Rockwell Automation T8831 User Manual

SDS-8831
Primary & Hot Spare Modules
Educate
Activ
Health
T8xxx
13579
111315171921232527293133353739Standb2468
10121416182022242628303234363840Educate
Activ
Health
T8xxx
13579
111315171921232527293133353739Standb2468
1012141618202224262830323436384
0
Trusted
TM
Industrial Control System
TrustedTM 40 Channel Analogue Input FTA Non Incendive – T8831

ASSEMBLY

into the metal slot retainer shown in the illustration at left.
To facilitate the need for on-line replacement of an unhealthy I/O module, the interface cable is designed to provide the user with two different methods for on-line maintenance. The first method involves the use of a dual connector hood. The dual connectors allocate an adjacent slot in the Trusted
TM
chassis for a hot-replacement
module. Refer to Figure 1 below for more details regarding a dedicated spare slot approach.
The second method of hot replacement uses a “one-to-many” approach. This feature is called the SmartSlot Link (SSL). The SSL furnishes the method to use a single I/O module slot as a hot replacement slot. This configuration reduces I/O chassis space by using a single slot for hot replacement of all modules of that type. In this case the I/O cable has a second socket on the back of the module end for connecting a cable to the hot replacement slot.

FEATURES

40 TMR input points
Easy to mount and
Industry standard
Standard DIN rail
Loop current
Small physical size
Low cost
On-board LED for
per module
replace
field device connections
compatibility
limiting and dropping resistors pre-installed
loop power integrity indication

DESCRIPTION

The 40-channel T8831 Trusted Termination Assembly (FTA) is the primary interface between the Trusted Input module and the field device (wiring) loop. The model T8831 is designed for use in non­incendive applications. The FTA is supplied with both 150 loop current and 250 dropping resistors.
The FTA is made up of several components: the interface cable connector and hood lock, loop power distribution, dropping resistors, and field input terminations.
To reduce integration time, the interface cable which connects the FTA and its I/O module is pre-assembled and fitted with a pair of specialized hoods. These hoods are used to secure the cable in place. The FTA hood fits
TM
Field
TM
TMR Analog
Dual Hood
r
T u t
s e d T M R
FTA
r
T u t
s e d T M R
Interface
Cable
Figure 1
SDS-8831
Trusted
TM
Industrial Control System
TrustedTM TMR Field Termination Assembly – Non-Incendive Analog Input-T8831

BLOCK DIAGRAM

(SmartSlot Link Connector is unused)
Dual Loop Power
+V 1 +
V 2
0
To I/O
Module
V
T
B1
S
K1
SK2
SmartSlot Link Connector
Channels 0 & 41 reserved for internal use
TB3
Dropping
Resistor
Typical
Analog Input
Non-incendive
Channel Schematic
Current L imiting
Resistor
TB2
1
2
3 - 40
Field I
nputs
Figure 2

ELECTRICAL SPECIFICATION

Number of Inputs Internal Use Inputs Type of Input Terminals Type of Power Terminals Acceptable Wire Sizes
UL 30-12 AWG 15A 300V
CSA 28-12 AWG 10A 300V
Din Rail Compatibility
Testing
Intrinsic Safety Dropping Resistor Current Limiting
40 2 MKKDS 3 MVSTBR 2.5
EN 50022 NS 35/7.5 NS 35/15 NS 32 100% electrical (continuity and short-circuit) External barrier 250E 0.5W On-board 150E 3W resistor
MECHANICAL SPECIFICATION
Dimensions (HxWxD):
335mm x 111mm x 51mm (13.2ins x 4.4ins x 2ins)
Weight:
0.9kg (2.0lbs)
ENVIRONMENTAL
Operating Temperature
-5°C to 60°C (23°F to 140°F)
Operating Humidity:
5 to 95%, non-condensing
Vibration:
10 to 57Hz ±0.075mm 57 to 150Hz 1.0g
Shock:
15g, ½ sine wave, 11ms
EMI (IEC 801):
ESD Air discharge to 15kV Contact discharge to 8kV Radiated Fields 10V/m, 27MHz to 500MHz Transients and Bursts 2kV, 2.5kHz for t=60 seconds