The TrustedTM TMR Zone Interface module has been designed to provide a configurable interface
specifically for use in Fire and Gas protection systems. The module interfaces to up to 40 Fire and
Gas field device inputs or actuators. Each of the 40 I/O Channels can be individually configured as
Analogue Input, Digital Input or Digital Output to provide all of the interfaces needed to protect one or
more Fire and Gas Zones. Interfacing to the field devices is through a Versatile Field Termination
Assembly type 8842, which provides the field loop conditioning for each of the types of signal, and
enables the connection of reset signals for latching type detectors without the need for external
hardware. The module is separated into 5 power groups each with 8 channels. Power groups can be
combined together to provide a configurable number of channels for each Fire/Gas Zone. All of these
functions provide data to the Trusted
TM
TMR system which acts as the logic solver.
Triplicated diagnostic tests are performed throughout the module, including measurements for current
and voltage on each portion of voted input or output channels. Tests are also performed for stuck on
and stuck off failures. All inputs are treated as analogue and are fully tested. Fault tolerance is
achieved through a Triple Modular Redundant (TMR) architecture within the module for each of the 40
channels.
Features
•40 Triple Modular Redundant selectable input/output points per module.
•Inputs interface to 4-20mA gas detectors, Fire and Heat detectors, Break Glass units etc.
•Programmable Field Device Reset signals (up to 5 individual resets)
•Two or Three Wire Field devices through 8842
•Fuse Protection of Inputs and Outputs through 8842
•High Power Digital Outputs to interface to Dampers, Extinguishant Release, Fire pumps
etc.
•5 Isolated Power Groups to allow flexible and efficient field configurations.
•Comprehensive automatic diagnostics and self-test.
•Automatic line monitoring per point to detect faults in field wiring and loads.
•2500V dc optical isolation barrier.
•Automatic over-current protection (per channel), no module fuses required
•On-board Sequence of Events (SOE) reporting with 1ms resolution.
•Module can be hot-replaced on-line using dedicated Companion (adjacent) Slot or
SmartSlot (one spare slot for many modules) configurations.
•TÜV Certified IEC 61508 SIL 3
Issue 14 Apr 10 PD-T8448 1
Trusted
Issue Record
Issue
Number Date Revised by Technical CheckAuthorised by Modification
TM
Module T8448
7
8Feb 06 Pete Stock Format correction
9Aug 06 N Owens I Vince P Stock Input power
10 Dec 06 V Middleton N Owens P Stock Weights & Dims
11 Mar 07 N Owens I Vince P Stock Accuracy
12 Nov 07 N Owens A Holgate P Stock STATE descriptions
13 Aug 08 I Vince N Owens P Stock Accuracy
14 Apr 10 S Blackett A Holgate N Owens Rack 7 changes
Table 19 Module Status LEDs................................................................................................................33
Table 20 I/O Status LEDs.......................................................................................................................34
Issue 14 Apr 10 PD-T8448 6
Trusted
TM
Module T8448
Notice
The content of this document is confidential to ICS Triplex Technology Ltd. companies and their
partners. It may not be given away, lent, resold, hired out or made available to a third party for any
purpose without the written consent of ICS Triplex Technology Ltd.
This document contains proprietary information that is protected by copyright. All rights are reserved.
Microsoft, Windows, Windows 95, Windows NT, Windows 2000, and Windows XP are registered
trademarks of Microsoft Corporation.
The information contained in this document is subject to change without notice. The reader should, in
all cases, consult ICS Triplex Technology Ltd. to determine whether any such changes have been
made. From time to time, amendments to this document will be made as necessary and will be
distributed by ICS Triplex Technology Ltd.
Information in this documentation set may be subject to change without notice and does not represent
a commitment on the part of ICS Triplex Technology Ltd.
The contents of this document, which may also include the loan of software tools, are subject to the
confidentiality and other clause(s) within the Integrator Agreement and Software License Agreement.
No part of this documentation may be reproduced or transmitted in any form or by any means,
electronic or mechanical, including photocopying and recording, for any purpose, without the express
written permission of ICS Triplex Technology Ltd.
Disclaimer
The illustrations, figures, charts, and layout examples in this manual are intended solely to illustrate the
text of this manual.
The user of, and those responsible for applying this equipment, must satisfy themselves as to the
acceptability of each application and use of this equipment.
This document is based on information available at the time of its publication. While efforts have been
made to be accurate, the information contained herein does not purport to cover all details or variations
in hardware or software, nor to provide for every possible contingency in connection with installation,
operation, or maintenance. Features may be described herein which are present in all hardware or
software systems. ICS Triplex Technology Ltd. assumes no obligation of notice to holders of this
document with respect to changes subsequently made.
ICS Triplex Technology Ltd. makes no representation or warranty, expressed, implied, or statutory with
respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of
the information contained herein. No warranties of merchantability or fitness for purpose shall apply.
