Rockwell Automation T8424 User Manual

SDS-8424
ed TMR 120 Vac Digital Input
Trusted
TM
Industrial Control System
TrustedTM TMR 120V ac Digital Input Module-T8424

FRONT PANEL

T8424 Trust

DESCRIPTION

The Trusted Input module interfaces to 40 field input devices. The module has broad voltage thresholds defined to IEC61131-2 and is designed to be used with Field Termination Assembly T8823 which provides a current sourcing interface. Comprehensive diagnostic tests are performed on each input channel, including tests for stuck on and stuck off failures. Fault tolerance is achieved through Triple Modular Redundancy (TMR) within the same module for each of the 40 input channels.
TM
TMR 120Vac Digital
The module provides on-board Sequence of Events (SOE) reporting with a resolution of 1ms. A change of state triggers an SOE entry.
Each triplicated section of the module, referred to as a slice, conditions and measures each channel independently. Each slice is opto-isolated up to 2500V dc. Each slice sends its data to a safety layer hardware voter that presents the information from all three slices to the Trusted fault is detected on a slice of the module, the Trusted Processor will flag the error, indicating the need to replace the module. The Trusted Processor will continue to use the information provided by the remaining two slices until a replacement module is available. Replacement modules can be located in a standby slot next to the module or in a designated SmartSlot with a temporary connection to the same Trusted Termination Assembly.
Modules may be placed in any I/O module slot in a Trusted Chassis or Expander chassis. Once the I/O module configuration is set, mechanical keying is available on all I/O modules to prevent inserting a module into an incorrect slot.
Configuration of the module is carried out using the Trusted running on an Engineering Workstation. Once configured and loaded into the Trusted replacement modules are on-line educated by the TMR Processor.
TM
TMR Processor. When a
M
T
TM
TMR
TM
Processor
TM
Toolset
TM
Controller,
TMR
TM

FEATURES

40 TMR input channels per
module
Comprehensive diagnostics
and self-test
2500V dc Opto-Isolation
On-board 1ms resolution
Sequence of Events reporting
Hot replaceable
Front panel status LEDs for
each channel
Module fault and status
indicators
IEC 61508, SIL 3 safety
applications
SDS-8424
Trusted
TM
Industrial Control System
TrustedTM TMR 120V ac Digital Input Module-T8424
FTA
Input Field
Device
VAC
Field Termination Unit (FTU)
FIU
A/D
CONVERTER
SLICE A
SLICE B
SLICE C
FRONT PANEL
SERIAL DISPLAY LATCHES
VOTED STATUS DISPLAY LEDs
FIELD LOGIC
CONTROL
HOUSEKEEPING
SLICE POWER
SUPPLY
ISOLATION BARRIER
FRONT PANEL VOTING LOGIC
HEALTH
INDICATORS
HIU
SLICE CONTROL A
TIME STAMP
SLICE B
SLICE C
BUS INTERFACE
HOUSEKEEPING
MODULE TEMP
SUPPLY DIAG
DSP REFERENCE
HIU POWERFIU POWER
REDUNDANT
SUPPLY
24V1 24V2

BLOCK DIAGRAM

ELECTRICAL SPECIFICATION

Number of Inputs Field Common Isolation
Sustained Working ±250V dc
Maximum Withstanding ±2.5kV dc
Input Voltage
Measurement Range 150V ac
Maximum Withstanding 250V ac RMS or dc
Channel Input Resistance Power Consumption Sample Update Interval (no filter) Self-Test Interval Sequence of Events
Event Resolution 1ms
Time-stamp Accuracy ±0.5ms
Thresholds
Turn-on Voltage 82V ±10%
Turn-off Voltage 26V ±10% Fusing Intrinsic Safety Circuit Type
40 Channels
25k: 15 to 18W 5ms
2 minutes
50mA on T8823 FTA External barrier Fault tolerant, fully triplicated
IMB A
IMB B
IMB C
MECHANICAL SPECIFICATION
Dimensions (HxWxD):
241mm x 30mm x 300mm (9.5ins x 1.2ins x 11.8ins)
Weight:
1.13kg (2.5lbs)
ENVIRONMENTAL
Operating Temperature:
-5°C to 60°C (23°F to 140°F)
Operating Humidity:
5 to 95%, non­condensing
Vibration:
10 to 57Hz ±0.075mm 57 to 150Hz 1.0g
Shock:
15g, ½ sine wave, 11ms
EMI (IEC 801):
ESD Air discharge to 15kV Contact discharge to 8kV
Radiated Fields 10V/m, 27MHz to 500MHz
Transients and Bursts 2kV, 2.5kHz for t=60 seconds
ICS Triplex
Technical data sheets are intended for information and guidance. The Company has a policy of continual product development and improvement. Specifications are subject to change without notice. For latest information, visit our Websi te:- www. icst ripl ex.co m