Rockwell Automation T8832 User Manual

SDS-8832
Trusted
TM
Industrial Control System
TrustedTM 60 Channel Analogue Input FTA - T8832

DESCRIPTION

The Trusted Channel is designed to act as the main interface between a field device generating a digital signal and the Trusted T8432.
The field supply is derived from dual 24V dc feeds, which are ‘commoned’ via diodes on the FTA. The supply is then fed to each channel. Channel 0 on the Trusted future to provide monitoring of the field power supply.
The supply voltage to the field is fed via a 50mA fuse. The incoming signal from the field device is developed across a 250R resistor, then connected to the appropriate input circuit on the Input Module. Line monitoring components (if required) provide the necessary thresholds used by the input module to detect the field loop/device status, i.e. open/short circuit, alarm etc.
The cable linking the 60 channels on the input module to the FTA is terminated at a 96-way socket. The dual dc power supplies are connected to the FTA via a single 4-way connector. Ten 12-way connectors are used for the field loops.
The FTA is designed to be mounted on either of the TS32 or TS35 DIN rails in the horizontal or vertical positions as required.
M
T
Field Termination Assembly (FTA) Analogue Input 60-
TM
Dual Analogue Input Module
TM
Dual Analogue Input Module will be configured in the

FEATURES

Sixty input channels per
FTA
Industry standard field
device connections (2-wire)
Standard DIN rail
compatibility
Simple installation and
connection
24V dc operation
Fused field power supply
per channel
Issue 5 Jan 2006
SDS-8832
Trusted
TM
Industrial Control System
TrustedTM 60 Channel Analogue Input FTA - T8832

BLOCK DIAGRAM

Single Channel Schematic

ELECTRICAL SPECIFICATION

Field Supply Range Fuses Maximum Current (Field Supply) Recommended Operating Current Power Consumption (Field Supply)
0 to 140V dc 61-off 50mA 3A 0 to 20mA per channel
6.5W maximum
MECHANICAL SPECIFICATION
Dimensions (HxWxD):
110mm x 455mm x 68mm (4.3ins x 17.9ins x 2.6ins)
Weight (fully populated)
762gms (1.68lbs)
ENVIRONMENTAL
Operating Temperature:
-5°C to 60°C (23°F to 140°F)
Operating Humidity:
5 to 95%, non­condensing
Vibration:
10 to 57Hz ±0.075mm 57 to 150Hz 1.0g
Shock:
15g, ½ sine wave, 11ms
EMI (IEC 801):
ESD Air discharge to 15kV. Contact discharge to 8kV
Radiated Fields 10V/m, 27MHz to 500MHz
Transients and Bursts 2kV, 2.5kHz for t=60 seconds
ICS Triplex
Technical data sheets are intended for information and guidance. The Company has a policy of continual product development and improvement. Specifications are subject to change without notice. For latest information, visit our Websi te:- www.icstr iple x.com