SDS-8432 
T8432 Trusted Dual Analogue Input
 TrustedTM Industrial Control System 
Trusted
TM
 Dual Analogue Input Module-T8432 
FRONT PANEL 
DESCRIPTION 
The Trusted 
module interfaces to 60 single-ended 
field input devices. A wide input 
voltage range and programmable 
thresholds allow the module to be 
used in current source and current 
sink configurations. Comprehensive 
diagnostic tests are performed on 
each input channel, including tests for 
stuck on and stuck off failures. Fault 
tolerance is achieved through Dual 
Redundancy within the same module 
for each of the 60 input channels. 
TM
 Dual Analogue Input 
The module can apply a digital filter to 
each input channel. Individual 
channels can be configured for high 
noise immunity (50Hz or 60Hz 
rejection), low noise immunity (fast 
response), or pass-through operation 
(no filtering). 
Each input channel has four 
configurable state thresholds which 
may be assigned to SOE reporting. A 
change of state triggers an SOE 
entry. The on-board Sequence of 
Events (SOE) reporting has a 
resolution of 1ms. 
Each dual section of the module, 
referred to as a slice, conditions and 
measures each channel 
independently. Each slice is optoisolated up to 2500V dc. Each slice 
sends its data to a safety layer 
hardware voter that presents the 
information from both slices to the 
Trusted 
fault is detected on a slice of the 
module, the Trusted 
Processor will flag the error, 
indicating the need to replace the 
module. The Trusted 
Processor will continue to use the 
information provided by the remaining 
slice until a replacement module is 
available. Replacement modules can 
be located in a standby slot next to 
the module or in a designated 
SmartSlot with a temporary 
connection to the same Trusted 
Termination Assembly. 
module slot in a Trusted 
Chassis or Expander chassis. Once 
the I/O module configuration is set, 
mechanical keying is available on all 
I/O modules to prevent inserting a 
module into an incorrect slot. 
TM
 TMR Processor. When a 
TM
 TMR 
TM
 TMR 
Modules may be placed in any I/O 
TM
 Processor 
Configuration of the module is carried 
out using the Trusted 
running on an Engineering 
Workstation. Once configured and 
loaded into the Trusted 
replacement modules are on-line 
educated by the TMR Processor. 
FEATURES 
 60 input channels per module 
 Comprehensive diagnostics 
 Line monitoring on a per 
 2500V dc Opto-Isolation 
 On-board 1ms resolution 
 Hot replaceable 
 Module fault and status 
 IEC 61508, SIL 3 safety 
 Configurable per channel line 
TM
TM
 Toolset 
TM
 Controller, 
and self-test 
channel basis 
Sequence of Events reporting 
indicators 
applications 
noise filter 
Issue 5 Jan 2006 

SDS-8432 
Trusted
TM
 Industrial Control System 
Trusted
TM
 Dual Analogue Input Module-T8432 
BLOCK DIAGRAM 
ELECTRICAL SPECIFICATION 
Number of Inputs 
Field Common Isolation 
Sustained Working  ±250V dc 
 Maximum Withstanding ±2.5kV dc 
Input Voltage 
Measurement Range  ±22mA 
 Maximum Withstanding ±25V dc 
Channel Input termination 
Resistance 
Power Consumption 
Sample Update Interval (no filter) 
Self-Test Interval 
Sequence of Events 
Event Resolution  1ms 
 Time-stamp Accuracy  ±0.5ms 
Long Term Accuracy (at 25
0
C) 
Input Resolution 
Fusing 
Intrinsic Safety 
Circuit Type 
60 Channels 
2509
15 to 18W 
5ms 
2 minutes 
0.2% of span 
12 bit (1 part in 4096) 
None, external if required 
External barrier 
Fault tolerant 1-00-2D 
MECHANICAL 
SPECIFICATION 
Dimensions (HxWxD): 
241mm x 30mm x 300mm 
(9.5ins x 1.2ins x 11.8ins) 
Weight: 
1.13kg 
(2.5lbs) 
ENVIRONMENTAL 
Operating Temperature: 
-5°C to 60°C 
(23°F to 140°F) 
Operating Humidity: 
5 to 95%, noncondensing 
Vibration: 
10 to 57Hz  ±0.075mm 
57 to 150Hz  1.0g 
Shock: 
15g, ½ sine wave, 11ms 
EMI (IEC 801): 
ESD 
Air discharge to 15kV 
Contact discharge to 8kV 
Radiated Fields 
10V/m, 27MHz to 
500MHz 
Transients and Bursts 
2kV, 2.5kHz for 
t=60 seconds 
ICS Triplex 
Technical data sheets are intended for 
information and guidance. The Company 
has a policy of continual product 
development and improvement.  
Specifications are subject to change 
without notice. For latest information, visit 