This document is based on information available at the time of its publication. While efforts have been made to be accurate, the information contained herein does not purport to cover all details or variations in hardware or software, nor to provide for every possible contingency in connection with installation, operation, or maintenance. Features may be described herein which are present in all hardware or software systems. ICS Triplex Technology Ltd. assumes no obligation of notice to holders of this document with respect to changes subsequently made.
ICS Triplex Technology Ltd. makes no representation or warranty, expressed, implied, or statutory with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein. No warranties of merchantability or fitness for purpose shall apply
Issue 3 Aug 06 PD-T8833 5
Trusted
TM
AI/DI FTA Loop Power T8833
Revision and Updating Policy
All new and revised information pertinent to this document shall be issued by ICS Triplex Technology Ltd. and shall be incorporated into this document in accordance with the enclosed instructions. The change is to be recorded on the Amendment Record of this document.
Precautionary Information
WARNING
Warning notices call attention to the use of materials, processes, methods, procedures or limits which must be followed precisely to avoid personal injury or death.
CAUTION
Caution notices call attention to methods and procedures which must be followed to avoid damage to the equipment.
Notes:
Notes highlight procedures and contain information to assist the user in the understanding of the information contained in this document
Warning
RADIO FREQUENCY INTERFERENCE
Most electronic equipment is influenced by Radio Frequency Interference (RFI). Caution should be exercised with regard to the use of portable communications equipment around such equipment. Signs should be posted in the vicinity of the equipment cautioning against the use of portable communications equipment.
MAINTENANCE
Maintenance must be performed only by qualified personnel, otherwise personal injury or death, or damage to the system may be caused.
Caution
HANDLING
Under no circumstances should the module housing be removed.
Associated Documents
Product Descriptions (PD) provide product specific information.
The Safety Manual contains the recommended safety requirements for the safety system design.
The PD8082B – Toolset Suite provides specific guidance on system configuration and application generation.
The Operator and Maintenance Manual contains general guidelines on maintenance and diagnostic procedures.
For technical support email: support@icstriplex.com
Issue 3 Aug 06 PD-T8833 6
Trusted
TM
AI/DI FTA Loop Power T8833
1. Description
The TrustedTM 20 Channel Isolated Analogue Input FTA, T8833, provides termination for a maximum
f 20 input channels from various types of field devices which generate a current loop signal. When
o used with a Trusted and individually isolated. Figure 2 below shows the configuration of a single channel.
M
T
T8433 TMR Isolated Analogue Input module each of the inputs is loop powered
CON1 VPOWER
CON1 COMMON
+
TB1 A
7V5
100R
TB1 B
CON1 VSENSE
Figure 2 Single Channel Schematic
The FTA is configured so that the 4-20 mA field current loop signal connects to TB1 A and the loop return connects to TB1 B. The current loop signal is then converted into a voltage by the circuit in Figure 2. This voltage is split into a 7.5V DC low current power supply to power the isolation amplifiers on the input module (VPOWER) and the precision 0-2V current sense signal (VSENSE) connected to the input module. Both of these voltages are referenced to (COMMON).
This means that input module operates on the loop power of the field devices. This way each field device is isolated from the other devices and from ground.
The connector linking the 20 channels on the input module to the FTA is terminated at CON1 which is a 96-way socket. A row of screw terminal connectors (TB1) are used to connect the field wiring.
Unused inputs should be terminated by wiring a 24V supply via a resistor (2K or 2K2) to the A terminal and wiring the B terminal to the associated zero volts.
Issue 3 Aug 06 PD-T8833 7
Trusted
TM
AI/DI FTA Loop Power T8833

2. Installation

The TrustedTM 20 Channel Isolated AI/DI FTA T8833 is designed to be mounted on either of the TS32
r TS35 DIN rails in the horizontal or vertical positions as required. The location of the connectors on
o the FTA are shown in Figure 3.
CON1
DIN41612
TB1 Screw Terminals
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
Figure 3 Connector locations

3. Associated Cable Selection

Refer to the Product Descriptions detailed below:
TM
PD-TC600 Trusted
PD-TC700 Trusted
NOTE
60 channel cables are used for this FTA due to the three wire per channel connection to the input module.
I/O SmartSlot Cables 60-Channel
TM
I/O Companion Slot Cables 60-Channel
Issue 3 Aug 06 PD-T8833 8
Trusted
TM
AI/DI FTA Loop Power T8833

