Rockwell Automation T8432 User Manual

SDS-8432
T8432 Trusted Dual Analogue Input
TrustedTM Industrial Control System
Trusted
TM
Dual Analogue Input Module-T8432

FRONT PANEL

DESCRIPTION

The Trusted module interfaces to 60 single-ended field input devices. A wide input voltage range and programmable thresholds allow the module to be used in current source and current sink configurations. Comprehensive diagnostic tests are performed on each input channel, including tests for stuck on and stuck off failures. Fault tolerance is achieved through Dual Redundancy within the same module for each of the 60 input channels.
TM
Dual Analogue Input
The module can apply a digital filter to each input channel. Individual channels can be configured for high noise immunity (50Hz or 60Hz rejection), low noise immunity (fast response), or pass-through operation (no filtering).
Each input channel has four configurable state thresholds which may be assigned to SOE reporting. A change of state triggers an SOE entry. The on-board Sequence of Events (SOE) reporting has a resolution of 1ms.
Each dual section of the module, referred to as a slice, conditions and measures each channel independently. Each slice is opto­isolated up to 2500V dc. Each slice sends its data to a safety layer hardware voter that presents the information from both slices to the Trusted fault is detected on a slice of the module, the Trusted Processor will flag the error, indicating the need to replace the module. The Trusted Processor will continue to use the information provided by the remaining slice until a replacement module is available. Replacement modules can be located in a standby slot next to the module or in a designated SmartSlot with a temporary connection to the same Trusted Termination Assembly.
module slot in a Trusted Chassis or Expander chassis. Once the I/O module configuration is set, mechanical keying is available on all I/O modules to prevent inserting a module into an incorrect slot.
TM
TMR Processor. When a
TM
TMR
TM
TMR
Modules may be placed in any I/O
TM
Processor
Configuration of the module is carried out using the Trusted running on an Engineering Workstation. Once configured and loaded into the Trusted replacement modules are on-line educated by the TMR Processor.

FEATURES

60 input channels per module
Comprehensive diagnostics
Line monitoring on a per
2500V dc Opto-Isolation
On-board 1ms resolution
Hot replaceable
Module fault and status
IEC 61508, SIL 3 safety
Configurable per channel line
TM
TM
Toolset
TM
Controller,
and self-test
channel basis
Sequence of Events reporting
indicators
applications
noise filter
SDS-8432
Trusted
TM
Industrial Control System
Trusted
TM
Dual Analogue Input Module-T8432

BLOCK DIAGRAM

ELECTRICAL SPECIFICATION

Number of Inputs Field Common Isolation
Sustained Working ±250V dc
Maximum Withstanding ±2.5kV dc
Input Voltage
Measurement Range ±22mA
Maximum Withstanding ±25V dc
Channel Input termination Resistance Power Consumption Sample Update Interval (no filter) Self-Test Interval Sequence of Events
Event Resolution 1ms
Time-stamp Accuracy ±0.5ms
Long Term Accuracy (at 25
0
C) Input Resolution Fusing Intrinsic Safety Circuit Type
60 Channels
2509
15 to 18W 5ms 2 minutes
0.2% of span 12 bit (1 part in 4096) None, external if required External barrier Fault tolerant 1-00-2D
MECHANICAL SPECIFICATION
Dimensions (HxWxD):
241mm x 30mm x 300mm (9.5ins x 1.2ins x 11.8ins)
Weight:
1.13kg (2.5lbs)
ENVIRONMENTAL
Operating Temperature:
-5°C to 60°C (23°F to 140°F)
Operating Humidity:
5 to 95%, non­condensing
Vibration:
10 to 57Hz ±0.075mm 57 to 150Hz 1.0g
Shock:
15g, ½ sine wave, 11ms
EMI (IEC 801):
ESD Air discharge to 15kV Contact discharge to 8kV
Radiated Fields 10V/m, 27MHz to 500MHz
Transients and Bursts 2kV, 2.5kHz for t=60 seconds
ICS Triplex
Technical data sheets are intended for information and guidance. The Company has a policy of continual product development and improvement. Specifications are subject to change without notice. For latest information, visit our Websi te:- www.icstr iplex. com