Issue 14 Apr 10 PD-T8448 7
Trusted
TM
Module T8448
Revision and Updating Policy
All new and revised information pertinent to this document shall be issued by ICS Triplex Technology
Ltd. and shall be incorporated into this document in accordance with the enclosed instructions. The
change is to be recorded on the Amendment Record of this document.
Precautionary Information
WARNING
Warning notices call attention to the use of materials, processes, methods, procedures or limits which
must be followed precisely to avoid personal injury or death.
CAUTION
Caution notices call attention to methods and procedures which must be followed to avoid damage to
the equipment.
Notes:
Notes highlight procedures and contain information to assist the user in the understanding of the
information contained in this document
Warning
RADIO FREQUENCY INTERFERENCE
Most electronic equipment is influenced by Radio Frequency Interference (RFI). Caution should be
exercised with regard to the use of portable communications equipment around such equipment.
Signs should be posted in the vicinity of the equipment cautioning against the use of portable
communications equipment.
MAINTENANCE
Maintenance must be performed only by qualified personnel, otherwise personal injury or death, or
damage to the system may be caused.
Caution
HANDLING
Under no circumstances should the module housing be removed.
Associated Documents
Product Descriptions (PD) provide product specific information.
The Safety Manual contains the recommended safety requirements for the safety system design.
The PD8082B – Toolset Suite provides specific guidance on system configuration and application
generation.
The Operator and Maintenance Manual contains general guidelines on maintenance and diagnostic
procedures.
For technical support email: support@icstriplex.com
Issue 14 Apr 10 PD-T8448 8
Trusted
TM
Module T8448
1. Description
M
The TMR Zone Interface module is a member of the Trusted
All Trusted
TM
I/O modules share common functionality and form. At the most general level, all I/O
modules interface to the Inter-Module Bus (IMB) which provides power and allows communication with
he TMR Processor. In addition, all modules have a field interface that is used to connect to module
t
specific signals in the field. All modules are Triple Modular Redundant (TMR).
T
range of Input/Output (I/O) modules.
Figure 1 Module Architecture
All High Integrity I/O modules are made up of 4 sections: Host Interface Unit (HIU), the Field Interface
Unit (FIU), the Field Termination Unit (FTU), and the Front Panel Unit (or FPU).
Issue 14 Apr 10 PD-T8448 9
Trusted
TM
Module T8448
Figure 2 shows a simplified block diagram of the TrustedTM Zone Interface Module.
Internal Voting Bus
TMR Intermodule Bus
Housekeeping
Module Temp
D
Back Plane
B
ack Plane Power Bus 1
P
ower Bus
Back Plane Power Bus 2
1
B
us
Interface
Bus
I
nterface
Bus
I
nterface
S
upply Diag
SP reference
Redundant Supply
Slice
Control
ime Stamp
T
A
Slice
Control
ime Stamp
T
B
Slice
Control
ime Stamp
T
B
Failsafe Bia s Control
S
lice Power
upply
S
Field Logic
Control
F
ailsafe Bias Control
Slice Power
Supply
Field Logic
Control
F
ailsafe Bias Control
S
lice Power
Supply
Field Logic
Control
Opto Isolat ion Boundary
Front Panel
V
oting Logic
Indicators
Health
Voted Status Display LEDs
Serial Dis play Latches
Front Pane l
OFIUHIU
A
H
B
Housekeeping
C
Housekeeping
D
iagnostic
onitor
M
ousekeeping
D
iagnostic
Monitor
D
iagnostic
Monitor
N.O.
N.O.
N.O.
FPIU
FPDU
Slice A
N
S
lice B
N.C.
Slice C
N.C.
OFTU
.C.
F
ield Interfa ce
rotection C ircuit
P
G
roup
Fail-Safe
S
witch
A B C
-
V
+V
Figure 2 Function Block Diagram
1.1. Field Termination Unit (FTU)
The Field Termination Unit (FTU) is the section of the I/O module that connects all three FIUs to a
single field interface. The FTU provides the Group Fail-safe switches and passive components
necessary for signal conditioning, over-voltage protection, and EMI/RFI filtering. When installed in a
Trusted
TM
Controller or Expander Chassis, the FTU field connector interconnects to the Field I/O Cable
Assembly attached at the rear of the chassis.
The SmartSlot link is passed from the HIU to the field connections via the FTU. These signals go
directly to the field connector and maintain isolation from the I/O signals on the FTU. The SmartSlot
link is the intelligent connection between active and standby modules for co-ordination during module
replacement.
1.2. Field Interface Unit (FIU)
The Field Interface Unit (FIU) is the section of the module that contains the specific circuits necessary
to interface to the particular types of field I/O signals. Each module has three FIUs, one per slice. For
the TMR Zone Interface Module, the FIU contains one stage of the output switch structure, and A/D
monitoring circuits for each of the channels Two additional A/D circuits provide optional monitoring of
the external field I/O supply voltage.