4. Assembly Pinout Connections

4.1. CON1 Connections

CON1 is a 96 Way DIN41612 socket. The connections are detailed below:
Row
Pin
1 N/C N/C N/C
2 N/C N/C N/C
3 CH1_VPOWER CH1_COMMON CH1_VSENSE
4 CH2_ VPOWER CH2_ COMMON CH2_ VSENSE
5 CH3_ VPOWER CH3_ COMMON CH3_ VSENSE
6 CH4_ VPOWER CH4_ COMMON CH4_ VSENSE
7 CH5_ VPOWER CH5_ COMMON CH5_ VSENSE
8 CH6_ VPOWER CH6_ COMMON CH6_ VSENSE
9 CH7_ VPOWER CH7_ COMMON CH7_ VSENSE
10 CH8_ VPOWER CH8_ COMMON CH8_ VSENSE
11 CH9_ VPOWER CH9_ COMMON CH9_ VSENSE
12 CH10_ VPOWER CH10_ COMMON CH10_ VSENSE
13 CH11_ VPOWER CH11_ COMMON CH11_ VSENSE
14 CH12_ VPOWER CH12_ COMMON CH12_ VSENSE
15 CH13_ VPOWER CH13_ COMMON CH13_ VSENSE
16 CH14_ VPOWER CH14_ COMMON CH14_ VSENSE
17 CH15_ VPOWER CH15_ COMMON CH15_ VSENSE
18 CH16_ VPOWER CH16_ COMMON CH16_ VSENSE
19 CH17_ VPOWER CH17_ COMMON CH17_ VSENSE
20 CH18_ VPOWER CH18_ COMMON CH18_ VSENSE
21 CH19_ VPOWER CH19_ COMMON CH19_ VSENSE
22 CH20_ VPOWER CH20_ COMMON CH20_ VSENSE
23 N/C N/C N/C
24 N/C N/C N/C
25 N/C N/C N/C
26 N/C N/C N/C
27 N/C N/C N/C
28 N/C N/C N/C
29 N/C N/C N/C
30 N/C N/C N/C
31 N/C N/C N/C
32 N/C N/C N/C
A B C
Table 1 CON1 Connections
Issue 3 Aug 06 PD-T8833 9
Trusted
TM
AI/DI FTA Loop Power T8833

4.2. TB1 Connections

TB1 is a row of screw terminals. Figure 3 shows how they are numbered. The connections are detailed below:
Pin Service Pin Service
1 CH1_A 21 CH11_A
2 CH1_B 22 CH11_B
3 CH2_A 23 CH12_A
4 CH2_B 24 CH12_B
5 CH3_A 25 CH13_A
6 CH3_B 26 CH13_B
7 CH4_A 27 CH14_A
8 CH4_B 28 CH14_B
9 CH5_A 29 CH15_A
10 CH5_B 30 CH15_B
11 CH6_A 31 CH16_A
12 CH6_B 32 CH16_B
13 CH7_A 33 CH17_A
14 CH7_B 34 CH17_B
15 CH8_A 35 CH18_A
16 CH8_B 36 CH18_B
17 CH9_A 37 CH19_A
18 CH9_B 38 CH19_B
19 CH10_A 39 CH20_A
20 CH10_B 40 CH20_B
Table 2 TB1 Connections
Issue 3 Aug 06 PD-T8833 10
Trusted
TM
AI/DI FTA Loop Power T8833

5. Specifications

Field Current Loop (Per Channel)
Field Loop Volt Drop at 20mA
Operating Temperature
Non-operating Temperature
Operating Humidity (Non – condensing)
Environmental Specifications
Dimension
Width Depth
Weight
s
Height
MIN MAX
2mA 30mA
9.5V
0
C (230F) 60
-5
0
C (-130F) 70
-25
0
C (1400F)
0
C (1580F)
5% RH 95% RH
Refer to Document 552517
120mm (4.72ins) 336mm (13.23ins) 50mm (1.97ins)
500gms (1.1lbs)
Issue 3 Aug 06 PD-T8833 11