Rockwell Automation T8449 User Manual

SDS-8449
T8449 Trusted TMR 24Vdc Valve Moni tor
OUT
IN
TrustedTM Industrial Control System
Trusted
TM
TMR 24Vdc Valve Monitor Module -T8449

FRONT PANEL

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19 20

DESCRIPTION

To meet the demanding requirements of Safety Integrity Level (SIL) calculations, final elements of a safety function such as shutdown valves require regular testing.
The TUV approved (AK6, SIL3) Trusted TMR Valve Monitor module, will control any valve connected to it and test the valve at regular intervals. It is used in place of a normal controlling output module where the automatic valve testing function is required. The Valve Monitor will perform the partial stroke tests, monitor the results and pass on information for display, alarm and historical record via the application program of the Trusted
TM
controller.
TM
Maximum test times are derived for each valve to ensure the test can only move the valve for a period which will not cause disturbance to the process. This method of partial stroke testing exercises the entire shutdown path from safety system logic to movement of the valve actuator. The test verifies the ability of the valve to perform its shutdown function.
Triple Modular redundancy (TMR) is used to ensure fault tolerance. The system will continue uninterrupted, safe operation in the presence of one or more internal discrepancies. Features typical of all Trusted
TM
output modules are included, such as, line monitoring, fuseless protected outputs, 1msec sequence of events (SOE) resolution, configurable LED colours and field signal monitoring.
The Valve Monitor connects to 20 valves by providing 20 control outputs and 20 monitoring inputs arranged together in pairs. These pairs are in 5 isolated groups with separate power feeds to each. The outputs connect directly to the Solenoid Operated Valve (SOV) or via an Intrinsically Safe interface in the usual way. Outputs can be normally energised or de-energised, open or closed. Feedback of valve position can be by limit switches or an analogue position sensor. The Valve Monitor connects to the field circuits via a Versatile Field Termination Assembly (VFTA). The VFTA allows the user to link configure an appropriate electrical loop for the control and monitoring signals.
The signals that control valve open and closed state, plus the requests to test, are derived from the application program running in the Trusted
TM
TMR Processor. The IEC1131 Toolset uses a pre­configured function block to marshall signals to and from the Valve Monitor. The unique characteristics of each valve such as test time, feedback thresholds and alarm conditions, are also set in the IEC 1131 Toolset and can be modified online. Control of the testing can be based on time of day, time interval or manually initiated from the Valve Manager operator interface.
The module has extensive automatic diagnostics. Should a fault in the module be detected, the Trusted
TM
TMR
Processor will flag the unhealthy
condition, indicating the need to replace the module. Control continues until a replacement (healthy) module is available. Replacement modules can be located in a Companion Slot next to the faulty module or in a designated SmartSlot with a temporary connection to the faulty module.
Modules may be placed in any I/O slot in a Trusted
TM
Processor Chassis or Expander chassis. Mechanical keying prevents insertion of the incorrect module.

FEATURES

40 TMR channels to control
and test 20 shutdown valves
Partial stroke testing
embedded in TMR safety system
Tests valves to AK6 or SIL3
application requirements
Use with single or dual SOV’s
for maximum process availability
No added hardware so no
increase in MTBF
spurious
Line monitoring
Automatic over-current
protection – no fuses required
Hot replaceable
Can be installed as retrofit
using existing field installation
Maximum increase to safety
integrity for minimum cost
On-board 1ms resolution
Sequence of Events reporting
SDS-8449
Trusted
TM
Industrial Control System
Trusted
TM
TMR 24Vdc Valve Monitor Module -T8449

BLOCK DIAGRAM

OFIUHIU
I
nternal Voting Bus
TMR Intermodule Bus
Housekeeping Module Temp
DSP reference
Back Plane
B
ack Plane Power Bus 1
Power Bus
Back Plane Power Bus 2
1
Bus
Interface
Bus
Interface
Bus
I
nterface
Supply Diag
Redundant Supply
S
lice
Control
ime Stamp
T
A
S
lice
Control
Time Stamp
B
Slice
Control
ime Stamp
T
B
Failsafe Bia s Control
S
lice Power
upply
S
Field Logic
Control
F
ailsafe Bias Control
S
lice Power
Supply
Field Logic
Control
F
ailsafe Bias Control
S
lice Power
Supply
Field Logic
Control
Opto Isolat ion Boundary
Front Panel
oting Logic
V
Indicators
Health
Voted Status Display LEDs
Serial Dis play Latches
F
A
D
iagnostic
onitor
M
ousekeeping
H
B
D
iagnostic Monitor
Housekeeping
C
D
iagnostic Monitor
Housekeeping
ront Panel
N.O.
N.O.
N.O.
FPIU
FPDU
Slice A
N
S
lice B
N.C.
Slice C
N.C.

ELECTRICAL SPECIFICATION

Number of channels
No. of Independent Power Groups Field Common Isolation
Sustained Working ±250V dc
Maximum Withstanding ±2.5kV dc
Field Supply Voltage
Measurement Range 0 to 32V dc
Maximum Withstanding -1 to 40V dc
Output Current Rating
Continuous 2 A
Minimum 50ma Output Off Resistance (effective leakage) Power Consumption at 24V (1A per channel) Output Turn On/Off Delay Self-Test Interval Output Short Circuit Protection Fusing Intrinsic Safety Circuit Type
40 Channels – 20 control, 20 monitoring 5, each of 4 outputs & 4 inputs
33k>
24W
0.5ms 2 minutes Automatic Not required External barrier Fault tolerant, fully triplicated with optional line monitoring
OFTU
.C.
F
ield Interfa ce
rotection C ircuit
P
G
roup
Fail-Safe
Switch
A B C
-
V
MECHANICAL SPECIFICATION
Dimensions (HxWxD):
241mm x 30mm x 300mm (9.5ins x 1.2ins x 11.8ins)
Weight:
1.13kg (2.5lbs)
ENVIRONMENTAL
+V
Operating Temperature:
-5°C to 60°C (23°F to 140°F)
Operating Humidity:
5 to 95%, non­condensing
Vibration:
10 to 57Hz ±0.075mm 57 to 150Hz 1.0g
Shock:
15g, ½ sine wave, 11ms
EMI (IEC 801):
ESD Air discharge to 15kV Contact discharge to 8kV
Radiated Fields 10V/m, 27MHz to 500MHz
Transients and Bursts 2kV, 2.5kHz for t=60 seconds
ICS Triplex
Technical data sheets are intended for information and guidance. The Company has a policy of continual product development and improvement. Specifications are subject to change without notice. For latest information, visit our Websi te:- www.icstr iple x.com
Loading...