The FIU receives isolated power from the HIU for logic. The FIU provides additional power
conditioning for the operational voltages required by the FIU circuitry. An isolated 6.25Mbit/sec serial
link connects each FIU to one of the HIU slices.
The FIU also measures a range of on-board “house-keeping” signals that assist in monitoring the
performance and operating conditions of the module. These signals include power supply voltages,
current consumption, on-board reference voltages, board temperature, and condensation.
Issue 14 Apr 10 PD-T8448 10
Trusted
FCR Interconnect Bus between slices to vote incoming IMB data and distribute outgoing I/O
Redundant power sharing of dual 24V dc chassis supply voltage and power regulation for logic
ordination during module
board housekeeping, which monitors reference voltages, current consumption and board
TM
Module T8448
1.3. Host Interface Unit (HIU)
The HIU is the point of access to the Inter-Module Bus (IMB) for the module. It also provides power
distribution and local programmable processing power. The HIU is the only section of the I/O module
to directly connect to the IMB backplane. The HIU is common to most high integrity I/O types and has
type dependent and product range common functions. Each HIU contains three independent slices,
commonly referred to as A, B, and C.
ll interconnections between the three slices incorporate isolation to prevent any fault interaction
A
between the slices. Each slice is considered a Fault Containment Region (FCR), as a fault on one
slice has no effect on the operation of the other slices.
The HIU provides the following services common to the modules in the family:
•High Speed Fault-Tolerant Communications with the TMR Processor via the IMB interface.
•
module data to the IMB.
•Optically isolated serial data interface to the FIU slices.
•
power to HIU circuitry.
•Magnetically isolated power to the FIU slices.
•Serial data interface to the FPU for module status LEDs.
•SmartSlot link between active and standby modules for co-
replacement.
•Digital Signal Processing to perform local data reduction and self-diagnostics.
•Local memory resources for storing module operation, configuration, and field I/O data.
•On-
temperature.
1.4. Front Panel Unit (FPU)
The Front Panel Unit (FPU) contains the necessary connectors, switches, logic, and LED indicators for
the front panel. For every module, the FPU contains the Slice Healthy, Active/Standby, the Educated
indicators (LEDs), and the module removal switches. Additional bi-colour LEDs provide status
indication for the individual I/O signals. Serial data interfaces connect the FPU to each of the HIU
slices to control the LED status indicators and monitor the module removal switches.
1.5. Input Line Monitoring Thresholds
Whether selected as a digital or an analogue input, the module measures the voltage applied to each
input and compares this with four user programmed thresholds and two fixed (minimum and
maximum) thresholds. These may be used within the application to signal a field device state.
Hysteresis is provided on the thresholds by upscale and downscale values, corresponding to the
thresholds for increasing and decreasing values respectively. The analogue voltage reading is also
provided to the application for conversion to engineering units and/or direct trip derivation.
Default threshold values used for non line monitored inputs are as follows (in raw units)
The Zone Interface Module automatically performs local measurements of several on-board signals
that can be used for detailed troubleshooting and verification of module operating characteristics.
Measurements are made within each slice’s HIU and FIU.
1.7. Fault Detection and Testing
From the IMB to the field connector, the I/O module contains extensive fault detection and integrity
testing. Most testing is performed in a non-interfering mode. Data input from the IMB is stored in
redundant error-correcting RAM on each slice portion of the HIU. Received data is voted on by each
slice. All data transmissions include a confirmation response from the receiver.
Periodically, the TMR Processor commands the onboard Digital Signal Processors (DSPs) to perform
a Safety Layer Test. The SLT results in the DSP verifying with the TMR Processor its ability to process
data with integrity. In addition, the DSP uses Cyclical Redundancy Checks (CRC) to verify the
variables and configuration stored in Flash memory.
Between the HIU and FIU are a series of optically isolated links for data and power. The data link is
synchronized and monitored for variance. Both FIU and HIU have onboard temperature sensors to
characterize temperature-related problems. Each FIU is also fitted with a condensation sensor.
The power supplies for both the HIU and FIU boards are redundant, fully instrumented and testable.
Together these assemblies form a Power Integrity Sub System.
1.8. Sequence of Events Characteristics
The module automatically measures the field voltage and current to determine the state of each
channel. An event occurs when the channel transitions from one state to another. When a channel
changes state, the on-board timer value is recorded. When the TMR Processor next reads data from
the module, the channel state and real-time clock value are retrieved. The TMR Processor uses this
data to log the state change into the system Sequence of Events (SOE) log. The user may configure
each channel to be included in the system SOE log. Full details of SOE are contained in PD-8013
Trusted
TM
SOE and Process Historian.
Issue 14 Apr 10 PD-T8448 12
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.